Uponor ETN4 Ecoflex Supra Standard Thermostat Instruction Manual
- June 11, 2024
- uponor
Table of Contents
ETN4 Eco flex Supra Standard Thermostat
Instruction Manual
Upon or Eco flex Supra Standard thermostat ETN4
Installation and operation manual
Upon or Eco flex Supra Standard thermostat ETN4
The Upon or Eco flex Supra Standard thermostat ETN4 is used to control the
constant resistant cable of the Upon or Eco flex Supra Standard pipes.
ETN4 is a universal purpose thermostat, which can be used in several
applications. In the following basic instructions are given for the use of
ETN4 in combination with Eco flex Supra Standard pipes.
1.1 Kit contents
Figure 1
Item | Description | Quantity |
---|---|---|
A | Upon or Eco flex Supra Standard thermostat ETN4 | 1 pc |
B | Lead-through M12 | 1 pc |
C | Lead-through M25 | 2 pcs |
D | Reducer M25/M12 | 1 pc |
E | Retaining nut M25 | 3 pcs |
F | External temperature sensor, 10 m | 1 pc |
G | Installation manual for the thermostat | 1 pc |
1.2 Installation instructions
Figure 2
Fix the base of the housing to a suitable place with 4 screws. The hole
distance should be 198 mm horizontally and 121 mm vertically.
1.3 Connection
Figure 2, 3 and 5
Yellow cable | Item | White cable |
---|---|---|
2 x 0,48 Ω/m – serial | A | 2 x 0,05 Ω/m – serial |
2 x 0,48 Ω/m + Cu return | B | 2 x 0,05 Ω/m + Cu return |
2 x 0,48 Ω/m – parallel +Cu return | C | 2 x 0,05 Ω/m – parallel +Cu return |
Description for figure 5
Connect the supply cable, heating cable and the sensor cable.
For detailed instructions, see the installation manual for Upon or Eco flex
Supra Standard cable set S1, or figure 5 in this document.
1.4 Start-up and use
Figure 4
Item | Description |
---|---|
A | Power switch |
B | Temperature – Down |
C | Temperature – Up |
D | Programming |
E | Supply cable |
F | Heating cable |
G | Sensor cable |
The thermostat has a big digital display for easy reading of temperature. The programmable control range of the thermostat is -19,5 … +70 °C. With Eco flex Supra Standard pipes, the recommended control range is 0 … +20 °C.
-
Use the power switch (A) to turn the thermostat OFF (position “0”) or ON (position “I”).
The relay will deactivate, when the switch is in position “0”, which will also save all settings. -
Use the three function buttons (B), (C) and (D) below the display to select parameter and set desired value.
• Select parameter with button (D)
• Set the desired value with buttons (B) [down] and (C) [up] • Whenever a button is pressed, the backlighting will come on and stay lit for 30 seconds after a button is last pressed. -
To select parameter, push button (D) for 3 seconds. The display will show SCA → Hi → 40.
The text “SCA” will be displayed first for 1 second, thereafter “Hi” and finally “40” will show on the display.
After this, the desired settings can be set with the arrow buttons.
To move to the next parameter, push button (D) again.
1.5 Parameter settings
Parameter descriptions
Parameter | Description |
---|---|
Adjust offset | If the actual temperature measured with a thermometer differs |
from the one displayed in the thermostat, the thermostat can be adjusted to
offset the difference.
Application| The application sets the thermostat function by selecting
required control type.
The different control types are described in a separate sub-section below.
Control method| Either PWM or ON/OFF control can be selected as control
method. ON/OFF is the traditional differential control (e.g. 0,3 °C) for other
tasks.
PWM is an advanced control method which calculates the most effective and
economical way to heat homes and other buildings.
Differential temperature| The differential temperature can be set when using
ON/OFF control.
The higher the differential temperature is, the lower is the number of relay
operations.
Frost protection| The lowest temperature for frost protection can be defined
when the function is activated via an external signal.
Example: The setpoint is 25 °C.
Frost protection = 8 °C means temperature setting = 8 °C.
Limit function| If the application “Lapp” is set to limit “Li”, the lowest
temperature at which heating is turned on can be defined in the limit
function.
Max. temperature| Maximum temperature is the highest temperature to which the
thermostat can be set.
Max. temperature limit| The maximum temperature limit allows the highest
permissible floor temperature to be set for wooden and other floor types, when
the control type has been set to room sensor with floor limit “AF”.
Measured floor temperature| Measured floor temperature displays the actual
floor temperature when a floor sensor is connected.
Measured room temperature| Measured room temperature displays the actual room
temperature.
Min. temperature| Minimum temperature is the lowest temperature to which the
thermostat can be set.
Min. temperature limit| The minimum temperature limit allows the lowest
permissible floor temperature to be set for tiled and other floor types, when
the control type has been set to room sensor with floor limit “AF”.
Night setback/ energy-saving
function| The night setback/energy-saving function can be used to define the
number of degrees the temperature setting shall be reduced. The function is
controlled via an external signal.
A minus sign “–” must precede the night setback setting.
Example: The setpoint is 25 °C.
Energy-saving function = –5 °C means temperature setting = 20 °C.
Energy-saving function = +3 °C means temperature setting = 28 °C.
PWM cycle time| The function allows cycle time to be set when using PWM
control.
Recommended time is at least 20 minutes.
Relay function| When the thermostat used for heating purposes, the relay
should be in the position normally open “NO” When the thermostat used for
cooling purposes, the relay should be turned to position normally closed “NC”
Scale| Choose between degrees Celsius and a numerical scale.
If the numerical scale is selected, the temperature is set on a scale from 0,0
to 10,0; where 0,0 corresponds to minimum temperature (SCA → Lo) and 10,0
corresponds to maximum temperature (SCA → Hi).
Software version| The thermostat displays the software version.
Standard| The thermostat complies with EN 50559 (VDE 0705-559) for electrical
floor heating.
This function is not applicable to other heating applications.
Temperature reading| The temperature reading defines which temperature is to
be shown on the start display: the setpoint “SP” or the actual, measured
temperature.
Application control types
Overview
| Available functions
---|---
Thermo- stat with connect ed sensor| APp → F
floor| APp → A room| APp → Li limit| APp → A F
room/ floor limit| APp → C regulator
Floor| √| | √| | √
Room| | √| | | √
Room and floor| √| √| √ *)| √| √
Without any sensor connected| | | | | √
*) No room sensor in use
Descriptions
Control type | Abbreviation | Description |
---|---|---|
Floor | F | The thermostat controls only the floor temperature; requires a |
connected floor sensor.
Room| A| The thermostat controls only the room temperature.
Limit| Li| Limit is an on/off function, in which the required limit is set in
Limit low (”Li” → ”Lo”) after selecting the “Li” option under “APp”.
Room/limit| AF| The thermostat controls the room temperature while respecting
min. and max. limits for the floor
temperature; requires a connected floor sensor.
Regulator| C| The thermostat is used as a simple regulator without any sensor
in use. The setting is defined in
percent (%).
Most important settings for Supra Standard
Parameter| Display text| Factory settings value| Supra
Standard setting value
---|---|---|---
Max. temperature| SCA → Hi → 40| 40 °C| Usually 20 °C
Min. temperature| SCA → Lo → 0| 0 °C|
Max. temperature limit| Li → Hi → 28| 28 °C| Desired max. temperature to
maintain (<20 °C recommended)
Min. temperature limit| Li → Lo → 15| 15 °C| Desired min. temperature to
maintain (>0 °C recommended)
Application| APp → F / A / Li / AF / C| F| F (control using external
temperature sensor)
Temperature hysteresis| Dif → 0,3| 0,3 °C| Desired hysteresis for temperature
control accuracy
These are the most important parameters for controlling the heating cable of
the Eco flex Supra Standard pipes.
Complete list of settings
The complete list of parameters for controlling the heating cable of the Eco
flex Supra Standard pipes.
Parameter| Display text| Factory settings value| Supra
Standard setting value
---|---|---|---
Max. temperature| SCA → Hi → 70| 70 °C (0,0/+70 °C)| 20 °C
Min. temperature| SCA → Lo → –19,5| –19,5 °C| 0 °C
| | (0/+10 °C)|
Max. temperature limit| Li → Hi → 28| 28 °C|
FLOOR 1)| | (–19,5/+70 °C + OFF)|
Min. temperature limit| Li → Lo → 15| 15 °C|
FLOOR 1)| | (–19,5/+70 °C + OFF)|
Min. temperature limit| Li → Lo → –19,5| –19,5 °C| Not in use, when App = F
Limit function 2)| | (–19,5/+70 °C + OFF)|
Frost protection| dEF → 8,0| 8,0 °C| 0 °C
| | (0/+10 °C)|
Night setback 3)| nSb → –5,0| –5 °C (–19,5/+30 °C)| 0 °C
Measured floor temperature| FLo → 24,0 (example) 4)| | Only display, no
setting
Measured room temperature| ro → 21,5 (example) 4)| | Only display, no setting
Application| APp → F / A / Li / AF / C
→ F (Floor sensor)
→ A (Room sensor)
→ Li (Limit function)
→ AF (Room sensor with floor
temperature limits)
→ C (Regulator)| F: Floor| F
Temperature hysteresis| Dif → 0,3| 0,3 °C| 0,3 °C
Scale| LCD → C| C = Celsius
(nub = numerical 0-100 %)| C
Temperature reading in start display| dF → SP| SP = Setpoint| tP
| | (tP = actual temperature)|
Adjust offset| Adj → 24,5 (example)| Actual temperature (+/–10 °C)| No action
Control method| PWM → On| ON| OFF
| | (OFF)|
PWM cycle time 5)| Cyc → 20| 20 minutes (10-60 minutes)| Not in use when PWM =
OFF
Differential temperature 6)| Dif → 0,4| 0,4 °C (0,3/10 °C)| 0,3 °C
Relay function| reel → no| no = normally open
(nc = normally closed)| No
EN 50559| Plie → 0| 0 min. (0-20 minutes)| 0
Software version| SU → x.xx| |
Note
Selecting Regulator (C) under Application will disconnect the floor and room
sensors, and the heating control will use a scale of 0-10, corresponding to
0-100 % of full
power.
- Only available if the Application setting is “AF”
- Only available if the Application setting is “Li”
- Only available with external timer
- With no or disconnected sensor, “– –” is shown on the display
- Only available when the control method PWM is in mode “ON”
- Only available when the control method PWM is in mode “OFF”
1.6 Troubleshooting
Error codes
If a fault occurs, the thermostat will display one of the following error
codes:
Error code | Fault description | Solution |
---|---|---|
E0 | Internal fault Thermostat defective | Replace the thermostat |
E2 | External floor sensor defective or short circuited (terminals 8-9) |
Replace the sensor/sensor cable
To continue to operate the system without sensor, set the control type to
“Regulator” under “Application”: APp → C regulator
E5| Internal overheating
Thermostat shuts off heating| Check the installations
Check that the heating cables are not overloaded or that ambient temperature
is excessive When the internal temperature drops, the thermostat
automatically reactivates
Factory reset
The factory reset allows the factory settings to be restored, and all personal
settings will be deleted from the thermostat.
Follow the below steps to reset the thermostat:
- Press and hold the centermost button (D) for 10 seconds
- The display is switched off and then on again
- The application is shown on the display: “APp → F”, followed by the temperature setting
1.7 Technical specifications
Description | Value |
---|---|
Nominal voltage | 230 V/400 V |
Load | Min. 230/400 W, max. 3680/6400 W |
Low voltage tests | EN 60730-1* and EN 60730-2-9** |
Operating temperature | –19,5 °C … +70 °C |
Installation space requirement | 231 x 238 x 118 mm |
Housing class | IP65 |
Temperature dependent sensor resistance | 0 °C: 34,6 kΩ |
20 °C: 14,7 kΩ
Marking| CE, VDE
*) EN 60730-1 Automatic electrical controls for household and similar use — Part 1: General requirements
**) EN 60730-2-9 Automatic electrical controls for household and similar use —
Part 2-9: Particular requirements for temperature sensing controls
Usable in all Europe
Declaration of conformity:
We hereby declare under our own responsibility that products dealt with by
these instructions are in conformity with the legislations in force below.
1.8 Legislations
The Upon or Eco flex Supra Standard thermostat ETN4 is in conformity with the
following directives of the European Parliament:
-
Low Voltage Directive 2014/35/EU
Harmonized standards applicable under Directive 2014/35/EU for Low Voltage (LVD) -
Directive 2014/30/EU (EMC)
Harmonized standards under Directive 2014/30/EU for Electromagnetic compatibility (EMC) -
RoHS Directive 2011/65/EU
Harmonized standards applicable under Directive 2011/65/EU (RoHS) for restriction of the use of hazardous substances in electrical and electronic equipment (EEE) -
WEEE Directive
Harmonized standards applicable under the WEEE Directive for waste of electrical and electronic equipment (EEE)
www.uponor.com
Upon or GmbH
Industriestraße 56,
D-97437 Hasfarm, Germany
1122086 v1_01_2022_INT
Production: Upon or/ELO
Upon or reserves the right to make changes, without prior notification,
to the specification of incorporated components in line with its policy of
continuous improvement and development.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>