tiko K-Box A6 Three Phase Energy Meter User Manual
- June 4, 2024
- tiko
Table of Contents
Energy Solutions AG
K-Box A6
User’s Manual
01.9006, CK-01.9006-P3
User’s Manual
**Safety Warnings and Working Instructions
**
Hazard Risk
| Read the user manual before installing and operating this product!
---|---
| Installation by a person with electronical expertise and training on this
product only!
| Disconnect all power sources before carrying out any manipulation!
| Always use appropriate protection equipment!
| Danger! High voltage!
| Never touch disconnected wires! Life hazard!
| Only use for current/voltage as indicated on the device label! Doing
otherwise can cause device damage and may pose an electrical shock or fire
hazard!
| Not properly tightened screws can cause a high contact resistance, lead to
overheating, and cause a fire hazard!
| Not properly connecting the Neutral will damage the device and pose a safety
risk!
| External voltage risk! An external voltage source can be connected to the
K-Box relay terminals. Even if all the main counters are open/disconnected,
there could still be high voltage on the relay terminal clamps coming from an
auxiliary source (e.g., ripple control, UPS, generator, PV, emergency PSU).
Before any handling verify that there is no voltage source wired to the K-Box.
Warnings
- Read the installation instructions before you connect the system to its power source.
- To prevent the system from overheating, do not operate it in an area that exceeds the maximum admitted ambient temperature of 55 °C.
- This product relies on the building’s installation for short-circuit (over current) protection. Ensure that a fuse or circuit breaker no larger than 420 VAC, 65 A is used on all current-carrying conductors.
- The circuit breaker shall be in front, close to the device, and easily reachable by the operator, and it shall be marked as the disconnecting breaker for the device.
- Do not work on the system or connect or disconnect cables during periods of lightning activity.
- The device is intended for indoor use only.
- Ultimate disposal of this product should be handled according to all national laws and regulations.
- Any usage of this device in a manner that does not conform to this manual specification can impair the provided safety protection.
Safety Instructions
Read these safety instructions carefully.
- Follow common household electrical safety practices.
- Read all cautions and warnings on the equipment.
- Do not put power on the electrical panel before putting back the cover of the home distribution box. No live contact shall be accessible.
- Disconnect this equipment from the distribution box before cleaning it. Do not use liquid or sprayed detergent for cleaning. Use a moisture sheet or cloth for cleaning.
- The openings on the enclosure are for air convection and protect the equipment from overheating. Do not cover the openings.
- Do not pour any liquid into the opening. This could cause fire or electrical shock.
- Do not open the enclosure of this product and/or alter this product in any way.
- Have the equipment checked by a service professional if one of the following situations arises:
- The line is damaged.
- Liquid has entered the equipment.
- The equipment has been exposed to moisture.
- The equipment does not work properly, or you cannot get it to work according to the user’s manual.
- The equipment has been dropped or damaged.
- The equipment has obvious signs of breakage.
- Keep this equipment away from excessive or condensing humidity.
- Do not leave this equipment in an unconditioned environment. Temperatures above 55 °C will damage the equipment.
- Keep this guide for later reference.
Feedback
You can submit comments via email to
info@tiko.energy
You can also submit your comments via regular mail by writing to the following
address:
tiko Energy Solutions AG
Pflanzschulstrasse 7
CH-8004 Zürich
We appreciate your comments.
Overview
Intended Use
K-Box is a custom energy meter with a remote-controlled relay to be only used
in tiko Energy Solutions AG authorized setups.
Any installation or usage which does not conform to tiko Energy Solutions AG
setup is strictly forbidden. tiko Energy Solutions AG is not responsible for
any improper installation/usage of this device.
Features
K-Box features:
- meters instantaneous energy consumption in 3 phases in both directions (consuming and generating)
- remotely controlled relay
- status LEDs showing connection and relay status.
Package Content
Open the package and check that you have all the following items:
- Instruction manual
- K-Box
If any of the parts are incorrect, missing, or damaged, please contact the
retailer where you made your purchase. Keep the carton box, including the
original packing materials, in
case you need to return the unit for repair.
Device
IMAGE 1 shows the device from the front. IMAGE 2 shows the device from the
bottom and indicates the phases and neutral terminals.
On the bottom side is a label indicating
- The manufacturer
- The device model number (REF) and the current rating
- The hardware (HW) and firmware (FW) version
- The unique serial/MAC address as text and as barcode code (SN/MAC)
Installation
Installation by a person with electronical expertise and training on this
product only!
Do not install the device unless you have removed the main power supply (main
breaker or fuses)!
Installing the K-Box
Step 1 | Remove power from the electrical panel. |
---|---|
Step 2 | Remove the cover panel so you can access the wires. |
Step 3 | Verify that there is no tension on the wires you intend to manipulate. |
Step 4 | Ensure that there is short-circuit protection for 3 phases (breaker or |
fuse) before the K-Box is not larger than 420 V 65 A.
Step 5| Put the K-Box on the DIN rail of the home distribution box and ensure
the hook is locked properly (IMAGE 3).
Remove the protective covers from the terminals (IMAGE 4).
Step 6| Prepare the cables. Refer to Specifications on page 8 for supported
ratings and cable diameters.
Step 7| Connect the wires to the K-Box (IMAGE 6):
• From left to right, connect Phase 1, Phase 2, Phase 3, and Neutral.
• Wires for top terminals are coming from the source.
• Wires for bottom terminals are going to load.
Tighten all clamp screws with enough torque. Insufficient clamping force
can result in high contact resistance that
leads to device heating and can result in a fire hazard.
Step 8| Lift the cover of the relay terminals (IMAGE 5). Connect the relay
contacts as indicated in IMAGE 7:
• COM – Change over
• NC – Normally closed
• NO – Normally open
Danger! An external voltage source can be present on the wires to be
connected to the relay clamps!
An auxiliary source (e.g., ripple control, UPS, generator, PV, emergency PSU)
can supply voltage even if all the main
counters are open/disconnected.
Before any handling verify that there is no voltage on any wires you handle.
Step 9| Close the relay cover. Put back the protective covers for the phase
and neutral terminals (IMAGE 8). Ensure the orientation of the covers (IMAGE
9).
Step 10| Put back the cover panel of the home distribution box to cover the
electrical contacts. Be sure that no electrical
contact can be touched.
Step 11| Power on the system by enabling power in the electrical panel.
Step 12| To finalize the installation, all tiko devices must be configured
using the installation app.
Operation
Device Operation
The operation of the K-Box is subject to the control of the full system and is
operated by the Data Center through the Gateway (M-Box). No user interaction
is required.
On the front, there are two buttons, offering the following functionalities:
- “Service” – not used anymore (no function assigned)
- “Heating Powered” or “Switch”:
- Single Press – change the relay state. If the K-Box is connected to the backend, the relay might switch back as it is overwritten by the backend settings.
- Long press (10 s) – reset the device.
LED Explanation
On the front, there are two green LEDs indicating:
- “Link” – on if connected via Gateway (M-Box) to backend
- “Heating Powered” or “Switch” – relay status (on if closed)
Uninstalling
**** External voltage risk! An external voltage source can be connected to the K-Box relay terminals. Even if all the main counters are open/disconnected, there could still be high voltage on the relay terminal clamps coming from an auxiliary source (e.g., ripple control, UPS, generator, PV, emergency PSU). Before any handling verify that there is no voltage source wired to the K-Box.
Step 1 | Remove power from the electrical panel. |
---|---|
Step 2 | Remove power from any auxiliary circuit (e.g., ripple control, UPS, |
generator, PV,
emergency PSU).
Step 3| Verify that there is no tension on the K-Box clamps.
Step 4| Remove the cover panel. Unwire and remove the device.
Step 5| Put the cover panel back. Ensure that no electrical contact can be
touched.
Step 6| Power on the system.
Step 7| If the device remains the property of tiko Energy Solutions AG or its
authorized reseller, it must be returned. Otherwise, the ultimate disposal of
a device shall be handled according to national laws and regulations.
Specifications
Device Characteristics
Product Number
| 01.9006
CK-01.9006-P3
---|---
Input / Output Voltage| 3 x 230/400 VAC
Input / Output Current| max. 65 A
Input / Output Wire Specification*| 1.5 mm² – 25 mm² (AWG 4 ~ 16)
Relay Switching Voltage| 100 V – 240 V
Relay Switching Current| max. 10 A
Relay Wire Specifications| 0.14 mm² – 1.5 mm² (AWG 16 ~ 26)
Frequency| 50 Hz
The voltage of breaker before K-Box| max. 420 V (3 phases)
Current breaker before K-Box| max. 65 A
Min. Measurable Current| ± 0.1 A
Max. Measurable Current| ± 65 A
Measurement Tolerance| ± 1% @ 1 A – 65 A
User Interface| 2 push buttons, 2 LEDs (green)
Connectivity| PLC HomePlug GreenPHY
Dimensions| 106 x 92 x 70 mm
Weight| 430 g
Max. Power Consumption| Relay activated: less than 2 W
Relay deactivated: less than 1.5 W
- Devices for Australia/New Zealand, with RCM mark and Hardware Version ≤ 3, must be connected to conductors of 2.5 mm² / AWG 14 minimum.
| Operating Conditions| Storage Conditions
---|---|---
Temperature (min.)| -10 °C| -20 °C
Temperature (max.)| +55 °C| +70 °C
Relative Humidity| 10% – 85% no condensation| 5% – 95% no condensation
Maximum Altitude| 2000 m| –
Obtaining the Declaration of Conformity
Intended Use
The K-Box is a custom three-phase energy meter with a remotely controlled
switch to be only used in tiko Energy Solutions AG authorized setups.
Safety Information
tiko Energy Solutions AG
Pflanzschulstrasse 7
CH-8004 Zürich
info@tiko.energy
The product 01.9006 in the form as delivered conforms to the provisions of the following European directives: 2011/65/EU on hazardous substances, 2014/35/EU on low voltage devices, 2014/30/EU on electromagnetic compatibility, partially 2004/22/EU on measuring instruments.
- The product 01.9006, with Hardware Version ≤ 3 and RCM mark, in the form as delivered, conforms to the relevant notices of the following Australian/New Zealand acts as required by ACMA: Radiocommunications Act 1992, Telecommunications Act 1997.
A copy of the declaration of conformity can be requested by writing to the postal address or is available on http://um.tiko.energy/9006
tiko Energy Solutions AG
IM-0005-0001 Rev. 12