SIEMENS 09175 Double Break Enclosed Safety Switch Owner’s Manual
- June 9, 2024
- SIEMENS
Table of Contents
09175 Double Break Enclosed Safety Switch
Safety Switches
Guide Form Specifications
Product Overview
Application
Short Circuit Withstand Ratings
General Duty
General Duty Switches are intended for applications where reliable performance
and continuity of service are needed, but where duty requirements are not
severe and usual service conditions prevail. (These switches are intended for
use primarily with supply circuits rated 240V AC or less where the available
fault current is less than 100,000A when used with Class R or T fuses or
10,000A max. when used with Class H fuses.)
Suitable for use on systems capable of delivering not more than 100,000 RMS symmetrical amperes of fault current as follows:
Sw. Rating 30-600A 30-600A 30-600A 100-600A
AIC Rating 10,000 10,000 100,000 100,000
Protective Devicea Circuit Breaker Class H Fuse Class R Fuse Class J or T Fuse
Heavy Duty
Double Throw
Heavy Duty Switches are intended for use in applications where:
1. Rugged construction, reliable performance, continuity of service and ease
of maintenance are emphasized, or
2. Available fault currents higher than 10,000A are likely to be encountered,
such as in manufacturing plants, mass production industries, and commercial,
institution-al and other large buildings served by network systems or
transformers of higher capacities.
3. System voltage is 600V AC or DC Max.
4. A Type 12 or 4 / 4X enclosure is required.
Double throw switches are intended to transfer loads from one power source to another. All 2 & 3 pole double throw switches are suitable for use as service equipment. All are UL Listed. Switches are rated for use on systems with an available fault current of up to 10,000 AIC when protected with Class H fuses or either 100,000 or 200,000 AIC when protected with Class R, J or Class T fuses. They can also be used to connect a single source of power to either of two loads, In this application it is necessary to field modify fusible switches so that the fuses are on the load side of the switching mechanism.
Suitable for use on systems capable of delivering not more than 200,000 RMS symmetrical amperes of fault current as follows:
Sw. Rating & Tpye All Heavy Duty & DT 30-600A HD & DT 60A Compact HD GD & 4P DT 30-600A HD 30-600A DTF & DTNF DTb 800 & 1200A HD & DTb
AIC Rating 10,000 10,000 100,000 100,000 200,000 200,000 200,000
Protective Devicea Circuit Breaker Class H Fuse Class R, J or T Fuse Class R, J or T Fuse Class R, J or T Fuse Class R, J or T Fuse Class L or T Fuse
Fuses
Fusible switches will accept the following UL class fuses:
30 “LF” – 30A max plug Fuses 30-600A “GF” Class H & K, Class R with kit
100-600A “GF” Class J-move base 100-200 “GF” Class T with kit 400-600A “GF”
Class T-move bases
Fusible switches will accept the following UL class fuses:
30-600A “HF” Class H & K, Class R with kit 30-400A, 600V “HF” Class J-move
base 100-600A, 240V “HF” Class J-move base 100-200A “HF” Class T with kit
400-600A “HF” Class T-move bases 800-1200A “HF” Class L, Class T with kitc
Fusible switches will accept the following UL class fuses:
30-200A “DT” & “F” Class H & K, Class R with kit 30 & 60A 600V “DT” Class
J-move base 100-200A “DT” Class J-move base, Class T with kit 400-600A “DT”
Class J-standard, Class T-move bases 400A 240v “F” Class H-standard 400A, 600V
& 600A “F” Class T-Standard
Cover Interlocks
Voidable cover interlocks on switches prevent the switch door from being opened when in the “ON” position. No cover interlock on 30-60A GD or on plug fuse type switches.
Voidable dual cover interlocks standard on all heavy duty switches. Prevents cover from being opened when switch is in the “ON” position and prevents switch from being turned “ON” when door is opened.
Dual cover interlocks standard on all double throw switches. Prevents cover from being opened when switch is in the “ON” position and prevents switch from being turned “ON” when door is opened.
Underwriters’ Listed by UL under file #E4776 as enclosed switches and also suitable for use as service equipment (where applicable). Laboratories, Inc. UL98 Enclosed and Deadfront Switches.
NEMA Specifications
Meet NEMA standard KS-1-2001 for type GD switches.
Meet NEMA standard KS-1-2001 for type HD switches.
Meet NEMA standard KS-1-2001 type GD for “DTG” & type HD for “DT”, “F” & “NF” switches.
Seismic
100-600A GD & all HD switches and “DT” type double throw switches have been tested and comply with the 2010 California Building Code (CBC)
Qualifications and with the 2009 International Building Code (IBC) – Compliance Level SDS = 1.85 g
Groundable Neutral
(All neutrals are
bondable for service
entrance use.)
Fusible switches have groundable neutral blocks factory installed. Non-fusible switches accept field addable neutrals.
All switches (both Fusible and Non-Fusible) are either supplied with factory installed neutrals or accept field addable neutrals.
All except 4 pole switches will accept field addable neutrals except that “DTG” 100 & 200A switches are also available with factory installed neutrals.
Padlocks
Padlockable cover latch. OFF padlock provisions on handle.
Padlockable cover latch and multiple OFF pad- Padlockable cover latch and multiple OFF pad-
lock provisions on handle.
lock provisions on handle.
HP & Load
All General Duty, Heavy Duty and Double Throw Switches are both load break and horsepower rated.
Break Ratings
a The protective device can either be a fuse installed in a fusible switch or an upstream fuse or circuit breaker protecting a non-fusible switch. The ampere rating of the
upstream protective device must not exceed the switch ampere rating. b All 4 pole and fusible double switches with catalog numbers starting with “F” are rated 100,000 AIC max.
c Class T kit available for 240V max. applications on 1200A switches.
Siemens Industry Inc., Industrial Control Catalog 18/3
18 SWITCHES
SWITCHES 18
Safety Switches
Feature Comparison
Product Overview
General Duty
b b b b b
b b b
b b
b be b
bf b
b
bg
b bd
Heavy Duty
b b b b b b b
b
b b b
b b b b b b
b
b
b
b
b
b b b
bag b b b bc b b
Double Throw
b b b b b
b
b
b b b
b b b b b b
b
b
b
b
b
b b
bag ba b b
b
Features / Ratings
30 thru 600 Amps 800 and 1200 Amps 240 Volt AC 600 Volt AC 250 Volt DC 600
Volt DC Double-break visible blade design (30-200A) Quick-make, quick-break
switching action (excludes 30A GD) Handle design for hook stick operation
Padlockable cover latch Padlockable handle Single voidable cover interlock
(excludes 30-60A GD) Dual voidable cover interlock Type 1 enclosure Type 3R
enclosure Type 12 enclosure Type 4 / 4X enclosures Generous wiring gutters
that meet UL and NEC wire-bending space requirements Lugs suitable for copper
or aluminum at 60° or 75°C CU/AL wire lugs that meet UL 486B requirements
Suitable for field-convertible compression connectors All plated copper
current carrying parts (except lugs) Spring reinforced Fuse Clips (except
30-60A GD)b Clear pivoting line terminal shield Replacement parts (except
30-60A GD) 200% neutral available for purchase separately Provisions for UL
Class T, R and H Fuses Provisions for UL Class J and L Fuses Metal nameplate
Aux. switch kits (excludes 30-60A GD) Type 4X with stainless steel interior
parts Rolled flange enclosure design (30-200A) Isolated ground kits
a 400, 600V & 600A fusible, double-throw switches accept only Class J or T
fuses. Only 800 & 1200A HD switches will accept Class L fuses.
b 30-60A general duty switches have fuse clips constructed of spring type
copper.
c 30-200A Type VBII in stainless steel enclosures. d 100-200A. e 60A only suitable for Cu at 75°.
18/4 Siemens Industry Inc., Industrial Control Catalog
on
in operation
off
Double Break Switching Action
Like the time-proven Vacu-Break Design, the Siemens VBII double break
switching action breaks the arc in two places in 30-600A ratings. This reduces
heat generation and increases switching speed by doubling the breaking
distance. The result is enhanced performance and increased longevity. We also
provide the most visible blade design available today. Unlike conventional
knife blade switches, the blades are self-aligning to ensure positive contact.
In addition, they have no wear and friction point since the “electrical hinge”
has been eliminated. The result is a very fast, positive and reliable
switching action for even the most severe applications.
f 200A general duty switches have aluminum neutral assemblies.
g 100-600A GD & DT and 100-1200A HD switches will accept Class T fuses.
Safety Switches
General Duty and Heavy Duty
Product Overview
Enclosure Types
hA Type 1 enclosures are intended for indoor use primarily to provide
protection against contact with the enclosed equipment in locations where
unusual service conditions do not exist.
hB Type 3R enclosures are intended for outdoor use primarily to provide a
degree of protection against falling rain and sleet and must remain undamaged
by the formation of ice on the enclosure. They are not intended to provide
protection against conditions such as dust, internal condensation, or internal
icing.
hC Type 4, 4X enclosures are intended for indoor or outdoor use primarily to
provide a degree of protection against windblown dust, rain, splashing water
and hose-directed water. They are not intended to provide protection against
conditions such as internal condensation or internal icing. Also meets 4X
definition by providing a high degree of protection against corrosion. Siemens
30-200A stainless steel 4X switches are supplied stainless interior parts and
hardware as standard.
hD Type 4 enclosures are intended for indoor or outdoor use primarily to
provide a degree of protection against windblown dust, rain, splashing water
and hose-directed water. They are not intended to provide protection against
conditions such as internal condensation or internal icing.
hE Type 12a enclosures are intended for indoor use primarily to provide a
degree of protection against dust, falling dirt and dripping water. They are
not intended to provide protection against conditions such as internal
condensation.
Type 7/9 enclosures for use in hazardous locations. Use with molded case
switches listed in Section 7.
Load Break Ratings
All Siemens safety switches are load break rated. The load break rating is
assigned by UL after the switching unit has successfully performed the
following tests:
Switch Ampere Rating 30100
200 400 600 800 1200
Number of ON/OFF
Operations per Minute
6
5
4
3
2
1
Number of Operations
With Without Current Current Total
6000
4000
10000
6000
2000
8000
1000
5000
6000
1000
4000
5000
500
3000
3500
500
2000
2500
Horsepower Ratings
All Siemens safety switches, where appropriate, are horsepower rated. Ratings
are approved by UL only after the switching unit has undergone testing to
determine its acceptability which includes repeated interruption of the locked
rotor current of the motor for which it is to be rated as follows:
Max HP Rating
100
500
Number of ON/OFF Operations per minute
6
1
Number of Cycles of Operation
50
10
h A
hB
hC hD
h E
Non- Fusible Safety Switch AIC Ratings When Protected by a Circuit Breakerbc
Breaker Frame
Non-Fused Switch
UL Listed Short Circuit Current Rating
NEG, NGB, ED4 NEB, NEG, NGG, NGB, ED4 NEB, NEG, NGG, NGB, ED4 ED6 FD6-A, JD6-A JD6-A, LD6-A JD6-A, LD6-A LD6-A LD6-A
30 DT (240V) 100A GD & DT (240V)
18 kA Thru 240 VAC 18 kA Thru 240 VAC
30-100A HD & DT (600V) 18 kA Thru 480 VAC
30-100A HD & DT (600V) 200A HD & DT (600V) 400A GD & DT (240V) 400A HD & DT (600V) 600A GD & DT (240V) 600A HD & DT (600V)
18 kA Thru 600 VAC 18 KA Thru 600 VAC 18 kA Thru 240 VAC 18 kA Thru 600 VAC 25kA Thru 240 VAC 25kA Thru 600 VAC
NNG
1200A HD & DT (600V) 25 kA Thru 600 VAC
a VBII Type 12 switches are also rated 3R & 3S for outdoor use. Type 3R is
defined in B above. 3S rated enclosures provide a degree of protection against
windblown dust and allow operation when the enclosure is ice laden.
b All switches above are rated at 10 KA when protected by any UL Listed CB c
Circuit breaker trip rating must not exceed switch ampere rating
Siemens Industry Inc., Industrial Control Catalog 18/5
18 SWITCHES
Safety Switches
Type VBII Safety Switch Catalog Numbering System
Product Overview
H F 3 6 4 N R CU A
Switch Type
L = General Duty Plug Fused LNF222RA (no hub provision)
G = Gen. Duty H = Heavy Duty DT = Double Throw DTG = General Duty DT
Fused or Non-Fused
F = Fused NF = Non-Fused
Number of Poles
1= 1 2= 2 3= 3
4= 4 6= 6
Voltage
1 = 120V or 120/240V 2 = 240V 6 = 600V
Amperes
1 = 30A 2 = 60A 3 = 100A 4 = 200A
5 = 400A 6 = 600A 7 = 800A 8 = 1200A
Series Type
A = 30A, 60A, 400A, 600A Omit = 30A-200A, 800A-1200A
Special Applications With:
CH = Crouse-Hinds Receptacle
CJ = Factory J Fuse Spacings
CR = Class R Clips Installed
CU = Factory-Installed Copper Lugs
G = Factory-Installed Ground Bar
H = Height or Size Reduced
L
= Oversized Enclosure
PN = Pyle-National Receptacle
PV = Photovoltaic rated
PVPG = Photovoltaic rated, Positive
Ground
W = Viewing Window
Enclosure Type
Omit = Type 1, Indoor R = Type 3R, Outdoor S = Type 4 / 4X, Stainless Steel SS
= Type 4 / 4X, 316 Grade
Stainless Steel X = Type 4 / 4X, Non-Metallic J = Type 12, Industrial XL =
Type 4/4X Non-Metallic
Less Line & Load Lugs
With or Without Neutral
Omit = Less Neutral N = With Neutral
SWITCHES 18
Type VBII Accessories Catalog Numbering System
Switch Type
H = Heavy Duty G = General Dutyc
HR 6 4 A
Series Type
A = 400A, 600A Omit = 30A-200A, 800A-1200A
Accessory Type
A1 = Auxiliary Switch 1/NO and 1/NC A2 = Auxiliary Switch 2/NO and 2/NC A3 =
Auxiliary Switch Low Current CL = Compression Lug Barrier / Mounting Kit CU =
Copper Lugc G = Ground Lug Kit G2 = Insulated Ground Lug Kit J = Class J Fuse
Kitb LC = Copper Lug Kitc N = Neutral N2 = 200% Neutralc NCM = Field
Replacement Lug Kitb P = Fuse Puller Kit R = Class R – Fuse Clip Kit T = Class
T – Fuse Kit
Amperes
1 = 30A 2 = 60A 12 = 30/60A 3 = 100A 23 = 60/100A 123 = 30/60/100A
1234 = 30/60/100/200A 4 = 200A 5 = 400A 56 = 400/600A 5678 = 400/600/800/1200A 6 = 600A 78 = 800/1200A
Maximum Voltage
2 = 240V Maxa 6 = 600V Max
Note: Catalog numbering systems above do not apply to 4-pole & Type “F” & “FR” double throw switches & accessories.
a For 400A, 600A use 680V max accessories except for T Fuse Kit.
b Only offered for 400A, 600A.
18/6 Siemens Industry Inc., Industrial Control Catalog
c For 30A-200A, 800A-1200A.
Safety Switches
Plug Fuse and 60A Special Application Type
Selection
Features
b Compact size b Horsepower rated b Indoor and outdoor enclosures b Quick
make-quick break mechanism b Visible “ON”-“OFF” indications b Padlock-off
handle feature b Door padlock provision b Bondable neutral (where indicated) b
Lugs suitable for copper or aluminum wire b UL Listed b Fuses — not included b
Switches accept Edison base plug
fuses
b Hubs — see page 18/23 b Lugs — see page 18/23
Dimensions (inches)
Type
Height Width
1
81/4
51/2
3R
81/4
53/8
Depth
3 31/8
Wire Range Table
Switch Type
Wire Range
120/240 Volt Fusible 30 Amp
Cu/Al #14 to #8 AWGd
240 Volt Non-Fusible 60 Amp
Cu #14 to #6 AWG
Ampere Rating
Indoor — Type 1
Catalog Number
Ship. Wt. (lbs.) Pkg. of 10
Outdoor — Type 3R
Catalog Number
120/240 Volt Fusible
1-Pole and Solid Neutralb
30
LF111N
35
2-Pole and No Neutral
30
Use 2-Pole and Solid Neutral
2-Pole and Solid Neutralb
30
LF211N
35
LF111NR LF211NR
240 Volt Non-Fusible
2-Pole Special Application Switch
30
—
60
—
60
—
1 or 2-Pole — No Fuse
—
LNF221RLAc
—
LNF222R Ac
—
LNF222RLe
Ship Wt. (lbs.) Pkg. of 10
Horsepower Ratings a
1-Phase, 2-Wire
Standard
Maximum
120 Volt — 1-Phase, 2-Wire
35
1/2
2
120/240 Volt — 1-Phase, 2-Wire
120/240 Volt — 1-Phase, 3-Wire
35
11/2
3
240 Volt — 1-Phase, 2-Wire
30
—
3
30
—
10
40
3
10
18 SWITCHES
For inches / millimeters conversion, multiply inches by 25.4.
a Dual horsepower ratings: Std. — applies when non-time delay plug fuses are
installed. Max — applies when time-delay plug fuses are installed.
b Has service entrance label. UL Listed as “Enclosed Switches” (suitable for use as service equipment where indicated) under File #E4776. (NEMA) — Type G.D. Federal Spec. — W-S-865C — type LD or type NDS
cBottom cable entry and exit only. No hub provision supplied. Ground lug is
included and factory installed.
dLine lugs will accept and are UL approved for #14 to #6 Cu/Al cable.
e Legacy style, oversize enclosure. Ground lug is included and factory
installed.
Siemens Industry Inc., Industrial Control Catalog 18/7
Safety Switches
General Duty Safety Switches
Features (60-600A)
11 9
5 10
3 6
1 8
4
7
2
1. Cover interlock
2. Tangential knockouts 100-600A for easy conduit lineup
3. Quick-make, quick-break operating mechanism that ensures positive
operation
4. Provisions for T, R, J, H, and K class fuses (T & J 100-600A)
5. Wiring gutters that meet or exceed NEC wire-bending space requirements
6. Visible blade, double-break switch action
7. Positive 2 or 3 point mounting
8. Highly visible red handle grip
9. Informative door labeling which includes replacement parts list
10. Handle and cover padlocking provisions
11. 100A and above have sidehinged door that opens 180 degrees for easier
wiring
Note. 400A and 600A GD switches include internal shields which meet 2020 NEC
230.62 touch safe requirements for service entrance equipment.
18/8 Siemens Industry Inc., Industrial Control Catalog
SWITCHES 18
Safety Switches
General Duty Safety Switches
Selection
18 SWITCHES
Indoor — Type 1
System
Ampere Rating
240 Volt Fusible
Ship Wt. (lbs.) Catalog Number Std. Pkg
2-Pole, 2-Fuse, and Solid Neutralbcd
030
GF221N A
060
GF222N A
100
GF223N
200
GF224N
030g 020f 023
047
Outdoor — Type 3R
Catalog Number
Ship Wt. (lbs.) Std. Pkg
GF221NR Ae GF222NR Ae GF223NR
GF224NR
030g 020f
23
48
Horsepower Ratinga
240V AC
1-Phase, 2-Wire
2-Phase, 4-Wire
Std. Max. Std. Max.
3-Phase,
3-Wire
Std. Max.
250 Volt DC
Std.
011/2 03 03 10 071/2 15
15 —
240 Volt AC/250 Volt DC
—
—
03
0071/2 05
—
—
071/2 015 10
—
—
15
030 20
—
—
25
060 40
3-Pole, 3-Fuse, and Solid Neutrald
030
GF321N A
060
GF322N A
100
GF323N
200
GF324N
400
GF325N A
600
GF326N A
240 Volt Non-Fusiblecd
2-Pole or 3-Pole
030 030 030 030 060 060 100 200 400 600
GNF221A GNF221LAi GNF321Ai GNF321LAj GNF222A GNF322A GNF323 GNF324 GNF325A GNF326A
a Dual horsepower ratings: Std.- applies when non-time delay fuses are
installed. Max.- applies when timedelay fuses are installed.
b These switches are UL-listed for application on grounded B-phase systems.
c Suitable for use on 3-phase motor loads.
030g 020f
25 49 94.6 95.6
GF321NR Ae GF322NR Ae GF323NR GF324NR GF325NR A GF326NR A
030g 020f 025 050 94.6 95.6
011/2 03 03 10 071/2 15 15 — 15 — 15 —
240 Volt AC/250 Volt DC
—
—
03
0071/2 05
—
—
071/2 015 10
—
—
15
030 20
—
—
25
060 40
—
—
50
125 50
—
—
75
200 —
020g 030g 020g 030g 030g 030g 023 046 114 116
GNF221R Ae
020g
GNF221RLAei
030g
GNF321R Aei
020g
GNF321RLAej
030g
GNF222R Ae
030g
GNF322R Ae
030g
GNF323R
024
GNF324R
047
Use 600V Switch — HNF365RA
Use 600V Switch — HNF366RA
d Service entrance labeled. e Has provision for ECHA type hub. f 5 switches
per standard package. g 10 switches per standard package. h Height reduced
switch (45.25 rather than 56 inches in
height) for use with 500MCM or smaller conductors.
240 Volt AC/250 Volt DC
—
03
—
—
—
—
05
—
03
—
—
—
—
05
—
03
—
—
0071/2 —
05
—
03
—
—
0071/2 —
05
—
10
—
—
015 —
10
—
10
—
—
015 —
10
—
15
—
—
030 —
20
—
15
—
—
060 —
40
—
15
—
—
125 —
50
—
15
—
—
200 —
—
i Not suitable for service entrance. j “L” in catalog number indicates
oversized enclosure. Internal shields for 30A to 200A switches to meet
2020 NEC 230.62 touch safe requirements for service entrance equipment can be
purchased separately. See accessory section for catalog numbers.
Siemens Industry Inc., Industrial Control Catalog 18/9
Safety Switches
Heavy Duty Safety Switches
Features
15 3
2
20
11
17
16
9
4 1
SWITCHES 18
18 6
5 13 19
8 14
12
1. Quick-make, quick-break operating mechanism 12. Unique enclosure design increases rigidity and
that ensures positive operation.
prevents cuts and scrapes to conductors and
installer’s hands.
7
2. Visible blade, double-break switching action.
13. Spring reinforced fuse clips that assure reliable
3. Arc chutes dissipate heat and prolong switch life. contact for cool operation.
4. Highly visible red handle grip. Designed for hook stick operation.
14. Door latch securely holds door closed and allows cover padlocking.
5. Defeatable dual cover interlock.
15. Front removable mechanical lugs that are
suitable for CU/AI 60 or 75° C conductors.
6. Center punch provided for field drilling
to allow ON padlocking.
16. Lugs are field convertible to copper
body and to a wide variety of compression
7. Handle can be padlocked in the OFF position
connectors.
10
with up to (3) padlocks with 5/16″ hasps.
17. Hinged clear line terminal shield
8. Generous top, bottom and side gutters that
with probe holes for inspecting or
meet or exceed NEC wire-bending space
testing line side terminals.
requirements.
18. Embossed aluminum nameplate on Heavy
9. Informative door labeling which includes
Duty Switches provides highly visible ON/OFF
replacement parts list.
indication.
10. Tangential knockouts through 600A for easy conduit lineup.
19. Drawn cover for increased rigidity and resistance to abuse.
11. Side-hinged door that opens past 180 degrees for easier wiring.
20. Top key hole and bottom mounting holes provide easy 2 or 3 point mounting.
18/10 Siemens Industry Inc., Industrial Control Catalog
Safety Switches
Heavy Duty Safety Switches
Selection
18 SWITCHES
System
Ampere Rating
Indoor — Type 1
Ship Wt. (lbs.) Catalog Number Std. Pkg
Outdoor — Type 3R
Catalog Number
Ship Wt. (lbs.) Std. Pkg
Horsepower Ratinga
240V AC 1-Phase, 2-Wire
2-Phase, 4-Wire
Std. Max. Std. Max.
3-Phase, 3-Wire
Std. Max.
250 Volt DC
Std.
240 Volt Fusiblee
2-Pole, 2-Fuse, and Solid Neutralc (Also used for 2-Pole, 2-Wire Applications)
240 Volt AC/250 Volt DC
30 60 100 200 400 600 800 1200
HF221N
HF222N HF223N HF224N HF225N A HF226N A HF227N HF228N
012 018 023 047
91.1 95.6 365 385
HF221NR
HF222NR HF223NR HF224NR HF225NR A HF226NR A HF227NR HF228NR
013 019 024 048
91.1 95.6 365 385
011/2
03 —
03 10 —
071/2
15 —
15 — —
15 — —
15 —
—
—-
—
—-
—
—
003 0071/2 05
—
0071/2 015
10
—
015 030 20
—
025 060 40
—
050 125 50
—
075 200 50
—
100 250 50
—
100 250 50
3-Pole, 3-Fuse, and Solid Neutral
(Also used for 3-Pole, 3-Wire Applications)
240 Volt AC/250 Volt DC
0030 0060 0100 0200 0400 0600 0800 1200
HF321N
HF322N HF323N HF324N HF325N A HF326N A HF327N
HF328N
014 019 025 049
94.6 99.6 375 395
HF321NR
HF322NR HF323NR HF324NR HF325NR A HF326NR A HF327NR
HF328NR
015 020 026 050
94.6 99.6 375 388
011/2 03
—
—
03 10 — —
071/2 15
—
—
15 — — —
15 — — —
15 — — —
—- —-
—- —-
003 0071/2 05
0071/2 015
10
015 030
20
025 060
40
050 125
50
075 200
50
100 250
50
100 250
50
240 Volt Fusiblee
2-Pole, 2-Fused
0030 0060 0100 0200
3-Pole, 3-Fused
0030 0060 0100 0200
400 600 800
240 Volt AC/250 Volt DC
Type 4/4X Stainlessg
HF221S
013
HF222S
019
HF223S
024
HF224S
048
Type 12 Industrialf
HF221J
013
HF222J
019
HF223J
024
HF224J
048
011/2
03
—
03 10 —
071/2
15
—
15 —
—
—
003 0071/2 05
—
0071/2 015
10
— 015 030 20
— 025 060 40
(Also used for 2-Pole, 2-Wire Applications in 400800A Ratings) 240 Volt AC/250 Volt DC
HF321S HF322S HF323S HF324S HF325SA HF326SA HF327S
014
HF321J
020
HF322J
025
HF323J
049
HF324J
93
HF325JA
98
HF326JA
370
HF327J
014
011/2
3–
—
003 0071/2 —
020
3
10 —
—
0071/2 015 10
025
071/2
15
—
— 015 030 20
049
15
—
—
— 025 060 40
93
15
—
—
—
50 125 50
98
15
—
—
—
75 200 50
365
—
—
— — 100 250 50
Built to order. Allow 3-5 weeks for delivery. a Height reduced switch (45.25
rather than 56 inches in
height) for use with 500MCM or smaller conductors. b Dual horsepower ratings:
Std.- applies when non-time
delay fuses are installed. Max.- applies when timedelay fuses are installed.
Product Category: HDSS
c These switches are UL-listed for application on grounded B-phase systems and
are suitable for 3-phase motor applications.
d When a neutral is required use a field installed neutral kit.
e Suitable for use as service entrance equipment. f Also rated Type 3S/3R. g
304 grade stainless steel. For switches with enclosures
constructed from 316 grade stainless steel, substitute “SS” in catalog number
for “S.”
Siemens Industry Inc., Industrial Control Catalog 18/11
Safety Switches
Heavy Duty Safety Switches
Selection
Indoor — Type 1
System
Ampere Rating Catalog Number
600 Volt Fusiblee
2-Pole, 2-Fusec
0030
HF261
0060
HF262
0100
HF263
Ship Wt. (lbs.) Std. Pkg
015 020 026
Outdoor — Type 3R
Catalog Number
Ship Wt. (lbs.) Std. Pkg
HF261R
015
HF262R
020
HF263R
027
Horsepower Ratingd
480V AC 1-Phase, 2-Wire
Std. Max.
3-Phase, 3-Wire
Std. Max.
600V AC 1-Phase, 2-Wire
3-Phase, 3-Wire
Std. Max. Std. Max.
250 600 Volt Volt DC DC
480 Volt AC/600 Volt AC/600 Volt DC
03 071/2 — — 03 10 — — 05 15 05 20 — — 10 25 — — 10 30 10 30 — — 15 40 — — 20
50
3-Pole, 3-Fuse
0030
HF361
14
0030
HF361Lg
19
0060
HF362
19
0060
—
—
0100
HF363
24
0200
HF364
48
0400
HF365Aa
93
0600
HF366Aa
98
0800
HF367
365
1200
HF368
383
3-Pole, 3-Fuse and Solid Neutral
0030
HF361N
014
0060
HF362N
019
0100
HF363N
025
0200
HF364N
049
0400
HF365NA
94.6
0600
HF366NA
99.6
0800
HF367N
375
1200
HF368N
395
HF361R HF361R Lg HF362R HF362RLg HF363R HF364R HF365R Aa HF366R Aa HF367R
HF368R
HF361NR HF362NR HF363NR HF364NR HF365NR A HF366NR A HF367NR HF368NR
015
03
020
03
020
05
025
05
025
05
049
25
157
—
161
—
365
—
385
—
015
03
020
05
026
10
050
25
94.6 —
99.6 —
375
—
388
—
480 Volt AC/600 Volt AC/250 Volt DCa
071/2 005 015 03 10 0071/2 020 05 — 071/2 005 015 03 10 0071/2 020 05 — 20 015
030 10 25 015 050 10 30h 20 015 030 10 25 015 050 10 30h 20 025 060 15 40 030
075 20 50h 50 050 125 30 50 060 150 40 50 — 100 250 — — 125 350 50 — — 150 400
— — 200 500 50 — — 200 500 — — 250 500 50 — — 200 500 — — 250 500 50 —
480 Volt AC/600 Volt AC/250 Volt DCa
071/2 005 015 03 10 0071/2 020 05 — 20 015 030 10 25 015 050 10 30h 30 025 060
15 40 030 075 20 50h
50 050 125 30 50 060 150 40 50
— 100 250 — — 125 350 50 —
— 150 400 — — 200 500 50 —
— 250 500 — — 250 500 50 —
— 250 500 — — 250 500 50 —
600 Volt Fusiblee (For 2-Pole Applications use outside poles of 3-Pole Switches)
2-Pole, 2-Fusec
Type 4/4X Stainlessi
0030
HF261S
015
0060
HF262S
020
0100
HF263S
027
Type 12 Industrialf
HF261J
015
HF262J
020
HF263J
027
480 Volt AC/600 Volt AC/600 Volt DC
03 071/2 — — 03 10 — — 05 15 05 20 — — 10 25 — — 10 30 10 30 — — 15 40 — — 20
50
3-Pole, 3-Fuse
0030 0060 0100 0200 0400 0600 0800 1200
HF361S HF362S HF363S HF364S HF365SAa HF366SAa HF367S HF368S
013
HF361J
020
HF362J
025
HF363J
049
HF364J
93
HF365JAa
98
HF366JAa
370
HF367J
388
HF368J
480 Volt AC/600 Volt AC/250 Volt DCa
014
— — 005 015 — — 0071/2 020 05 —
020
— — 015 030 — — 015 050 10 30h
025
— — 025 060 — — 030 075 20 50h
049
— — 050 125 — — 060 150 40 50
93
— — 100 250 — — 125 350 50 —
98
— — 150 400 — — 200 500 50 —
365
— — 200 500 — — 250 500 50 —
388
— — 250 500 — — 250 500 50 —
Built to order. Allow 3-5 weeks for delivery. a 60-600A 3-Pole switches are
also rated 600V DC. b Height reduced switch (45.25 rather than 56 inches in
height) for use with 500MCM or smaller conductors. c Use 3-Pole switch for
200A applications. d Dual horsepower ratings: Std.- applies when non-time
delay fuses are installed. Max.- applies when time-
delay fuses are installed. e Suitable for use as service entrance equipment
except on
1200 Amp solidly grounded wye systems per NEC 230.95. f Also rated Type 3S/3R.
g Indicates oversized enclosure (30A switch with 60A
lugs in a 60A enclosure or 60A switch with 100A lugs in a 100A enclosure).
h 600V DC & 600V DC horsepower rating shown requires (2) poles to be connected
in series.
i 304 grade stainless steel. For switches with enclosures constructed from 316
grade stainless steel, substitute “SS” in catalog number for “S.”
18/12 Siemens Industry Inc., Industrial Control Catalog
Product Category: HDSS
SWITCHES 18
Safety Switches
Heavy Duty Safety Switches
Selection
System
Indoor — Type 1 Outdoor — Type 3R
Ampere Catalog Rating Number
Ship
Catalog
Wt. (lbs.) Number
Ship Wt. (lbs.)
Horsepower Rating
240 Volt
480 Volt
600 Volt
250V
1-Phase 3-Phase 1-Phase 3-Phase 1-Phase 3-Phase DC
600V DC
600 Volt Non-Fusibled
2-Polec
30 HNF261 60 HNF262 100 HNF263
12 HNF261R 19 HNF262R 24 HNF263R
480 Volt AC / 600 Volt AC / 600 Volt DC
13
—
—
071/2
—
10
—
5
15
20
—
—
20
—
25
—
10
30
25
—
—
30
—
40
—
20
50
3-Pole
30 HNF361
12
30 —
—
60 HNF362Hb
11
60 HNF362a
18
60 —
—
100 HNF363a
23
200 HNF364a
46
400 HNF365Aa
75
600 HNF366Aa
77
800 HNF367
295
1200 HNF368
305
600 Volt Non-Fusibled
2-Polec
30 60 100
Type 4 / 4X Stainlessh
HNF261S
13
HNF262S
20
HNF263S
25
HNF361R
13
HNF361RLf
19
HNF362RHb
11
HNF362Ra
19
HNF362RLf
24
HNF363Ra
24
HNF364Ra
47
HNF365RAa
75
HNF366RAa
77
HNF367R
295
HNF368R
307
Type 12 Industriale
HNF261J
13
HNF262J
20
HNF263J
25
480 Volt AC / 600 Volt AC / 250 Volt DC
5
10
071/2
20
10
30
5
—
5
10
071/2
20
10
30
5
—
10
20
20
50
20
40
10
—
10
20
20
50
25
60
10
30g
10
20
20
50
25
60
10
30g
15
40
30
75
40
100
20
50g
15
60
50
125
50
150
40
50
15
125
50
250
50
350
50
—
15
200
50
400
50
500
50
—
15
250
50
500
50
500
50
—
15
250
50
500
50
500
50
—
480 Volt AC / 600 Volt AC / 600 Volt DC
—
—
071/2
—
10
—
5
15
—
—
20
—
25
—
10
30
—
—
30
—
40
—
20
50
3-Pole
30 60 60 100 200 400 600 800 1200
HNF361S HNF362SHb HNF362Sa HNF363Sa HNF364Sa HNF365SAa HNF366SAa HNF367S HNF368S
13 HNF361J 15 HNF362JHb 19 HNF362Ja 24 HNF363Ja 47 HNF364Ja 75 HNF365JAa 77 HNF366JAa 295 HNF367J 310 HNF368J
480 Volt AC / 600 Volt AC / 250 Volt DC
13
5
10
071/2
20
10
30
5
—
14
10
20
20
50
20
40
10
—
19
10
20
20
50
25
60
10
30g
24
15
40
30
75
40
100
20
50g
47
15
60
50
125
50
150
40
50
75
15
125
50
250
50
350
50
—
77
15
200
50
400
50
500
50
—
295
15
250
50
500
50
500
50
—
310
15
250
50
500
50
500
50
—
Built to order. Allow 3-5 weeks for delivery. a 60-600A 3-Pole switches are
also rated 600V DC. b Compact switch (11.1″H, 6.6″W box less cover and
handle).
Short circuit withstand rating–100,000 RMS sym. amps. c Use 3-Pole switch for
200A application.
Product Category: HDSS
d Suitable for use as service entrance equipment except for 1200 when used on
a 480 or 600V grounded wye system.
e Also rated type 3S / 3R. f Indicates oversized enclosure (30A switch in a
60A
enclosure or a 60A switch in a 100A enclosure.
g 600V DC and 600V DC horsepower rating shown requires (2) poles to be
connected in series.
h 304 grade stainless steel. For switches with enclosures constructed from 316
grade stainless steel, substitute “SS” in catalog number for “S.”
Siemens Industry Inc., Industrial Control Catalog 18/13
18 SWITCHES
Safety Switches
Heavy Duty Safety Switches
Type 3R, 4/4X, & 12 with Viewing Window
Description
30600A, 3-pole 600V max. in fusible and nonfusible versions in Type 4/4X
stainless steel, and Type 12, and select 3R enclosures.
All allow viewing of visible blade position with the door closed. 30200A also
allow viewing of indicating type fuses.
Features
b Rugged installer-friendly enclosure design features a gasket flange with
continuously welded seams
b Tool-free cover latches
b Two, three and four point mounting
b Metal handle with large insulating grip features a positive stop in both ON
and OFF position
b Ground lugs provided as standard in Type12 and 4X switches
b Type 12 enclosures are fabricated from galvanized steel and are also rated
for 3R/3S outdoor applications
b Type 4X stainless steel switches (30200A) are provided with stainless steel
interior parts
b The widest range of accessories available including 200% neutrals, gold
plated PLC auxiliary contacts and isolated ground kits
Maximum Horsepower Ratingb
System
Ampere Rating Catalog Number
Ship
240V AC
Wt. (lbs.) 1-Phase, 2-Wire
3-Phase
3-Pole, 3-Wire Fusible, Type 3Rd
30 HF361RW
17
3
71/2
60 HF362RW
22
10
15
800 HF367NRW
375
—
—
1200 HF368NRW
388
—
—
3-Pole, 3-Wire Non-Fusible, Type 3Rd
30 HNF361RW
14
3
10
60 HNF362RW
21
10
20
800 HNF367RW
295
15
250
1200 HNF368RW
307
15
250
3-Pole, 3-Wire Fusible, Type 12cd
30 HF361JW
17
3
60 HF362JW
22
10
100 HF363JW
26
15
200 HF364JW
53
—
400 HF365JWA
93
—
600 HF366JWA
98
—
800 HF367JW
365
—
1200 HF368JW
388
—
3-Pole, 3-Wire Non-Fusible, Type 12cd
71/2 15 30 60 125 200 — —
30 HNF361JW
14
3
10
60 HNF362JW
21
10
20
100 HNF363JW
25
15
40
200 HNF364JW
51
15
60
400 HNF365JWA
75
15
125
600 HNF366JWA
77
15
200
800 HNF367JW
295
15
250
1200 HNF368JW
310
15
250
3-Pole, 3-Wire Fusible, Type 4X Stainless Steeldf
30 HF361SW
17
3
60 HF362SW
23
10
100 HF363SW
28
15
200 HF364SW
55
—
400 HF365SWA
75
15
600 HF366SW
98
—
800 HF367SW
365
—
1200 HF368SW
388
—
3-Pole, 3-Wire Non-Fusible, Type 4X Stainless Steeldf
71/2 15 30 60 125 — — —
30 HNF361SW
15
3
10
60 HNF362SW
23
10
20
100 HNF363SW
27
15
40
200 HNF364SW
54
15
60
400 HNF365SWA
75
15
125
800 HNF367SW
295
15
250
1200 HNF368SW
310
15
250
480V AC 3-Phase
15 30 500 500
20 50 500 500
15 30 60 125 250 400 500 500
20 50 75 125 250 400 500 500
15 30 60 125 250 400 500 500
20 50 75 125 250 500 500
600V AC 3-Phase
250V DC
600V DC
600 Volt AC / 250 Volt DCa
20
5
—
50
10
30e
500
50
—
500
50
—
600 Volt AC / 250 Volt DCa
30
5
—
60
10
30e
500
50
—
500
50
—
600 Volt AC / 250 Volt DCa
20
5
—
50
10
30e
75
20
50e
150
40
50
350
50
—
500
50
—
500
50
—
500
50
—
600 Volt AC / 250 Volt DCa
30
5
—
60
10
30e
100
20
50e
150
40
50
350
50
—
500
50
—
500
50
—
500
50
—
600 Volt AC / 250 Volt DCa
20
5
—
50
10
30e
75
20
50e
150
40
50
350
50
—
500
50
—
500
50
—
500
50
—
600 Volt AC / 250 Volt DCa
30
5
—
60
10
30e
100
20
50e
150
40
50
350
50
—
500
50
—
500
50
—
a 200A switches are also rated 600V DC. b Maximum HP ratings listed apply only
when time delay
fuses are used. c Also rated 3S/3R for outdoor use.
d All switches are suitable for use as service entrance equipment.
e 600V DC and 600V DC horsepower rating shown requires (2) poles to be
connected in series.
f 304 grade stainless steel. For switches with enclosures constructed from 316 grade stainless steel, substitute “SS” in catalog number for “S.”
18/14 Siemens Industry Inc., Industrial Control Catalog
Product Category: HDSS
SWITCHES 18
Safety Switches
Type ECS Elevator Control Switches
Catalog Logic
Elevator Control Switches
Application Siemens Type (ECS) Elevator Control disconnect switches are
designed for single cable or hydraulic elevator application to interrupt the
incoming AC power upon receiving a signal from the Fire Alarm Control Panel
(FACP).
Description The Elevator Control switch units come completely assembled for
quick installation, eliminating the labor and time needed to assemble
individual components. Therefore, the numbering system assures that you get
all of the correct components, assembled with the correct ratings, without
having to individually order accessories.
It is easy to meet Code requirements for selective coordination in a fully
fused system. Siemens Type (ECS) Elevator Control disconnect switches utilize
Class J fuses that easily coordinate with any upstream fuse by simply using a
2:1 lineside to load-side fuse ratio.
Standards UL 98 Enclosed and Dead Front Switch
Guide 96NK3917, File E182262
Catalog Number System The following catalog numbering system defines an
Elevator Control Switch construction.
ECS 1 T2 R2 G F1 3 N B C
Elevator Control Switches
Ampere rating 1 = 30 A 2 = 60 A 3 = 100 A 4 = 200 A 5 = 400A
Control Transformer T2 = 208 V T3 = 240 V T1 = 480 V T4 = 600 V
Fire Safety Interface Relay (3PDT, 10 A, 120 V) R2 = 24 Vdc Coil R1 = 120 Vac
Coil
Pilot Light ON G = Green R = Red W = White
Fire Alarm Voltage Monitoring Relay (To Monitor Shunt Trip Voltage) F1 =
Single-Polec F3 = Three-Pole
Enclosure options (NEMA 1 Standard With No Suffix Designation Required) 3 =
NEMA 3R D = NEMA 12 P = NEMA 4 Painted Steel
Neutral Lug N = Isolated Full Capacity
Auxiliary Contacts (1NO/1NC) B = Main Switch
Surge Protection C = Integrated surge protection device
a 100 VA with Primary and Secondary fusing (120 V Secondary) b For information
on Siemens TPS3 03 protection device refer to
product literature or Speedfax c F1 must be selected if 24 Vdc Coil for safety
interface relay (R2) is selected
Siemens Industry Inc., Industrial Control Catalog 18/15
18 SWITCHES
Safety Switches
Type ECS Elevator Control Switches
Features
Elevator Control Switches
Standard Features 30-400 A, 600 Vac, 3-phase fused power switch 200 kA RMS
assembly short-circuit current rating Shunt trip 120 V Control power terminal
block Ground lug compliant with the National Electric Code Class J fuse
mounting only (Class J fuses not included) Key to test switch Pilot light
“ON” Mechanically interlocked auxiliary contact for hydraulic
elevators with battery backup (5 A, 120 Vac rated) Handle designed for hook
stick operation OSHPD Special Seismic Certification Preapproval (OSP)
Configurable Standard Features Control power transformer with fuses and blocks
Fire safety interface relay Isolated neutral lug Fire Alarm Voltage Monitoring
Relay (to monitor Shunt
Trip Voltage) NEMA 3R, 4, and 12 enclosures available
Optional Features Oversized 200% rated neutral option available where
required by excessive non-linear loads Additional auxiliary contact (1NO /
1NC) Integrated surge protection device (TPS3 03).
Externally viewable though window in door
Other Options Optional features include contact closure, i.e. battery
lowering/ door opening system. The B option offers support for the states of
Arizona, Oregon, and Texas requirements to prevent “nuisance” fire alarms by
over-riding the “Control Power not Available” signal when the Siemens Elevator
control disconnect is manually (intentionally) turned off, and distinctive
signaling for ON-OFF-TRIPPED conditions (Option B).
All Siemens Elevator Control elevator disconnect switches are UL-Listed and designed for safe access by qualified personnel. When maintenance or shutdown service is required, no energized parts are exposed inside the enclosure when the disconnect switch is manually turned to the OFF position. For proper maintenance safety precautions, always turn off incoming power to the Siemens Elevator Control elevator switch when possible. When servicing any live electrical equipment, always wear appropriate personal protective equipment.
Shunt-Trip Operation The disconnect means is a shunt-trip operated switch. The
control power source for the shunt-trip operator is a 120 Vac supply
originating in the Siemens Elevator Control switch. Current to the shunt-trip
device is switched by an isolation relay, which is in turn controlled by the
FACP.
The control signal may be either 24 Vdc from the FACP (Option R2) or a “dry”
contact closure in the FACP (Option R1). In the case of a “dry” contact
closure, the sensing voltage is 120 Vac originating in the Siemens Elevator
Control switch.
A key test switch (Option K) is included for testing the shunttrip circuit.
Supervisory Indication
Additionally, an optional separate relay can be specified to monitor the 120
Vac control power source in the Siemens Elevator Control switch. This relay
(Option F1 or F3) is used to provide supervisory indication of “Control Power
Available” as required by NFPA 72 Section 6.15.4.4.
Transformer Fuse Details
ECS Voltage/ Transformer Voltage
Primary Fuse (amps)
208/120
FNQ-R-2
240/120
FNQ-R-2
480/120
FNQ-R-1
600/120
FNQ-R-1
Secondary Fuse (amps)
FNM-1 1/4 FNM-1 1/4 FNM-1 1/4 FNM-1 1/4
ULA / NECB Listed Horsepower Ratings
30A
Voltage / Poles
Stdb
208VAC / 3 PoleB
2
240VAC / 3 PoleA
2
480VAC / 3 PoleA
5
6008VAC / 3 PoleA
7½
Maxa 5 7½ 15 20
60A Stdb
5 7½ 15 15
Fuse and Short Circuit Information This switch is suitable for use with Class J Fuses ONLY.
Maxa 10 15 30 50
100A Stdb 10 15 25 30
Maxa 15 30 60 75
200A Stdb 20 25 50 60
Maxa 40 60 125 150
400A Stdb 40 50 100 125
Maxa 75 75 150 200
a Max HP with time delay Class J Fuses. b Max HP with non-time delay Class J Fuses.
18/16 Siemens Industry Inc., Industrial Control Catalog
SWITCHES 18
Safety Switches
Type VBII 4 & 6-Pole Heavy Duty Safety Switches
Selection
Application
4 & 6-pole Switches are commonly used as a disconnecting means for two-speed,
two-winding motors. Fused switches provide both over current and short circuit
protection. Non-fusible switches normally provide a local disconnection means
for twospeed motors which are remote from their motor controller. 4-pole
switches are also used in 3-phase, 4-wire circuits when a switching neutral is
required. All 4 & 6-pole switches are service entrance rated.
Description
4 & 6-pole switches are available in 30-200A ratings and in both fusible and
non-fusible versions. 4-pole switches are supplied with either Type 1 or
Type12/3R enclosures. 6-pole switches are available with either Type 12/3R or
Type 4X stainless steel enclosures.
Standards
b UL & CUL listed under file #E4776 b Meets UL98 for enclosed switches b 4 &
6-Pole switches are suitable for
use as service entrance
b Meets NEMA Standard KS-1 for enclosed switches
b Meets NEC wire bending space requirements
Features
b Visible blade, double break switching action
b Highly visible ON/OFF indication b Defeatable dual cover interlock b Padlock
option in OFF position b All copper current carrying partsa b Tangenital
knockouts (Type 1,
4-pole switches)
HNF662J
4-Pole Type VBII Switchesab
System
Amp Rating
Indoor Type 1
Type 12/3R Industriale
Catalog
Ship Wt. Catalog
Ship Wt.
Number
(lbs.) Number
(lbs.)
Fusible 600 Volt AC, 250 Volt DC — 4-Pole, 4 Fused
Horsepower Ratingsc 240V, 2Ø, 4W 240V 3Ø
Std. Max. Std. Max.
480V, 3Ø
600V, 3Ø
250V
Std. Max. Std. Max. DC
30
HF461
60
HF462
100
HF463
200
HF464
36
HF461J
40
HF462J
43
HF463J
88
HF464J
Non-fusible 600 Volt AC, 250 Volt DC — 4-Pole
36
3
10
3
71/2
5
15
71/2
20
5
40
71/2
20
71/2
15
15
30
15
50 10
43
15
30
15
30
25
60
30
75 20
88
25
50
25
60
50 125
60 150 40
30
HNF461
60
HNF462
100
HNF463
200
HNF464
32
HNF461J
34
HNF462J
36
HNF463J
78
HNF464J
32
—
10
—
10
—
20
—
30
5
34
—
20
—
20
—
50
—
60 10
36
—
30
—
40
—
75
— 100 20
78
—
50
—
60
— 125
— 150
4
6-Pole Type VBII Switchesabe
Type 12/3R Industrial
Type 4X Stainless Steel
Amp
Catalog
Ship Wt.
Catalog
Ship Wt.
System Rating Number
(lbs.)
Number
(lbs.)
Fusible 600 Volt AC, 250 Volt DC — 6-Pole, 6 Fused
30 HF661J
37
HF661S
37
60 HF662J
41
HF662S
41
100 HF663J
44
HF663S
44
200 HF664J
90
HF664S
90
Non-fusible 600 Volt AC, 250 Volt DC — 6-Pole
30
HNF661J
33
HNF661S
33
60
HNF662J
35
HNF662S
35
100
HNF663J
37
HNF663S
37
200
HNF664J
80
HNF664S
80
240V 3Ø Std.
3 71/2 15 25
— — — —
Max.
Horsepower Ratingsc
480V, 3Ø
600V, 3Ø
Std.
Max.
Std.
Max.
250V DC
71/2
5
15
71/2
20
5
15
15
30
15
50
10
30
25
60
30
75
20
60
50
125
60
150
40
10
—
20
—
30
5
20
—
50
—
60
10
40
—
75
—
100
20
60
—
125
—
150
40
18 SWITCHES
Built to order. Allow 3-5 weeks for delivery. a Lugs are aluminum alloy as
standard. Optional cop-
per body lugs are available. b All 4 & 6-pole VBII switches are suitable for
use as
service equipment when a neutral is installed or equipment ground kit is
properly connected.
Product Category: HDSS
c Dual horsepower ratings: Std. applies when non-time-delay fuses are
installed. Max. applies when time delay fuses are installed.
d Fusible switches accept Class H Fuses as the standard. Class R & J fuses can
also be installed and increase the rating from 10,000 to 200,000 AIC. For
Class J, the load base is moved upward. For Class R fuses, rejection kits are required. e Supplied with factory installed ground lugs.
Siemens Industry Inc., Industrial Control Catalog 18/17
Safety Switches
Special Application Safety Switches
Interlocked Receptacle Switches
Application
Receptacle Safety Switches provide cord connection protection of heavy-duty
portable equipment (welders, infrared ovens, batch feeders, portable
conveyors, assembly line fixtures and tools, refrigerator trucks, etc.) under
load or fault conditions.
Standards
All receptacle switches are UL listed under file #E4776. Those with a viewing
window are also CSA certified under file #1079316.
Descriptionab
Type 12 and 4/4X Receptacle Safety Switches are available with 3-phase, 4-wire
grounded type Crouse-Hinds ArkiteTM 2 or Pyle-National receptacle, pre-wired
and mounted with interlock linkage to the switch mechanism. Insertion or
removal of the plug is prevented by the interlock linkage while the switch is
in the “ON” position. Receptacle prevents operation of switch if incorrect
plug is inserted.
Crouse-Hinds Interlocked Receptacle Switches
Ampere Ratingd
Type 12e Catalog Number
Type 4/4Xf Catalog Number
Shipping Wt. (lbs.) Std. Pkg.
240V Fusible, 3-Pole, 3-Wire
30
HF321JCH
—
23
60
HF322JCH
—
30
100
HF323JCH
HF323SCHs
36
600V Fusible, 3-Pole, 3-Wire
30
HF361JCH
HF361SCH
24
60
HF362JCH
HF362SCH
30
100
HF363JCH
HF363SCHs
36
600V Non-Fusible, 3-Pole, 3-Wire
30
HNF361JCHs
HNF361SCHs
22
60
HNF362JCH
HNF362SCH
29
100
HNF363JCHs
HNF363SCHs
35
600V Fusible, 3-Pole, 3-Wire with Viewing Window
30
HF361JCHWs
HF361SCHWs
24
60
HF362JCHW
HF362SCHW
30
100
HF363JCHWs
HF363SCHWs
36
600V Non-Fusible, 3-Pole, 3-Wire with Viewing Window
30
HNF361JCHWs
HNF361SCHWs
22
60
HNF362JCHW
HNF362SCHWs
29
100
HNF363JCHWs
HNF363SCHWs
35
Accepts Crouse-Hinds Arktitea Plug Catalog Number
APJ3485 & NPJ3485 APJ6485 & NPJ6485 APJ10487 & NPJ10487
APJ3485 & NPJ3485 APJ6485 & NPJ6485 APJ10487 & NPJ10487
APJ3485 & NPJ3485 APJ6485 & NPJ6485 APJ10487 & NPJ10487
APJ3485 & NPJ3485 APJ6485 & NPJ6485 APJ10487 & NPJ10487
APJ3485 & NPJ3485 APJ6485 & NPJ6485 APJ10487 & NPJ10487
Pyle-National Interlocked Receptacle Switches
3-Poles Fusible and Non-Fusible
Ampere Rating Switch Receptacle
30
30
60
60
Voltage Rating
600 (F) 600 (N-F) 600 (F) 600 (N-F)
Type 12 Catalog Number e
HF361JPNs
HNF361JPN HF362JPNs HNF362JPN
Shipping Wt. (lbs.) Std. Pkg.
23 21 28 27
Accepts Pyle-National QuelArcTM bc Plugs Plug Catalog Number
JPD-83046
JPD-116046
HF362JCH
SWITCHES 18
s Built to order. Allow 68 weeks for delivery.
a ArktiteTM is a registered trademark of the CrouseHinds Company. Plugs are
not sold or supplied by Siemens.
b Indicates plug with maximum diameter cable bushing. c QuelArcTM is a
registered trademark of the Pyle-
National Company.
18/18 Siemens Industry Inc., Industrial Control Catalog
d Ampere rating of both switch and receptacle. e Also rated Type 3R/3S. f
Enclosure is constructed of Type 304 stainless steel.
Product Category: HDSS
Safety Switches
Special Application Safety Switches
Type VBII Non-Metallic & 316 Grade Stainless Steel
Application
Siemens Non-metallic and 316 grade stainless steel switches provide a superior
level of corrosion resistance to assure trouble free performance in the most
severe conditions. 316 grade stainless steel provides increased corrosion
resistance when compared to 304 grade, especially in atmospheres containing a
high level of chlorine commonly encountered in marine and waste management
applications. Our non-metallic enclosures are constructed from fiberglass
reinforced polyester and are extremely resistant to a wide range
of corrosive atmospheres. They allow a wide range of operating temperatures
and their insulating properties virtually eliminate problems caused by
internal condensation.
Description
30-200A, 600V Max, fusible and nonfusible switches are available in both non-
metallic and 316 grade stainless steel versions. All are supplied with factory
installed ground bars as standard. Viewing windows are also available in the
stainless offering.
Type 4/4X Non-Metallic
Ampere Catalog Rating Number
Horsepower Rating–3-Phase
Ship Weight Std. pkg.
240 Volt AC
480 Volt AC
600 Volt AC
(lbs.)
Std. Max. Std. Max. Std. Max.
3-Pole, 4-Wire, 240 Volt Fusible, Type 4Xe
30 HF321NX
21
60 HF322NXs
22
3
71/2
—
— —
—
71/2
15
—
— —
—
3-Pole, 4-Wire, 600 Volt AC Fusible, Type 4Xbce
30 HF361NX
21
60 HF362NX
22
100 HF363NXsa
39
200 HF364NXsa
83
3
71/2
5
15
71/2
20
71/2
15
15
30 15
50
15 30 25
60 30
75
25 60 50 125 60 150
3-Pole, 3-Wire, 600 AC Volt Non-Fusible,a Type 4Xbc
30 HNF361X
20
60 HNF362X
20
—
71/2
—
20 —
30
— 15
—
50 —
60
100 HNF363Xs
38
200 HNF364Xs
81
— 30 — 60
—
75
— 125
— 100 — 150
250 Volts DC
5 10
5 10 20 40
5 10 20 40
600 Volts DC
— —
15d 30d 50d 50
15d 30d 50d 50
18 SWITCHES
s Built to order. Allow 68 weeks for delivery. a Also used for 240 volt
applications.
Product Category: HDSS
b Add “L” to end of catalog number for switches less line & load lugs with
mounting hardware for crimp type or copper body lugs.
c 200A switches are also rated 600V DC max.
d 600V DC voltage and horsepower rating shown requires (2) poles to be
connected in series.
e Supplied with factory installed neutral.
Siemens Industry Inc., Industrial Control Catalog 18/19
Safety Switches
Enclosed Solar Photovoltaic (PV) Switches
Application, Description, Selection
Application
Solar disconnect switches are designed to be used in the DC portion of
photovoltaic power generation circuits. They incorporate powerful magnets
within the switch line base which work in combination with a double break
switching action to quickly dissipate the very hot arc that is generated when
a 600V DC circuit is opened under load. These circuits are defined by article
690 of the NEC which requires the grounded conductor to be at ground potential
at all times and therefore cannot be switched.
Description
30-200A switches are available in both Type 1 and 3R enclosures and in both
fusible and nonfusible versions. They are provided with an additional door
mounted warning label as required by the NEC and are supplied with a factory
installed equipment ground bar. They are built to UL98 requirements but are UL
listed in file number E335018 as UL1741 photovoltaic disconnect switches. They
are 3 pole switches that are approved to switch 3 separate 600V DC circuits
(one per pole). The design incorporates
many of the standard VBII switch features including a rolled out enclosure front flange, a large metal operating handle, oversized line and load lugs and large wire gutters. 1000VDC photovoltaic switches are UL98B listed for solar applications and comply with article 690 of the NEC. The new 400-600Amp switches are also UL98B listed at 600VDC and come in NEMA Type 3R.
Solar Photovoltaic Enclosed Disconnect Switches
Ampere Rating
Indoor Type 1 Catalog Number
Ship Wt* Std. Pkg.
Outdoor Type 3R Catalog Number
Ship Wt* Std. Pkg.
Rated Isc Per NEC Article 690
Negative Ground 3 Pole 3 Wire Fusible 600Volt DC
30
HF361PV
14
HF361RPV
15
19.2 A
60
HF362PV
20
HF362RPV
21
38.4 A
100
HF363PVs
25
HF363RPV
26
64.0 A
200
HF364PVs
49
HF364RPV
50
128.0 A
Negative Ground 3 Pole 3 Wire Non-Fusible 600Volt DC
30
HNF361PV
12
HNF361RPV
13
24.0 A
60
HNF362PV
19
HNF362RPV
20
48.0 A
100
HNF363PVs
24
HNF363RPV
25
80.0 A
200
HNF364PVs
47
HNF364RPV
48
160.0 A
Positive and Negative Ground, 1 Pole, Fusible 1000 Volt DC
200
HF1104NPVs
52
HF1104NRPVs
53
128.0A
Positive and Negative Ground, 1 Pole, Non-Fusible 1000 Volt DC
200
HNF1104NPVs
50
HNF1104NRPVs
51
160.0A
Positive Ground 3 Pole 3 Wire Fusible 600Volt DC
30
HF361PVPG
14
HF361RPVPG
15
19.2 A
60
HF362PVPGs
20
HF362RPVPG
21
38.4 A
100
HF363PVPGs
25
HF363RPVPGs
26
64.0 A
200
HF364PVPGs
49
HF364RPVPGs
50
128.0 A
Positive Ground 3 Pole 3 Wire Non-Fusible 600Volt DC
30
HNF361PVPG
12
HNF361RPVPG
13
24.0 A
60
HNF362PVPGs
19
HNF362RPVPG
20
48.0 A
100
HNF363PVPGs
24
HNF363RPVPGs
25
80.0 A
200
HNF364PVPGs
47
HNF364RPVPGs
48
160.0 A
Positive and Negative Ground, 2 Wire, 600Volt DC, Type 3R
Amperage Rating
400A 400A 600A 600A
No. Poles 1 1 1 1
Fuse Type Fusible Non-fusible Fusible Non-fusible
Catalog Number HF165NRPVs HNF165NRPVs HF166NRPVs HNF166NRPVs
Ship Wt* Std. Pkg 165 127 167 129
Rated Isc Per NEC Article 690 256A 256A 384A 384A
s Built to order. Allow 68 weeks for delivery.
- In pounds (lbs)
Note: All disconnects are rated at 10,000 AIC per UL requirements when used with or protected by Class K, J or R fuses rated at 600VDC.
HF361PV HNF361RPV HF362RPV
18/20 Siemens Industry Inc., Industrial Control Catalog
Product Category: HDSS
SWITCHES 18
Safety Switches
General and Heavy Duty Safety Switches
Accessories
HR612
Class R Fuse Clip Kits
All General Duty and Heavy Duty Switches are field convertible to accept Class
R Fuse Clip Kits. The kits prevent the installation of Class H and K fuses
(one kit required per 3-pole switch).
Class R Fuse Clip Kits
Catalog Number
HR21A HR21 HR612 HR22A HR62 HR63 HR64 HR65A HR66A
Description 30A, 240V Kit (GD only) 30A, 240V Kit (HD only) 30A, 600V Kit 60A 240V Kit (GD only) 60A, 600V Kit 100A Kit 200A Kit 400A Kit 600A Kit
Class J Fusing
All 30-600A, 600V and 100-600A,240V fusible Heavy Duty Switches are field convertible to accept Class J fuses by moving the load base to a pre-drilled J fuse position. All 100-600A, 240V fusible General Duty switches can also be field converted to accept Class J fuses.
Class J Fuse Kits
Catalog Number
HJ66A
Description 600A, 240V/600V Kit
Internal Shield Kits (for fusible switches)
Kits provide a clear plastic inner door to prevent accidental contact with live parts. Test probe holes are provided and fuses can be replaced without removal of kit.
Internal Shield Kitsc
Switch Ampere Rating
30-60A GD Non-fusible 30A GD Fusible
60A GD Fusible
100A GD
200A GD 30A HD Fusibleb 60A HDb 100A HDb 200A HDb
Kit Catalog Number
HSK212BA
HSK21BA HSK22BA HSK23B HSK24B HSK61SSW HSK62SSW HSK63SSW HSK64SSW
Coverage
Line side
Line side Line side Line side Line side Full Full Full Full
HT63
Class T Fuse Adapter Kits
All 100-600A, General Duty and 100200Amp and 1200Amp Heavy Duty Switches are
field convertible to accept Class T fuses.
Class T Fuse Adapter Kitsa
Catalog Number
HT23 HT63 HT24 HT64s HT25A HT65A HT26A HT66A TFAK72 TFAK75 TFAK82
Description 100A, 240V Kit 100A, 600V Kit 200A, 240V Kit 200A, 600V Kit 400A, 240V Kit 400A, 600V Kit 600A, 240V Kit 600A, 600V Kit 800A, 240V Kit 800A, 600V Kit 1200A, 240V Kit
HN612
Neutral Kits
Standard Neutral Kits can be field installed in General and Heavy Duty Switches.
Neutral Kits
Switch Ampere Rating 30 GD 30 HD 60 GD 60, 100 HD, 100 GD 200 400 & 600 800 &
1200
Kit Catalog Number n/a HN612 HN22A HN623 HN64 HN656A HN678
s Built to order. Allow 68 weeks for delivery.
a One kit per pole required. b Not designed for use in Non-metallic 4X safety
switches. Not designed for use with Auxiliary Contacts.
HN264
200% Neutral Kits
UL listed 200% Neutrals are available on 100-600A Heavy Duty Switches. They
are typically used with non-linear transformers or where increased neutral
ampacity/lug capacity is required.
200% Neutral Kits
Switch Kit Ampere Catalog Rating Number
Wire Range Line & Load Lugs (Cu/Al)
100
HN263 (2) #14-1/0 AWG
200
HN264 (2) #6 AWG-300 Kcmil
400
HN656A
(2) 1/0 AWG-600 Kcmil (2) #6 AWG-300 Kcmil
600
HN678A
(4) 1/0 AWG – 600 Kcmil (2) #6 AWG – 300 Kcmil
HP61
Fuse Puller Kits
Fuse Puller Kits are field installable in 30-100A Type VBII Heavy Duty
Switches (one kit required per 3-pole switch).
Fuse Puller Kits
Switch Ampere Rating
030
Fuse Puller Kit Catalog Number
HP61
060
HP62s
100
HP63s
c Internal shields meet 2020 NEC 230.62 touch safe requirements for service entrance.
Product Category HDSS
Siemens Industry Inc., Industrial Control Catalog 18/21
18 SWITCHES
Safety Switches
General and Heavy Duty Safety Switches
Accessories
HA261234
HA265678
HLC612
HG261234
Auxiliary Contacts
Auxiliary Contacts are available only for Heavy Duty Switches. The auxiliary
contacts are available in 1 normally open and 1 normally closed or 2 normally
open and 2 normally closed configurations. Siemens offers a PLC Auxiliary
Switch (30600A) that has very low resistance for low voltage and current
typical in PLC circuits. All auxiliary contacts make after and break before
main switch contacts.
Auxiliary Contactsa
Kit Ampere Rating
Switch Ampere
Aux. Switch Catalog Number
125V AC Max.
250V AC Max.
28V DC Max.
With 1 NO & 1 NC Isolated Contacts
30-600 HA161234
10
10
7
800-1200 HA165678
10
10
—
With 2 NO & 2 NC Isolated Contacts
30-600 HA261234
10
10
7
800-1200 HA265678
10
10
7
Low Current PLC Type with 1 NO & 1 NC Gold Plated Contacts
30-600 HA361234
10
10
7
800-1200 HA365678
10
10
—
Horsepower Rating
125V AC Max.
250V AC Max.
1/2
3/4
1/2
3/4
1/2
3/4
1/2
3/4
1/2
3/4
1/2
3/4
Copper Lug Kits
Heavy duty switches are UL approved to accept field installed copper lug kits.
Copper Lug Kits
Switch Ampere Rating
3060 100 200
400-600 8001200
Copper Lug Catalog Number
HLC612 HLC63s HLC64s HCU656A HLC65678
Description (9) Lugs/ Kit #14-4 AWG Cu (9) Lugs/ Kit #14-1/0 AWG Cu (9) Lugs/ Kit #6 AWG-300 Kcmil Cu (1) Lugs/Kit #1/0 AWG-600 Kcmil Cu (1) Lugs/Kit #1/0 AWG-600 Kcmil Cu
s Built to order. Allow 68 weeks for delivery. Purchase field replacement kit
along with lugs. a Series A 400A and 600A switches use HA161234, HA261234 or
HA361234 auxiliary
contacts. Earlier 400A and 600A switches use HA165678, HA265678 or HA365678
auxiliary contacts.
18/22 Siemens Industry Inc., Industrial Control Catalog
Quick Connects
They provide two point control power take-off capability and are normally used
on two poles on the line side when it is required to have control power
available when the switch is in the OFF position. They provide a mounting
provision for standard ¼” quick connect terminal. Installed in the line or
load side. 30A VBII switches have lugs UL listed to accept (2) wires per pole
as standard so a 30A kit is not required.
Quick Connects
Catalog Number
Description
HCQ62 HCQ63 HCQ64
60A 2 wire quick connect kit 100A 2 wire quick connect kit 200A 2 wire quick connect kit
Isolated Ground Kits
Isolated Ground Kits are available on 30-600A Heavy Duty Switches. They are
normally used on circuits with a high content of computer or other electronic
loading which require a ground which is isolated from the building ground and
neutral circuits. The kit includes both isolated and grounded terminals as
listed below.
Isolated Ground Kits
Switch Ampere Rating 30200
400600
Catalog Number HG261234
HG2656A
Number of Terminals
Isolated Grounded
2
2
4
4
Wire Range Per Terminal (Cu/Al)
14-4 AWG
2/0-14 AWG 2/0-6 AWG
Equipment Ground Kits
Equipment Ground Lug Kits are available for all General and Heavy Duty Switches. They are field installable in Type 1 and Type 3R Switches and are factory installed as standard in Type 4 / 4X and Type 12 and also in all VBII 4&6-pole Switches.
Equipment Ground Kits
Switch Ampere Rating
30200 GD 30200 HD 400 & 600 8001200
Catalog Number
HG61234 HG61234 HG656A HG678
Number of Terminals
2 2 4 8
Wire Range Per Terminal (Cu/Al)
14-4 AWG #14-4 AWG 2/0-6 AWG #6 AWG-250 Kcmil
Product Category HDSS
SWITCHES 18
Safety Switches
General and Heavy Duty Safety Switches
Hub and Lug Selection
Interchangeable Hubs
Conduit hubs are available for Type 3R, 12 and 4 / 4X applications. 30-200A
Type 3R Switches are provided with a conduit hub provision and a removable hub
plate on their top rainshed.
Conduit
Size
Catalog
(inches) Number
Type 3Ra
Cover ECHA000
3/4
ECHA075
1
ECHA100
1 1/4
ECHA125
Cover ECHS000
3/4
ECHS075
1
ECHS100
1 1/4
ECHS125
1 1/2
ECHS150
2
ECHS200
2 1/2
ECHS250
2 1/2
ECHV250
3
ECHV300
3 1/2
ECHV350
4
ECHV400
Type 4/4Xb
3/4
SSH075
1
SSH100
1 1/4
SSH125
1 1/2
SSH150
2
SSH200
Used On 3060A GD Only
100200A GD 30200A HD
4001200A
30200A
Note: 30 thru 200A. Type 3R Switches have removable hub plates on rainshed. 400A and larger Type 3R Switches have no provisions for mounting hubs. Drill or punch hole in the field to accommodate hub size desired.
Field Replacement Kits and Neutral Barrier Kits
All Heavy Duty Switches are field convertible for (Crimp) type lugs. When
compression lugs are required for 30-100A switches, a neutral barrier kit is
required for 1-Phase, 3W or 3-Phase, 4W applications. When compression lugs
are required on 400-1200A switches, lug mounting kits are required.
Field Replacement Kits and Neutral Barrier Kits
Switch Ampere Catalog Rating Number
Kit Description
30 60 & 100 400
400
600
600
800 & 1200e
HCL612
Neutral Barrier Kit
HCL623
Neutral Barrier Kit
HCM65A HNCM65A HCM66A HNCM66A
HCL65678
240V/600V Fusible Kit
240/600V NonFusible Kit
240V/600V Fusible Kit
240V/600V NonFusible Kit
1 Pole, Compression Lug Mounting Kit
Lugs
30 & 60A HD Switches are suitable for use with 60° or 75°C wire. 1001200A are
suitable for use with 75°C rated wire.
Multiple Padlock Accessory
A tamper-proof device to provide for multiple padlocking to meet OSHA or plant
requirements. Accepts up to 6 1/4″ padlocks. Catalog number SL0420. Standard
Carton-12.
SSH125 ECHV300
ECHS200
Wire Ranges (Line, Load and Standard Neutral)
Switch Ampere Rating 30GD 60GD 30HD 60HDhj
100 200i
400g
600g
800
1200
Wire Range with Wire Bending Space Per NEC Requirements
14-8 AWG (Cu/AI)
14-6 AWG (Cu)
14-6 AWG (Cu/AI)
14-3 AWG (Cu/AI)
14-1/0 AWG (Cu/Al)
6 AWG-250 Kcmil (Cu/Al)
(1) 1/0 AWG-600 Kcmil (Cu/Al) (2) 1/0 AWG-500 Kcmil (Cu/Al)
(1) 1/0 AWG-600 Kcmil (Cu/Al) (2) 1/0 AWG-500 Kcmil (Cu/Al)
(3) 1/0 AWG-750 Kcmil (Cu/Al) Line Load (4) 1/0 AWG-750 Kcmil (Cu/Al) neutral
(4) 3/0 AWG-750 Kcmil (Cu/Al) Line Load (4) 1/0 AWG-750 Kcmil (Cu/Al) neutral
Lug Wire Range #14-2 AWG (Cu/Al)f #14-2 AWG (Cu)f #14-2 AWG (Cu/Al) #14-2 AWG
(Cu/Al) #14-1/0 AWG (Cu/Al) #6 AWG-300 Kcmil (Cu/Al)
(2) 1/0 AWG-600 Kcmil (Cu/Al)
(2) 1/0 AWG-600 Kcmil (Cu/Al)
(3) 1/0 AWG-750 Kcmil (Cu/Al) Line Load (4) 1/0 AWG-750 Kcmil (Cu/Al) neutral
(4) 1/0 AWG-750 Kcmil (Cu/Al) Line Load (4) 1/0 AWG-750 Kcmil (Cu/Al) neutral
SL0420
Built to order. Allow 3-4 weeks for delivery.
a Hubs suitable for 3R Switches. b Also suitable for Type 12 applications. c
Neutral Barrier kits are required on 30-100A switches
only and only with 1-Phase / 3W or 3-Phase / 4W loads. Compression Lugs
mounting kits are required on 400-1200A switches only. d Provides mounting for
a single line or load lug. e Provides mounting for (2) compression lugs per
phase on line or load. f Neutral lugs (only) are UL approved to accept #14-4
CU/Al cable. g Max. wire size for height reduced switches is 500 kcmil
(Cu/Al). h Compact HD NF switches are also UL approved for #2 Cu/Al
conductors. i All 200A Heavy Duty Switches have a wire range & wire bending
space for (1) #6-300 Kcmil (Cu/Al). j Also for 30A oversized heavy duty
switches. Also for 60A oversized heavy duty switches.
Product Category: HDSS & RESI
Siemens Industry Inc., Industrial Control Catalog 18/23
18 SWITCHES
Safety Switches
General and Heavy Duty Safety Switches
Dimensions
Safety Switch Dimensions (Inches)* & Shipping Weights
Catalog Number
GF221NA GF221NRA GF222NA GF222NRA GF223N GF223NR GF224N GF224NR GF225NA
GF225NRA GF226NA GF226NRA GF321NA GF321NRA GF322NA GF322NRA GF323N GF323NR
GF324N GF324NR GF325NA GF325NRA GF326NRA GF326NA GF326NRA GNF221A GNF221RA
GNF321LA, GN221LA GNF321RLA, GN221RLA GNF222A LNF222RA, LNF221RLA GNF222RA
GNF321A GNF321RA GNF322A GNF322RA GNF323 GNF323R GNF324 GNF324R GNF325A
GNF326A HF221J also HF261J HF221N also HF261 HF221NR also HF261R HF221S also
HF261S HF222J also HF262J HF222N also HF262 HF222NR also HF262R HF222S also
HF262S HF223J also HF263J HF223N also HF263 HF223NR also HF263R HF223S also
HF263S HF224J HF224N HF224NR HF224S HF225NRA HF225NA HF226NA HF226NRA HF227N
HF227NR HF228N HF228NR
Height
Box A
8.4 8.4 9.91 9.91 21.95 21.95 29.9 29.9 45.32 45.32 45.32 45.32 8.4 8.4 9.91
9.91 21.95 21.95 29.9 29.9 45.32 45.32 45.32 45.32 45.32 6.18 6.18 8.4 8.4 8.4
8.4 8.4 6.18 6.18 8.4 8.4 21.95 21.95 29.9 29.9 33.47 33.47 14.27 14.26 14.34
14.27 16.22 16.26 16.26 16.22 21.96 21.95 21.95 21.96 29.96 29.9 29.9 29.96
45.32 45.32 45.32 45.32 66.67 66.67 66.67 66.67
With Door B
8.56 8.56 10.07 10.07 23.15
— 31.07
— 45.81 45.81 45.81 45.81
8.56 8.56 10.07 10.07 23.15
— 31.07
— 45.81 45.81 45.81 45.81 45.81
6.35 6.35 8.56 8.56 8.56 8.56 8.56 6.35 6.35 8.56 8.56 23.15
— 31.07
— 33.96 33.96 17.33 14.60
— 17.33 19.31 16.62
— 19.31 23.16 23.15
— 23.16 31.07 31.07
— 31.07 45.81 45.81 45.81 45.81 67.16
— 67.16
—
With Rain Shed C
— 8.56
— 10.07
— 23.46
— 31.42
— — — — — 8.56 — 10.07 — 23.46 — 31.42 — — — — — — 6.35 — 8.56 — 8.56 8.56 —
6.35 — 8.56 — 23.46 — 31.42 — — — — 14.91 — — — 16.93 — — — 23.46 — — — 31.42
— — — — — — 67.74 — 67.74
Width
Box D
5.08 5.08 6.06 6.06 9.64 9.64 14.62 14.61 22.4 22.4 22.4 22.4 5.08 5.08 6.06
6.06 9.64 9.64 14.62 14.61 22.4 22.4 22.4 22.4 22.4 4.2 4.2 5.08 5.08 5.08
5.08 5.08 4.2 4.2 5.08 5.08 9.64 9.64 14.62 14.61 22.4 22.4 6.65 6.64 6.64
6.65 9.17 9.16 9.16 9.17 9.65 9.64 9.64 9.65 14.62 14.62 14.61 14.62 22.4 22.4
22.4 22.4 38.4 38.4 38.4 38.4
With Handle E
5.44 5.44 6.42 6.42 11.7 11.67 16.68 16.68 23.404 23.404 23.404 23.404 5.44
5.44 6.42 6.42 11.7 11.67 16.68 16.68 23.404 23.404 23.404 23.404 23.404 4.56
4.56 5.43 5.43 5.43 5.43 5.43 4.56 4.56 5.43 5.43 11.7 11.67 16.68 16.68
23.404 23.404 9.02 7.75 7.88 9.02 11.47 10.37 10.41 11.47 12.02 12.01 11.97
12.02 16.95 16.98 16.99 16.95 23.404 23.404 23.404 23.404 39.96 39.96 39.96
39.96
Depth
Box F
2.93 2.93 3.21 3.21 5.05 5.05 6.36 6.36 6.94 6.94 6.94 6.94 2.93 2.93 3.21
3.21 5.05 5.05 6.36 6.36 6.94 6.94 6.94 6.94 6.94 2.88 2.88 2.93 2.93 2.93
2.93 2.93 2.88 2.88 2.93 2.93 5.05 5.05 6.36 6.36 6.94 6.94 5.32 4.71 5.00
5.32 5.33 4.71 5.05 5.33 5.34 5.05 5.05 5.34 6.63 6.36 6.36 6.63 6.94 6.94
6.94 6.94 9.24 9.24 9.24 9.24
With Handle G
3.96 3.96 4.24 4.24 8.63 8.7 10.92 10.92 9.93 9.93 9.93 9.93 3.96 3.96 4.24
4.24 8.63 8.7 10.92 10.92 9.93 9.93 9.93 9.93 9.93 3.93 3.93 3.95 3.95 3.95
3.95 3.95 3.93 3.93 3.95 3.95 8.63 8.7 10.92 10.92 9.93 9.93 10.46 8.89 9.18
10.46 10.46 8.67 9.21 10.46 10.46 10.17 10.17 10.46 12.58 12.33 12.33 12.58
9.93 9.93 9.93 9.93 14.68 14.68 14.68 14.68
Knockout Diagrama
S4 S5 S21 S22 S10 S11 S12 S13 S18 S19 S18 S19 S4 S5 S21 S22 S10 S11 S12 S13
S18 S19 S19 S18 S19 S4 S5 S4 S5 S4 S20 S5 S4 S5 S4 S5 S10 S11 S12 S13 S18 S18
— S6 S8 — — S16 S17 — — S10 S11 — — S12 S13 — S19 S18 S18 S19 — — — —
Shipping Weight (lbs.)
30(10) 30(10)
20(5) 20(5)
23 24 47 48 91.1 91.1 95.6 95.6 30(10) 30(10) 20(5) 20(5) 25 25 49 50 94.6
94.6 99.6 99.6 99.6 20(10) 20(10) 30(10) 30(10) 30(10) 30(10) 30(10) 20(10)
20(10) 30(10) 30(10) 23 24 46 47 75 77 13 13 14 13 19 18 19 19 24 23 24 24 48
47 48 48 91.1 91.1 95.6 95.6 360 362 362 364
SWITCHES 18
*For inches / millimeters conversion, multiply inches by 25.4.
18/24 Siemens Industry Inc., Industrial Control Catalog
a Knocks not provided on Type 4 / 4X and 12 or in 800 & 1200A switches.
Safety Switches
General and Heavy Duty Safety Switches
Dimensions
Safety Switch Dimensions (Inches)* & Shipping Weights
Catalog Number
HF261 HF261R HF262 HF262R HF321J HF321N HF321NR HF321S, SS HF322J HF322N
HF322NR HF322S, SS HF323J HF323N HF323NR HF323S, SS HF324J HF324N HF324NR
HF324S, SS HF325JA HF325NA HF325NRA HF325SA HF325SSA HF326JA HF326NA HF326NRA
HF326SA HF326SSA HF327J HF327N HF327NR HF327S HF328N HF328NR HF361, PV, PVPG
HF361J, JW HF361L HF361N HF361NR HF361R, RPV, RPVPG HF361RL, RW HF361S, SS,
SSW, SW HF362, PV, PVPG HF362J, JW HF362N HF362NR HF362R, RPV, RPVPG, RW
HF362RL HF362S, SS, SSW, SW HF363, PV, PVPG HF363J, JW HF363N HF363NR HF363R,
RPV, RPVPG HF363S, SS, SSW, SW HF364, PV, PVPG HF364J, JW HF364N HF364NR
HF364R, RPV, RPVPG HF364S, SS, SSW, SW HF365A HF365JA, JWA HF365NA HF365NRA
Height
Box A
14.26 14.34 16.26 16.26 14.27 14.26 14.34 14.27 16.27 16.26 16.26 16.27 21.96
21.95 21.95 21.96 29.96 29.9 29.9 21.96 45.32 45.32 45.32 45.32 45.32 45.32
45.32 45.32 45.32 45.32 66.67 66.67 66.67 66.67 66.67 66.67 14.26 14.27 16.26
14.26 14.34 14.34 16.26 14.27 16.26 16.27 16.26 16.26 16.26 21.95 16.27 21.95
21.96 21.95 21.95 21.95 21.96 29.9 29.96 29.9 29.9 29.9 29.96 45.32 45.32
45.32 45.32
With Door B
14.60 —
16.62 —
17.33 14.60
— 17.33 19.31 16.62
— 19.31 23.16 23.15
— 23.16 31.07 31.07
— 31.07 45.81 45.81 45.81 45.81 45.81 45.81 45.81 45.81 45.81 45.81 67.16
67.16
— 67.16 67.16
— 14.60 17.33 17.46 14.60
— — — 17.33 16.62 19.31 16.62 — — — 19.31 23.15 23.16 23.15 — — 23.16 31.07
31.07 31.07 — — 31.07 45.81 45.81 45.81 45.81
With Rain Shed C
— 14.91
— 16.93
— — 14.91 — — — 16.93 — — — 23.46 — — — 31.42 — — — — — — — — — — — — — 67.74
— — 67.74 — — — — 14.91 14.91 16.93 — — — — 16.93 16.93 23.46 — — — — 23.46
23.46 — — — — 31.42 31.42 — — — — —
Width
Box D
6.64 6.64 9.16 9.16 6.65 6.64 6.64 6.65 9.17 9.16 9.16 9.17 9.65 9.64 9.64
9.65 14.62 14.62 14.61 14.62 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4
38.4 38.4 38.4 38.4 38.4 38.4 6.64 6.65 9.15 6.64 6.64 6.64 9.16 6.65 9.16
9.17 9.16 9.16 9.16 9.64 9.17 9.64 9.65 9.64 9.64 9.64 9.65 14.62 14.62 14.62
14.61 14.61 14.62 22.4 22.4 22.4 22.4
With Handle E
7.75 7.88 10.37 10.41 9.02 7.75 7.88 9.02 11.47 10.37 10.41 11.47 12.02 12.01
11.97 12.02 16.95 16.98 16.99 16.95 23.404 23.404 23.404 23.404 23.404 23.404
23.404 23.404 23.404 23.404 39.96 39.96 40.25 39.96 39.96 40.25 7.75 9.02
11.53 7.75 7.88 7.88 10.41 9.02 10.37 11.47 10.37 10.41 10.41 11.97 11.47
12.01 12.02 12.01 11.97 11.97 12.02 16.98 16.95 16.98 16.99 16.99 16.95 23.404
23.404 23.404 23.404
Depth
Box F
4.71 5.00 4.71 5.05 5.32 4.71 5.00 5.32 5.33 4.71 5.05 5.33 5.34 5.05 5.05
5.34 6.63 6.36 6.36 6.63 6.97 6.94 6.94 7.34 7.34 6.97 6.94 6.94 7.34 7.34
9.24 9.24 9.24 9.24 9.24 9.24 4.71 5.32 5.05 4.71 5.00 5.00 5.05 5.32 4.71
5.33 4.71 5.05 5.05 5.05 5.33 5.05 5.34 5.05 5.05 5.05 5.34 6.36 6.63 6.36
6.36 6.36 6.63 6.94 6.97 6.94 6.94
With Handle G
8.89 9.18 8.67 9.21 10.46 8.89 9.18 10.46 10.46 8.67 9.21 10.46 10.46 10.17
10.17 10.46 12.58 12.33 12.33 12.58 10.05 9.93 9.93 10.347 10.347 10.05 9.93
9.93 10.347 10.347 14.68 14.68 14.68 14.68 14.68 14.68 8.89 10.46 10.17 8.89
9.18 9.18 9.21 10.46 8.67 10.46 8.67 9.21 9.21 10.17 10.46 10.17 10.46 10.17
10.17 10.17 10.46 12.33 12.58 12.33 12.33 12.33 12.58 9.93 10.05 9.93 9.93
Knockout Diagrama
S6 S8 S16 S17 — S6 S8 — — S16 S17 — — S10 S11 — — S12 S13 — — S18 S19 — — —
S18 S19 — — — — — — — — S6 — S16 S6 S8 S8 S17 — S16 — S16 S17 S17 S11 — S10 —
S10 S11 S11 — S12 — S12 S13 S13 — S18 — S18 S19
Shipping Weight (lbs.)
13 14 18 19 14 13 14 14 20 18 19 20 25 25 26 25 49 49 50 49 93 94.6 94.6 93 93
98 99.6 99.6 98 98 367 380 383 367 382 385 13 14 19 13 14 14 19 15 18 20 18 19
19 25 20 24 25 25 26 25 25 48 49 49 48 49 49 93 93 94.6 94.6
18 SWITCHES
*For inches / millimeters conversion, multiply inches by 25.4.
a Knocks not provided on Type 4 / 4X and 12 or in 800 & 1200A switches.
Siemens Industry Inc., Industrial Control Catalog 18/25
Safety Switches
General and Heavy Duty Safety Switches
Dimensions
Safety Switch Dimensions (Inches)* & Shipping Weights
Height
Width
Catalog Number
HF365RA HF365SA, SS, SWA, SSWA HF366A HF366JA, JWA HF366NA HF366NRA HF366RA
HF366SA, SSA HF367 HF367J, JW HF367N HF367NR HF367R, RW HF367S, SW HF368, J,
S, JW, SW HF368N HF368NR HF368R, RW HFC221N HFC221NR HFC222N HFC222NR HFC261
HFC261R HFC262 HFC262R HFC321N HFC321NR HFC322N HFC322NR HFC361 HFC361N
HFC361NR HFC361R HFC362 HFC362N HFC362NR HFC362R HNF365JA, JWA HNF365RA
HNF365SA, SSA, SWA, SSWA HNF366SA, SSA HNF366JA, JWA HNF366RA HNF361, PV, PVPG
also HNF261 & HNF362H, HNFC261, HNFC361 HNF361J, JW also HNF261J & HNF362JH
HNF361R, RPV, RPVPG also HNF261R & HNF362RH, HNFC261R, HNFC361R HNF361RL,
HNF362R, RPV, RPVPG also HNF262R, HNFC262R, HNFC362R HNF361S, SS, SSW, SW also
HNF261S & HNF362SH HNF362, PV, PVPG also HNF262, HNFC262, HNFC362 HNF362J, JW
also HNF262J HNF362RL, HNFC262R, HNFC362R HNF362S, SS, SSW, SW also HNF262S
HNF363, PV, PVPG also HNF263 HNF363J, JW also HNF263J HNF363R, RPV, RPVPG also
HNF263R HNF363S, SS, SSW, SW also HNF263S HNF364, PV, PVPG HNF364J, JW
HNF364R, RPV, RPVPG HNF364S, SS, SSW, SW
HNF365JA, JWA
Box A
45.32 45.32 45.32 45.32 45.32 45.32 45.32 45.32 66.67 66.67 66.67 66.67 66.67
66.67 66.67 66.67 66.67 66.67 14.26 14.34 16.26 16.26 14.26 14.34 16.26 16.26
14.26 14.34 16.26 16.26 14.26 14.26 14.34 14.34 16.26 16.26 16.26 16.26 45.32
33.47 33.47 33.47 45.32 33.47
11.11
11.12
11.09
16.26
11.12
16.26
16.27 21.95 16.27 21.95 21.96 21.95 21.96 29.9 29.96 29.9 29.96 45.32
With Door B
45.81 45.81 45.81 45.81 45.81 45.81 45.81 45.81 67.16 67.16 67.16
— — 67.16 67.16 67.16 — — 14.6 — 16.62 — 14.6 — 16.62 — 14.6 — 16.62 — 14.6
14.6 — — 16.62 16.62 — — 45.81 33.96 33.96 33.96 45.81 33.96
11.45
14.14
—
—
14.14
16.62
17.46 —
17.46 23.15 23.16
— 23.16 31.07 31.07
— 31.07 45.81
With Rain Shed C
— — — — — — — — — — — 67.74 67.74 — — — 67.74 67.74 — 14.91 — 16.93 — 14.91 —
16.93 — 14.91 — 16.93 — — 14.91 14.91 — — 16.93 16.93 — — — — — —
Box D
22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 38.4 38.4 38.4 38.4 38.4 38.4 38.4
38.4 38.4 38.4
6.64 6.64 9.16 9.16 6.64 6.64 9.16 9.16 6.64 6.64 9.16 9.16 6.64 6.64 6.64
6.64 9.16 9.16 9.16 9.16 22.4 22.4 22.4 22.4 22.4 22.4
—
6.64
—
6.65
11.76
6.64
16.93
9.16
—
6.65
—
— 23.46
— — — 23.46 — — — 31.42 — —
9.16
9.17 9.64 9.17 9.64 9.65 9.64 9.65 14.62 14.62 14.61 14.62 22.4
With Handle E
23.404 23.404 23.404 23.404 23.404 23.404 23.404 23.404 39.96 39.96 39.96
40.25 40.25 39.96 39.96 39.96 40.25 40.25
7.75 7.88 10.37 10.41 7.75 7.88 10.37 10.41 7.75 7.88 10.37 10.41 7.75 7.75
7.88 7.88 10.37 10.37 10.41 10.41 23.404 23.404 23.404 23.404 23.404 23.404
Depth
Box F
6.94 7.34 6.94 6.97 6.94 6.94 6.94 7.34 9.24 9.24 9.24 9.24 9.24 9.24 9.24
9.24 9.24 9.24 4.71 5 4.71 5.05 4.71 5 4.71 5.05 4.71 5 4.71 5.05 4.71 4.71 5
5 4.71 4.71 5.05 5.05 6.97 6.94 7.34 7.34 6.97 6.94
7.72
4.7
9.02
5.56
7.88
5
10.41
5.05
9.02
5.56
10.26
11.47 11.97 11.47 12.01 12.02 11.97 12.02 16.98 16.95 16.99 16.95 23.404
4.71
5.33 5.05 5.33 5.05 5.34 5.05 5.34 6.36 6.63 6.36 6.63 6.97
With Handle G
9.93 10.347
9.93 10.05
9.93 9.93 9.93 10.347 14.68 14.68 14.68 14.68 14.68 14.68 14.68 14.68 14.68
14.68 8.89 9.18 8.67 9.21 8.89 9.18 8.67 9.21 8.89 9.18 8.67 9.21 8.89 8.89
9.18 9.18 8.67 8.67 9.21 9.21 10.05 9.93 10.347 10.347 10.05 9.93
Knockout Diagrama
S19 —
S18 —
S18 S19 S19
— — — — — — — — — — — S6 S8 S16 S17 S6 S8 S16 S17 S6 S8 S16 S17 S6 S6 S8 S8
S16 S16 S17 S17 — S19 — — — S19
9.15
S7
10.46
—
8.91
S9
Shipping Weight (lbs.)
93 93 98 98 99.6 99.6 98 98 380 380 382 386 382 380 383 385 388 385 13 14 18
19 13 14 18 19 13 14 18 19 13 13 14 14 18 18 19 19 75 75 75 77 77 77
11
13
12
9.14
S17
18
10.46
—
13
9.04
S16
17
10.46
—
19
10.17
S11
24
10.46
—
19
10.17
S10
23
10.46
—
24
10.17
S11
24
10.46
—
24
12.33
S12
46
12.58
—
47
12.33
S13
47
12.58
—
47
10.05
—
75
SWITCHES 18
*For inches / millimeters conversion, multiply inches by 25.4.
18/26 Siemens Industry Inc., Industrial Control Catalog
a Knocks not provided on Type 4 / 4X and 12 or in 800 & 1200A switches.
Safety Switches
General and Heavy Duty Safety Switches
Dimensions
Safety Switch Dimensions (Inches)* & Shipping Weights
Height
Width
Catalog Number
HNF365RA HNF365SA, SSA, SWA, SSWA HNF366JA, JWA HNF366RA HNF366SA HNF367, J,
JWA HNF367R, RW HNF367S, SW HNF368, J, S, SW, JW HNF368R, RW LF111N LF111NR
LF211N LF211NR US2:HF361PV US2:HF361PVPG US2:HF361RPV US2:HF361RPVPG
US2:HF362PV US2:HF362PVPG US2:HF362RPV US2:HF362RPVPG US2:HNF361PV
US2:HNF361PVPG US2:HNF361RPV US2:HNF361RPVPG US2:HNF362PV US2:HNF362PVPG
US2:HNF362RPV US2:HNF362RPVPG
Box A
33.47 33.47 45.32 33.47 33.47 54.67 54.67 54.67 54.67 54.67
7.97 8.07 7.97 8.07 14.26 14.26 14.34 14.34 16.26 16.26 16.26 16.26 11.11
11.11 11.09 11.09 16.26 16.26 16.26 16.26
With Door B
33.96 33.96 45.81 33.96 33.96 55.16
— 55.16 55.16 55.16
8.13 —
8.13 —
14.6 14.6
— — 16.62 16.62 — — 11.45 11.45 — — 16.62 16.62 — —
With Rain Shed C
— — — — — — 55.7 — — — — 8.16 — 8.16 — — 14.91 14.91 — — 16.93 16.93 — — 11.76
11.76 — — 16.93 16.93
Box D
22.4 22.4 22.4 22.4 22.4 38.4 38.4 38.4 38.4 38.4
5.5 5.16 5.5 5.16 6.64 6.64 6.64 6.64 9.16 9.16 9.16 9.16 6.64 6.64 6.64 6.64
9.16 9.16 9.16 9.16
With Handle E
23.404 23.404 23.404 23.404 23.404 39.96 40.25 39.96 39.96 40.25
5.94 5.94 5.94 5.94 7.75 7.75 7.88 7.88 10.37 10.37 10.41 10.41 7.72 7.72 7.88
7.88 10.26 10.26 10.41 10.41
Depth
Box F
6.94 7.34 6.97 6.94 7.34 9.24 9.24 9.24 9.24 9.24 3 3.13 3 3.13 4.71 4.71 5 5
4.71 4.71 5.05 5.05 4.7 4.7 5 5 4.71 4.71 5.05 5.05
With Handle G
9.93 10.347 10.05
9.93 10.347 14.68 14.68 14.68 14.68 14.68
5.38 5.38 5.38 5.38 8.89 8.89 9.18 9.18 8.67 8.67 9.21 9.21 9.15 9.15 8.91
8.91 9.04 9.04 9.14 9.14
Knockout Diagrama
S19 — —
S19 — — — — — — S2 S3 S1 S3 S6 S6 S8 S8
S16 S16 S17 S17
S7 S7 S9 S9 S16 S16 S17 S17
Shipping Weight (lbs.)
75 75 77 77 77 302 304 302 305 307 35 (10) 35 (10) 35 (10) 35 (10) 13 13 14 14
18 18 19 19 11 11 12 12 17 17 18 18
Type 1 or 3R 30-60A GD
Type 1 or 3R 100-200A GD, 30-200A HD Type VBII
Type 4/4X or 12 30-200A HD Type VBII
18 SWITCHES
Type 1 or 3R 400-1200A Type VBII (GD & HD)
Type 4/4X or 12 400-1200A HD Type VBII
*For inches / millimeters conversion, multiply inches by 25.4.
a Knocks not provided on Type 4 / 4X and 12 or in 800 & 1200A switches.
Siemens Industry Inc., Industrial Control Catalog 18/27
Safety Switches
General and Heavy Duty Safety Switches
Knockout Diagrams Type 1 & 3R Enclosures
S4 Embossed .25 in. mounting holes (3 places)
2 0.25 dia. K.O’s
3 K.O.’s for Conduit 0.5-0.75-1 in.
Removable plate covering
HA Type Hub opening (Max. 1.25 Conduit)
S5 Embossed .25 in. mounting holes (3 places)
2 0.25 dia. K.O’s
2 K.O.’s for Conduit 0.5-0.75-1 in.
Removable plate covering HS Type Hub opening (Max. 2.5 Conduit)
S8
2 K.O.’s for Conduit 0.75, 1 in.
5 K.O.’s for Conduit 0.50, 0.75, 1 in.
1 0.25 dia. K.O.
Removable plate covering HS Type Hub opening (Max. 2.5 Conduit)
S9
2 K.O.’s for Conduit 0.75, 1 in.
5 K.O.’s for Conduit 0.50, 0.75, 1 in.
1 0.25 dia. K.O.
SWITCHES 18
*For inches / millimeters conversion, multiply inches by 25.4.
18/28 Siemens Industry Inc., Industrial Control Catalog
Safety Switches
General and Heavy Duty Safety Switches
Knockout Diagrams
Type 1 & 3R Enclosures
18 SWITCHES
Removable plate covering
HA Type Hub opening (Max. 1.25 Conduit)
S22 Embossed .25 in. mounting holes (3 places)
2 0.25 dia. K.O’s
3 K.O.’s for Conduit 0.5-0.75-1 in.
S20 Embossed .25 in. mounting holes (3 places)
2 0.25 dia. K.O’s
2 K.O.’s for Conduit 0.5-0.75-1 in.
S21 Embossed .25 in. mounting holes (3 places)
2 0.25 dia. K.O’s
5 K.O.’s for Conduit 0.5-0.75-1 in.
*For inches / millimeters conversion, multiply inches by 25.4.
Siemens Industry Inc., Industrial Control Catalog 18/29
Safety Switches
Special Application: Non-Metallic
Dimensions
Non-Metallic
SWITCHES 18
Catalog
Dimensions (Inches) Non-Metallic
Number
H
W
D
A
B
C
E
F
G
HF321NX
18.75
12.11
10.25
16.59
10.97
7.00
17.50
1.98
.46
HF322NX
18.75
12.11
10.25
16.59
10.97
7.00
17.50
1.98
.46
HF361NXa
18.75
12.11
10.25
16.59
10.97
7.00
17.50
1.98
.46
HF362NXa
18.75
12.11
10.25
16.59
10.97
7.00
17.50
1.98
.46
HF363NXa
26.95
14.87
13.25
24.84
13.72
6.25
25.75
3.75
.46
HF364NXa
33.41
27.47
13.19
31.31
26.31
18.50
32.25
3.91
.47
HNF361Xa 18.75
12.11
10.25
16.59
10.97
7.00
17.50
1.98
.46
HNF362Xa
18.75
12.11
10.25
16.59
10.97
7.00
17.50
1.98
.46
HNF363Xa
26.95
14.87
13.25
24.84
13.72
6.25
25.75
3.75
.46
HNF364Xa
33.41
27.47
13.19
31.31
26.31
18.50
32.25
3.91
.47
J
9.20 9.20 9.20 9.20 12.15 12.10
9.20 9.20 12.15 12.10
VBII Interlocked Receptacle Switches
Ampere
Dimensions (Inches)
Rating
A
B
C
D
E
F
G
Cr-H Type Fusible (240 & 600V)
30
14.27
7.42
9.02 6.22
1.52
6.1
6.0
60
16.27
9.17 11.47 6.34
1.52
6.4
7.4
100
21.96
9.65 12.02 6.80
1.52
6.5
7.6
Cr-H Type Non-Fusible (600V max.)
30
14.27
7.42
9.02 6.22
1.52
6.1
6.0
60
16.27
9.17 11.47 6.34
1.52
6.4
7.4
100
21.96
9.65 12.02 6.80
1.52
6.5
7.6
Pyle-National Type Fusible (240 & 600V)
30
14.27
7.42
9.02 6.22
1.52
3.5
3.0
60
16.27
9.17 11.47 6.34
1.52
5.0
4.5
Pyle-National Type Non-Fusible (600V max.)
30
14.27
7.42
9.02a 6.22
1.52
3.5
3.0
60
16.27
9.17 11.47a 6.34
1.52
5.0
4.5
*For inches / millimeters conversion, multiply inches by 25.4.
a Dimensions also apply to “L” suffix switches (less lugs).
18/30 Siemens Industry Inc., Industrial Control Catalog
Safety Switches
Special Application: 4-Pole & 6-Pole
Dimensions
4 & 6-Pole Safety Switch Dimensions Inches (mm)
Catalog Number
Enclosure
Mounting
A
B
C
D
Figure 1, 4-Pole Fusible and Non-fusible, Type 1
HNF461 HF461 HNF462 HF462 HNF463 HF463 HNF464 HF464
24.50 (622) 29.12 (740) 24.88 (632) 33.53 (852) 27.62 (702) 36.44 (926) 36.00 (914) 49.48 (1257)
9.53 (242) 9.53 (242) 11.50 (292) 11.50 (292) 12.18 (309) 12.18 (309) 19.12 (486) 19.12 (486)
6.09 (155) 6.09 (155) 6.09 (155) 6.09 (155) 6.09 (155) 6.09 (155) 6.42 (163) 6.42 (163)
Figure 2, 4 & 6-Pole Fusible Type 12/3R and 4X
19.00 (483) 23.50 (597) 19.00 (483) 27.50 (699) 19.36 (492) 28.11 (714) 30.88 (784) 45.50 (1130)
HF461J, HF661J, HF661S HF462J, HF662J, HF662S HF463J, HF663J, HF663S HF464J, HF664J, HF664S
29.50 (622) 33.53 (852) 36.44 (926) 49.48 (1257)
9.53 (242) 11.50 (292) 12.18 (309) 19.12 (486)
6.48 (165) 6.48 (165) 6.48 (165) 6.78 (172)
Figure 2, 4 & 6-Pole Non-fusible Type 12/3R and 4X
31.65 (804) 35.69 (907) 38.67 (982) 51.64 (1312)
HNF461J, HNF661J, HNF661S HNF462J, HNF662J, HNF662S HNF463J, HNF663J, HNF663S HNF464J, HNF664J, HNF664S
24.50 (622) 24.88 (632) 27.54 (700) 36.00 (914)
9.53 (242) 11.50 (292) 12.18 (309) 19.12 (486)
6.48 (165) 6.48 (165) 6.48 (165) 6.78 (172)
26.65 (667) 27.03 (687) 29.77 (756) 38.16 (969)
E
6.75 (171) 6.75 (171) 9.38 (238) 9.38 (238) 8.00 (203) 8.00 (203) 15.00 (381)
15.00 (381)
5.47 (139) 8.00 (203) 8.47 (215) 13.44 (341)
5.47 (139) 8.00 (203) 8.47 (215) 13.44 (341)
F
0.268 (7) 0.268 (7) 0.268 (7) 0.268 (7) 0.268 (7) 0.268 (7) 0.44 (11) 0.44
(11)
0.27 (7) 0.27 (7) 0.27 (7) 0.33 (8)
0.27 (7) 0.27 (7) 0.27 (7) 0.33 (8)
Figure 1: Type 1
Figure 2 : Type 12/3R and 4X
18 SWITCHES
Siemens Industry Inc., Industrial Control Catalog 18/31