tiko CMB-01.1011-01-P1 Athos Bridge-Box User Manual

June 4, 2024
tiko

tiko CMB-01.1011-01-P1 Athos Bridge-Box User Manual

Safety Warnings and Working Instructions

Hazard Risk

  • Read the user manual before installing and operating this product!

  • Installation by person with electronical expertise and trained on this product only!

  • Disconnect all power sources before carrying out any manipulation!
    Safety Symbol

  • Always use appropriate protection equipment!
    Safety Symbol

  • Danger! High voltage!

  • Never touch disconnected wires! Life hazard!

  • Only use for current/voltage as indicated on the device label! Doing otherwise can cause device damage and may pose an electrical shock or fire hazard!

  • Not properly tightened screws can cause a high contact resistance, lead to  overheating, and cause a fire hazard!

Warnings

  • Read the installation instructions before you connect the system to its power source.
  • To prevent the system from overheating, do not operate it in an area that exceeds the maximum admitted ambient temperature of 55 °C.
  • This product relies on the building’s installation for short-circuit (over current) protection. Ensure that a fuse or circuit breaker no larger than 230 VAC, 10 A is used on all current-carrying conductors.
  • The circuit breaker shall be in front, close to the device, easily reachable by the operator, and it shall be marked as the disconnecting breaker for the device.
  • Do not work on the system or connect or disconnect cables during periods of lightning activity.
  • Device is intended for indoor use only.
  • Ultimate disposal of this product should be handled according to all national laws and regulations.
  • Any usage of this device in a manner that does not conform to this manual specification can impair the provided safety protection.

Safety Instructions

Read these safety instructions carefully.

  • Follow common household electrical safety practices.
  • Read all cautions and warnings on the equipment.
  • SBUS cables shall not be close to power cables. Minimum clearance is 10 mm.
  • Do not put power to the electrical panel before putting back the cover of the home distribution box. No live contact shall be accessible.
  • Disconnect this equipment from the distribution box before cleaning it. Do not use liquid or sprayed detergent for cleaning. Use moisture sheet or cloth for cleaning.
  • The openings on the enclosure are for air convection and protect the equipment from overheating. Do not cover the openings.
  • Do not pour any liquid into opening. This could cause fire or electrical shock.
  • Do not open the enclosure of this product and/or alter this product in any way.
  • Have the equipment checked by a service professional if one of the following situations arises:
    • The line is damaged.
    • Liquid has entered the equipment.
    • The equipment has been exposed to moisture.
    • The equipment does not work properly, or you cannot get it to work according to user’s manual.
    • The equipment has been dropped or damaged.
    • The equipment has obvious signs of breakage.
  • Keep this equipment away from excessive or condensing humidity.
  • Do not leave this equipment in an unconditioned environment. temperatures above 55 °C will damage the equipment.
  • Keep this guide for later reference.

Feedback

You can submit comments via email to info@tiko.energy
You can also submit your comments via regular mail by writing to the following address:
tiko Energy Solutions AG
Pflanzschulstrasse 7
CH-8004 Zürich
We appreciate your comments.

Overview

Intended Use

The Bridge is a power supply and communication interface for other tiko devices and only to be used in tiko Energy Solutions AG authorized setups.

The Bridge presents on both sides an SBUS connector (IMAGE 1) to be daisy chained with other devices of the same family.

Any installation or usage which does not conform to tiko Energy Solutions AG setup is strictly forbidden. tiko Energy Solutions AG is not responsible for any improper installation/usage of this device.

Features

Bridge features:

  • power supply unit (PSU) for SBUS devices to source ca. 10 W @ 5 VDC with short-circuit and overload protection
  • independent short-circuit / overload protection on the SBUS to keep the Bridge powered even in case of short-circuit on the SBUS
  • GreenPHY PLC bridge between SBUS devices and gateway (M-Box)
  • Status LEDs showing data link and device errors
  • Button to hard reset the device
Package Content

Open the package and check that you have all the following items:

  • Instruction manual
  • Bridge
  • 50 cm SBUS interconnection cable or SBUS inter-connector (IMAGE 2)
  • Clip A and Covers B and C (IMAGE 3)

If any of the parts are incorrect, missing, or damaged, please contact the retailer where you made your purchase. Keep the carton box, including the original packing materials, in case you need to return the unit for repair.

Device

IMAGE 4 shows the device from front and top view. It indicates the LEDs, the button, and the clamping terminals for Line In ❶, Neutral In ❷. On the left side are two labels indicating

  • The manufacturer
  • The device model number (REF) and the current rating
  • The hardware (HW) and firmware (FW) version
  • The unique serial/MAC address as text and as Aztec 2D code (SN/MAC)

Installation

Installation by person with electronical expertise and trained on this product only!

Do not install the device unless you have removed the main power supply (main breaker or fuses)!
Safety Symbol

Installing the Bridge
  • Step 1: Remove power from the electrical panel.

  • Step 2: Remove the cover panel so you can access the wires.

  • Step 3: Ensure that there is a short-circuit protection (breaker or fuse) before the Bridge no larger than 230 VAC 10 A.

  • Step 4 Put the Bridge on the DIN rail of the home distribution box and ensure the hook is locked properly (IMAGE 5).
    Connect the right SBUS of the Bridge to the left SBUS of any other device that is part of the installation. Chain as many devices to the right side of the Bridge as required for the installation.
    An SBUS is connected in one of the 2 ways:

    • Using the SBUS interconnector: Plug the SBUS connector in one of the devices and slide the Bridge along the DIN rail towards it (IMAGE 6). Use the Clip A to prevent the SBUS from being disconnected (IMAGE 7).
    • Using the SBUS cable: Connect the Bridge to the other device using the provided SBUS cable. Warning: SBUS cables shall not be close to power cables. Minimum clearance is 10 mm.
      Use Cover B and Cover C (IMAGE 3) to close the left openings of the Bridge (IMAGE 8).
  • Step 6: Connect the wires to the Bridge (IMAGE 9):

    • Connect a phase to the left terminal clamp ❶.
    • Connect a neutral to the right terminal clamp ❷.
      Tighten all clamp screws with appropriate torque. Insufficient clamping force can result in high contact resistance that leads to device heating and can result in a fire hazard.
  • Step 7: Put back the cover panel of the home distribution box to cover the electrical contacts. Be sure that no electrical contact can be touched.

  • Step 8: Power on the system by enabling power in the electrical panel.

  • Step 9: To finalize the installation, all tiko devices must be configured using the installation app.

Operation

Device Operation
The Bridge features one hardware push button:

  • A single press generates a hardware reset.
  • 10 times pressing at the speed of one press per second triggers a firmware upgrade of the device.

Any further operation of the Bridge is subject to the control of the full system and operated by the Data Center through the Gateway (M-Box). No user interaction is required.

LED Explanation
The Bridge features two LEDs: a red LED at the top, and a green LED at the bottom.

  • In normal operation:

#

| Color| Status|

Notes

---|---|---|---
Top LED| Steady Green| PLC connection ac- tive| incoming traffic in the last 60 seconds
Bottom LED| Steady Green| Device operational|
Bottom LED| Yellow| PSU failure: running in backup|
Bottom LED| Red| Device POST failure| Device Power-On Self-Test has failed. Device requires service.

  • In firmware upgrade mode:

#

| Color| Status|

Notes

---|---|---|---
Top LED| Steady Green| Device is running a firmware upgrade|
Bottom LED| Blinks  Red @ 0.5 Hz| One blink each 2 seconds.

Uninstalling

  • Step 1: Remove power from the electrical panel.
  • Step 2: Remove the cover panel. Unwire and remove the device. Keep in mind that other devices of the tiko installation need the Bridge to run.
  • Step 3: Put the cover panel back. Ensure that no electrical contact can be touched.
  • Step 4: Power on the system.
  • Step 5: If the device remains property of tiko Energy Solutions AG or its authorized reseller, it must be returned. Otherwise, the ultimate disposal of a device shall be handled according to national laws and regulations.

Specifications

Device Characteristics|
---|---
Product Number
Product Number| CMB-01.1011-01-P1
Rating| 230 VAC – 0.07 A – 17 W
Wire specification| 0.25 mm² – 4.0 mm² (AWG 12 ~ 24)
Frequency| 50 Hz
Overvoltage Category| OVC II
Voltage of breaker before the Bridge| max. 230 V
Current of breaker before the Bridge| max. 10 A
Connectivity| PLC HomePlug GreenPHY
User Interface| 1 push button + 2 bi-color LEDs
Dimensions| 94 x 66 x 38 mm
Weight| 120 g
| Operating Conditions| Storage Conditions
---|---|---
Temperature (min.)| -10 °C| -20 °C
Temperature (max.)| +55 °C| +70 °C
Relative Humidity| 10% – 85%
no condensation| 5% – 95%
no condensation
Maximum Altitude| 2000 m| –

Bridge-Box

Bridge-Box
Bridge-Box
Bridge-Box

Obtaining the Declaration of Conformity

Intended Use

The Bridge is a power supply and Power Line Communication bridge to be only used in tiko Energy Solutions AG authorized setups.

Safety Information
tiko Energy Solutions AG
Pflanzschulstrasse 7
CH-8004 Zürich
info@tiko.energy

Icons
The product CMB-01.1011-01-P1 in the form as delivered conforms to the provisions of the following European directives: 2011/65/EU on hazardous substances, 2014/35/EU on low voltage devices, 2014/30/EU on electromagnetic compatibility, 2014/53/EU on radio equipment.

Furthermore, the product CMB-01.1011-01-P1 in the form as delivered conforms to the relevant notices of the following Australian/New Zealand acts as required by ACMA: Radiocommunications Act 1992, Telecommunications Act 1997.

A copy of the declaration of conformity can be requested by writing to the postal address or is available onhttp://um.tiko.energy/1011