TOYOTOMI THMU414-1R32 Air Conditioners Owner’s Manual

June 13, 2024
TOYOTOMI

TOYOTOMI THMU414-1R32 Air Conditioners

TOYOTOMI-THMU414-1R32-Air-Conditioners-product

Product Information

Thank you for choosing our commercial air conditioners. This Owner’s Manual contains important information for the operation and maintenance of the product. Please read this manual carefully and keep it for future reference.

To Users
Thank you for selecting our product. Please read this instruction manual carefully before installing and using the product to ensure correct usage. Some functions mentioned in this manual may only be applicable to specific product models. The illustrations and information provided are for reference purposes only. We may continuously improve and innovate the product without prior notice. We are not liable for any personal injury, property loss, or damage caused by improper operation, installation, maintenance, or violation of laws and rules mentioned in this manual. The final interpretation of this instruction manual belongs to TOYOTOMI CO, LTD.

Safety Notices:

  • Do not install the control panel in damp or sun-exposed areas.
  • Use shielded twisted pairs for signal lines and communication lines if the air conditioning unit is installed in an area subject to electromagnetic interference.
  • Ensure proper wiring of communication lines to avoid communication failures.
  • Avoid beating, tossing, or frequently assembling and disassembling the control panel.
  • Do not operate the control panel with wet hands.

General Instructions:
The Compact Type ATW Heat Pump hydria+ provides space heating, space cooling, and water heating functionalities. The control panel features various icons and menus for easy operation and control.

Home Page:

  • Space heating
  • Space cooling
  • Water heating
  • Outdoor temperature
  • Leaving water temperature of the main unit
  • Leaving water temperature of the auxiliary electric heater
  • Remote room temperature
  • Error
  • Menu
  • Card out/Failed disinfection
  • Switchover between cooling and heating
  • Child lock
  • ON/OFF

Operation Instructions:
To start the heating mode, adjust the temperature setting accordingly. The controller will regulate the heat output based on the set temperature. For water heating, refer to the specific guidelines provided in the manual.

Menu Page:
Above the menu, you will see the corresponding icon based on the mode and status of the controller. The menu options include:

  1. Current mode: Displays the current operating mode.
  2. Data: Shows the current data.
  3. Time: Displays the current time.
  4. Function setting: Allows access to the user setting page.

Thank you for choosing commercial air conditioners. Please read this Owner’s Manual carefully before operation and retain it for future reference.

To Users

Thank you for selecting this product. Please read this instruction manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve expected operating effect, we hereby instruct as below:

  1. This instruction manual is a universal manual, some functions are only applicable to particular product. All the illustrations and information in the instruction manual are only for reference.
  2. All the illustrations and information in the instruction manual are only for reference. In order to make the product better, we will continuously conduct improvement and innovation without further notice.
  3. For personal injury or property loss and damage caused by improper operation such as improper installation and debugging, unnecessary maintenance, violation of related national laws and rules and industrial standard, and violation of this instruction manual, etc., we will bear no liability
  4. The final right to interpret this instruction manual belongs to TOYOTOMI CO, LTD

Safety Notices (Please be sure to abide)

  • Do not install the control where it is damp or exposed to direct sunlight.
  • Once the air conditioning unit is installed where possibly subject to electromagnetic interference, shielded twisted pairs should be used as signal lines and other communication lines.
  • Be sure communication lines are wired to the correct ports, or normal communication would fail.
  • Do not beat, toss or frequently assemble and disassemble this control.
  • Do not operate the control with wet hands!

General

  • This display panel uses the capacitor touch screen for input operation. The valid touching area indicates the black rectangle when the display panel lights off.
  • This control panel is of high sensitivity and will response to unexpected click by the foreign matters on the display panel. Therefore, please keep it clean during operation.
  • This is a generous-purpose controller, whose control functions might not be completely the same as those of the actually purchased. As the control program will update, the actual always prevails.
Home Page

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(2\)

Notes

  • The ON/OFF icon will turn to green when the control is turned on.
  • When the control mode is “Room temperature”, the temperature displayed at the upper right corner indicates the remote room temperature; when the control mode is “leaving water temperature”, it indicates the leaving water temperature of the auxiliary electric heater under the water heating mode, or the leaving water temperature of the main unit under the cooling/heating mode or combined modes.
  • Under the combined modes, the temperature set point is for space heating or cooling. Only under the water heating mode, it is for water heating.
  • It will go back automatically to the homepage when there is no any operation in ten minutes.

Above the menu, the corresponding icon will be displayed based on the mode and status of the controller.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(4\)TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(5\)

Notes

  • The “Cooling” mode is unavailable to the heating only unit.
  • The “Hot water” mode is unavailable to the heating only unit.
  • The “Heating + Hot water” (“Hot water” takes the priority) is unavailable to the mini chiller.
  • The “Hot water + Heating” (“Heating” takes the priority) is unavailable to the mini chiller.
  • The “Cooling + Hot water” (“Hot water” takes the priority) is unavailable to the mini chiller.
  • The “Hot water + Cooling” (“Cooling” takes the priority) is unavailable to the mini chiller.
  • The “Sanitation” function is unavailable to the mini chiller.
Backlight
  • Among the general setting page, when “Back light” is set to “Energy save”, the display panel will light off when there is no operation in 5 minutes. However, it will light on again by touching any valid area.
  • When “Back light” is set to “Lighted”, the display panel will be kept lighting on. It is suggested to set it to “Energy save” so as to extend its service life.

Operation Instructions

ON/OFF

[Operation Instructions]
At the menu page, by touching ON/OFF, the unit will be turned on/off.

Notes

  • It is defaulted to be OFF upon first power-on.
  • ON/OFF operation will be memorized by setting “On/Off Memory” to be “On” at the “GENERAL.” setting page.

That is, in case of power failure the unit will resume running upon power recovery. Once “On/off Memory” is set to be “Off”, in case of power failure the unit will keep “Off” upon power recovery.

Function Setting

Operation Instructions

  1. At the menu page, by touching “FUNCTION”, it will go to the function setting page as shown in the figure below.
  2. At the function setting page, by touching the page turning key, it will access to the last or next page. When setting is finished, by touching the menu page icon, it will directly back to the menu page; by touching the back icon, it will back to the upper menu.
  3. At the function setting page, by pressing the desired function, it will access to the corresponding setting page of this option.
  4. At the function setting page of some function option, by touching “OK”, this setting will be saved; by touching the “CANCEL” key, this setting will be canceled.

Notes

  1. At the function setting page with setting of any function changed, if the function is set to be memorized upon power failure, this setting will be saved automatically and memorized upon next power-on.
    When there is submenu for the selected function option, by pressing it the control will go directly the setting page of the submenu.

  2. “NA” will be displayed for unavailable functions of the heating only units and mini chillers. When setting these functions, the controller will tell setting of this parameter is unallowed.

Function Setting

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(9\) TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(10\)

Mode

Operation Instructions
At the function setting page with the unit turned off, by touching “Mode”, it will go to the mode setting page, where desired mode can be selected. Then by touching “OK” this setting will be saved and the display panel will back to the function setting page.

Notes

  • The default mode is “Heat” upon first power-on.
  • Mode setting is allowed only when the unit is turned off, otherwise a dialog box will pop up, saying “Please turn off the system first!”
  • When the water tank is unavailable, only “Heat” and “Cool” mode are allowed.
  • When the water tank is available, “Cool”, “Heat”, “Hot water”, “Cool+ Hot water”, and “Heat+ Hot water” are allowed.
  • For the heat pump, the “Cool” mode is allowed; for the heating only unit, “Cool+ Hot water” and “Cool” are unallowable.
  • This setting can be memorized upon power failure.

Fast Hot Water

Operation Instructions
At the function setting page with the unit turned off, by touching “Fast hot water”, the display panel will go to the corresponding setting page, where desired option can be selected. Then by pressing “OK” this setting will be saved and the display panel will back to the function setting page.

Notes

  • This function can be set to “On” only when the water tank is available. When the water tank is unavailable, this function will be reserved.
  • It will be memorized upon power failure.
  • This function is unavailable to mini chillers.

Cool + Hot water

Operation Instructions
At the function setting page with the unit turned off, by touching “Cool + hot water”, the display panel will go to the corresponding setting page, where desired option can be selected. Then by pressing “OK” this setting will be saved and the display panel will back to the function setting page.

Notes

  • When the water tank is unavailable, it will be reserved; when it is unavailable, the default priority will be given to “How water”.
  • It will be memorized upon power failure.
  • This function is unavailable to mini chillers.

Heat + Hot water

Operation Instructions
At the function setting page with the unit turned off, by touching “Heat + hot water”, the display panel will go to the corresponding setting page, where desired option can be selected. Then by pressing “OK” this setting will be saved and the display panel will back to the function setting page.

Notes

  • When the water tank is unavailable, it will be reserved; when it is unavailable, the default priority will be given to “Hot water”.
  • It will be memorized upon power failure.
  • This function is unavailable to the heating only unit and the mini chiller.

Quiet Mode

Operation Instructions

  • At the function setting page with the unit turned off, by touching “Quiet mode”, there will be a choice box, where “Quiet mode can be set to “On”, “Off’, or “Timer”.
  • When it is set to “Timer”, it is also required to set the “Start timer” and “End timer”. Unless otherwise stated, otherwise time setting is all the same.

This setting will be saved by touching the corner at the upper right corner.

Notes

  • It can be set under both ON and OFF statuses, but will work only when the main unit is turned on.
  • When it is set to “On”, it will automatically back to “Off’ when the main unit is turned off; while it is set to “Timer”, this setting will remain when the main unit is turned off and can only be canceled manually. olt will be memorized upon power failure.

Weather Depend

Operation Instructions
At the function setting page, by touching “Weather depend”, there will be a choice box, where it is able to set it to “On” or “Off”, and also it is able to set the weather-dependent temperature.

Notes

  • When “Weather depend” has been activated; it cannot be deactivated by ON/OFF operation but done manually.
  • It is available to find the weather-dependent target temperature at that parameter viewing pages.
  • When this function has been activated, it is still allowed to set the room temperature, however, this setting becomes valid only when “Weather depend” has been deactivated.
  • This function can be set to “On” no matter the unit is turned on or off, but works only when the unit is turned on.
  • It works under the “Cool” or “Heat” mode. Under the “Cool +Hot water” or “Heat +Hot water” modes, it works only when the current mode is “Cool” or “Heat”. Under the “Hot water” mode, it doesn’t work.
  • Temperature setting relative to the cooling mode is allowed to the heating only unit.
  • It will be memorized upon power failure.
  • When the set point of “Upper WT-Heat”/ “Upper WT-Cool” is lower than that of the “Lower WT-Heat”/ “Lower WT-Cool”, or “Lower WT-Heat”/ “Lower WT-Cool” is higher than “Upper WT-Heat”/ “Upper WT-Cool”, a window will pop up, saying “Enter wrong!”, and then resetting is required.

Weekly Timer

Operation Instructions

  1. At the function setting page, by touching “Weekly timer”, it will go to the setting page as shown below.
  2. At the “Weekly timer” setting page, as shown in the figure below, the weekly timer can be set to “On” or “Off”.
  3. At the “Weekly timer” setting page, by touching the desired day (Monday~Sunday) it will access to the setting page of this option.
  4. At the weekday setting page, it is able to set the timer to “Valid” or “Invalid”. Also, it is able to set three timing periods, each of which can be set to “Valid” or “Invalid”.
  5. Then, by touching the “Save” icon, this setting will be saved.

Notes

  • Three periods can be set for each day. The start time should be earlier than the end time for each period, otherwise this setting will be invalid. In the same way, the latter should be earlier than the former.

  • When the weekly timer has been activated, the display panel will act based on the current mode and temperature setting.

  • Timer setting for the weekday
    “Valid” it indicates this setting works only when “Weekly timer” has been activated, unaffected by the holiday mode.

  • “Invalid” indicates this setting does not work even though the “Weekly timer” has been activated.

  • When both “Weekly timer” and “Holiday release” have been activated, setting of “Weekly timer” is invalid. Only when “Holiday release” has been deactivated, setting of “Weekly timer” works.

  • The priority sequence for timer setting from high to low is “Temperature timer”, “Clock timer”, “Preset mode” and “Weekly timer”. Setting with lower priority sequence is allowed but does not work when setting with higher priority has been activated. However, it will work when the setting with higher priority has been deactivated.

  • It will be memorized upon power failure.

Holiday Release

Operation Instructions
At the function setting page, by touching “Holiday release”, it will go to the corresponding setting page, where it can be set to “On” or “Off

Notes

  • When this function has been activated, at the ‘Weekly timer” setting page, some week day can be set to “Holiday release”. In this case, the setting of the “Weekly timer” at this day is invalid unless it has been manually set to “Valid”.
  • It will be memorized upon power failure.

Disinfection

Operation Instructions

  1. At the function setting page, access to “Disinfection” setting page.
  2. At the “Disinfection” setting page, it can select the disinfection clock, disinfection temperature and disinfection week and the corresponding setting page will pop up at the right side.
  3. Then, this setting will be saved by touching the “Save” icon.

Notes

  • This function is unavailable to mini chillers.
  • This setting can be activated only when “Water tank” is set to “With”. When “Water tank” is set to “Without”, this function will be deactivated.
  • This setting can be done no matter if the unit is turned on or off.
  • When “Emergen.mode”, “Holiday mode”, “Floor debug’, “Manual defrost”, or “Refri. recovery” has been activated, this function cannot be activated at the same time. When “Disinfection” has been activated, “Emergen. mode”, “Holiday mode”, “Floor debug” “Manual defrost”, or “Refri. recovery” setting will fail and a window will pop up, saying “Please disable the disinfect mode!” “Disinfection” can be activated no matter if the unit is turned on or off. This mode will take priority over the “Hot water” mode.
  • When disinfection operation fails, the display panel will tell “Disinfection faill”. Then, by pressing OK it will be cleared.
  • When “Disinfection” has been activated, if communication error with the indoor unit or malfunction of the water tank heater occurs, it will automatically quit.
  • It will be memorized upon power failure.

Clock Timer

Operation Instructions

  1. At the function setting page, access to the “Clock timer” setting page.
  2. At the “Clock timer” setting page, it can be set to “On” or “Off’.
  3. The option “Mode” is used to time the desired mode; “WOT-Heat” and “T-water tank” is used to set the corresponding water temperature; “Period” is used to for time setting. After that, by touching the “Save” icon, all settings will be saved.

Notes

  • When “Clock timer” has been set and “Hot water” mode is involved, in this case, if “Water tank” is changed to “Without”, “Hot water” will be automatically switched to “Heat”, and “Cool/Heat + Hot water” will be switched to “Cool/Heat”.
  • When “Weekly timer” and “Clock timer” have been set at the same time, the priority will be given to the former.
  • When the water tank is available, “Heat”, “Cool”, “Hot”, “Heat + Hot water”, and “Cool + Hot water” are allowed; however, when the water tank is unavailable, only “Heat” and “Cool” are allowed.
  • When the end time is earlier than the start time, this setting is invalid.
  • Water tank temperature can be set only when “Hot water” is involved in the operation mode.
  • The setting of “Clock timer” only works once. If this setting is needed again, it should be set again.
  • It will be deactivated when the unit is turned on manually.
  • When “Weather depend” has been activated and the mode for “Clock timer” is set to “Hot water”, “Weather depend” will be deactivated when the setting mode has been switched.
  • This function will be memorized upon power failure.

Temp. Timer

  • At the function setting page, access to the “Temp.timer” setting page.
  • At the “Temp.timer” setting page, it can be set to “On” or “Off”.

Select “Period 1″/”Period 2” and a window will pop up, where time period can be set. Then select “WT-Heat1/WT-Cool 1/2” and also a window will pop up where temperature can be set.

Notes

  • When “Weekly timer”, “Preset mode”, “Clock timer” “Temp. timer” have been set at the same time, then the latter takes the priority.
  • This setting is valid only when the unit is turned on.
  • Under the “Cool” or “Cool+Hot water” mode, the setting targets at “WT-Cool”; while under the “Heat” or “Heat+Hot water” mode, the setting targets at “WT-Heat”.
  • When start time of period 2 is the same as that of period 1, then the former takes prevalence.
  • “Temp.timer is judged based on timer.
  • During this setting, when temperature is set manually, then this setting will take prevalence.
  • Under the “Hot water” mode, this function will be reserved.
  • This function will be memorized upon power failure.

Emergen. Mode

Operation Instructions

  1. At the function setting page, set the mode to “Heat” or “Hot water”.
  2. At the function setting page, select “Emergen.mode” and set it to “On” or “Off”.
  3. When “Emergen.mode” has activated, the corresponding icon will appear at the upper side of the menu page.
  4. When the mode is not set to “Heat” or “Hot water”, the display panel will tell “Wrong running mode!”

Notes

  • The emergency mode is allowed on conditions that there is some error or protection and the compressor has stopped at least for three minutes. If the error or protection has not been recovered, the unit can access to the emergency mode through the wired controller (when the unit is off).
  • Under the emergency mode, “Hot water” or “Heat” cannot be performed at the same time.
  • When the running mode is set to “Heat”, if “Other thermal” or “Optional E-Heater” is set to “Without”, the unit will fail to access to the “Emergen. mode”.
  • When the unit performs “Heat” under “Emergen. mode” and the controller detects “HP-Water Switch”, “Auxi. heater 1”, “Auxi. heater 1”, and “Temp-AHLW”, this mode will quit at once. In the same way, when errors mentioned above occur, “Emergen. mode” cannot be activated.
  • When the unit performs “Hot water” under “Emergen. mode” and the controller detects “Auxi.-WTH”, this mode will quit at once. In the same way, when errors mentioned above occur, “Emergen. mode” cannot be activated.
  • When this function has been activated, “Weekly timer”, “Preset mode”, “Clock timer”,and “Temp timer” will be deactivated. Beside “On/Off’, “Mode”, “Quiet mode”, “Weekly timer”, “Preset mode”, “Clock timer”,and “Temp timer” operation are unavailable.
  • Under “Emergen. mode”, the thermostat does not work.
  • This function can be activated only when the unit is turned off. If dosing so with the unit keeping “On”, a window will pop up, saying “Please turn off the system first!”.
  • “Floor debug”, “Disinfection”, and “Holiday mode” cannot be activated at the same with this function. When doing so, a window will pop up, saying “Please disable the emergen. mode!”.
  • Upon power failure, “Emergen. mode” will back to “Off”.

Holiday Mode

Operation Instructions
At the function setting page, select “Holiday mode” and set it to “On” or “Off”.

Notes

  • This function can be activated only when the unit has been turned off, otherwise a prompt dialog box will pop up, saying “Please turn off the system frist!”.
  • When “Holiday mode” has been activated, the operation mode will automatically switch to “Heat”. Mode setting and “On/Off” operation through the controller will be unavailable.
  • When “Holiday mode” has been activated, the controller will automatically deactivate the “Weekly timer” and “Preset mode”and “Clock timer” and “Temp.timer”.
  • Under the “Holiday mode”, when the unit is under the control of room temperature, the set point (room temperature for heating) should be set to 10°C; when it is under the control of leaving water temperature, the set point (leaving water temperature for heating) should be 30°C.
  • When this function has been activated, “Floor debug”, “Emergen.mode”, “Disinfection”, “Manual defrost”, “Preset mode”, “Weekly timer”, “Clock timer”, and “Temp.timer” cannot be activated at the same time, meanwhile a window will pop up, saying “Please disable the holiday mode!”.
  • This function will be memorized upon power failure.

Preset Mode

Operation Instructions
At the function setting page, select “Preset mode” and go to the corresponding setting page.

At the time period setting page, each time period can be set to “Valid” or “Invalid”

The option “Mode” is used to preset the mode; “WOT-Heat” is used to set the leaving cold/hot water temperature; “Start timer”/End timer” is used to for time setting. After that, by touching the “Save” icon, all settings will be saved.

Notes

  • When “Preset mode” has been set to “Hot water” and “Water tank” is to set to “Without”, the preset “Hot water” mode will be automatically switched to “Heat”.
  • When “Weekly timer” and “Preset mode” both have been set, priority will be given to the latter.
  • When the water tank is available, the preset mode can be “Heat”, “Cool”, or “Hot water”; however, when the water tank is unavailable, the preset mode can only be “Heat” or “Cool”.
  • “Start timer” should be earlier than “End timer”, otherwise a dialog will pop up, saying “time setting wrong”.
  • The setting for “Preset mode” will works until it has been canceled manually.
  • When “Start timer” is reached, the unit will perform the preset mode. In this case, mode and temperature setting are still allowed but will not be saved to the preset mode. When “End timer” is reached, the unit will perform OFF operation.
  • This function will be memorized upon power failure.
  • When “Weather depend” has been activated and the mode for “Preset mode” is set to “Hot water”, “Weather depend” will be deactivated when the setting mode has been switched.

Error Reset

Operation Instructions
At the function setting page, by touching “Error reset”, a choice box will pop up, where by touching “OK” the error will be reset and by touching “Cancel the error will not be reset.

Notes
It can be performed only when the unit is turned off.

WiFi Reset

Operation Instructions
At the function setting page, by touching “WiFi”, a choice box will pop up, where by touching “OK”, the WiFi setting will be reset, and by touching “Cancel” the choice box will quit and WiFi will not be reset.

Reset

Operation Instructions
At the function setting page, by touching “Reset”, a choice box will pop up, where by touching “OK” all user parameter settings will be reset and by touching “Cancel” it will back to the function setting page.

Notes

  • This function is allowed only when the unit has turned off.
  • This function is valid for “Temp. timer”, “Clock timer”, “Preset mode”, “Weekly timer”, and “Weather depend”.

Child Lock

Operation Instructions

  • At the function setting page, by touching “Child Lock”, it can be set to “On” or “Off”.
  • When it is set to “On”, the controller will go back to the home page and a lock icon shown in the figure below. will be diplayed, as shown in the figure below.

In this case, the controller is locked and any touch operation does not work. By touching in for six seconds, the controller will be unlocked and touch operation will work. However, the setting of “Child Lock” will remain to be “On”, and if there is no any operation in 30 seconds, the controller will be locked again. Only when it is set to “Off”, this function will be really disenabled.

User Parameter Setting

Operation Instructions

  1. At the menu page, by touching “PARAMETER”, it will back to the parameter setting page, as shown in the figure below.
  2. At the menu setting page, by touching the page turning keys, it is able to switch to the page where the desired parameter Is.
  3. After that, this setting will be saved by touching “OK” and then the unit will run based on this setting. While this setting will give up by touching “Cancel”.

Notes

  • For parameters with different defaults under different conditions, when conditions changes, the default value also will change as the corresponding condition changes.
  • All parameters will be memorized upon power failure.

Parameter Setting

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(26\) TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(27\)

Commissioning Parameter Setting

Operation Instructions
At the menu page, by touching “Commission” and then entering the correct password (000048) in the pop-up window, the commissioning parameter page will be accessed, where the left side is for the function setting and the right side is for the parameter setting, as shown in the figure below.

Notes

  • At the commissioning parameter setting page, when the state of any function changes, the system will automatically save this change and this change will remain upon power failure.
  • Do not modify any commissioning parameter except the approved qualified servicemen, as it would give birth to adverse effects to the unit.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(29\) TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(30\)

Ctrl. state

Operation Instructions
At the commissioning parameter setting page, by touching “CtrI. state”, it can be set to “T-water out” or “T-room”

Notes

  • When “Remote sensor” is set to “With”, this setting can be set to “T-water out” or “T-room”. When “Remote sensor” is set to “Without”, this setting can only be set to “T-water out”.
  • This setting will be memorized upon power failure.

2-Way valve

Operation Instructions
At the commissioning parameter setting page, by touching “Cool 2-Way valve” or “Heat 2-Way valve”, the control panel will access to the corresponding setting page.

Notes

  • This setting is unavailable to heating only units.
  • Under “Cool”, or “Cool + Hot water” mode, “Cool 2-Way valve” will decide the status of the 2-way valve; while under “Heat” or “Heat + Hot water”, “Heat 2-Way valve” will decide the status of the 2-way valve.
  • It will be memorized upon power failure.

Solar Setting

Operation Instructions

  1. This setting is unavailable to mini chillers.
  2. At the commissioning parameter setting page, by touching “Solar setting”, the control panel will access to its submenu page.
  3. At the submenu page, “Solar setting” can be set to “With” or “Without”.
  4. At the submenu page, the “Solar heater” can be set to “On” or “Off”.

Notes

  • This setting can be done no matter if the unit is turned on or off.
  • This setting is allowed only when the water tank is available. When the water tank is unavailable, this setting will be reserved.
  • It will be memorized upon power failure.

Water Tank

Operation Instructions
At the commissioning parameter setting page, by touching “Water tank”, the control panel will access to the corresponding setting page, where “Water tank” can be set to “With” or “Without”.

Notes

  • This setting will be memorized upon power failure.
  • This setting will become valid only when the unit is turned off.

Thermostat

Operation Instructions

  1. At the commissioning parameter setting page, by touching “Thermostat”, the control panel will access to the corresponding setting page.
  2. At the “Thermostat” setting page, it can be set to “Air”, “Without”, “Air + hot water” and “Air + hot water2” When it is set to “Air”. “Air + hot water” or “Air + hot water2”, the unit will run based on the mode set by the thermostat; when it is set to “Without”, the unit will run based on the mode set by the control panel. For mini chillers, it can be set to “On” or “Off”.
  3. For mini chillers, it can be set to “On” or “Off”.

Notes

  • When “Water tank” is set to “Without”, the “Air + hot water” or “Air + hot water2” mode is unavailable.
  • When “Floor debug” and “Emergen.mode” have activated, function of the thermostat will be invalid.
  • When “Thermostat” is set to “Air”, “Air + hot water” or “Air + hot water2”, “Temp.timer” will be deactivated automatically and the unit will run based on the mode set by the thermostat. Meanwhile, mode setting and On/Off operation by the control panel will be ineffective.
  • When “Thermostat” is set to “Air”, the unit will run based on the setting of the thermostat.
  • When “Thermostat” is set to “Air + hot water”, when the thermostat is turned off, the unit can still perform the “Hot water” mode. In this case, the ON/OFF icon at the homepage does not indicate the running status of the unit. Running parameters are available at the parameter viewing pages.
  • When “Thermostat” is set to “Air + hot water”, operation priority can be set by the control panel
  • When the “Thermostat” is set to “Air + hot water?”, there are two kinds of responses for the units. For one, if CN26 receives the “OFF” signal (dry contact, OVac), the unit will take the priority to “Hot water”. Once operation conditions for “Hot water” are ready, the unit will run for “Hot water”. Then, when “Hot water” is satisfied, the unit will run on the demands of the thermostat. For the other, if CN26 has not received the “OFF” signal, the unit will run on the demands of the thermostat.
  • The status of the thermostat can be changed only when the unit is turned off.
  • When it has been activated, “Floor debug”, “Air removal”, and “Emergen.mode” are not allowed to be activated.
  • This setting will be memorized upon power failure.

Other Thermal

Operation Instructions

  1. At the commissioning parameter setting page, by touching “Other thermal”, the control panel will access to the corresponding setting page.
  2. At the “Other thermal” setting page, “Other thermal” can be set to “With” or “Without”, “T-Other switch on” can be set to the desired value. When “Other thermal” is set to “With”, it is allowed to set the operating mode for the backup thermal source.

Notes

  • This setting will be memorized upon power failure.
  • There are three working logics for it.

Logic 1

  1. The set point of other thermal should be equal to that of “WOT-Heat” in “Heat” mode and “Heat + hot water” mode; The set point should be the smaller one between “T-Water tank” +5°C and 60°C in “Hot water” mode.
  2. The water pump for other thermal must be always active under the “Heat” mode.
  3. Under the “Heat” mode, the 2-way valve will be controlled based on the setting of the control panel. During heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water pump will start but the other thermal will stop.

Under the “Hot water” mode, the 3-way valve will switch to the water tank, the water pump of the heat pump will always stop but the other thermal will start. Under the “Heat + Hot water” mode, the other thermal only works for space heating, and the electric heater of the water tank works for water heating. In this case, the 2-way valve is controlled based on the setting of the control panel, and the 3-way valve will always stop. During heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water pump will start.

Logic 2

  1. The set point of other thermal should be equal to that of “WOT-Heat” and both are or lower than 60 C in “Heat” mode and “Heat + hot water”mode; The set point should be the smaller one between “T-Water tank” +5°C and 60°C in “Hot water” mode.
  2. The water pump for other thermal must be always active under the “Heat” mode.
  3. Under the “Heat” mode, the 2-way valve will be controlled based on the setting of the control panel. During heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water pump will start but the other thermal will stop.

Under the “Hot water” mode, the 3-way valve will switch to the water tank, the water pump of the heat pump will always stop but the other thermal will start.

Under the “Heat + Hot water” mode (“Heat” takes the priority), the other thermal only works for space heating, and the electric heater of the water tank works for water heating. In this case, the 2-way valve is controlled base d on the setting of the control panel, and the 3-way valve will always stop. During heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water pump will start. Under the “Heat + Hot water” mode (“Hot water” takes the priority), the other thermal works for space heating and water heating. The other thermal will work for water heating firstly, after reached “-water tank”, other thermal turns to space heating.

Logic 3
The heat pump will only send a signal to other thermal, but all the logic of control must be “stand alone”.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(36\)

Optional E-Heater

Operation Instructions

  1. At the commissioning parameter setting page, by touching “Optional E-Heater”, the control panel will access to the corresponding setting page.
  2. At the “Optional E-Heater” setting page, it can be set to “1”, “2” or “Off”.
  3. This setting is used to compare with the ambient temperature. Different comparison results are for different status of the optional electric heater.

Notes

  • This setting will be memorized upon power failure.
  • Neither “Other thermal” or “Optional E-Heater can be activated at the same time.
  • There are two working logics for “Optional E-heater”.
    • Logic 1: the heat pump and the optional electric heater cannot be started at the same time.
    • Logic 2: the heat pump and the optional electric heater can be started at the same time when the ambient temperature is lower than T-Eheater.
  • Optional E-Heater and water tank heater won’t be started together.

Remote Sensor

Operation Instructions
At the commissioning parameter setting page, by touching “Remote sensor”, the control panel will access to the corresponding setting page, where it can be set to “With” or “Without”.

Notes

  • This setting will be memorized upon power failure.
  • Only when “Remote sensor” is set to “With”, the “Ctrl. State” can be set to “T-room”.

Air Removal

Operation Instructions
At the commissioning parameter setting page, by touching “Air removal”, the control panel will access to the corresponding setting page, where it can be set to “On” or “Off”.

Notes

  • This setting will be memorized upon power failure.
  • This setting can be done only when the unit is turned off. And when it is set to “On”, the unit is not allowed to be turned on.

Floor Debug

Operation Instructions

  1. At the commissioning parameter setting page, by touching “Floor debug”, the control panel will access to the correspondina settina page.
  2. At the setting page, “Floor debug”, “Segments”, “Period 1 temp”, “Segment time”, and “AT of segment” can be set.TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(40\)
  3. When this setting is finished, by pressing “Start” this setting will be saved and start working, and by pressing “Stop” the function will halt.

Notes

  • This function can be activated only when the unit is turned off. When it is done with the unit keeping “On”, a window will pop up, saying “Please turn off the system first!”.
  • When this function has been activated, “On/Off” operation will be deactivated. By pressing On/Off, a window will pop up, saying “Please disable the floor debug!”.
  • When “Floor debug” has been activated; “Weekly timer”, “Clock Timer”, “Temp timer” and “Preset mode” will be deactivated.
  • “Emergen. mode”, “Disinfection”, “Holiday mode”, “Manual defrost”, “Forced mode” and “Refri. recovery” cannot be activated at the same time with “Floor debug’. If doing so, a window will pop up, saying “Please disable the floor debug!”.
  • Upon power failure, “Floor debug” will back to “Off” and the runtime will be zeroed.
  • When “Floor debug” has been activated, “T-floor debug” and “Debug time” can be viewed.
  • When “Floor debug has been activated and works normally; the corresponding icon will be displayed at the upper side of the menu page.
  • Before activating “Floor debug”, make sure “Segment time” of each segment is not zero. If so, a window will pop up, saying “Segment time wrong!” In this case, “Floor debug” is allowed to be activated only when “Segment time” has changed.

Manual Defrost

Operation Instructions
At the commissioning parameter setting page, by touching “Manual defrost”, the control panel will access to the corresponding setting page.

Notes

  • This setting will not be memorized upon power failure
  • This setting can be set only when the unit has turned off. When this function has been activated, ON operation is un-allowed.
  • Defrosting will quit when the defrosting temperature goes to 20 C or the defrosting duration is equal to 10 minutes.

Force Mode

Operation Instructions

  1. At the commissioning parameter setting page, by touching “Force mode”, the control panel will access to the corresponding setting page.
  2. At the “Force mode” setting page, it can be set to “Force-cool”, ‘Force-heat”, and “Off”. When it is set to “Force-cool” or “Force-heat”, the control panel will directly go back to the menu page and response to any touching operation except the ON/OFF operation, with a window popping up, saying “The force-mode is running!”. In this case, by touching ON/OFF, “Force mode” will quit.

Notes

  • This function is allowed only when the unit has just repowered and not turned on. For the unit which once has been put into operation, this function is unavailable, alerting “Wrong operation!”
  • It will not be memorized upon power failure.

Gate-Ctrl.

Operation Instructions
At the commissioning parameter setting page, by touching “Gate-CtrI.”, the control panel will access to the corresponding setting page.

Notes

  • When “Gate-Ctrl.” has been activated; the display panel will detect the card state. When the card has inserted, the unit will run normally. When the card is drawn out, the controller will turn off the unit at once and back to the homepage. In this case, all touching operation become ineffective, and a prompt dialog box will pop up. The unit will resume normal operation until the card has inserted back and the ON/OFF status of the control panel will resume to that before the card is drawn out.
  • This setting will be memorized upon power failure.

Current Limit/ Power Limit

Operation Instructions

  1. At the commissioning parameter setting page, by touching “C/P limit”, it can be set to “Off, “Current limit” or “Power limit”.
  2. When it is set it “Off’, current limit and power limit both cannot be set. When it is set to “Current limit” or “Power limit”, they can be set.
  3. After that, this setting will be saved by touching the “Save” icon.

Notes
This setting will be memorized upon power failure.

Address

Operation Instructions
At the commissioning parameter setting page, by touching “Address”, it can be set the address.

Notes

  • It is used to set the address of the control panel for being integrated to the centralized control system.
  • This setting will be memorized upon power failure.
  • The setting range is 1~125 and 127~253.
  • The defaulted address is 1 upon first power-on.

Refrigerant Recovery

Operation Instructions
At the commissioning parameter setting page, by touching “Refri. recovery”, it will access to the refrigerant recovery page.
When “Refri. recovery” is set to “On”, the control panel will go back to the home page. At this time, any touch operation except ON/OFF will get no response, with a prompt dialog box popping up, saying “The refrigerant recovery is running!” By touching ON/OFF, refrigerant recovery will quit.

Notes

  • This function is allowed only when the unit has just repowered and not turned on. For the unit which once has been put into operation, this function is unavailable, alerting “Wrong operation”.
  • This function will not be memorized upon power failure.

Control Logic of the Water Tank Heater

Operation Instructions
At the commissioning parameter setting page, by touching “Tank heater”, it will access to the setting page of control logic for the water tank heater.

Notes

  • “Reserved” will be displayed when the water tank is unavailable.
  • This setting can be done only when the unit is off.
  • This function can be memorized upon power failure.
  • Logic 1: NEVER allowed the Unit’s Compressor and the Water Tank Electric Heater or the Optional Electric Heater to work at the same time.
  • Logic 2: While Heating/ Cooling + Hot water mode (Hot Water priority) Tset ≥ THPmax + Thot water +2, when water tank temperature reach THmax, the water tank EH will be ON and start to do hot water, at the same time, the compressor wil turn to heating/cooling mode, water tank EH and Compressor will be ON together.

Gate Control Memory

Operation Instructions
At the commissioning parameter setting page, by touching “Gate-Ctri Memory”, it will access to the setting page.

Notes

  • When it is enabled, “Gate-Ctr” will be memorized upon power failure.
  • When it is disabled, “Gate-Ctr” will not be memorized upon power failure.

3-Way valve1

Operation Instructions
At the commissioning parameter setting page, by touching “3-Way valve1”, it will access to the setting page.

Notes

  • It will be memorized upon power failure.
  • Three options are available, “Without”, “DHW”, and “AIR”.When it is set to “AIR”, it will be closed (230VAC) under the cooling/heating mode and opened under the DHW(Hot water) mode; when it is set to “DHW”, it will be closed (230VAC) under the DHW(Hot water) mode and opened under the cooling/heating mode.
  • This setting is allowed only when the unit has been turned off.

Parameter Setting

Operation Instructions
At the commissioning parameter setting page, by touching “PARAM.”, it will access to the pages as shown below.

At this page, select the desired option and then go to the corresponding page. After that, by pressing “OK”, this setting will be saved and then the unit will run based on this setting; or by pressing “Cancel”, this setting will not be saved and quit.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(43\)

Notes

  • For parameters with different defaults at different conditions, once the current condition changes, the corresponding default also will change.
  • All parameters at this page will be memorized upon power failure.
Viewing

Operation Instructions

  1. At the menu page, by touching “VIEW”, the control panel will go to the sub-menu page as shown in the figure below.

Status Viewing

Operation Instructions

  1. At the “VIEW” page, by touching “Status”, it is able to view status of the unit, as shown in the figure below.

Viewable Status

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(46\)

Parameter Viewing

Operation Instructions

  1. At the “VIEW” page, by touching “Parameter”, it is able to view each parameter of the unit, as shown in the figure below.

Viewable Parameters

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(48\)

Error Viewing

Operation Instructions
At the “VIEW” page, by touching “Error”, it is able to view errors of the unit, as shown in the figure below.

Notes

  • The control panel can display real-time errors. And at these pages, all errors will be listed here.
  • Each page displays at most 5 pieces of errors. Others can be viewed by touching the page turning keys.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(50\) TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(51\)

Error Log

Operation Instructions
At the “VIEW” page, by touching “Error log”, the control panel will go to the error log page, where it is able to view error records.

Notes

  • The error log can accommodate up to 20 pieces of error. Name and occurrence time are available for each error.
  • When error log exceeds 20, the latest will supersede the earliest.

Version Viewing

Operation Instructions
At the “VIEW” page, by touching “Version”, the control panel will go to the version view page, where it is able to view both the program version and protocol version.

General Setting

Operation Instructions

  1. At the menu page, by touching “GENERAL”, the control panel will go to the setting page, as shown in the figure below, where it is able to set “Temp.unit”, “On/off memory”, “Beeper”, “Back light”, “Time & Date” and “Language”

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(55\)

Clock Setting

Operation Instructions

  1. At the “GENERAL” setting page, by touching “Time&Data”, it will go to the setting page as shown in the figure below.
  2. The mouse roller can change the date and time value. After it, by touching the “Save” icon, this setting will be saved and directly displayed; while by touching the “Back” icon, this setting will give up and the control panel will directly go back to the “GENERAL” setting page.

Intelligent Control

As shown in the figure below, remote control via a smart phone is available for the control panel.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(58\)

Notes

  • Make sure the smart phone or tablet computer adopts standard Android or los operation system. For detailed version, please refer to the APP.
  • The Wi-Fi function doesn’t support Chinese Wi-Fi network name.
  • The devices can be connected and controlled only in Wi-Fi and 4G hotspot modes.
  • Software operation interface is universal and its control functions may not be completely corresponding to the unit. Software operation interface may vary along with APP upgrading or different operation system. Please refer to the actual program.
Installing Ewpe Smart APP

Operation Instructions

  1. Scan the following QR code with your smart phone to download and install Ewe Smart APP directly.
  2. Open Ewpe Smart APP and click “Sign up” for registration.
  3. Except sign in in the prompt interface, you can also enter the homepage and click the profile picture at the left upper corner to sign in.TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(61\)
  4. Click “+” at the right upper corner of homepage to add device.TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(62\)

After selecting “ATW Heat Pump”, the APP interface will provide relevant operation instructions.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(64\)TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(65\)

Reset the air conditioner (refer to the operation instructions in APP interface) and click “Next” to add home appliance automatically (Wi-Fi password shall be input). Or after setting and energizing the air conditioner, click “Add appliance manually” at the right upper corner to select the wireless network for controlling the device. Then confirm family Wi-Fi and arrange configuration.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(66\)

After accomplishing device reset and filling correct information, search device and arrange configuration.

Setting Main Functions
  1. Set mode and temperature.TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(69\)
  2. Click Func at the left lower corner in device operation interface to enter advanced settings.
Setting Other Functions

Click the profile picture at the left upper corner of homepage and set each function in the following menu.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(71\)

Home management
Click “Home management” to create or manage family. You can also add family members according to the registered account.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(72\)TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(73\)

Help
Click “Help” and view the operation instructions of the APP.

TOYOTOMI-THMU414-1R32-Air-Conditioners-fig- \(74\)

Feedback
Click “Feedback” to submit feedback.

OFFICIAL REPRESENTATIVE ITALY TOYOTOMI ITALIA S.R.L.

  • VIA T. EDISON, 11 20875 BURAGO DI MOLGORA (MB)
  • Tel: +39 039 6080392
  • Fax: +39 039 6080316
  • http://www.toyotomi.it

OFICIAL REPRESENTATIVE NETHERLANDS TOYOTOMI EUROPE SALES B.V.