NICOTRA COPRA Direct Driven Radial Fans Without Scroll Instruction Manual

May 15, 2024
NICOTRA

NICOTRA logoNICOTRA COPRA Direct Driven Radial Fans Without Scroll - logo
2 DIRECT DRIVEN RADIAL FANS
WITHOUT SCROLL
RELEASE VERSION 1.2

NICOTRA COPRA Direct Driven Radial Fans Without Scroll

Important information

The fans are state-of-the-art and fulfil the basic safety and health requirements of the EC Machinery Directive. The fans offer a high level of operating safety and a high standard of quality, which is guaranteed by a certified quality management system (EN ISO 9001). Before leaving the factory, all fans are checked and have a CE quality mark applied. Any fan can potentially present hazards:

  • if it is not installed, operated and maintained by trained personnel.
  • if it is not used for the intended use.

This can present hazards to the life and limbs of personnel, as well as material damage to systems and the building, while the benefits associated with the product can also be impaired.

NOTE
All persons that are commissioned to work on the fan must both read and observe these Operating Instructions.

The Operating Instructions:

  • describe the intended use of the fan and offer protection from improper use.
  • include safety instructions that must always be observed.
  • warn of hazards that can also potentially occur during the intended use.
  • provide important notes on safe and efficient use of the fan, as well as helping to secure the full benefits associated with the product.
  • are to be supplemented by specialist and country-specific standards/regulations and policies.

Nicotra Gebhardt GmbH accepts no liability for any damage or malfunctions that can be attributed to failure to observe the Operating Instructions.
The manufacturer warranty ceases to apply as soon as any unauthorised modifications or changes are made to the fan. No liability is accepted for consequential damage.

Safety instructions

DANGER
Indicates a hazard which, if not avoided, will result in serious injury or death.
WARNING
Indicates a hazard which, if not avoided, could result in serious injury or death.
CAUTION
Indicates a hazard which, if not avoided, could result in minor or moderate personal injury.
NOTICE
Indicates information considered important, but not hazard-related (e.g. messages relating to property damage).

Technical description

3.1. COPRA product description
CAUTION
The fans are designed for installation in devices or systems and do not offer any dedicated touch protection as standard. Corresponding protective measures as per DIN EN ISO 13857 should therefore be implemented.

The fans are driven by a permanent magnet synchronous motor (PM motor). The optimised radial impeller with backward curved, dust repellent hollow-profile aluminum blades is mounted directly to the motor shaft. This is statically and dynamically balanced as per DIN ISO 21940-11. Performance measurements in accuracy class 1 according to DIN 24166 on certified test benches according to ISO 5801. Noise measurements according to DIN 45635. The fans of the COPRA series have an integrated controller (EC/PM technology). Surface corrosion protection systems are available in both galvanized steel and powdercoated steel and aluminum.

COPRA Core
Motor impeller unit can be fitted in each installation orientation.

COPRA Plug
Fan module with support unit and inlet nozzle, installed and adjusted in the factory. COPRA can be fitted in each installation orientation.

NICOTRA COPRA Direct Driven Radial Fans Without Scroll -
COPRA

3.2. Specifi cations
Specifications and permitted limit values should be taken from the type plate, the technical datasheet, the tender information or the respective technical catalogue and always observed.

3.3. Intended use
The fans are suitable for conveying dust-free air and other non-aggressive gases/vapours. They are designed as components for installation in devices or systems.

Permitted conveying medium temperature at a density of 1.2 kg/m³.

Series COPRA
Temperature -20°C to +40°C

NOTICE
Max. ambient temperature at the drive motor: +40°C. Any other use is considered improper use. No liability is assumed for personal injuries and/or damage to property resulting from this.
The recommendations of the device manufacturer for preventing electromagnetic interference (EMI) are to be observed (earthing, cable lengths, cable screens, etc.).

NOTICE

3.4. Improper use
The following are examples of improper use (conveying media):

  • Media at impermissibly high or low temperatures
  • Very wet media
  • Aggressive (e.g. strongly acidic or alkaline) media with pH values < 5 or > 8 media
  • Very dusty media
  • Abrasive media
  • Chlorinated media
  • Explosive media

Unauthorized operating conditions:

  • No operation above the indicated rotational speed (type plate, specifications).
  • No operation in rotational speed ranges with increased vibration (resonance) after commissioning in the system.
  • No operation in rotational speed ranges outside the permitted characteristic range (flow instability).
  • No operation if the fan becomes heavily soiled or imbalanced.
  • No operation if the fan has not been mounted in a way that prevents forces and stress from acting on it.
  • No operation in potentially explosive atmospheres.

This can lead to the following consequences: Motor damage, corrosion damage, imbalance, vibration, deformation, abrasion damage.

WARNING
Avoid dynamic stress of the impeller, as well as frequent load cycles. The following can potentially occur here: Personal injuries and damage to property due to impeller breakages, shaft breakages, fatigue fractures, fire and explosions caused by sparking.

Transport

4.1. Transport damage
Deliveries are to be immediately checked in the presence of the carrier as being intact and complete.

NOTICE
Transport fans carefully.
Improper transport (for example setting the fan down roughly or at an angle) can lead to the following:

  • Fan impellers getting jammed.
  • Shafts getting deformed.
  • Bearings getting damaged.
  • Frequency converters getting damaged.

The devices are packaged and secured in a box on a pallet in the factory.

4.2. Transport safety

  • The transport medium should be selected according to the weight and packaging of the fan (type plate, datasheet).
  • Always secure the load in accordance with applicable regula-tions.
  • Use appropriate lifting points based on the installation situation and the centre of gravity position.

DANGER
Never spend time below suspended loads, as there is a risk of injury from components falling down .

4.3. The attachment points on the fan:
4.3.1. COPRA Plug SeriesNICOTRA COPRA Direct Driven Radial Fans Without
Scroll - COPRA Plug Series

4.3.2. COPRA Core SeriesNICOTRA COPRA Direct Driven Radial Fans Without
Scroll - COPRA Core Series

NOTICE
Use the lifting aid available in the accessories to unpack the COPRA Core component.

NOTICE
No attachment points are: nozzle, impeller, motor, electronics.

4.4. Temporary storage

  • When storing the fan temporarily, always observe the following points:
  • Store the fan in its packaging, adding any other protection dictated by its storage environment.
  • The storage location must be dry and free of dust. The relative humidity must be < 70%, non-condensing.
  • Maximum permitted storage temperature: -40°C to +85 °C.
  • The impellers must be periodically rotated several times (at least every 3 months) and this must also be documented.

4.4. Temporary storage

  • When storing the fan temporarily, always observe the following points:
  • Store the fan in its packaging, adding any other protection dictated by its storage environment.
  • The storage location must be dry and free of dust. The relative humidity must be < 70%, non-condensing.
  • Maximum permitted storage temperature: -40°C to +85 °C.
  • The impellers must be periodically rotated several times (at least every 3 months) and this must also be documented.

Installation

5.1. Safety instructions
WARNING

  • The installation may only be carried out by specialist personnel, observing the information provided in the operating instructions and also applicable regulations.
  • Any guards that were removed in order to perform installation work must be reattached immediately once this work has been completed (and before the electrical connection is re-established).
  • The fans must be mounted in such a way that they are held securely in place at all times during operation.
  • Attach the fans to the supporting structure (Plug) or the on-site motor installation plate (Core).

CAUTION
Shoring up the weight at other points leads to fan damage and is dangerous.

5.2. Installation location

  • The installation location must be appropriate and suitable for the respective fan in terms of its nature, condition, ambient temperature and ambient medium (also observe sections 3.3 and 3.4).
  • The substructure must be flat and have the requisite load capacity.
  • Include monitoring units if operational cannot be performed visibly.
  • If condensation is likely to form, the fan may only be installed in the “shaft horizontal“ or “rotor at bottom” configurations. Ensure led draining of the condensation.

5.3. Installation / mounting
Attach the fan or base frame to the substructure without any tension or stress.

CAUTION
Tension leads to fatigue fractures. These in turn adversely affect the function of the fan and can lead to personal injury and property damage.

  • No forces from system components may be transferred to the fan.

5.4. Mounting instruction
The COPRA™ series fans have been designed for installation with horizontal or vertical shaft on a baffle. The baffle must be adequately dimensioned to handle the mass of the device without causing any vibrations. Please note that no assembly materials are included as standard. Nicotra Gebhardt recommends mounting the fan permanently to the baffle and sealing it. This can be performed on site using a sealing strip.

Type Impeller ø ◻ X
COPRA P/C-25 250 288
COPRA P/C-28 280 318
COPRA P/C-31 315 353
COPRA P/C-35 355 393
COPRA P/C-40 400 438
COPRA P/C-45 450 514
COPRA P/C-50 500 564
COPRA P/C-56 560 624
COPRA P/C-63 630 694
COPRA P/C-71 710 774

5.5. Recommended distances
As a distance to the chamber wall or to the nearest arranged fans in a fan grid, we recommend a ratio of 1.6 or higher to the nominal impeller diameterr:

Size| COPRA Plug
Height/ Width (mm)| **H1*
(mm)**
---|---|---
250| 325| 39,5
280| 355| 48,5
315| 390| 59
355| 430| 71
400| 475| 84,5
450| 580| 72
500| 630| 87
560| 690| 105
630| 760| 126,5
710| 840| 150,5

NICOTRA COPRA Direct Driven Radial Fans Without Scroll - Mounting
instruction 2

5.6. Electrical connection
WARNING

5.6.1. Safety instructions

  • The electrical installation of the fan and the components may only be performed by specialist personnel that have received corresponding training, observing the information provided in these Operating Instructions and applicable regulations.
  • The following standards and directives must be observed here: IEC 60364-1 / DIN VDE 0100; DIN EN 60204-1.
  • Local regulations of the energy supply companies.
  • As protection against unexpected start-up, fit devices in accordance with EN 60204–1 (for example lockable isolators).
  • Always earth the fan properly.
  • No potentially hazardous operating conditions may occur due to malfunctions of protective systems or their equipment.
  • Protective systems should be provided on site. However, these are not included as standard by Nicotra Gebhardt.

DANGER
There is electrical voltage in the intermediate circuit of the electronics and at the main connection when the permanent magnet motor is rotating.

  • Do not perform any work on the fan when the impeller/motor is rotating freely.
  • Lock the impeller using suitable means.

5.6.2. EMC compliant installation

NOTE
Electromagnetic Compatibility directive according to 2014/30/EU is only applicable if the listed types and series are installed and commissioned in accordance with the operating instructions. If the listed types and series are integrated as system components  into a system or operated with other components such as control or control devices, the operator or manufacturer of the entire system is responsible for compliance with the directive according to 2014/30/EU.

NOTE
According to EN 61000-3-2, these types/series are professional devices. Connection to the public low-voltage network is permitted as long as this has been coordinated with the respective energy supply company.

5.6.3. Mains connection/connection plan

NOTE
Establish the mains connection as per the information provided in these operating instructions. The COPRA™ fans controller must be wired according to the locally adopted version of the NEC. A licensed, qualified electrician should complete the wiring for this product.
The controller is designed to operate with 230/460 Vrms, three phase power. For the AC mains connector, the wire gauge should be no larger than 14 AWG for 1.3kW motors, and no larger than 12 AWG for 4.5kW and 8kW motors. The wire can be single or stranded. The wire insulation should be stripped to approximately 0.59-0.62”. The connectors for analog and digital I/O can accept bare wire between 16-24 AWG, with the insulation stripped to approximately 0.35”(min) Per datasheet 9mm = 0.35”.

Overview Supply Connections

  • 1,3 kW
  • 4,5 kW / 8 kW

NICOTRA COPRA Direct Driven Radial Fans Without Scroll -
Overview

5.6.4. Supply Connections

  • L1: Connection terminal for phase 1
  • L2: Connection terminal for phase 2
  • L3: Connection terminal for phase 3
  • PE: Connection terminal for protective conductor

5.6.5. Control connections

  • DIN1: Digital input 1; Factory setting: Motor enable when at +10 to 24 Vdc
  • DIN2: Digital input 2; Factory setting: Specification fixed speed
  • DIN3: Digital input 3; Factory setting: Specification fixed speed
DIN3 DIN2 Speed
0 0 0
0 1 Speed1 (40%)
1 0 Speed2 (60%)
1 1 Speed3 (80%)
  • Further common specifications of digital inputs DIN1, DIN2, DINS: Input impedance of 67 kO, max. voltage: 24 Vdc, LOW/HIGH: <2.6 Vde/>3.3 Vde.
  • GND: Reference potential (0 V) for digital and analog control signals; all GND terminals are internally connected
  • DOUT: Digital output; Factory setting: Display of actual speed by PWM signal (3.3 Vdc / 100 Hz)
  • +424V: 24 Vdc supply for external display/control/regulation devices; max. current: 100 mA
  • BUSA, BUS B: RS485 interface for Modbus RTU connectiong
  • +10V: 10 Vdc supply for external potentiometer; max. current: 100mA
  • 0-10 V: Analog input for 0-10 V control signal; input impedance: 11 kΩ, max. voltage: 24 Vdc (0 -11.5 V readable)
  • 4-20mA: Analog input for 4-20 mA control signal; input impedance: 150 Ω, max. voltage: 24 Vdc, max. current 30 mA (0 -22 mA readable)
  • PWM: Analog input for pulse-width modulated voltage signal; voltage range: 10 – 24 V, frequency range: 50 – 1000 Hz, control range-duty cycle: 5 – 95 % (0 – 100 % readable)
  • ROUT, RCOM: Potential-free relay contacts for indicating faults or operation; factory setting: indication of faults (wire-break-proof design; contact closes shortly after switching on the power supply and opens in case of fault or interruption of the power  supply), max. switching voltage/current: 2A max/30Vdc or 2A max/30Vac, rated contact resistance: 100 mΩ

Maximum and minimum input values

Input| Unit| Minimum value| Nominal value| Maximum value
Mains voltage (230 V)| V| 200 V| 230 V| 240 V
Mains voltage (460 V)| V| 380 V| 460 V| 480 V

Commissioning

6.1. Check and ensure the following before performing commis sioning:

  • All mechanical and electrical protective devices must be attached and connected.
  • Secure touch protection as per DIN EN ISO 13857 based on the installation conditions.
  • Design guards in such a way that no falling objects are drawn in by the fan (DIN EN 60529).
  • Check the duct system and fan for foreign objects (tools, small parts, construction waste, etc.and remove where appropriate.
  • Check that impeller is free by turning it manually.
  • Check the current type, voltage and frequency of the mains connection to ensure that it matches the type plate of the fan or motor.
  • Check that connected elements are working properly.
  • Close off any inspection openings (insofar as present).

WARNING
Only when all guards have been attached and the impeller has been secured as per DIN EN ISO 13857 may the fan be started up. The suitability of the protective devices and their fixtures to the fan must be assessed within the overall safety concept of the installation.

NOTE
The entire system must be assessed in the concrete application to ensure compliance with applicable standards and directives with regard to EMC. This is the responsibility of the customer.

6.2. Test run
Switch on the fan for a short time and check the direction of rotation of the impeller by comparing the rotary direction arrow on the fan..
CAUTION
Risk of injury from rotating impeller. Wait for the impeller to come to a stanastill.

6.3. Check the power consumption

NOTICE
Once the operating speed of the fan has been reached, immediately measure the current consumption and compare it with the nominal current stated on the motor or fan type plate. If overcurrent persists, shut down the device immediately.

6.4. Check for smooth running

NOTICE
Check that fan runs smoothly. If unusual oscillations, vibrations, temperatures and bearing noises are determined, the device must be shut down immediately. The impeller must not drag against the inlet nozzle (audible test) under operating conditions. If it continues to drag, shut down the fan immediately.

6.5. Volume flow measurement device
The fans are equipped with a volume flow measurement device as standard. This facilitates easy volume flow determination and monitoring of the fan when installed.

qv Volume flow m³/h
K Calibration factor m²s/h
p Gas density kg/m³
ΔpDü Differential pressure nozzle Pa

For fans that are fitted in a chamber, the pressure difference between stable pressure in the suction side chamber and the pressure at the inlet nozzle should be measured. It is important to ensure that the static pressure (measured upstream of the inlet nozzle) is not distorted by dynamic pressure effects. If the differential pressure is routed via a pressure sensor, the signal can also be used for purposes. In order to calculate the volume flow, a calibration factor K is required for the respective fan. This is determined by a comparison measurement on a standard test rig with unimpaired inflow.

COPRA P/C Size| Calibration factor K10| COPRA P/C Size| Calibration factor K10
---|---|---|---
250| 73| 450| 156
280| 79| 500| 190
315| 89| 560| 242
355| 106| 630| 310
400| 128| 710| 385

Calib. factor deviation: Standard calibration factor K10 < 10%

If the simplified formula qV = K x (delta_p)^0,5 excl. gas density (rho) shall be used in stead, the K-factor needs to be multiplied with (2/ρ)^0,5, e.g. 1,291 for gas density ρ = 1,2 kg/m3.
When installing the measuring hose, it is important to ensure that the hose is well secured and cannot rub against the impeller. Furthermore it is important to ensure that the hose is not excessively crushed or kinked.

NOTICE
Certain parameters are required for commissioning. These are factory presets. Incorrect parameters can lead to problems, particularly during start-up.

6.6. Operating modes
The speed can be set by analog control signal (0-10 V, 4-20 mA), PWM or by Modbus RTU. The control behavior of the individual interfaces is explained in the following sections.

6.6.1. Analog control (analog input signal)NICOTRA COPRA Direct Driven
Radial Fans Without Scroll - Analog control

6.6.2. PWM (PWM input)
Another method of setting the fan speed is with PWM input. Pin [PWM] accepts a PWM signal at a frequency anywhere between 50Hz and 1kHz. The duty cycle of the PWM frequency determines the fan speed, with the minimum duty cycle of 5% corresponding with minimum demand and increasing linearly to 100% demand at

95% duty cycle.

Duty Cycle (%)=Turn on Time/(Turn on Time + Turn off time)*100NICOTRA COPRA
Direct Driven Radial Fans Without Scroll - PWM

6.6.3. Modbus operation
The Modbus interface has the following default communication settings:

  • Protocol: Modbus RTU (8 bit data)
  • Address/ID: 247
  • Baud rate: 115200
  • Stop bits: 1
  • Parity: none
  • Minimum response time: 50 ms
  • Response timeout: >500 ms

The Modbus interface can be used for the following purposes:

  1. Adjustment of:
    • Modbus communication settings and monitoring (timeout)
    • Settings/functions of digital/analog inputs/outputs, -min./max. speed, ramp times, frequency blanking etc.

  2. Control:
    • Enable/disable, presetting of speed

  3. Monitoring:
    • Query of operating data, such as actual speed, power, fault messages, actual state of digital/analog inputs/outputs

A complete list of read only and read/write parameters are identified in the COPRA Products Modbus Spec.

6.7. Self protective function of the electronics (faults and motor protections)
COPRA™ Fans have two layers of motor protections: UL safety features, and non- UL safety features. The UL safety features are backup protections if the non UL safety faults fails to shuts down or activate limits/derating. If UL safety faults exceeds four counts, the safety-core firmware will automatically perform a microler reset

Non UL Safety/application level protections:

  • Over Voltage
  • Under Voltage
  • Over Temperature
  • Loss of Input Phase

UL Safety-core level protections:

  • Locked Rotor
  • Loss of Output Phase
  • Over Load
  • Hardware Faults

6.7.1. Non UL – Over Voltage

  1. Drive shuts down on over voltage when DC bus voltage exceeds the threshold voltage (see table below)
    Model| Over Voltage Threshold (DC)| Approximate AC Input Voltage
    ---|---|---
    230 V| 450 V DC| 318 V AC
    460 V| 830 V DC (1.3 kW)| 586 V AC
    460 V| 850 V DC (4.5 – 8 kW)| 600 V AC
  2. Drive will try to restart after a delay of 2 seconds. If the over voltage condition persists, drive will shut down and indicate an over voltage fault and keeps retrying after the fault wait delay expires. Note that the number of retries is not limited.

6.7.2. Non UL – Under Voltage

  1. Drive shuts down on under voltage when DC bus voltage falls below the threshold voltage (see table below)
    Model| Under Voltage Threshold (DC)| Approximate AC Input Voltage
    ---|---|---
    230 V| 220 V DC| 155 V AC
    460 V| 440 V DC| 311 V AC
  2. Drive will try to restart after a delay of 2 seconds. If the under voltage condition persists, drive will shut down and indicates an under voltage fault. Drive will keep retrying after the fault wait delay expires. Note that the number of retries is not limited.

6.7.3. Non UL – Over Temperature

  1. Drive shuts down on Over Temperature when IPM temperature exceeds the internal threshold.
  2. Drive will try to restart after a delay of 30 seconds. If the over temperature condition persists, drive will shut down and indicates an over temperature fault. Drive will keep retrying after the fault wait delay expires. Note that the number of retries is not limited.

6.7.4. Non UL – Utility supply power input phase

  1. Drive shuts down when loss of input phases is detected and significant power (>50% of rated power) is used.
  2. Drive will try to restart after a delay of 30 seconds. If the loss of phase persists, drive will shut down and indicates a loss of phase fault and keeps retrying after the fault wait delay expires. Note that the number of retries is not limited.

6.7.5. UL – Locked Rotor

  1. Drive shuts down on locked rotor on start-up if the locked rotor condition is detected.
  2. Drive will try to restart after a delay of 30 seconds. If the locked rotor condition persists, drive will shut down and indicates an UL Locked Rotor Fault and keeps retrying after the fault wait delay expires. Note that the number of retries is not limited.

6.7.6. UL – Loss of Motor Phase

  1. Drive shuts down if a sudden loss of one of the motor phases is detected while the motor is running.
  2. This fault is not detected when the drive’s output current is zero (when motor is in idle state).
  3. Drive will try to restart after a delay of 30 seconds. If the loss of motor phase condition persists, drive will shut down and indicates an UL Loss of Motor Phase Fault and keeps retrying after the fault wait delay expires.
    Note that the number of retries is not limited.

6.7.7. Non UL – Derating

  • There are three types of derating: 1. Current Derating, 2. Power Derating, 3. Temperature Derating
  • Each of these has the following settings: 1. Threshold – Derate threshold, 2. Hysteresis – Threshold below which derate will stop, 3. Derate period – Wait period before next RPM reduction, 4. Derate RPM – Amount of RPM to reduce.
  • If the measured value exceeds the threshold, the speed will be dropped periodically to keep the measured value until it is below the hysteresis threshold
  • Typical temperature threshold is 110 deg C for 1.3kW and 107 deg C for 4.5 kW and 8 kW.

6.7.8. UL – Over Load

  • If the measured phase current into the motor is above the UL over load threshold, motor will shut down on Over Load fault.
  • Drive will try to restart after a delay of 30 seconds. If the condition persists, drive will shut down and indicates an UL Fault and keeps retrying after the fault wait delay expires. Note that the number of retries is not limited.

6.7.9. UL – Hardware Faults

  1. Drive shuts down on hardware faults if a hardware fault is detected by safety core.
  2. Drive will try to restart after a delay of 30 seconds. If the condition persists, drive will shut down and indicates an UL Fault and keeps retrying after the fault wait delay expires. Note that the number of retries is not limited.

NOTICE
After 4 total UL Faults within a power cycle, motor will not attempt restart until after 120 seconds..

Maintenance / repairs

7. 1 . Safety instructions
Before working on the fan, it is imperative to ensure the following:

  • All drives have been disconnected from the mains.
  • Wait until the impeller has come to a standstill.
  • Check the surface temperature to avoid any risk of burns.
  • Ensure that the fan cannot start up in an unled manner while performing the maintenance work (for example lockable isolators).
  • Observe the regulations of the motor manufacturer and also the inverter manufacturer (where applicable).

DANGER
There is electrical voltage in the intermediate circuit of the electronics and at the main connection when the permanent magnet motor is rotating.

  • Do not perform any work on the fan when the impeller/motor is rotating freely.
  • Lock the impeller using suitable means.
  • Before performing maintenance work, use suitable means to remove all harmful or hazardous residual materials that have found their way into the fan as a result of the conveying media.

Recommissioning is then performed once the safety inspections stated in Chapter 6 “Commissioning / safety inspections“ have been completed. However, work that can only be performed during operation in compliance with the applicable safety and accident prevention regulations is excluded from this. This for example includes measurement of vibrations and shock pulses.

WARNING
Failure to observe these points can present hazards to the life or physical condition of the maintenance personnel.

NOTICE
If the condition of the fan does not allow repair by appropriate means, the fan must be shut down immediately and, if necessary, replaced.

7.2. Maintenance intervals
During extended periods of non-use, the fan should be started up regularly for a short period as a way of avoiding bearing damage due to mechanical stress or ingress of moisture. After being stored for an extended period of time, the motor bearings should both be checked before installation.

NOTICE
The maintenance regulations of the motor manufacturer, as well as information from the manufacturers of the switch and devices and the frequency converter must be observed.
To maintain correct operation and ensure safety, we recommend having the function and condition of fans checked at regular intervals by qualified personnel or a specialist company and having the results documented. The type, scope and maintenance intervals, as well as any further actions that are necessary, should all be specified on the basis of how the fans are used, as well as the conditions in place on site. For the maintenance and inspection recommendations based on VDMA 24186–1, please refer to our our website: www .nicotra-gebhardt.com.

NOTICE
Do not use any high-pressure cleaners (steam cleaners). Do not use cleaning agents that contain strong acids or alkalis!

7.2.1. Vibrations
The fan should be checked regularly for mechanical vibrations. The maximum vibration velocity in the radial direction on the level of the motor is 4.5 mm/s. In the case of impellers with nominal diameters of up to 315 mm, up to 7.1 mm/s is permitted when fitted. If the permitted vibration values are exceeded, it is mandatory to rebalance the entire rotating unit in accordance with DIN ISO 21940-11.

7.2.2. Impeller mounting
Following impeller mounting and remounting, the fan must be checked for mechanical vibrations. It may also need to be rebalanced.

7.3. Spare parts
Only use original spare parts as specified in the spare parts list.

NOTE
We do not accept any liability for damage caused by the use of nonoriginal parts.

Breakdowns/malfunctions

Deviations from the standard operating conditions of the fan indicate malfunctions and should be investigated promptly by the maintenance personnel.

CAUTION
Malfunctions that persist for an extended period of time can lead to destruction of the fan and also system components, as well as personal injuries.
If the maintenance personnel is unable to rectify the issue, please request a visit from our mobile customer service.

Troublshooting Guide

9.1. Fault Indication – LED Blink Codes
When a fault is indicated, the LED will blink the number of times specified in the chart below followed by a 2 second pause before it blinks again.

Fault Modbus fault code LED Code Description
No Fault 0 0 No Fault
Motor soft- ware fault 1 1 Sensorless loop in soft- ware lasted too long
Under Voltage 2 2 DC bus voltage falls be- low the threshold voltage
Over Voltage 4 3 DC bus voltage exceeds the threshold voltage
Over Temperature 8 4 IPM temperature is above threshold.
Speed Feed- back 16 5 Measured speed does not match reference speed
Start Up 32 6 Open to close loop tran- sition failed
Loss of input phase 64 7 Disconnection of motor phases
Reserved 128 8 tbd
Hardware Fault 256 9 Hardware over voltage or short circuit fault
UL Safety fault 512 10 One of the UL safety core faults
Internal Communication Loss 1024 11 Internal communication between micro

control- lers lost
Software Error| 2048| 12| Motor firmware error

9.2. Troubleshooting Faults
When the troubleshooting below calls for “power cycle” here is the procedure: turn off power to the motor, wait 30 seconds, turn power back on to the motor to restart. Note that the drive automatically retries after the 30 second wait time. Number of retries is not limited; drive will retry until the fault condition is cleared and a successful restart is achieved..

Fault Description Possible Remedy
Motor soft- ware fault Sensorless loop in software lasted too long Power

cycle to reset drive
Under Voltage| DC bus voltage falls below the threshold voltage| Check line voltage to verify it is within 10% of nameplate voltage
Over Voltage| DC bus voltage exceeds the threshold voltage| Check line voltage to verify it is within 10% of nameplate voltage
Over Tempera- ture| IPM tempera- ture is above threshold| Turn off motor and remove power to allow drive to cool. Verify that the chimney of the drive is not blocked. Restart and retry.
Speed Feed- back| Measured speed does not match reference speed| Check if fan is loose and retighten. Check if shaft is physically locked and try to free. Restart and retry
Start Up| Open to close loop transition failed| Check if fan is loose and retighten. Check if shaft is physically locked and try to free. Restart and retry
Loss of output phase| Disconnection of motor phase/ winding| Please contact your service partner
Over current| Hardware over voltage or short circuit fault| Power cycle and try again. If problem persists, replace motor
UL Safety fault| One of the UL safety core faults| UL safety core faults occur for various reasons such as a locked rotor or an overloaded situation. Turn off motor and verify the shaft is not locked and retry. Power cycling can reset the fault
Internal Communication Loss| Internal communication between micro lers is lost| Power cycle and try again. If problem persists, replace motor
Software Error| Motor firmware error| Power cycle and try again. If problem persists, replace motor

Recycling/disposal

The protection of the environment and the conservation of resources are important issues for Nicotra Gebhardt. We therefore pay attention to sustainable, environmentally friendly designs, as well as technical safety and health protection when developing our fans. When disposing of components or waste, please observe the applicable country-specific legal regulations.

10.1. Disassembly
The disassembly of the product must be performed or monitored by specialist personnel. The disassembly process should be prepared as follows:

  • Disconnect the machine from the mains and remove all cables.
  • Transport the machine to a suitable location for the disassembly process.

WARNING
The products include certain components that are quite heavy. These can fall down during disassembly. This may cause serious physical injury, death and material damage. Secure machine parts that are to be disassembled to prevent them from falling down.

10.2. Component disposal/recycling
The machine is made predominantly from metallic materials. These are fully recyclable. Please separate the components into the following categories:

  • Steel and iron, aluminium, non-ferrous metal, insulating materials, cables and leads
  • Electronic scrap (where present), plastics
  • Electronic components must be disposed of as electronic scrap

Service

We offer all of our partners the following service:
Mobile customer service
Phone +49 (0)7942 101 0
[email protected]
www.nicotra-gebhardt.com

Manufacturer’s notification

Our products are manufactured in compliance with applicable international standards and regulations. If you have questions regarding the use of our products, or if you are planning a special application, please contact us.

UL CERTIFIED
UL FILE NUMBER:
XDNW2.E306123 – ELECTRONICALLY PROTECTED MOTORS COMPONENT

Appendix

Original
EC declaration of incorporation
for the EC Machinery Directive (2006/42/EC)

The manufacturer: Nicotra Gebhardt GmbH
Gebhardtstraße 19-25, 74638 Waldenburg, Germany
hereby declares that the following product:

Product designation: Radial fan without housing with direct drive
Type designation: COPRA CB-C…, COPRA PA-C…
Serial number: See type plate
Year of manufacture: See type plate

as a partly completed machine in the sense of Article 2, clause “g” meets the following basic requirements of the Machinery Directive (2006/42/EC): Appendix I, Articles 1.1.2, 1.3.7
This partly completed machine may only be commissioned once it has been determined that the machine into which it is to be fitted complies with the provisions of the Machinery Directive (2006/42/EC).

The following harmonised standards 1) were applied:
DIN EN ISO 12100: Safety of machinery – General principles for design
DIN EN ISO 13857: Safety of machinery – Safety distances to prevent hazard zones being reached by upper and lower limbs
Additional national standards and technical specifications 2), in particular: VDMA 24167: Fans – Safety requirements
The manufacturer is committed to providing the special documents required for the partly completed machine as per Appendix VII, Part B to any national authority on request by post/e-mail.
Waldenburg/Ciserano, June 01, 2023
Authorised representative for the technical documentation: Klaus Gundel

NICOTRA COPRA Direct Driven Radial Fans Without Scroll -
Signature

Production Director / Production Director / Head of Research and Development
pp. Ulrich Reichert / pp. Paolo Di Dionisio / pp. Dr. J. Anschütz

  1. Please refer to the documentation provided by the manufacturer for a complete list of applicable standards and technical specifications
  2. Insofar as no corresponding harmonised standards are yet available

Original


EC declaration of conformity
for the European Ecodesign Directive (2009/125/EC)
We hereby declare that the product stated below complies with the ecodesign requirements, as stipulated by Regulation (EU) No, 327/2011 of the Commission in Appendix I, Section 2, based on the degree of efficiency of the corresponding fan type specified in the technical documentation and the measurement/efficiency category.

Designation: Radial fan without housing with direct drive
Fan type: COPRA CB-C…, COPRA PA-C…
Device number: See type plate
Year of manufacture: See type plate
Relevant EC Directives : EC Directive on the environmentally friendly “ecodesign” of energy-related products (2009/125/EC)

Waldenburg/Ciserano, June 01, 2023 NICOTRA COPRA Direct Driven Radial Fans
Without Scroll - Signature

Production Director / Production Director / Head of Research and Development pp. Ulrich Reichert / pp. Paolo Di Dionisio / pp. Dr. J. Anschützz

Original


EC declaration of conformity
for the European Electromagnetic Compatibility Directive (2014/30/EU) for the Eurpean Low Voltage Directive (2014/35/EU)
Herewith we declare that the machinery designated below, on the basis of its design and construction in the form brought onto the market by us is in accordance with the relevant EU Council Directives as mentioned below. If alterations are made to the machinery without prior consultations with us, this declaration becomes invalid.

Designation: Radial fan without housing with direct drive
Fan type: COPRA CB-C…, COPRA PA-C…
Device number: See type plate
Year of manufacture: See type plate
Device Number: See type plate
Year of manufacture: See type plate
Relevant EC Directives: EU-Directive of Electromagnetic
Compatibility (2014/30/EU)
Low Voltage Directive (2014/35/EU)
Applied harmonized standards, in particular
DIN EN 60335-1, DIN EN 60204-1
DIN EN 61000-3-2, DIN EN 61000-3-3
DIN EN 61000-6-2, DIN EN 61000-6-4
DIN EN 61000-4-3,DIN EN 61000-4-6
DIN EN 61000-4-13

The sole responsibility for issuing this declaration of conformity lies with the manufacturer.
Waldenburg, June 01, 2023

NICOTRA COPRA Direct Driven Radial Fans Without Scroll -
Signature

Production Director / Production Director / Head of Research and Development pp. Ulrich Reichert / pp. Paolo Di Dionisio / pp. Dr. J. Anschütz

*Electromagnetic Compatibility directive according to 2014/30/EU is only applicable if the listed types and series are installed and commissioned in accordance with the operating instructions. If the listed types and series are integrated as system components into a system or operated with other components such as control or control devices, the operator or manufacturer of the entire system is responsible for compliance with the directive according to 2014/30/EU.

OI COPRA™ FANS C/P 1.2

Original
UK declaration of incorporation
UK Machinery (Safety) Regulation 2008

The manufacturer:
Gebhardtstraße 19-25,| Nicotra Gebhardt GmbH
74638 Waldenburg, Germany
---|---

hereby declares that the following product:

Product designation: Radial fan without housing with direct drive
Type designation: COPRA CB-C…, COPRA PA-C…
Serial number: See type plate
Year of manufacture: See type plate

as a partly completed machine in the sense of Article 2, clause “g” meets the following basic requirements of the Machinery (Safety) Regulation 2008: Appendix I, Articles 1.1.2, 1.3.7
This partly completed machine may only be commissioned once it has been determined that the machine into which it is to be fitted complies with the provisions of the Machinery (Safety) Regulation 2008.

The following harmonised standards 1) were applied:
DIN EN ISO 12100: Safety of machinery – General principles for design
DIN EN ISO 13857: Safety of machinery – Safety distances to prevent hazard zones being reached by upper and lower limbs

Additional national standards and technical specifications 2), in particular: VDMA 24167: Fans – Safety requirements
The manufacturer is committed to providing the special documents required for the partly completed machine as per Appendix VII, Part B to any national authority on request by post/e-mail.

WaldenburgCiserano, June 01, 2023
Authorised representative for the technical documentation: Klaus Gundel

NICOTRA COPRA Direct Driven Radial Fans Without Scroll -
Signature

Production Director / Production Director / Head of Research and Development pp. Ulrich Reichert / pp. Paolo Di Dionisio / pp. Dr. J. Anschütz

  1. Please refer to the documentation provided by the manufacturer for a complete list of applicable standards and technical specifications
  2. Insofar as no corresponding harmonised standards are yet available

Original

UK Declaration of Conformity
The Ecodesign for Energy-Related Products Regulations 2010

The manufacturer:| Nicotra Gebhardt GmbH
Gebhardtstraße 19-25,
74638 Waldenburg, Germany
---|---

We hereby declare that the product named below, based on the efficiency grade of the respective fan type and the measurement and efficiency category specified in the technical documentation, complies with the eco-design requirements of the UK Legislation as mentioned below.

Designation: Centrifugal fan without scroll direct driven
Fan type: COPRA CB-C…, COPRA PA-C…
Serial no: See type plate
Year of manufacturing: See type plate
Relevant UK Legislation: The Ecodesign for Energy-Related Products Regulations 2010

The sole responsibility for issuing this declaration of conformity lies with the manufacturer.
Waldenburg/Ciserano, June 01, 2023

NICOTRA COPRA Direct Driven Radial Fans Without Scroll -
Signature

Production Director / Production Director / Head of Research and Development pp. Ulrich Reichert / pp. Paolo Di Dionisio / pp. Dr. J. Anschütz

Original

UK Declaration of Conformity
UK-Directive of Electromagnetic Compatibility Regulations 2016 and for the Low Voltage Directive 2016

The manufacturer: Nicotra Gebhardt GmbH
Gebhardtstraße 19-25, 74638 Waldenburg, Germany
Herewith we declare that the machinery designated below, on the basis of its design and construction in the form brought onto the market by us is in accordance with the relevant Council Directives as mentioned below. If alterations are made to the machinery without prior consultations with us, this declaration becomes invalid.

Designation: Cirect driven fan without scroll
Fan type: COPRA CB-C…, COPRA PA-C…
Serial no: See type plate
Year of manufacturing: See type plate
Relevant UK Legislation: UK-Directive of Electromagnetic Compatibility Regulations 2016* Low Voltage Directive 2016

Applied harmonized standards, in particular:
DIN EN 60335-1, DIN EN 60204-1, DIN EN 61000-3-2, DIN EN 61000-3-3,
DIN EN 61000-6-2, DIN EN 61000-6-4, DIN EN 61000-4-3, DIN EN 610004-6,DIN
EN 61000-4-13

The sole responsibility for issuing this declaration of conformity lies with the manufacturer.
Waldenburg/ciserano, June 01, 2023

NICOTRA COPRA Direct Driven Radial Fans Without Scroll -
Signature

Production Director / Production Director / Head of Research and Development pp. Ulrich Reichert / pp. Paolo Di Dionisio / pp. Dr. J. Anschütz

*Electromagnetic Compatibility directive according to 2016 is only applicable if the listed types and series are installed and commissioned in accordance with the operating instructions. If the listed types and series are integrated as system components into a system or operated with other components such as control or control devices, the operator or manufacturer of the entire system is responsible for compliance with the directive according to 2016.

Direct driven Radial fans without scroll
Regal Rexnord
Contact us: rexnord.com/contact regalrexnord.com
The proper selection and application of products and components, including assuring that the product is safe for its intended use, are the responsibility of the customer. To view our Application Considerations, please visit https://www.regalrexnord.com/Application-Considerations.
To view our Standard Terms and Conditions of Sale, please visit https://www.regalrexnord.com/
Terms-and-Conditions-of-Sale (which may redirect to other website locations based on product family).
“Regal Rexnord” is not indicative of legal entity. Refer to product purchase documentation for the applicable legal entity. Regal Rexnord and Nicotra Gebhardt are trademarks of Regal Rexnord Corporation or one of its affiliated companies.

Power Efficiency Solutions
Nicotra Gebhardt GmbH
Phone: +49 (0)7942 101 0
[email protected]
regalrexnord.com/brannds/nicotra-gebhardt
FORM
REV. 1.2
JUNE 2023
Further languages available on request
Revision index
Revision Date
BA-CFD-COPRA 1.1-04/2023
© 2023 Regal Rexnord Corporation. All Rights Reserved.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NICOTRA User Manuals

Related Manuals