Danfoss MBC 5000 Pressure Switch Installation Guide

June 9, 2024
Danfoss

MBC 5000 Pressure Switch
Installation Guide

Electrical connection

Danfoss MBC 5000 Pressure Switch -

Danfoss: 93Z19.11

  1. Input
  2. Normally closed (NC)
  3. Normally open (NO)
    ETS-Lindgren 8000-040 RF Power Amplifier - icon 6 Connected to enclosure of pressure control

Attention: Use only the accompanying plug, also when replacing.
Contact load
6 A, 120/250 V AC
1/4 hp (2.9 FLA/17.4 LRA), 120/250 V AC
1.16 A steady state PD, 120/250 V AC
Caution: Disconnect power supply before wiring conmen citronade made to avoid possible electrical shock or damage to equipment. All wiring should conform to the National Electrical Code and local regulations.

Adjustment

Danfoss MBC 5000 Pressure Switch- Fig

Machinal differential. one full turn 360° of the MBC setting-screw is approx. equal to 7% of the full setting rang

Operation temperature| Piston version: -40 – 140 °F
Diaphragm version: 14 – 140 °F
---|---
Maximum media temperature| 185 °F

Danfoss MBC 5000 Pressure Switch- Fig 1

Mounting and pressure connection

Note