APC SRV1KUXI-IN Online UPS External Battery User Manual
- June 10, 2024
- APC
Table of Contents
SRV1KUXI-IN Online UPS External Battery
User Manual Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Important Safety Instructions
SAVE THESE INSTRUCTIONS – This manual contains important instructions that
should be followed during installation and maintenance of the Easy UPS.
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it. The
following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of this symbol either to a “Danger” or “Warning” safety label
indicates that an electrical hazard exists which will result in personal
injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
For Professional Business Applications – Not for Consumer Use
Product Handling Guidelines
<18 kg <40 lb
18-32 kg 32-55 kg 40-70 lb 70-120 lb
55 kg >120 lb
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if
there is any damage.
Read the Safety Guide before installing the UPS.
· This UPS is for indoor use only.
· Do not operate this UPS in direct sunlight, in contact with fluids, or where
there is excessive dust or high humidity.
· Do not operate the UPS near open windows or doors.
· Be sure the air vents on the UPS are not blocked. Allow adequate space for
proper ventilation. NOTE: Allow a minimum of 20 cm clearance on both front and
rear sides of the Easy UPS.
· Environmental factors impact battery life. Elevated ambient temperatures and
poor quality utility power causing frequent discharges will shorten battery
life. Follow the battery manufacturer recommendations.
Electrical safety
· When grounding cannot be verified, disconnect the equipment from the utility
power outlet before installing or connecting to other equipment. Reconnect the
power cord only after all connections are made.
· Connection to the branch circuit (mains) must be performed by a qualified
electrician.
· The protective earth conductor for the UPS carries the leakage current from
the load devices (computer equipment). An insulated ground conductor is to be
installed as part of the branch circuit that supplies input power to the UPS.
The conductor must have the same size and insulation material as the grounded
and ungrounded branch circuit supply conductors. The conductor will be green
and with or without a yellow stripe.
· The grounding conductor is to be grounded to earth at the service equipment,
or if supplied by a separately derived system, at the supply transformer or
motor generator set.
2
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Battery safety
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE · Replace the battery at
least every 5 years or at the end of its service
life, whichever is earlier.
· Replace the battery immediately when the UPS indicates battery replacement
is necessary.
· Replace batteries with the same number and type of batteries as originally
installed in the equipment.
· Replace the battery immediately when the UPS indicates a battery over-
temperature condition, or when there is evidence of electrolyte leakage. Power
off the Easy UPS, unplug it from the AC input, and disconnect the batteries.
Do not operate the Easy UPS until the batteries have been replaced.
Failure to follow these instructions can result in minor or moderate injury
and equipment damage.
· Replace batteries with the same number and type of batteries as originally
installed in the equipment.
· Over charging, over heating or other misuse of batteries can result in a
discharge of battery electrolyte. Released electrolyte is toxic and may be
harmful to the skin and eyes.
· Use tool with insulated handles. · Wear rubber gloves and boots. · CAUTION:
Before installing or replacing the batteries, remove jewelry
such as wristwatches and rings. High short circuit current through conductive
materials could cause severe burns. · CAUTION: Do not dispose of batteries in
a fire. The batteries may explode. · CAUTION: Do not open or mutilate
batteries. Released material is harmful to the skin and eyes and may be toxic.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
3
Hardwiring safety
· Verify that all branch circuit (mains) and low voltage (control) circuits
are de-energized, and locked out before installing cables or making
connections, whether in the junction box or to the UPS.
· Wiring by a qualified electrician is required. · Adhere to national and
local codes. · Select wire size and connectors according to national and local
codes. · All openings allowing access to UPS hardwiring terminals must be
covered. Failure to do so may result in personal injury or equipment damage.
Radio Frequency Warning
This UPS is a category C2 product as per IEC 62040-2. In a residential
environment, this product may cause radio interference, in which case the user
may be required to take additional measures.
Product Description
The APC by Schneider Electric Easy UPS is a high performance, uninterruptible
power supply (UPS). The Easy UPS helps to provide protection to connected
equipment from utility power blackouts, brownouts, sags, surges, small utility
fluctuations and large disturbances. The Easy UPS also provides battery backup
power to connected equipment until utility power returns to normal levels or
the batteries are fully discharged.
This user manual is available on the APC by Schneider Electric Web site,
www.apc.com.
4
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Package Contents
Easy UPS
Front bezel
su o1526 a
PowerChute software download guide
Dear Customer,
TM SERIAL SHU TDO WN
Congratulations on y our Easy UPS purchase.
For convenient control, monitoring and graceful operating system
shutdown, it is highly recommended that you install the latest version of
Power ChuteTM Serial Shutdown software on all
servers protected by your Easy UPS. Learn more and download for free from
https://www.apc.com/pcss.
NOTES :
· PowerChute is a 64-bit only application and cannot be inst alled on a 32-bit
operat ing syst em.
· A USB driver is required to communicate with PowerChute over USB. For more
information, please refer to Knowledge Base article FA000223363on the APC
website (htt ps://www. ap c.com/us/ en /fa qs/ho me ).
990- 91611A
User documentation
USB cable
Serial communication cable
Rack-mount bracket x1 pair Stabilizer brackets x2 pairs
suo136 7a
Flat head screws x8
su o13 66a
Pan head screws x4
Utility power cable
Battery cable
NOTE: Supplied with SRV1KUXI-IN model only.
NOTE: The model and serial numbers are located on a label in the top panel.
The packaging is recyclable; save it for reuse or dispose of it properly.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
5
Optional Accessories
Refer to the APC by Schneider Electric Web site, www.apc.com, for available
accessories.
Specifications
Environmental specifications
NOTICE
RISK OF EQUIPMENT DAMAGE · Easy UPS must be used indoors only.
· The installation location should be sturdy to withstand the weight of the
Easy UPS.
· Do not operate Easy UPS where there is excessive dust or where the
temperature or humidity are outside specified limits.
Failure to follow these instructions can result in equipment damage.
Operating Temperature
Storage Operating
Elevation
Storage Humidity International Protection Code
SRV1KUXI-IN SRV2KUXI-IN SRV3KUXI-IN
· 0 to 40 °C at rated load · 40 to 50 °C linearly derated to 80% of maximum
load
capacity -20 to 60 °C
· 0 to 2,000 m: Normal operation · 2,000 to 3,000 m: The output power reduces
@ 1% for
increase in height of every 100 m · > 3,000 m: UPS will not work 0 to 15,000 m
0 to 95% relative humidity, non-condensing
IP20
Physical specifications
SRV1KUXI-IN SRV2KUXI-IN SRV3KUXI-IN
Dimensions with package 500 x 240 x 550 mm Width x Height x Depth (19.7 x 9.5 x 21.7 in)
545 x 240 x 700 mm (21.5 x 9.45 x 27.6 in)
Dimensions without package Width x Height x Depth
Weight with package (approx.)
Weight without package (approx.)
438 x 86.2 x 332.2 mm (17.2 x 3.4 x 13.1 in)
10.3 kg
7.2 kg
438 x 86.2 x 462.2 mm (17.2 x 3.4 x 18.2 in)
13.9 kg
13.7 kg
9.8 kg
10.1 kg
6
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Dimension D1 and D2
D1
D2 Depth
s uo2067a
D1 D2 Depth
SRV1KUXI-IN 300 mm (11.8 in) 392 mm (15.4 in) 332.2 mm (13.1 in)
SRV2KUXI-IN 430 mm (16.9 in) 522 mm (20.6 in) 462.2 mm (18.2 in)
SRV3KUXI-IN 430 mm (16.9 in) 522 mm (20.6 in) 462.2 mm ( 18.2 in)
Input specifications
SRV1KUXI-IN SRV2KUXI-IN SRV3KUXI-IN
Nominal input voltage
230 VAC
Input frequency*
40 – 70 Hz (auto-sensing)
Input voltage range (100% load)
160 to 280 VAC at 35 °C
Input voltage range (50% load)
Input power factor (100% resistive load at nominal voltage)
Input protection
110 to 280 VAC 0.95
Circuit breaker
*NOTE: Refer to product specifications for derating in frequency converter mode.
Output specifications
Easy UPS Capacity Nominal output voltage Other programmable voltage Efficiency
at rated load Output voltage regulation Output voltage distortion
Frequency – On battery
SRV1KUXI-IN SRV2KUXI-IN SRV3KUXI-IN 1000 VA / 800 W 2000 VA / 1600 W 3000 VA /
2400 W
230 VAC 220 VAC, 240 VAC
88%
90%
±1% static
· 3% max. for full linear load · 6% max. for full non linear load (100% VA, 0.8 PF) · 15% for the last 60 seconds of the backup time
50 Hz ± 0.5 Hz / 60 Hz ± 0.5 Hz
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
7
Frequency – AC mode Crest factor Waveform Output connection Bypass
Battery bank
SRV1KUXI-IN SRV2KUXI-IN SRV3KUXI-IN
50 Hz ± 3 Hz / 60 Hz ± 3 Hz 3:1
Sinewave Refer “Rear Panel Features” on page 13 for details.
Internal Lower setting: 161/173/184/196 VAC Upper setting: 242/253/265/276 VAC
Configuration
Type
Battery bank voltage Charging Voltage Max Ah capacity
SRV1KUXI-IN
SRV2KUXI-IN
SRV3KUXI-IN
External battery
Sealed maintenance free valve regulated lead acid type (SMF)/ Tubular (TUB) type
24 VDC
72 VDC
27.2 V
81.6 V
81.6 V
84 Ah
Tower Installation
CAUTION
RISK OF FALLING EQUIPMENT · The Easy UPS is heavy.
· Always practice safe lifting techniques adequate for the weight of the
equipment.
· Do not lift the Easy UPS by holding the front panel display.
· Ensure that the stabilizer brackets are installed along with the Easy UPS in
tower orientation.
Failure to follow these instructions can result in minor or moderate injury
and equipment damage.
8
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Front panel display rotation
suo1529a
Installing stabilizer brackets
suo1534a
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
9
Install the front bezel.
suo1396a suo1397a
NOTE: Maintain approximately 35 mm distance from the edge of the unit, when installing the stabilizer brackets to the Easy UPS.
suo1604a
35 mm
35 mm
10
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Rack-Mount Installation
CAUTION
RISK OF FALLING EQUIPMENT · The Easy UPS is heavy. · Always practice safe
lifting techniques adequate for the weight of
the equipment. · Do not lift the Easy UPS by holding the front panel display.
· Always install the UPS at the bottom of the rack. · Always use the
recommended number of screws to secure brackets
to the UPS. · Given the heavy weight, the use of rack-mount brackets is
mandatory during rack installation (guide with L-shaped support). · Secure the
unit in the rack using all the screws supplied for the
purpose. Failure to follow these instructions can result in minor or moderate
injury and equipment damage.
Optional Rail Kit accessories SRVRK1 to enable the installation of Easy UPS in
rack-mount configuration is available for purchase.
Install the rack-mount brackets.
suo1 404 a
x8
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
11
su o1 40 5a
Lift the Easy UPS module and slide it into rack enclosure.
Secure the Easy UPS module to the rack with screws, nuts and washers (not
supplied in the package).
Install the front bezel.
suo1406a
suo1407a
12
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
suo1525a
Rear Panel Features
SRV1KUXI-IN
SRV2KUXI-IN and SRV3KUXI-IN
suo1524a
Actual UPS may differ in appearance from the illustration.
Input circuit breaker
USB port
Utility power connector
Battery charging current selector switch
Intelligent slot for management accessories
Battery type selector switch
Battery connector
Battery backup outlets
Ground screw
Input terminal block
Serial communication port
Output terminal block
Emergency power off (EPO) connector
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
13
Hardwiring – SRV2KUXI-IN and SRV3KUXI-IN
CAUTION
RISK OF ELECTRIC SHOCK · Adhere to all national and local electrical codes. ·
All electrical work must be performed by a qualified electrician. · Turn off
all power to this equipment before working on the
equipment. · Switch the external circuit breaker off. Practice lockout/tagout
procedures. · Do not wear jewelry when working with electrical equipment. ·
Select wire size and connectors according to national and local
codes. Failure to follow these instructions can result in moderate injury.
suo1578a
LN
LN
Input hardwiring · Use 12 AWG (4 mm2) wire (not supplied) for hardwiring the
input.
1. Locate the cover of the input hardwire terminal block on the rear panel.
2. Remove the screws securing the cover and remove the cover. 3. Connect the
line, neutral and earth/ground wires to the terminal block.
Terminals are labeled for proper wire configuration. 4. Replace and secure the
cover using the screws removed in step 2.
14
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Output hardwiring · Use 12 AWG (4 mm2) wire (not supplied) for hardwiring the
output.
1. Locate the cover of the 16 A output hardwire terminal block on the rear
panel.
2. Remove the screws securing the cover and remove the cover. 3. Connect the
line, neutral and ground wires to the terminal block.
Terminals are labeled for proper wire configuration. 4. Replace and secure the
cover using the screws removed in step 2.
Connect the Battery Bank to Easy UPS
CAUTION
RISK OF ELECTRIC SHOCK · Adhere to all national and local electrical codes. ·
All electrical work must be performed by a qualified electrician. · Identify
the polarities of the battery terminals before connecting the
battery. Be sure grounding is connected firmly. · Do not short the battery
terminals. · Do not touch multiple terminals in the battery at the same time.
· Do not wear jewelry when working with electrical equipment. Failure to
follow these instructions can result in moderate injury.
NOTICE
RISK OF IMPROPER CONNECTION Connect the battery according to the battery
voltage indicated on the rear panel. If the connected battery voltage is
incorrect, UPS may be damaged and cannot be repaired. Therefore, be sure to
confirm that the battery voltage is in accordance with the UPS specification.
Failure to follow these instructions can result in equipment damage.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
15
suo1581a
Easy UPS Battery
NOTE: The illustration is shown for SRV2KUXI-IN and SRV3KUXI-IN Easy UPS.
Follow the same procedure to connect the battery to SRV1KUXI-IN Easy UPS.
1. Locate the battery connector cover on rear panel of Easy UPS. 2. Remove
the screws securing the cover and remove the cover. 3. Use the supplied
battery connection cable. 4. Crimp the appropriate size lugs suitable for the
battery to each end of the
loose wires of the battery connection cable. 5. Connect the lugs of the
positive (red) and negative (black) wires, to the
positive and negative terminals respectively, on the battery bank. NOTE:
Connect the ground wire of the battery connection cable to the to the metal
frame housing the batteries. If a metal frame is not used for housing the
batteries, then be sure to properly insulate this ground wire. 6. Plug the
battery cable connector into the battery connector receptacle on the rear side
of the UPS. 7. Insert and tighten the screws removed in step 2 to secure the
battery connector receptacle to the battery connector of Easy UPS. 8. Connect
the ground wire at the battery cable connector end to the ground terminal in
the Easy UPS.
16
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Start Up
Connect equipment and input power to the Easy UPS
CAUTION
RISK OF ELECTRIC SHOCK · All electrical work must be performed by a qualified
electrician. · Turn off all power to this equipment before working on the
equipment.
· Practice lockout/tagout procedures.
· Do not wear jewelry when working with electrical equipment. Failure to
follow these instructions can result in moderate injury.
1. Connect equipment to SRV1KUXI-IN Easy UPS. Refer “Rear Panel Features” on
page 13 for details. Connect equipment either to the 6 A outlets or to the 16
A hardwire terminal block in SRV2KUXI-IN and SRV3KUXI-IN Easy UPS. For
connecting equipment to the 16 A hardwire terminal block refer “Output
hardwiring” on page 15 for details.
2. Connect battery bank to the Easy UPS. Refer “Connect the Battery Bank to
Easy UPS” on page 15 for details.
3. Set the battery type using the battery type selector switch on the rear
panel. Refer “Battery type and Charger current selection” on page 24 for
details.
4. Set the charger current for the batteries connected to the Easy UPS. Refer
“Battery type and Charger current selection” on page 24 for details.
5. Connect input utility power to the Easy UPS. For SRV1KUXI-IN connect input
utility power cable to the utility power connector. For SRV2KUXI-IN and
SRV3KUXI-IN refer “Input hardwiring” on page 14 for details.
6. Switch on the input utility power. The Easy UPS display panel will
illuminate.
Start the Easy UPS
Press and hold the POWER ON/OFF button located on the front panel of Easy UPS
until a beep is heard. The Status LED will illuminate green.
· Be sure to charge the battery to its full capacity initially. · Do not
expect full backup time during this initial charge period.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
17
Cold start the Easy UPS
Use cold start feature to supply power to connected equipment from the
batteries.
Press and hold the POWER ON/OFF button located on the front panel of Easy UPS
until a beep is heard. The display panel will illuminate.
Press the POWER ON/OFF button again to supply battery power to the connected
equipment.
Turn off Easy UPS
To turn off the Easy UPS, press and hold the POWER ON/OFF button on the front
panel display until a beep is heard.
Connect and install management software
Easy UPS SRV models are provided with PowerChute management software for
unattended operating system shutdown, UPS monitoring, UPS control and energy
reporting. The following diagram is a representation of a typical server
installation.
1. Connect the USB cable from the rear of the UPS to the protected device
such as a server. Note: A USB driver is required to communicate with
PowerChute over USB. For more information, please refer to Knowledge Base
article FAQ000223363 on the APC website (https://www.apc.com/us/en/faqs/
home).
2. For a server or other device with an operating system, download and
install latest version of the PowerChute Serial Shutdown from
www.apc.com/pcss. PowerChute Serial Shutdown supports graceful shutdown in the
event of an extended power outage. Note: PowerChute is a 64-bit only
application and cannot be installed on a 32-bit operating system.
3. A built-in serial port is also available for additional communication
options with serial cable. Note: Both RS232 Serial Port and USB Communication
Port cannot be used at the same time
18
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
suo2098a
TM
SERIAL SHUTDOWN
Connect the USB cable from the rear of the Easy UPS to the computer. Download
and install the latest version of PowerChute Serial Shutdown from
https://www.apc.com/pcss A built-in serial port is also available for
additional communication options with
serial cable.
Additional communication options are available via the built-in intelligent
slot. Refer to APC by Schneider Electric Web site, www.apc.com for more
information.
Emergency Power Off
NOTICE
RISK OF EQUIPMENT DAMAGE · Adhere to all national and local electrical codes.
· All electrical work must be performed by a qualified electrician. · Do not
connect the EPO interface to any circuit other than an
unused circuit. Failure to follow these instructions can result in equipment
damage.
The Emergency Power Off (EPO) function is a feature that will immediately
remove power to all connected equipment.
The EPO switch is internally powered by the Easy UPS for use with non-powered
switches or potential free normally closed (N/C) contacts.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
19
Connecting normally closed (N/C) contacts
Loosen the screws of terminals 1 and 2 in Remove the metal link between
the EPO connector.
pins 1 and 2.
x2
12 suo1412a
12
suo1413a
Connect N/C relay contacts between Secure the EPO connector screws
pins 1 and 2 of the EPO terminal block. Use 0.5 to 1 mm2 wire.
beneath pins 1 and 2.
x2
12
suo1414a
12 suo1415a
NOTE: If the N/C contact is open, the Easy UPS will turn off. Power to the
connected equipment will be immediately turned off.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it
only to other SELV circuits. The EPO interface monitors circuits that have no
determined voltage potential. Such closure circuits may be provided by a
switch or relay properly isolated from the utility. To avoid damage to the
Easy UPS, do not connect the EPO interface to any circuit other than an unused
circuit. Use one of the following cable types to connect the Easy UPS to the
EPO switch.
· CL2: Class 2 cable for general use. · CL2P: Plenum cable for use in ducts,
plenums, and other spaces
used for environmental air. · CL2R: Riser cable for use in a vertical run in a
floor-to-floor
shaft.
20
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Operation
Front panel display features
Easy UPS models are equipped with an intuitive and configurable LCD display.
The display complements the software interface as they convey similar
information and either may be used to configure the Easy UPS settings.
suo1830b
Mute / Esc
POWER ON/ Press the POWER ON/OFF button to turn on the Easy UPS. OFF button Press and hold the POWER ON/OFF button until a beep is heard to turn off the Easy UPS. Press the POWER ON/OFF button to reset alerts.
Alert LED The Alert LED illuminates red when the Easy UPS detects an internal
error and blinks red for Easy UPS notifications. Refer “Alerts and
Notifications” on page 29 for details.
UP/DOWN Press the UP/DOWN ARROW button to scroll through the main menu options ARROW and display screens. button
ENTER button
Press the ENTER button to enter the menu or to select a menu item/value during navigation.
MUTE/ESC Press the MUTE/ESC button: button · To acknowledge audible alerts and suppress them temporarily. · To exit a sub menu and return to the main menu.
LCD
The display interface options are visible on this LCD screen. Press any
Display button to activate LCD, if the display is not illuminated.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
21
Status LED
The Status LED illuminates green when the power is on. The LED indicates two
different states of output power: · Output off: LED blinks on and off. Press
POWER ON/OFF button to turn
the output power on. · Output on: LED illuminates green continuously.
Front panel display icons
On Line: The Easy UPS is drawing utility power and performing double conversion to supply power to the connected equipment.
ON BATT
BYPASS
X
A LA RM
On Battery: The Easy UPS is supplying battery backup power to the connected
equipment.
Replace Battery: The battery is not connected securely or the battery is
nearing the end of its service life and should be replaced.
Bypass: The Easy UPS is in bypass mode, sending utility power directly to
connected equipment. Bypass mode operation is the result of an internal UPS
event, an overload condition, or a user initiated command either through the
display interface or through an accessory. Battery operation is not available
while the Easy UPS is in bypass mode. Refer “Alerts and Notifications” on page
29 for details. System Alerts: The Easy UPS has detected an internal error.
See “Alerts and Notifications” on page 29 in this manual.
Overload: The equipment connected to the Easy UPS is drawing more power than
rated.
Battery Charge: The battery charge level is indicated by the number of bar
sections illuminated. When all five blocks are illuminated, the battery is
fully charged. Each bar represents approximately 20% of the battery charge
capacity.
Load Level: The load percentage is indicated by the number of load bar
sections illuminated. Each bar represents approximately 20% of the load.
Mute: An illuminated line through the icon indicates that the audible alert is
disabled.
Green Mode: An illuminated icon indicates that the unit is working in Green
mode. The connected equipment is receiving the utility input directly as long
as the input voltage and frequency are within the configured limits.
Alert or notification: The Easy UPS has detected an internal error or the Easy
UPS is in configuration mode. Refer “Alerts and Notifications” on page 29 for
details.
22
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
EVENT LOG
Event: The icon is illuminated when the user is viewing the event log.
Status Indicators
Audible Alert
Condition
Continuous beeps, every half second
Low Battery State – The battery is nearing its discharge state. The Easy UPS
is about to shutdown.
Overload condition – The equipment connected to the Easy UPS is drawing more
power than rated.
4 beeps every 30 sec
On Battery State – The Easy UPS is supplying battery
(first beep starts after 4 sec on backup power to the connected equipment.
battery)
Continuous beeps
Alert State – Easy UPS has detected an internal error. Refer “Alerts and Notifications” on page 29 for details.
Short beep every 2.5 sec
Battery disconnected.
Continuous short beeps for
Replace battery.
every half second for 1 minute,
repeats every 5 hours
Two short beeps every 5 sec
Event Bypass State – Easy UPS has detected an internal error. Connected equipment receives utility input power through the bypass relay.
Easy UPS Display Parameters
Operational data displayed in the display panel is given in the table. Navigate using the UP/DOWN ARROW buttons.
Parameter
Units
Indicator Icons
Output voltage Output frequency Input voltage Input frequency State of battery charge Battery voltage Ambient temperature Remaining On Battery runtime Load level in percentage (Maximum of Watts or VA) Load level in kVA Total Ah capacity of connected battery
VAC Hz VAC Hz % VDC °C Minutes
%
kVA Ah
OUT, V OUT, Hz IN, V IN, Hz BAT, % BAT, V NUMBER, C BAT, Min
OUT, %
OUT, kVA BAT, Ah
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
23
Configuration
Battery type and Charger current selection 1. Locate the cover of the battery
type and charging current selector switches on the rear panel. Refer “Rear
Panel Features” on page 13 for details. 2. Remove the screws securing the
cover and remove the cover. 3. Set the type of battery through the battery
type selector switch. 4. Set the charger current through the charger current
selector switch. 5. Replace and secure the cover removed in step 2.
WARNING
RISK OF FIRE Select the correct charger current for the batteries connected to
the Easy UPS. Failure to follow this instruction could result in death or
serious injury.
Charging current SMF battery capacity Tubular battery capacity
1 A
7 Ah to 10 Ah
2 A
12 Ah to 20 Ah
4 A
26 Ah to 42 Ah
40 Ah
8 A > 65 Ah
60 Ah
Easy UPS settings
Configure Easy UPS settings using the display interface. Refer “Configure Easy
UPS parameters” on page 27 to edit the parameters.
Function
Factory Default
Output voltage
230 VAC
Audible alert (Enable)
User Selectable Options
Description
220, 230, 240 VAC
Allows the user to select output voltage while the Easy UPS is in standby mode.
(Enable) (Disable)
Easy UPS will mute audible alerts when set to disable or when the display panel buttons are pressed.
24
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Function
Factory Default
User Selectable Options
Description
Green mode / high efficiency mode
(Disable)
(Enable) (Disable)
When this mode is enabled, connected equipment receives utility input power through the bypass relay as long as input voltage is within the range of ±5% of configured output voltage and ±3 Hz of configured output frequency. Inverter is turned off during this mode. If utility power input goes out of range, inverter is turned on and the load is transferred to online mode or battery mode. The power to the connected equipment may be interrupted up to 10 milliseconds.
Battery Ah 7 Ah capacity
7 to 200 Ah
Allows the user to set the Total Ah of the batteries connected to the Easy UPS.
Minimum 0% battery capacity to restart setting
0%, 15%, 50%, 90%
Easy UPS output will not be turned on until the battery is charged to a level such that it can provide the runtime configured by this setting. If configured to 0%, Easy UPS output is turned on immediately after utility power returns.
Low battery 2 min state indication setting
2 min, 5 min, 7 min, 10 min
The Easy UPS will emit an audible alarm when the remaining run time reaches the limit set by the user when the Easy UPS is in battery mode. Audible alarm will continue in online mode till the run time of the Easy UPS reaches the set limit.
Bypass setting Lower voltage
184 VAC
161, 173, 196 VAC
Allows the user to set the upper and lower voltage settings for Bypass.
Upper voltage
276 VAC
253, 242, 265 VAC
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
25
Advanced Display Navigation
The Easy UPS display has five menu options in the main menu options. Press the
ENTER button from the Home Screen to access these menu options. Use the
UP/DOWN ARROW buttons to navigate between the menu options.
Menu option
Description
Configure the Easy UPS Use this menu option to configure the Easy UPS parameters. Press the ENTER button to see the configuration options. Refer “Configure Easy UPS parameters” on page 27 for details. Press the MUTE/ESC button to return to the Home Screen.
Show Event Log Use this menu option to see the Easy UPS event log. The Easy UPS records the last 10 events and displays the codes in this log. Press the ENTER button to see the log. Use the UP/DOWN ARROW buttons to see the logged events. The UP ARROW button navigates towards old events and the DOWN ARROW button navigates to new events. Every log entry has a numeric and textual event code. At the end of the log, the word “End” will be displayed. Press the MUTE/ESC button to return to the Home Screen.
Show Easy UPS information Use this menu option to see the Easy UPS information. Press the ENTER button to see the rating of the Easy UPS. Press the UP ARROW button to see the Easy UPS firmware version. Press the MUTE/ESC button to return to the Home Screen.
User Command to bypass Use this menu option to switch the Easy UPS to bypass
mode or bring the Easy UPS to online mode from bypass mode. Press ENTER
button:
Put: Use to switch the Easy UPS to bypass mode of operation.
NOTE: Power to the connected equipment will drop, if the mains voltage is not within the threshold limits.
Out: Bring the Easy UPS out of bypass and restore clean power to the connected equipment.
The Easy UPS will start a count down on the display while switching to Bypass mode or coming out of Bypass mode.
26
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Menu option
Description
Execute Battery Self Test Use this menu option to conduct a self test and determine the battery status. Press the ENTER button to initiate the test. If the test command is accepted, the Easy UPS will initiate a self test and will start a count down on the display. Display messages are shown at the end of the test.
Test refused. The output is off or battery is not charged or battery is disconnected.
Test not passed.
Test passed.
Test is aborted due to internal reasons.
Press the MUTE/ESC button to return to the Home Screen.
Configure Easy UPS parameters
Follow the steps to configure parameters in the Easy UPS:
1. Press the ENTER button. 2. Press the UP/DOWN ARROW buttons to navigate to
“Set”. 3. Press the ENTER button. 4. Navigate through the parameters using the
UP/DOWN ARROW buttons. 5. Press the ENTER button to edit a parameter. Icons
start flashing to indicate
the editing. 6. Press the UP/DOWN ARROW buttons to navigate between the
options
available for the selected parameter. 7. Press the ENTER button to select the
option or MUTE/ESC button to abort
the editing of current parameter. Flashing of icons stops after this. 8. Press
the UP/DOWN ARROW buttons to navigate between parameters. 9. Press the
MUTE/ESC button to exit menu navigation.
Troubleshooting
Use the table below to solve minor installation and operation problems. Refer
to the APC by Schneider Electric Web site, www.apc.com for assistance with
complex Easy UPS problems.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
27
Problem and/or Possible Cause
Solution
Easy UPS will not turn On when utility input is available
The Easy UPS is not turned on. Press the POWER button to turn on the Easy UPS.
The Easy UPS is not connected Check that the power cable from the Easy UPS to the
to utility power supply.
utility power supply is securely connected at both ends.
Input circuit breaker on the Easy Press the input thermal circuit breaker RESET button in
UPS is tripped.
the rear panel.
The Easy UPS is operating on battery, while connected to the input utility power
Input voltage and frequency are beyond specifications.
Connect the UPS to a different outlet on a different circuit. Test the utility input power to ensure the unit is receiving input power. If display is on, navigate and check the input voltage and frequency.
Easy UPS, when connected to battery, is not supplying power to the connected equipment
The Easy UPS is not turned on. If the Easy UPS has shutdown (the display is not on), follow the “Cold start the Easy UPS” on page 18 for procedure.
The battery is not connected.
Connect battery to the Easy UPS. Refer “Connect the Battery Bank to Easy UPS” on page 15 for details.
Low battery cut off. Easy UPS may have discharged the battery due to utility power outage and turned the output off due to low battery condition.
Wait for the utility power to return and charge the battery.
Easy UPS emits an audible beeping sound at long intervals
The Easy UPS is operating normally when running on battery.
The Easy UPS is operating on battery. See the status of the Easy UPS in the display panel.
Alert LED is illuminated. The Easy UPS displays an alert message and emits a constant beeping sound
The Easy UPS has detected an Refer “Alerts and Notifications” on page 29 for details. internal error.
No audible sounds from Easy UPS even when the Alert LED is illuminated
Audible alert is disabled.
Change the Easy UPS configuration to enable audible alerts.
Easy UPS is not providing expected backup time
Battery is not charged properly. Be sure that the battery is charged to its full capacity.
Charger taking more time to charge battery.
· Be sure that the correct charging current is selected using the charging
selector switch.
· Input voltage is low to charge the battery with full current.
28
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Problem and/or Possible Cause
Solution
The battery is near the end of its If the battery is near the end of its service life, consider
service life.
replacing the battery, even if the replace battery indicator
is not illuminated.
Easy UPS is not turning off
POWER OFF button not pressed Press and hold the POWER OFF button until the beep is
properly.
heard to power off the Easy UPS.
Easy UPS is in Bypass mode and the LED is not illuminated red
Easy UPS is configured to stay in Change the configuration to exit bypass mode. the bypass mode.
Easy UPS is in Bypass mode and the LED is illuminated red
Easy UPS is in bypass mode even Wait for some time for the Easy UPS to come back to after over temperature alarm is online mode. cleared.
The Easy UPS has experienced an overload condition and transferred to bypass.
Connected equipment exceeds the maximum load as defined in specifications. The alerts remain on until the overload condition is corrected. Disconnect nonessential equipment from the Easy UPS to eliminate the overload condition. The Easy UPS continues to supply power as long as it is in bypass mode and the circuit breaker does not trip. The Easy UPS will not provide battery power in the event of an utility voltage interruption.
Easy UPS detected an internal Refer “Alerts and Notifications” on page 29 for details. error and transferred to bypass.
Alerts and Notifications
Easy UPS displays a text code and a numeric code on the display when it
detects an internal error.
Alerts
Display code
Description
Solution
Easy UPS has experienced a short circuit at the output.
Easy UPS is experiencing an overload condition.
Check if there is any short circuit at the Easy UPS output. Remove the short
circuit and press POWER ON/OFF button to start the Easy UPS.
Disconnect nonessential equipment from the Easy UPS to eliminate the overload
condition. Wait for the Easy UPS to auto-recover.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
29
Display code
Description
Solution
The Easy UPS has
If the Easy UPS does not recover automatically,
detected a DC voltage
contact APC by Schneider Electric.
error. Unit will try to
auto-recover from this
condition.
Temperature of the unit is Disconnect non-essential equipment from the
rising above the set limits. Easy UPS to reduce the Easy UPS load.
Ensure that ambient temperature is within limits.
Ensure that adequate clearance is maintained.
Easy UPS has detected a Press POWER ON/OFF button to start the
charger error.
Easy UPS.
If the error is detected again contact APC by
Schneider Electric Customer Support.
Contact APC by Schneider Electric for all other alert codes.
Notifications
Display code
Description
Battery is not connected.
Solution
Connect battery to the Easy UPS. Refer “Connect the Battery Bank to Easy UPS”
on page 15 for details.
Service
If the unit requires service, do not return it to the dealer. Follow these
steps:
1. Review the Troubleshooting section of the manual to eliminate common
problems.
2. If the problem persists, contact APC by Schneider Electric Customer
Support.
a. Note the model number and serial number and the date of purchase. The model
and serial numbers are located on a label in the top panel of the unit.
b. Call APC by Schneider Electric Customer Support and a technician will
attempt to solve the problem over the phone. If this is not possible, the
technician will issue a Service Request Number.
c. If the unit is under warranty, the repairs are free.
An Authorized Service Representative will visit your location and try to
resolve the issue.
30
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
Limited Factory Warranty
Schneider Electric IT Business India Private Ltd. (SEITBIPL), warrants its
products to be free from defects in materials and workmanship for a period of
two (2) years from the date of purchase. The SEITBIPL obligation under this
warranty is limited to repairing or replacing, at its own sole option, any
such defective products or parts there of. Repair or replacement of a
defective product or part thereof does not extend the original warranty
period.
This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase. Products may be registered
online at warranty.apc.com or by mailing in the completed warranty
registration card that is included with the documentation.
SEITBIPL shall not be liable under the warranty if its testing and examination
disclose that the alleged defect in the product does not exist or was caused
by end user or any third person misuse, negligence, improper installation,
testing, operation or use of the product contrary to SEITBIPL recommendations
or specifications. Further, SEITBIPL shall not be liable for defects resulting
from: 1) unauthorized attempts to repair or modify the product, 2) incorrect
or inadequate electrical voltage or connection, 3) inappropriate on site
operation conditions, 4) Acts of God, 5) exposure to the elements, 6) theft.
In no event shall SEITBIPL have any liability under this warranty for any
product where the serial number has been altered, defaced, or removed, 7)
normal wear resulting from frequent use.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY
OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR
FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEITBIPL DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND
FITNESS FOR A PARTICULAR PURPOSE.
SEITBIPL EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY
AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEITBIPL RENDERING OF
TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
Easy UPS On-Line SRV1KUXI-IN, SRV2KUXI-IN and SRV3KUXI-IN
31
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEITBIPL’S
SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. SEITBIPL WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT
EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEITBIPL, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES
BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE
DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS,
WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEITBIPL HAS BEEN ADVISED IN ADVANCE
OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEITBIPL IS NOT LIABLE FOR
ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS
OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS
OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
To obtain service under warranty you must call customer support. Customers
with warranty claims issues may access the SEITBIPL worldwide customer support
network through the SEITBIPL Web site: www.apc.com. Select your country from
the country selection drop down menu. Open the Support tab at the top of the
web page to obtain information for customer support in your region. Refer to
the product user manual for more information on how to contact customer
support.
APC by Schneider Electric Customer Support
Internet Toll Free E-mail
http://www.apc.com/in 18001030011/18004194272 indiainfo@se.com
© 2022 APC by Schneider Electric. APC, the APC logo, and PowerChute are owned by Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their respective owners.
EN 990-91394B 12/2022