MBC 5000 Pressure Switch
Installation Guide
Electrical connection
Danfoss: 93Z19.11
- Input
- Normally closed (NC)
- Normally open (NO)
Connected to enclosure of pressure control
Attention: Use only the accompanying plug, also when replacing.
Contact load
6 A, 120/250 V AC
1/4 hp (2.9 FLA/17.4 LRA), 120/250 V AC
1.16 A steady state PD, 120/250 V AC
Caution: Disconnect power supply before wiring conmen citronade made to
avoid possible electrical shock or damage to equipment. All wiring should
conform to the National Electrical Code and local regulations.
Adjustment
Machinal differential. one full turn 360° of the MBC setting-screw is approx. equal to 7% of the full setting rang
Operation temperature| Piston version: -40 – 140 °F
Diaphragm version: 14 – 140 °F
---|---
Maximum media temperature| 185 °F
Mounting and pressure connection