nVent GM-TA Thermostat User Manual

June 9, 2024
nVent

RAYCHEM
GM-TA Thermostat
Installation and Operation Manual

GM-TA Thermostat

Figure B : Ambient Temp. Sensor GM-TA-AS

Precautions!

nVent RAYCHEM GM-TA is an electronic thermostat to control heating cables in roof & gutter snow melting applications. nVent recommends the use of this thermostat for roof & gutter heating circuits up to a maximum length of 30 m.

  • Electrical installation and commissioning must be done by authorised personnel.
  • To be installed and commissioned in accordance with local safety and electrical regulations.
  • Do not exceed the maximum electrical ratings for the product.

GM-TA is to be DIN-Rail mounted within an electrical enclosure (indoor installation).
The ambient temperature sensor GM-TA-AS is to be installed outside of the building but protected from direct sun light.

Functional description

The heating is switched on in accordance with the temperature range that has been set by the user. The control relay will switch ON the heating cable when the ambient temperature falls below the temperature set point (default: +2°C). If the temperature decreases below the lower temperature set point (e.g. SP1: –10°C) the control relay switches the heating cable OFF.

Installation

The GM-TA thermostat is intended for installation within a distribution panel. The thermostat is to be powered from a 230 Vac electrical supply in accordance with local electrical regulations. The heating cable and earthing connections need to be made in accordance with the circuit wiring diagram (figure C – last page).
Outdoor installation of the GM-TA thermostat is possible by using the nVent GM-TA-OUTDOOR-BOX (PCN 1244-017966) with IP65 rating.
The GM-TA-AS sensor must be installed outside the building and securely fastened to the wall (preferably north facing) (figure B). The sensor must be connected with a sensor cable (e.g. round 3 x 1,5 mm², max. 100 m) to the GM- TA thermostat.

Display

nVent GM-TA Thermostat - Figure C

A-LED Display (temperature and alarm)
0 -Off: Heating cable OFF
-On: Heating cable ON
-Blinking: Post heating or Test

  1. Program mode selection ON /OFF
  2. Reduce value (change set temperatures)
  3. Increase value (change of set temperature)

Operation

Set Point

nVent GM-TA Thermostat - Figure D

Firmware revision| Temperature set point| Display set and actual temperature

Thermostat Control Relay: On or Off Mode

nVent GM-TA Thermostat - Figure E

Parameter settings SP1; SP2; SP3 or Test

nVent GM-TA Thermostat - Figure F

Low temperature set point SP 1

nVent GM-TA Thermostat - Figure G

Post heating time SP 2

nVent GM-TA Thermostat - Figure H

Sensor correction value SP 3

nVent GM-TA Thermostat - Figure I

Test Control Relay – 30 minutes

Technical data

Technical data GM-TA (PCN 1244-017783)

Supply voltage 230 Vac, +10%/-10%, 50 Hz
Relay switching capacity Max 16 A (resistive load)
Power consumption Max 5 VA
Terminal size Max. 2,5 mm2, screwed
Storage temperature -20°C to +50°C
Operation ambient temperature range -25°C to +40°C
Switching hysteresis +/-1 K
Accuracy +/- 1,5 K incl. sensor accuracy
Programmable parameters Default
--- ---
Temperature setting range Set point : 0°C to 6°C
Lower temperature range -5°C to -25°C
Post heating time 0 to 3 hours
Operating modus On: normal operation

Off: relay off (open)
Test: relay On (30 minutes)
Enclosure thermostat

Installation| DIN-rail-mounted
IP rating| IP 20
Ambient sensor GM-TA-AS (PCN 1244-017965) included
IP rating| IP 65
Installation| Wall mounted / outdoors
Ambient sensor type| 202AT +/-1% NTC 2.0 K @ 25°C

Approvals
CE, UKCA, RoHS, REACH
Error codes

E1| Ambient sensor open circuit or short circuit / Check connections and resistance
---|---
E2| Internal error / Replace GM-TA

nVent GM-TA Thermostat - Figure K

Temp. sensor GM-TA-AS (202AT +/-1% NTC 2.0 KΩ @ 25°C)

TEMP. R (kΩ)
–40°C 32,34
–35°C 24,96
–30°C 19,48
–25°C 15,29
–20°C 12,11
–15°C 9,655
–10°C 7,763
–5°C 6,277
0°C 5,114
+5°C 4,188
+10°C 3,454
+15°C 2,862
+20°C 2,387
+30°C 1,684
+40°C 1,211

België/Belgique
Tel +32 16 21 35 02
Fax +32 16 21 36 04
salesbelux@nVent.com
Bulgaria
Tel +359 5686 6886
Fax +359 5686 6886
salesee@nVent.com
Česká Republika
Tel +420 606 069 618
czechinfo@nVent.com
Danmark
Tel +45 70 11 04 00
salesdk@nVent.com
Deutschland
Tel 0800 1818205
salesde@nVent.com
España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
ntm-sales-es@nVent.com
France
Tél 0800 906045
salesfr@nVent.com
Hrvatska
Tel +385 1 605 01 88
Fax +385 1 605 01 88
salesee@nVent.com| Italia
Tel +39 02 577 61 51
Fax +39 02 577 61 55 28
salesit@nVent.com
Lietuva/Latvija/Eesti
Tel +370 5 2136633
Fax +370 5 2330084
info.baltic@nVent.com
Magyarország
Tel +36 1 253 7617
Fax +36 1 253 7618
saleshu@nVent.com
Nederland
Tel 0800 0224978
salesnl@nVent.com
Norge
Tel +47 66 81 79 90
salesno@nVent.com
Österreich
Tel 0800 29 74 10
salesat@nVent.com
Polska
Tel +48 22 331 29 50
Fax +48 22 331 29 51
salespl@nVent.com
Republic of Kazakhstan
Tel +7 7122 32 09 68
Fax +7 7122 32 55 54
saleskz@nVent.com| Россия
Тел +7 495 926 18 85
Факс +7 495 926 18 86
salesru@nVent.com
Serbia and Montenegro
Tel +381 230 401 770
Fax +381 230 401 770
salesee@nVent.com
Schweiz/Suisse
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoBaar@nVent.com
Suomi
Puh 0800 11 67 99
salesfi@nVent.com
Sverige
Tel +46 31 335 58 00
salesse@nVent.com
Türkiye
Tel +90 560 977 6467
Fax +32 16 21 36 04
salesee@nVent.com
United Kingdom
Tel 0800 969 013
salesthermalUK@nVent.com
---|---|---

nVent.com/RAYCHEM
©2023 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its
affiliates. All other trademarks are the property of their respective owners. nVent reserves the right
to change specifications without notice.
RAYCHEM-IM-EU1014-GMTA-ML-2302

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals