telkonet Aida Wireless Thermostat User Guide
- June 11, 2024
- telkonet
Table of Contents
- UPDATES
- Chapter 1: Overview
- Chapter 2: Installation
- VOLTAGE OPTIONS-SUMMARY
- REQUIRED EQUIPMENT
- LOCATION PLANNING
- SENSITIVITY ZONES
- PLACEMENT GUIDELINES
- INSTALLATION – HIGH VOLTAGE (NON-CLASS 2)
- NORTH AMERICAN UL RATING SCHEDULE – NON-CLASS
- INSTALLATION – LOW VOLTAGE (CLASS 2)
- DRYWALL MOUNTING INSTRUCTIONS (LOW VOLTAGE)
- JBOX USING VERTICAL MUD RING INSTRUCTIONS
- STEPS COMMON TO ALL LOW VOLTAGE INSTALLATION METHODS
- NORTH AMERICAN UL RATING SCHEDULE – CLASS 2
- EUROPEAN CE RATING SCHEDULE – SELV
- Chapter 3: Add Ons
- Chapter 4: User Interface
- Chapter 5: Appendices
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
telkonet Aida Wireless Thermostat
UPDATES
Revision 4: add FCC RF Exposure statement and Canadian RF Exposure Statement
Chapter 1: Overview
INTENDED AUDIENCE
These instructions are intended for:
- l Installers who are either Telkonet certified installers or have completed a series of Telkonet micro-training courses (contact your Telkonet Project Manager for details)
- Facilities engineers who will maintain Telkonet devices
WHAT IS AIDA?
Aida thermostats are like traditional thermostats in that they are wired to
the HVAC system. They feature six relays, and the occupants interact with them
to adjust room climate.
Aida thermostats are different than traditional thermostats in that they are
“smart”. Aida thermostats feature occupancy sensors, so it is important to
install them in the location where they can best sense occupancy.
WHAT CAN THE TELKONET THERMOSTAT DO?
The Telkonet thermostat will automatically learn and adapt to the heating and
cooling patterns of each room.
For example, a room on the east side of a building will receive direct
sunlight in the morning and will either need less heating or more cooling.
However, as the day progresses, the room will need more heating or less
cooling as it moves into the shade. A Telkonet thermostat will continually
monitor the room, learn its patterns, and adjust its heating and cooling
profiles accordingly. Telkonet thermostats also learn and adapt to occupant
schedules. When a room is unoccupied, the thermostat will enter an energy-
saving mode, allowing the room to drift away from the desired set point.
During this drift period, the thermostat will operate the HVAC unit less
often, reducing energy costs. When the room becomes occupied again, the
Telkonet Recovery Time™ technology built into each thermostat will return the
room to the setpoint without the occupant noticing.
SAMPLE USE CASES
Telkonet thermostats are available in several possible configurations, to address specific requirements of multiple applications including hotels, classrooms, university housing, military residence halls, senior living facilities, multi-dwelling units, and a wide variety of other commercial and industrial spaces.
MAXIMUM NUMBER OF ASSOCIATED DEVICES
Aida can accept associations with up to 32 total Telkonet and other compatible wireless devices, such as occupancy sensors and door contacts.
HOW TO GET SUPPORT
DURING INSTALLATION
Contact your dedicated Telkonet Project Manager if you have any installation questions.
AFTER INSTALLATION
Contact the Telkonet Support Center at support@telkonet.com, 414-302-2203, or the phone number you were provided at installation, based on your support subscription plan.
FCC COMPLIANCE STATEMENT
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help. Operation with non-approved equipment is likely to result in interference to radio and TV reception. The user is cautioned that changes and modifications made to the equipment without the approval of the manufacturer could void the user’s authority to operate this equipment.
FCC RF Exposure Statement: To comply with FCC RF exposure compliance requirements, the device must be installed to provide a separation distance of at least 20 cm from all persons.
CANADIAN COMPLIANCE STATEMENT
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that
may cause undesired operation of the device.
Canadian RF Exposure Statement: This equipment complies with Canada radiation
exposure limits set forth for an uncontrolled environment. This equipment
should be installed and operated with minimum distance 20 cm from the radiator
and your body.
FCC ID
Aida: tbd
ABOUT THIS PRODUCT
This product is intended for outlet box mounting.
This product utilizes relays as the load-controlling/switching elements.
This product does not include GCFI functionality (as commonly required for
systems that control in-floor radiant electric heat).
This product has a “marked off” position but have the capacity to open only
one pole of the load supply circuit. Accordingly, this product is limited to
the control of loads having only one ungrounded supply pole (120 or 277 V ac
circuits). In the off position the ungrounded pole is opened when the
thermostat is placed in the off position.
This product is not suitable for safety or limiting applications.
This product is not suitable for plenum applications/installations.
Chapter 2: Installation
VOLTAGE OPTIONS-SUMMARY
High Voltage Installation Option
(30 V or greater)| Low Voltage Installation Option
---|---
There is only one installation option:
- JBox with Vertical Mud Ring Mount: requires adapter plate as shown in FIGURE 3.
| There are 3 options. Select based on code and desired look:
- Drywall mount: no conduit required; no JBox adapter plate required.
- JBox with Vertical Mud Ring Mount: requires adapter plate .
- JBox with Horizontal Mud Ring Mount.
REQUIRED EQUIPMENT
Required Equipment | High Voltage | Low Voltage |
---|---|---|
Anchors: EZ-Lock plus provided screws: 4 – 50 lb. (if drywall mount) | x | |
Backplate (included) | x | |
Drill | x | x |
Aida (included) | x | x |
Electrical tape | x | x |
Flathead screwdriver | x | x |
JBox (if applicable) (not included) | x | x |
Level | x | x |
Screw Terminal Block as applicable (included) | x | x |
Pen | x | |
Screwdriver-Phillips Head | x | x |
Screwdriver-precision set | x | |
Screws-four #5 ½” coarse thread (vertical JBox mount) | x | x |
Screws-two #6-32 1” (vertical or horizontal JBox mount) | x | x |
Speed nut (if applicable) | x | |
UL rated caulk | x | x |
Voltmeter | x | x |
Wire harnesses as applicable (included) | x | |
Wire nuts | x | x |
Wire stripper | x | x |
LOCATION PLANNING
The Aida features a passive infrared (PIR) occupancy sensor, so where you install it is important. If you install it in an out-of-the-way area where it cannot sense occupancy, the heat or air conditioning will be more likely to shut off or drift while the room is occupied.
NOTE: Be sure to install the Aida within view of the bed as shown below.
SENSITIVITY ZONES
Mounting Con siderations | Best Practices |
---|---|
Distance to Occupant | If the occupants will likely be stationary (e.g., |
sleeping in bed)… | position within 0-9 feet of their expected location. |
If the occupants will move occasionally (e.g., working at a desk)… | position |
within 18 feet of their expected location.
If the occupants will move regularly (e.g., walking down a hall) …| position
within 25 feet of their expected location.
The thermostat has a 140° wide horizontal viewing angle.
If no door contacts or remote occupancy sensors are used in a residence, then
the thermostat should either be located with 9 feet of the bed with an
unobstructed view or have delays adjusted with “night locking” to pre vent
setback during the evening hours.
PLACEMENT GUIDELINES
Placement Guidelines
Point toward main sleeping area if possible (max 9′ from bed)…
…otherwise, point to center of room
Mount ON wall, not IN wall
Vents in backplate require proper air flow
Standard height is 60″ from finished floor; ADA height is above 15″ and below
48″
Mount on an interior wall if possible
Avoid spinning fan blades
Avoid direct sunlight
Avoid heat registers
Avoid heat and cold sources in walls (e.g. exterior walls with poor
circulation, walls with pipes circulating hot water, walls near radiators,
etc.)
INSTALLATION – HIGH VOLTAGE (NON-CLASS 2)
CAUTION!
- High voltage installation should only be performed by a qualified heating & air conditioning contractor or licensed electrician.
- Failure to understand and follow all instructions carefully before installing or operating this device could cause personal injury and/or property damage.
- All wiring must conform to local and national electrical ordinances and codes.
- Prevent electrical shock, personal injury, and equipment damage: prior to installation or service, disconnect system’s electric power at main fuse or circuit breaker box.
- Ensure the JBox (not provided by Telkonet) has been installed with a vertical single gang mud ring.
- Turn off power at the Aida or mounting location using a disconnect switch or breaker lockout/tag out on appropriate breaker panel.
- Test that power is off by using a voltmeter.
- Strip the LINE wire back 0.25 inches.
- Cap the LINE wire with a wire nut or electrical tape.
- Cut the COMMON wire so the copper is flush with the insulation.
- Strip all wires except for COMMON back 0.25 inches.
- Remove the safety screw from the top of the thermostat using the Phillips head screwdriver
- Separate the backplate from the thermostat: use a flathead screwdriver to GENTLY press the tab next to the screw hole to allow the thermostat to pop open. WARNING: Using too much force can break the tab.
- Place thermostat backplate against the JBox adapter plate. The adapter plate and backplate holes should align if both are correctly oriented.
- Connect wires and harnesses as per the pinout tables in the Tables section.
- Mount the Aida backplate on top of the JBox adapter plate, using four #5 ½” coarse thread screws (or other appropriate mounting screws).
- Feed wire harnesses through the applicable holes in the backplate.
- Connect the harnesses to the Aida.
REMINDER: Wiring to the screw terminal block must exit the enclosure at Opening A of the backplate. Wiring to all other connectors must exit the enclosure at Opening B of the backplate.
Class 2 and Non-Class 2 wiring must not be mixed within a junction box or conduit run.
FIGURE 2-1: Backplate Openings A and B, Separate High, Low Voltage Wire
NOTE: For variable output connections: see See Proportional Valve Control; Analog Output on page 20
- Line up the hinges on the thermostat to the notches on the backplate.
- Press the top of the thermostat tightly against the backplate.
- Slowly lower the bottom side toward the wall. Use care not to force the faceplate closed. If you encounter resistance, check to make sure no wires are pinched between components.
- Return the electrical circuit to operation. Remove all lockouts or tags from the circuit breaker and enable any disconnects.
- Verify the thermostat display is active.
- Test all components to make sure that you can engage both the heat and cool, and all supported fan settings (high, low, etc.). Wiring is complete.
- Once the thermostat has been snapped onto the back plate, use a Phillips head screwdriver to insert the safety screw.
NORTH AMERICAN UL RATING SCHEDULE – NON-CLASS
Inputs
J1 Input Table
J1
Pin| Signal| Type
1| Dry Contact #1| Input
2| Dry Contact #2| Input
3| RS485 #1P (VDA)| UART
4| RS485 #1N (VDA)| UART
5| RS485 #2 P (General)| UART
6| RS485 #2 N (General)| UART
7| Analog Output #1| Output (0-10V)
8| Analog Output #2| Output (0-10V)
9| 3.3V Output| Output
10| Ground|
J2 Input Table
J2
Pin| Signal| Type
1| Dry Contact #3| Input
2| Dry Contact #4| Input
3| NTC – Probe #1| Input
4| NTC – Probe #2| Input
5| NTC Probe Ground (shared)| Input
6| CT Input A1| Input
7| CT Input A2| Input
8| CT Input B1| Input
9| CT Input B2| Input
10| Ground|
Screw Terminal Block Table
Screw Terminal Block (Wire Gauge 12-28)
Pin| Signal| Type
1| (C) – Power In – Common| Input
2| (Aux) – Auxillary| Output
3| (W1) – Heat| Output
4| (R) – Power In| Input
5| (Y1) – Cool| Output
6| (G)- Fan| Output
7| (O) (G2) – Changeover / Med Fan| Output
8| Switched Power 2 (G / O / W2)| Input
9| (W2) (Y2) (G2)(G3) – Multi-speed| Output
Other Inputs Table
Other Inputs
J5| Console Port
J9| External module for Salto/Saflok
Outputs
Output Table
Position Relay | Terminal | Ratings |
---|---|---|
Current/Power | Voltage | Load Type |
Design
RLY1, RLY2, RLY3| RLY1: STB* (R) and STB (AUX) RLY2: STB (W1/Y1) and STB (W1)
RLY3: STB (W1/Y1) and STB (Y1) See note 1| 5A| 125/250/277 V ac| General Use|
Operating 1.C
RLY5,
RYL7
| RLY5: STB (G/O/W2) and STB (G) See Note 3 RLY7: STB (G/O/W2) and STB (O)
See Note 3
See Note 1| 10A| 125 V ac| General Use| Operating
1.C
| 8A| 277 V ac| General Use|
| 1/10HP| 125 V ac| Motor|
| | 1/6HP| 250 V ac & 277 V ac| Motor|
RLY8| STB (G/O/W2) and STB (W2) See
Note 3 See Note 1| 11A| 277 V ac| Resistive (including Fixed Electric Space
Heating) See Note 2| Operating
1.A See Note 2
| | 1HP| 250 V ac| Motor|
| | 1HP| 277 V ac| Motor|
| | 1/2 HP| 125 V ac| Motor|
*STB: Screw Terminal Block
Note 1: STB (R), STB (W1/Y1), and STB (G/O/W2) – must be connected to the
same pole of the same supply circuit. Relay contacts must be connected in a
same polarity fashion.
Note 2: Relay RLY8 is the only output device rated for the control of
fixed electric space heating equipment. This relay will de-energize when the
On/Off switch is adjusted to the “OFF” position. RLY8 only interrupts one pole
of the supply circuit. Accordingly, the thermostat/relay is restricted to
controlling fixed electric space heating loads with a single ungrounded
conductor – such as loads connected to a 120 or 277 V ac circuit.
Note 3: The total connected load of Relays 5, 7, and 8 should not exceed
16 Amps (through common terminal J3-9STB).
Note 4: Wiring to STB must exit the enclosure at Opening A of the
backplate. Wiring to all other connectors must exit the enclosure at Opening B
of the backplate. Class 2 and Non-Class 2 wiring must not be mixed within a
junction box or conduit run.
INSTALLATION – LOW VOLTAGE (CLASS 2)
Always ensure power has been turned off before starting installation.
- Turn off power at the Aida mounting location using a disconnect switch or breaker lockout/tag out on appropriate breaker panel.
- Test that power is off by using a voltmeter.
- Remove the safety screw from the left side of the thermostat using the hex wrench.
- Separate the back plate from the thermostat: Use a flathead screwdriver to GENTLY press the tab next to the screw hole to allow the thermostat to pop open. WARNING: Using too much force can break the tab.
- For drywall mounting instructions, see below. For JBox vertical installation instructions: See JBox Using Vertical Mud Ring Instructions.
DRYWALL MOUNTING INSTRUCTIONS (LOW VOLTAGE)
NOTE: Requires four 50 lb. EZ-Lock anchors and screws
-
Strip the LINE wire back 0.25 inches.
-
Cap the LINE wire with a wire nut or electrical tape.
-
Cut the COMMON wire so the copper is flush with the insulation.
-
Strip all wires except for COMMON back 0.25 inches.
-
Verify the wiring now looks similar to this:
FIGURE 2-1: Drywall Mount Wiring -
Ensure the appropriate wires are jumped between R and SW2 (assuming they are controlling all fan and modes from the same voltage as powering the thermostat). If installing on a heat pump, ensure that Y1 and W1 are jumped together.
-
Connect wires and harnesses as per the tables.
-
Verify each wire is secure by gently tugging on it.
-
Hold backplate against wall at appropriate height. Using a pen, level-mark your holes.
-
Use appropriate drill for anchor and insert anchors into holes.
-
Screw backplate to the wall and into the anchors. Re-check that it is still level.
-
Screw the wires to the screw terminal block.
-
Next: See Steps Common to all Low Voltage Installation Methods.
JBOX USING VERTICAL MUD RING INSTRUCTIONS
NOTE: Requires Telkonet JBox Adapter Plate and two #6-32 1” screws.
-
Strip the LINE wire back 0.25 inches.
-
Cap the LINE wire with a wire nut or electrical tape.
-
Cut the COMMON wire so the copper is flush with the insulation.
-
Strip all wires except for COMMON back 0.25 inches.
-
Determine which end of the adapter should be situated on top, and which end should be situated on the bottom.
-
Mount the Aida mounting plate to the mud ring with two #6-32 1” screws.
-
Mount Aida backplate on top of JBox adapter plate, using four #5 ½” coarse thread screws.
-
Screw down each wire to the matching screw terminal on each block. (If controlling proportional valve or ECM fan, any unused wires must be capped according to NEC standards.)
NOTE: For variable output connections: See Analog Outputs on page 21. -
Connect all other wires and harnesses.
-
Mount the Aida backplate on top of JBox adapter plate, using four #5 ½” coarse thread screws.
-
Feed wire harnesses through the applicable holes in the backplate. High and low voltage wires must be fed through separate holes.
-
Connect the harnesses to the Aida.
-
Ensure backplate has appropriate jumpers between R, SW1 and SW2. If installing on a head pump, ensure there is a jumper between Y1 and W1.
STEPS COMMON TO ALL LOW VOLTAGE INSTALLATION METHODS
- Hook the thermostat to the hinges on the top of the backplate.
- Line up the hinges on the thermostat to the notches on the backplate. Press the top of the thermostat tightly against the back plate.
- Slowly bring the top down as shown. Use care not to force the faceplate closed. If you encounter resistance, make sure no wires are pinched between components and that no pins are bent.
- Once the thermostat has been snapped onto the back plate, use a Phillips head screw driver to insert the safety screw.
- Remove all lockouts or tags from the circuit breaker.
- Return the electrical circuit to operation.
- Test all components to make sure that you can engage both the heat and air conditioning, and all supported fan settings (high, low, etc.). Wiring is complete.
NORTH AMERICAN UL RATING SCHEDULE – CLASS 2
See North American UL Rating Schedule – Non-Class.
EUROPEAN CE RATING SCHEDULE – SELV
tbd
Chapter 3: Add Ons
ABOUT WIRING THE AIDA
The Aida interconnects with the existing HVAC system via standard wiring conventions, using 24-277 V ac OR 24 V dc voltage supplied by the HVAC system itself.
NOTE: The Aida allows for three different control voltages.
Telkonet provides bare wire leads on all connectors. It is up to the installer to connect these leads using an appropriate method described herein. Wiring conventions follow industry standards; however, it is important to note that the relay configuration is dynamic and can be modified at the factory or in the field. It is important to always follow site specific wire diagrams.
NTC PROBE
All Aida models have two inputs. Temp probes can be used for multiple purposes:
- HVAC Discharge Air temp
- HVAC Return Air temp
- Supply Water Temp
- AquaStat Mode (switches thermostat’s Heat/Cool)
For temperature probe if not using Telkonet provided external temperature probe, a probe with a Beta R0 must match. Alternatively, a probe can be provided to Telkonet for lab calibration. Required specifications:
US Sensor model USP10972 or equivalent, per the following:
- Resistance at 25 degrees C = 10 000 ohms +/- 1%
- Resistance/Temperature curve = “J”
- Beta ( 0 to 50 degrees C ) = 3892 degrees K nominal
Other models may be compatible; provide model number and specifications.
CT INPUTS
All Models have 2 inputs. The CT inputs are commonly used for
monitoring/alerting on fan motors, compressors or other equipment with
excessive load or for determining a failure. The CT Inputs must be used with a
compatible CT and sized appropriately for the load they will be connected to.
Current Transformer (CT) approved models from Sentran Corp.:
Rated loads are 100, 50, 30, 20 and 10 A respectively.
BCF-100A: 0.025A
LCF-50A: 0.025A
LCF-30A:0.025A
LCF-20A:0.025A
LCF-10A: 0.01A
Preferred operating range is between 10 and 80% of rated load.
Other models may be compatible: provide model number and specifications.
If not sized correctly the CT may damage the thermostat.
Chapter 4: User Interface
Chapter 5: Appendices
PROPORTIONAL VALVE CONTROL; ANALOG OUTPUT
PROPORTIONAL VALVE CONTROL
ANALOG OUTPUTS
(Standard on Aida and Aida Controller)
The Analog outputs can be used to control multiple functions. The desired function must be specified at the time of programming.
- Fan Coils Variable Valve Control (Both Heat & Cool)
- ECM Fan motor variable control between speeds. (0-10VDC)
JBOX MOUNTING OPTIONS
(JBox not provided by Telkonet.)
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>