JA SOLAR Solar Photovoltaic Module Instruction Manual
- June 9, 2024
- JA SOLAR
Table of Contents
Solar Photovoltaic Module
Instruction Manual
JA SOLAR INSTALLATION MANUAL
Solar Photovoltaic Module
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important safety instructions for the Solar
Photovoltaic Modules (hereafter referred to as “Modules”) of Shanghai JA Solar
Technology Co., Ltd. (hereafter referred to as “JA Solar”). Installers should
follow all safety precautions described in this guide as well as local codes
when installing a Module.
Installing solar photovoltaic systems requires specialized skills and
knowledge. Installation should only be performed by qualified personnel.
Before installing a solar photovoltaic system, installers should familiarize
themselves with its mechanical and electrical requirements. Keep this guide in
a safe place for future reference and in case of sale or disposal of the
Modules.
For any questions, please contact our Global Quality and Customer Service
department for further information.
INTRODUCTION
Thank you for choosing JA SOLAR Modules!
This Installation Manual contains essential information for electrical and
mechanical installation that you must know before handling, installing JA
Solar Modules. This Manual also contains safety information you need to be
familiar with. All the information described in this Manual is the
intellectual property of JA Solar and is based on the technologies and
experience that have been acquired and accumulated by JA Solar.
This Manual does not constitute a warranty, expressed or implied. JA Solar
does not assume responsibility and expressly disclaims liability for loss,
damage, or expense arising out of or in any way connected with installation,
operation, use or maintenance of Modules. No responsibility is assumed by JA
Solar for any infringement of patents or other rights of third parties that
may result from use of Modules. JA Solar reserves the right to make changes to
the product, specifications or installation manual without prior notice.
Failure to comply with the requirements listed in this manual will invalidate
the Limited Warranty for Modules as provided by JA Solar at the same time of
sale to the direct customer. Additional recommendations are provided to
enhance safety practices and performance results. Please provide a copy of
this manual to the PV system owner for their reference, and inform them of
all relevant aspects of safety, operation, and maintenance.
CODES AND REGULATIONS
The mechanical and electrical installation of PV systems should be performed in accordance with all applicable codes, including electrical codes, building codes and electric utility interconnect requirements. Such requirements may vary for mounting location, such as building rooftop or motor vehicle applications. Requirements may also vary with system voltage, and for DC or AC application. Contact local authorities for governing regulations.
GENERAL
Figure 1 Modules components and cross-section of the laminated assembly
1. Aluminum Frame | 2. Glass | 3. Encapsulating EVA | 4. Cell |
---|---|---|---|
5. Backsheet | 6. Silicone adhesive | 7. Junction Box | 8. Nameplate |
9. Cable | 10.Connector | 11.Mounting hole | 12.Grounding hole |
13.Drainage holes | 14.Cell |
3.1 Product Identification
Each module has three labels providing the following information:
- Nameplate: describes the product type; Peak power, Max. power current, Max. power voltage, open circuit voltage, short circuit current, all as measured under standard test conditions; Certification marks, the maximum system voltage etc.
- Current Sorting: According to the Max. power current, Modules are sorted into three classes: H,M or L(H means the highest current). And the class is marked as a symbol “Current class X” on the back sheet of the Modules. To get optimal performance of Modules, it is recommended to connect the Modules with the same class in a string.
- Barcode: each individual Module has a unique serial number. The serial number has 15 digits. The 1st and the 2nd digits are the year code, and the 3rd is the month code. For example, 121PXXXXXXXXXXX means the Module was assembled and tested in the January of 2012. It is permanently attached to the interior of the Modules and is visible from the top front of the Module. This barcode is inserted prior to laminating. In addition, you can find a same barcode beside the nameplate.
3.2 Conventional Safety
JA Solar Modules are designed to meet the requirements of IEC 61215 and IEC
61730, application class A. Modules rated for use in this application class
may be used in system operating at greater than 50V DC or 240W, where general
contact access is anticipated. Modules qualified for safety through IEC
61730-1 and IEC 61730-2 and within this application class are considered to
meet the requirements for safety class II equipment’s. When Modules are
mounted on rooftops, the roof must have a fire resistant covering suitable
for this application. Rooftop PV systems should only be installed on rooftop
that is capable of handling the additional weighted load of PV system
components, including Modules, by a certified building specialist or engineer
and have a formal structure of the complete analysis result.
For your safety, do not attempt to work on a rooftop until safety precautions
have been identified and taken including without limitation fall protection
measures, ladders or
stairways, and personal protective equipment.
For your safety, do not install or handle Modules under adverse conditions,
including without limitation strong or gusty winds, and wet or frosted roof
surfaces.
3.3 Electrical Performance Safety
Photovoltaic Modules can produce DC electricity when exposed to light and
therefore can produce an electrical shock or burn. DC voltage of 30 Volts or
higher is potentially lethal.
Modules produce voltage even when not connected to an electrical circuit or
load. Please use insulated tools and rubber gloves when working with Modules
in sunlight.
Modules have no on/off switch. Modules can be rendered inoperative only by
removing them from sunlight, or by fully covering their front surface with
cloth, cardboard, or other completely opaque material, or by working with
Modules face down on a smooth, flat surface.
In order to avoid arcs and electrical shock, please do not disconnect
electrical connections under load. Faulty connections can also result in arcs
and electrical shock. So please keep connectors dry and clean, and ensure
that they are in proper working condition. Never insert metal objects into the
connector, or modify them in any way in order to secure an electrical
connection.
Reflection from snow or water can increase sunlight and therefore boost
current and power.
In addition, colder temperatures can substantially increase voltage and power.
If the glass or other material is damaged, please wear personal protection
equipment and separated the Modules from the circuit.
Do not touch the Modules if they are wet, unless during the cleaning
procedure. If you need to clean the modules, please follow the cleaning
requirements mentioned in the manual.
Do not touch the wet connector without protecting yourself with personal
protection equipment or rubber gloves.
Do not use mirrors or other magnifiers to concentrate sunlight onto the
Modules.
3.4 Operating Safety
Do not open packages of JA Solar Modules during transportation and storing
until they are ready to be installed.
At the same time please protect the package from damage. Do make the Pallets
of Modules falling over directly.
Do not exceed the maximum height of pallets to be stacked, as indicated on the
pallet packaging.
Store pallets in a ventilated, rain-proof and dry location until the Modules
are ready to be unpacked.
Please follow
Do not lift the Modules by grasping the Module’s junction box or electrical
cables under any condition.
Do not stand or step on the Modules.
Do not drop the Modules on another Module.
Do not place any heavy objects on the Modules to avoid damaging the glasses..
Be cautious when setting the Modules down on to a surface, especially on the
corner of the Modules.
Inappropriate transportation and installation may break the Modules.
Do not attempt to disassemble the Modules, and do not remove any attached
nameplates or components from the Modules.
Do not apply paint or adhesive to the Modules top surface.
To avoid damage to the back sheet, do not scratch or hit the back sheet.
Do not drill holes in the frame. This may compromise the frame strength and
cause corrosion of the frame.
Do not scratch the anodized coating of the frame (except for grounding
connection). It may cause corrosion of the frame or compromise the frame
strength.
Do not attempt to repair the Modules with damaged glass or back sheet.
Work only under dry conditions, and use only dry tools. Do not handle Modules
when they are wet unless wearing appropriate protective equipment.
When storing uninstalled Modules outdoor for any period of time, always cover
the Modules and ensure that the glass faces down to stop water from collecting
inside the Modules and causing damage to exposed connectors.
3.5 Fire Safety
Consult your local authority for guidelines and requirements for building or
structural fire safety. JA Solar Modules have been listed as Class C according
to IEC 61730-2 standard.
For roof installations, Modules should be mounted over a fire resistant
covering suitable for this application, with adequate ventilation between the
Modules back sheet and the mounting surface.
Roof constructions and installations may affect the fire safety of building.
Improper installation may create hazards in the event of a fire.
In order to maintain the fire class rating, the distance between the Modules
frame surface (glass) and the roof surface shall be at least 10 cm.
Use appropriate components such as fuses, circuit breakers and grounding
connectors as required by local authority.
Do not use Modules where flammable gases may be generated.
INSTALLATION CONDITION
4.1 Installation Position and Working Environment
JA Solar Modules are intended for use in terrestrial applications only—no for
outer space use.
Modules must not be installed nor operated in areas where, salt, hail, snow,
sand, dust, air pollution, chemically active vapors, acid rain, soot, etc.,
are excessive.
Please adopt appropriate measures to ensure the performance and safety of the
Modules when they are installed or operated in the areas where produces heavy
snow, extremely cold, strong wind ,or near the island or desert where is
prone to produce salt fog, or near water.
Modules must be mounted on appropriate mounting structures positioned on
suitable buildings, the ground, or other structures suitable for Modules (e.g.
carports, building facades or PV trackers). Modules must not be mounted on
moving vehicles of any kind.
Modules must not be installed in locations where they could be submerged in
water.
The recommended ambient temperature should be within –20°C (-4°F) to 46°C
(115°F).
The temperature limits are defined as the monthly average high and low of the
installation site. The limit operating temperature should be–40°C (-40°F) and
85°C (185°F).
Ensure Modules are not subject to wind or snow loads exceeding the maximum
permissible loads.
The Modules should be installed in a location where there’s no shading
throughout the year. Ensure there’s no obstacle to block light near the
installation site.
Lightning protection is recommended for PV systems that are to be installed in
locations with high probability of lightning strikes.
Do not use Modules near equipment or in locations where flammable gasses may
be generated or collected.
JA Solar Modules must not be sited in locations where aggressive substances
such as salt or salt-water, or any other type of corrosive agent, could affect
the safety and/or performance of the Modules.
JA Solar Modules have passed salt mist corrosion resistance test according to
IEC 61701, but galvanic corrosion can occur between the aluminum frame of the
Modules and mounting or grounding hardware if such hardware is comprised of
dissimilar metals. JA Solar recommends that only stainless steel and aluminum
metal directly contact Modules in seaside installations to limit corrosion.
4.2 Tilt Angle Selection
The tilt angle of the Modules is measured between the surface of the Modules
and a horizontal ground surface. The Modules generates maximum power output
when it faces
the sun directly.
In the northern hemisphere, Modules should typically face south, and in the
southern hemisphere, Modules should typically face north.
For detailed information on the best installation angle, please refer to
standard solar photovoltaic installation guides or consult a reputable solar
installer or systems integrator.
In order to maintain corresponding fire rating, the angle should be not less
than 5 in/ft (127 mm/305 mm) when Modules are installed on the rooftop.
Dust building up on the surface of the Modules can impair with Modules
performance. JA solar recommends installing the Modules with a tilt angle of
at least 10 degrees, making it easier for dust to be washed off by rain.
MECHANICAL INSTALLATION
5.1 Conventional Requirement
Ensure the installation method and supporting system of Modules is strong
enough to make the Modules to able to withstand all the load conditions. The
Installer must provide this guarantee. The installation supporting system
must be tested by the third-party organization with the analysis ability of
Static Mechanical, according to the local national or international standards
such as DIN1055 or equivalent standards.
The Modules mounting structure must be made of durable, corrosion-resistant
and Resistant material.
Modules must be securely attached to the mounting structure.
In regions with heavy snowfall in winter, select the height of the mounting
system. So that the lowest edge of the Modules is not covered by snow for any
length of time. In addition, ensure that the lowest portion of the Modules is
placed high enough so that it is not shaded by plants or trees or damaged by
flying sand.
When the Modules are supported parallel to the surface of the building wall or
roof, a minimum clearance of 10 mm between the Modules frame and the surface
of the wall or the roof is required to allow air to circulate behind the
Modules and to prevent wiring damage.
Do not attempt to drill holes in the glass surface and the Modules frames of
the Modules as this will void the warranty.
Before installing Modules on a roof, ensure that the roof construction is
suitable. In addition, any roof penetration required to mount the Modules must
be properly sealed to prevent leaks.
Observe the linear thermal expansion of the Modules frames (the recommended
minimum distance between two Modules is 1 cm).
Always keep the back sheet of the panel free from foreign objects or
structural elements, which could come into contact with the panel, especially
when the panel is under mechanical load.
JA Solar Modules have been certified for a maximum static load on the back
side of 2400 Pa (i.e. wind load) and a maximum static load on the front side
of either 2400 Pa or 5400 Pa (i.e. wind and snow load), depending on the
Modules type (please refer to Figure 4 for detailed installation method.
The mounting method must not result in the direct contact of dissimilar metals
with the aluminum frame of the Modules that will result in galvanic corrosion.
An addendum to UL Standard 1703 “Flat Plate Photovoltaic Modules and Panels”
recommends metal combinations not exceed an electrochemical potential
difference of 0.6 Volts.
JA Solar Modules can be mounted in landscape or portrait orientation.
5.2 Installation Methods
Modules can be installed on the frame using mounting holes, clamps or an
insertion system. Modules must be installed according to the following
examples. Not mounting the Modules according to these instructions may void
the warranty.
5.2.1 Modules installed with mounting holes
Modules should be bolted to support structures through mounting holes located
in the frame’s back flanges. Refer to what is shown in Figure 2 (Mounting
Details).
For your reference, please use the components specified in below:
- Bolt Material: Stainless Steel Size and Length: M8*16mm
- Washer Material: Stainless Steel Size: M8
- Spring Washer Material: Stainless Steel Size: M8
- Nut Material: Stainless Steel Size: M8
Recommended torque is between 14N.m to 20N.m.
5.2.2 Modules installed with clamp
Modules should be mounted using specialized clamps as shown in Figure 3.
A) Modules should be attached on a supporting structure rail by metal clamps.
It is recommended to use the clamps under the following condition or approved
by system installation:
Size: No less than 38mm) width
Thickness: No less than 3mm
Material: Aluminum Alloy
Bolt: M8
B) Recommended bolt torque range: 18N.m to 24N.m.
C) The Modules clamps must not contact the front glass or deform the frame in
any way.
Avoid shading effects from the Modules clamps. Drainage holes on the Modules
frame must not be closed or obscured by the clamps.
5.2.3 Description of the installation position
The following low/normal level of load conditions is applicable to the
installation in most environment: the maximum static load on the back of the
Modules is 2400 Pa (i.e. wind load), and the maximum static load on the front
of the Modules is 2400 Pa (i.e. wind and snow load).
The higher level of load conditions is applicable to the installation in
extreme environment: the maximum static load on the back of the Modules is
2400 Pa (i.e. wind load) and the maximum static load on the front of the
Modules is 5400 Pa (i.e. wind and snow load), depending on the pressure level
that it would endure according to IEC standard.
For the dynamic loads, such as wind, the safety factor needs to be increased
by 3 times.
It means that the maximum dynamic load is 800 Pa when the wind speed is less
than 130 km/h.
ELECTRICAL INSTALLATION
6.1 Electrical Property
Rated electrical characteristics such as Sic, Voc and Pax are measured within
+/- 3% of measurement uncertainty at Standard Test Conditions. Standard Test
Conditions: 1000 W/m² Irradiance, 25°C Cell Temperature and 1.5 Air Mass.
Under normal conditions, photovoltaic Modules may produce higher current
and/or voltage than reported at Standard Test Conditions. Accordingly, the
values of short circuit current, Sic, and open circuit voltage, Voc, marked
on Modules should be multiplied by a factor of 1.25 when determining component
voltage ratings, conductor capacities, fusing sizes, and size of controls
connected to the Modules output.
Voltages are additive when Modules are connected directly in series, and
Modules currents are additive when Modules are connected directly in parallel,
as illustrated in Figure 5. Modules with different electrical characteristics
must not be connected directly in series.
Figure5 : Electrical diagrams of series and parallel wiring
The maximum number of Modules that can be connected in a series string must be
calculated in accordance with applicable regulations in such a way that the
specified maximum system voltage (The maximum system voltage of JA Solar
Modules is DC 1000V according to the safety appraisal of the IEC61730) of the
Modules and all other electrical DC components will not be exceeded in open-
circuit operation at the lowest temperature expected at the PV system
location.
Correction factor for the open-circuit voltage can be calculated based on the
following
formula: Civic=1-βVoc×(25-T). T is the lowest expected ambient temperature at
the system location. β(%/℃) is the temperature coefficient of the selected
module Voc (Refer to corresponding datasheet).
An appropriately rated over-current protection device must be used when the
reverse current could exceed the value of the maximum fuse rating of the
Modules. An over- current protection device is required for each series string
if more than two series strings are connected in parallel
6.2 Cables and Wiring
These junction boxes have been designed to be easily interconnected in series
for their well-connected cable and the connector with IP67 protection grade.
Each Modules has two single-conductor wires, one positive and one negative,
which are pre-wired inside the junction box. The connectors at the opposite
end of these wires allow easy series connection of adjacent Modules by firmly
inserting the positive connector of a Module into the negative connector of an
adjacent Module until the connector is fully seated.
Use field wiring with suitable cross-sectional areas that are approved for use
at the maximum short-circuit current of the Modules. JA Solar recommends
installers use only sunlight resistant cables qualified for direct current
(DC) wiring in PV systems. The minimum wire size should be 4mm2.
Rating Required Minimum Field Wiring
Testing Standard | Wire size | Temperature Rating |
---|---|---|
TÜV 2 PfG 11694 | 4mm2 | -40ºC to +90ºC |
Cables should be fixed to the mounting structure in such a way that mechanical
damage of the cable and/or the Modules is avoided. Do not apply stress to the
cables. For fixing, use appropriate means, such as sunlight resistant cable
ties and/or wire management clips specifically designed to attach to the
Modules frame. While the cables are sunlight resistant and waterproof, where
possible, avoid direct sunlight exposure and water immersion of the cables.
Keep connectors dry and clean, and ensure that connector caps are hand tight
before connecting the Modules. Do not attempt to make an electrical connection
with wet, soiled, or otherwise faulty connectors. Avoid sunlight exposure and
water immersion of the connectors. Avoid allowing connectors to rest on the
ground..
Faulty connections can result in arcs and electrical shock. Check that all
electrical connections are securely fastened. Make sure that all locking
connectors are fully engaged and locked.
6.4 Bypass Diodes
The junction boxes used with JA Solar Modules contain bypass diodes wired in
parallel with the PV cell strings. In the case of partial shading, the diodes
bypass the current generated by the non-shaded cells, thereby limiting Modules
heating and performance losses. Bypass diodes are not over-current protection
devices.
Bypass diodes divert current from the cell strings in the event of partial
shading. See Figure 7 for a diagram showing how the cell strings are
electrically connected with the diodes.
In the event of a known or suspected diode failure, installers or maintenance
providers should contact JA Solar. Never attempt to open the junction box by
yourself.
GROUNDING
JA Solar Modules use an anodic oxidized aluminum frame to resist corrosion. So
the frame of Modules must be connected to the equipment grounding conductor to
prevent thunder and static injury.
The grounding device must fully contact with the inside of the aluminum alloy,
and must penetrate the surface of the frame oxidation film.
Please don’t drill any additional grounding hole on the frame of the Modules,
otherwise JA Solar expressly disclaim liability for IN validness of the
warranty.
For optimal performance, JA Solar recommend the DC cathode of the Modules
array is connected to ground, Failure to comply with this requirement may
reduce the performance of the system.
The grounding method must not result in direct contact of dissimilar metals
with the aluminum frame of the Modules that will result in galvanic corrosion.
An addendum to UL Standard 1703 “Flat Plate Photovoltaic Modules and Panels”
recommends metal combinations not exceed an electrochemical potential
difference of 0.6 Volts.
The frame rails have pre-drilled holes marked with a grounding sign. These
holes should be used for grounding purposes and must not be used for mounting
the Modules.
The following grounding methods are available.
7.1 Grounding by Using Grounded Clamp
There is a grounding hole with 4.2 mm diameter on the edge side closer to the
middle of the back frame of the Modules. The middle line of the grounding mark
is overlapped with the grounding hole, and the direction is same as the
longer frame.
The grounding between Modules must be approved by qualified electrician. And
the grounding device must be produced by qualified electrical manufacture. The
recommended twist torque value is 2.3 Nm. A copper core in size of 12 AWG can
be used as grounding clamp. The copper wire should not be compressed during
the installation.
Figure 6: Installation Methods
Note: The figure above is using TYCO. 1954381-1 (recommended)
7.2 Grounding by Using Unused Grounding Hole
The existing grounding holes which have not been used can be used for
grounding.
A) Direct the grounding clamp to the mounting hole on the frame. Thread the
grounding clamp and the frame with grounding bolt.
B) Put the toothed gasket into the other side, then tighten and lock the nut.
The recommended torque of locking the nut is 2.0 N•M~2.2 N•M.
C) Thread the grounding clamp with grounding wire. The materiel and size of
grounding wire should meet the relevant requirements of the national, regional
and local rule, law and standard.
D) Finish the mounting with tightening the binding bolt of the grounding wire.
Figure 7: Installation Methods
7.3 Additional Third-party Grounding Devices
JA Solar Modules can be grounded using third party grounding devices so long
as they are certified for grounding Modules and the devices are installed
according to the manufacturer’ s specified instructions
OPERATION AND MAINTENANCE
It is required to perform regular inspection and maintenance of the Modules, especially within warranty scope. It is the user’s responsibility to report to the supplier regarding the damages found within 2 weeks.
8.1 Cleaning
The dust accumulated on the front transparent substrate may reduce the power
output, and may even cause regional hot-spot effect. The industrial effluents
or bird drops may be serious, and the extent of the severity depends on the
transparency of the foreign objects. It’s usually not dangerous for the
accumulated dust to reduce the sunshine,
because the light intensity is still homogeneous and the power reduction
usually is not usually obvious.
When Modules are working,there should not be environmental influence factors
to cast shadows and cover part or even all of the Modules, such as other
Modules, system support, bird drops and a lot of dust, clay or plant and so
on, these may distinctly reduce the power output. JA Solar advises that there
should be no obstructed object over the Modules surface at any time.
The cleaning frequency depends on the accumulating frequency of the fouling.
In many instances the front surfaces of the Modules will be cleaned with the
rain, and we can decrease the cleaning frequency. It is recommended to wipe
the glass surface with a wet sponge or soft cloth. Please do not clean the
glass with a cleaning agent which contains acid or alkali.
8.2 Visual Inspection of Modules
Inspect the Modules visually to find whether there are appearance defects, the
following three types need particularly special attention::
A) Whether the glass is broken;
B) Corrosion along the cells’ bus-bar.
The corrosion is caused by the dampness infiltrated into the Modules because
that the surface encapsulation materials are damaged during the installation
or transportation.
C) Whether there is burning vestige on the back sheet.
8.3 Inspection of Connector and Cable
It’s recommended to implement the following preventive maintenance every 6
months:
A) Check the encapsulation of the connector with the cable.
B) Check the sealing gel of the junction box.
PRODUCT SUPPLEMENT
1 Electrical Characteristics
The electrical characteristics are within +/-3% of the indicated values of
Sic, Voc, and Pax under Standard Test Conditions (irradiance of 1000 W/m2, AM
1.5 spectrum, and a cell temperature of 25℃).
Remarks:
“***”shows the Peak power of the Modules,It is equal to “Max Power at STC”.
“(BK)” means black Modules.
For example, “JAM5(L)-72-215/SI” means the Modules made with 72 pieces of
5-inch mono cells, and the modules’ peak power are 215W.
“JAM5(BK)(L)-72-215/SI” means the Black Modules made with 72 pieces of 5-inch
mono cells, and the modules’ peak power are 215W.
2 Design Size of Modules www.jasolar.com
JA SOLAR HOLDNGS CO., LTD.
Add:No.36,Jiang Chang San Road,Zhabei,Shanghai,China 200436
Tel:+86(21)60955999/60955888
Fax:+86(21)60955959/60955858
Hefei JA Solar Technology Co., Ltd.
Add:No.999, Chang Ning Road, Hefei Hi-tech Zone Hefei, Anhui Province, P.R.
China 230088
Tel : +86 (551) 530 5522
Fax: +86 (551) 530 5533
Shanghai JA Solar Technology Co., Ltd.
Add:E6, E8 Plot, Minhang Export Processing Zone, Feng Xian, Shanghai 201401,
China
Tel: +86(21)3718 1000 / 3718 1111
Fax: +86(21)3718 1234
Yangzhou JA Solar Technology Co., Ltd.
Add:No.1, Jianhua Road, Bali Town, Economic Development Zone, Yangzhou,
Jiangsu225000, China
Tel: +86 514 8554 8123
Fax: +86 514 8554 9999
JA Solar 11.2012 V1.1 RECYCLE
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>