MHI SC-SL2NA-E Air Conditioning Control System User Manual

June 10, 2024
MHI

SC-SL2NA-E Air Conditioning Control System

Technical Manual: Air Conditioning Control System – Central

Control

Product Information

The Air Conditioning Control System – Central Control is a
system that allows for the centralized control of up to 64
air-conditioning units or 16 groups of units. It includes the
SC-SL2NA-E and SC-SL3NA-AE, BE central control units.

The system can be used with both New Super Link (new SL) and
Previous Super Link (previous SL) models, depending on the
compatibility of the units connected to the network.

The system offers individual, group, or batch operation and
setting, status monitoring, program setting, and administration and
control functions.

Product Usage Instructions

Connecting Units

The number of units that can be connected to each central
control unit depends on the model and combination of units being
used. Please refer to the “Number of units” table in the user
manual for more information.

When controlling the same indoor units with a plural number of
central controls, it may affect the allowable number of indoor
units for connection. Please consult your dealer for further
details.

Operation and Setting

The system offers individual, group, or batch operation and
setting for air-conditioners up to 64 units or 16 groups. Please
refer to the user manual for instructions on how to operate and set
the system.

Status Monitoring

Status monitoring may be applied in the unit of group or
air-conditioner. Please refer to the user manual for instructions
on how to use this function.

Program Setting

The operation program can be set in the unit of group. It is
possible to register the ON/OFF time or ON time + Temperature
setting at 4 times a day. Operation time can be designated in the
unit of minute. Please refer to the user manual for instructions on
how to program the system.

Administration and Control

The system offers administration and control functions. Please
refer to the user manual for instructions on how to use this
function.

Installation

When installing the system, make sure to separate the power
supply wire and signal wire to prevent malfunctions. Follow the
installation procedure outlined in the user manual, which includes
connecting the power supply wire, signal wire, and electrical
box.

TECHNICAL MANUAL

Manual No. ’10 · SC-T-154

AIR CONDITIONING CONTROL SYSTEM

CENTRAL CONTROL

SC-SL2NA-E SC-SL3NA-AE SC-SL3NA-BE

’10 · SC-T-154
CONTENTS
1 CENTRAL CONTROL SC-SL2NA-E …………………………………………………………2 2 CENTRAL CONTROL SC- SL3NA-AE and SC-SL3NA-BE ……………………….10 3 TROUBLESHOOTING …………………………………………………………………………..36 4 CONNECTION EXAMPLE ……………………………………………………………………..38

Number of units in combinations of SC-SL1N-E, SC-SL2NA-E and SC-SL3NA-AE, BE (per system)

In case of new SL (Super Link)

SC-SL3NA-AE, BE 0 0 0 0 0 0 1 1 1 1 1 2 2 2 2 2 2

SC-SL2NA-E

0 1 2 3 4 5~8 1 2 3 4 5~8 0 1 2 3 4 5~8

In case of previous SL

SC-SL3NA-AE, BE 0 0 0 0 1

SC-SL2NA-E

0 1 2 3 1 (3)(1)

Notes (1) In case of previous SL, since SC-SL3NA-AE, BE is for connection of 3 Super Link systems, one unit of SC-SL2NA-E can be connected to each system.
(2) Number of units in combination as shown above is applicable to when the indoor units being controlled by each central control are not duplicated. When controlling the same indoor units with a plural number of central controls, it may affect the allowable number of indoor units for connection. For further details, please consult your dealr.

Check indicator table

SL2NA-E SL3NA-AE, BE
Error code Red LED

Indoor unit control PCB Outdoor unit control PCB Location of trouble
Red LED Green LED Red LED Green LED

Description of trouble

Repair method

SL2NA-E

· Communication error (Defective communication circuit on the main unit of

Keeps flashing Stays OFF Keeps flashing Stays OFF Keeps flashing SL3NA-AE, BE SL2NA-E or SL3NA-E)

Replacement

– 1 –

1 CENTRAL CONTROL SC-SL2N-E

/

/

’10 · SC-T-154

New Super Link (new SL):

All units connected to the network are models compatible with New Super Link

(KXE6 model or later models. Central controller and I/F are from “N” models.) and

SL setting is unchanged from shipment (“New” or “AUTO”).

Previous Super Link (previous SL): Units do not meet the conditions of New SL. When even a single unit connected to

the network is an earlier model than KXE4 or the connected model is not compatible

with New SL. Setting explained in Note (5) is required.

– 2 –

PJZ000Z281

’10 · SC-T-154
– 3 –

’10 · SC-T-154
(2) Operation and setting
Operation or setting is implemented individually, in the unit of group or in a batch for air-conditioners up to 64 units or 16 groups.
(3) Status monitor
Status monitor may be applied in the unit of group or air-conditioner.
– 4 –

’10 · SC-T-154
(4) Program setting
Operation program can be set in the unit of group. It is possible to register the ON/OFF time or ON time + Temperature setting at 4 times a day. Operation time can be designated in the unit of minute.
(5) Administration and control
·
(6) Outline drawing

– 5 –

’10 · SC-T-154

(7) Installation procedure

(a)

wire, signal wire, and electrical box.

Keep the power supply wire and signal wire separated to prevent malfunctions.

(b) Open the top case by following the procedure below. Grasp the indentations on the right and left sides, and pull forward to open the cover downward. Use a phillips-head screwdriver to remove the screw. (Be careful not to lose the screw.) Open the top section in the direction 4 while gently pressing the top section.

3

3

4

(c) Connect the power supply wire to the terminal. (See section (8) Electrical wiring.)

4 2 1
(d) Use the supplied pan-head screws to secure the central control to the electrical box or control board.

(e) Use a precision screwdriver to make the control selector settings. (For details, see section (10) Control switch selection.)
(f) Peel off the protective sheet on the screen of central control.

(g) Insert the top case back into its original location in the bottom case as before, and tighten the case mounting screws [(b), ]. This completes the installation procedure.

Important Please peel off the protective sheet on the air conditioner screen when transferring the central control to the customer. Peel off before mounting the top case.

Caution The case and power supply kit are an integrated unit. Please do not separate them.

(8) Electrical wiring

For safety reasons, please use the round crimping terminals with insulated sleeves for connecting all wires to the central control.

c Please do the grounding work. Please do not connect earth line with gas pipes, water pipes, lightning rods and grounding line of

telephone.

c Please do not turn on the power supply (local switch) until all of the work is completed.

c Please wait at least two minutes after the indoor and outdoor units are turned on before turning on the power supply.

c

lamps, etc.).

c Please be sure to build the breaker which is easily accessible with building equipment’s wiring.

c Please be sure to use the supplied round crimping terminals when connecting wires to the power supply terminal block and

Super Link terminal block.

c Please use demand input device, emergency stop input device and external timer input device comply with a relevant IEC safety

standard.

– 6 –

’10 · SC-T-154

(9) Installation work

Please install the central control after turning off the power for fear of electric shock.

Please arrange or protect the wiring so that excessive force is not applied to the electrical wires.

Control PCBs (printed circuit boards) are mounted to both the top and bottom cases.

Be careful that you do not damage the PCBs when using a screwdriver and other tools.

The PCBs can be damaged by static electricity, and so be sure to discharge any static electricity accumulated on your body before

starting the work.

(a) Installation place

Please install in an indoor location that is not exposed to electromagnetic waves, water, dust, or other foreign substances.

Install in a location where the ambient temperature remains within the operating temperature range.

However, if the operating temperature range is exceeded, be sure to implement corrective measures such as installation of a

cooling fan.

Be aware that continued usage of this of this central control outside the operating temperature range can result in operation

problems.

(b) Space required for installation

– 7 –

’10 · SC-T-154

(c) In case of installing on the control board Please be sure to lock the control board to protect persons from the electric shock. Avoid usage of heat- retaining materials and heat-insulating materials because these can result in heat buildup and adversely affect the operation of the central control.

(d) In case of embedding in a wall

central control on the control board.

Caution

Please do not install devices that can cause the ambient

temperature to rise in the same control board. Also, do

not install multiple controllers in the same control board.

These can cause heat to build up and result in false

operation. If multiple central control must be installed in

the same control board, take corrective measures to ensure

that the temperature in the control board does not rise

When performing the continued installation of multiple controllers, be sure to obtain the distance between units and service

– 8 –

’10 · SC-T-154

(10) Control switch selection

It is possible to change the setting as follows by settings of the PCB switches SW1 to SW10, J1, J2, and J3 on the central control.Please change the control on site as necessary. It is recommended to change the setting by using a precise driver.

(a) Switch

Power failure compensation function selector

(b) Jumper wires

(11) Setting the control target units

Make the settings for the units to be controlled by the central control.

For the setting procedure, see the user’s manual attached to the central contrl.

At shipping, none of the units are set as target units for control, and so the units to be controlled by this

central control must be set as control target units.

Three types of settings are available.

Units are selected as control targets for central control and controlled as a group /Group setting

Units are selected as control targets for central control but not grouped

/Individual setting

Units are not selected as control targets for central control

/Not target units for control

(or units will be controlled by another central control)

Be sure to set the current time. This is needed for the program settings and error history display.

Turn on the power and press the three buttons (MENU, RESET, GROUP No. 1

initialize the setting contents.

c Group control when using multiple units This central control can control up to 64 target units (up to 48 units when using the previous Super Link setting). Multiple central controls must be installed to control 65 or more air conditioner units.

When connecting multiple central controls on a single network, any group settings can be made for each central control.

– 9 –

’10 · SC-T-154
2 CENTRAL CONTROL SC-SL3NA-AE and SC-SL3NA-BE

/ /

(2) Operation and setting
Operation and setting is implemented in group or in a batch for the maximum 128 groups (144 for previous SL).
Note (1) Operation or setting cannot be done in block.

– 10 –

PJZ000Z284

’10 · SC-T-154

New Super Link (new SL):

All units connected to the network are models compatible with New Super Link

(KXE6 model or later models. Central controller and I/F are from “N” models.) and

SL setting is unchanged from shipment (“New” or “AUTO”).

Previous Super Link (previous SL): Units do not meet the conditions of New SL. When even a single unit connected to

the network is an earlier model than KXE4 or the connected model is not compatible

with new SL.

Use the “Function setting” screen of main unit to set new or previous Super Link (new or previous SL). When the connecting network consists of previous Super Link, it is necessary to change the selection.

(3) Control selection setting
It is possible to change the setting as follows by setting on the “Function Setting”

– 11 –

(4) Status monitor
Status monitor can be applied in the unit of block, group or air-conditioner.

’10 · SC-T-154

(5) Schedule setting
This schedule can be set by each group every one minute. It is possible to register the RUN/STOP time, operation mode, remote controller Lock/Unlock setting, temperature setting at 16 times a day.(*)

(*) e.q

750
940
1000 … 2300

RUN/STOPRUN RUN/STOPSTOP RUN/STOPRUN
RUN/STOPSTOP

Lock/Unlock­ Lock/UnlockALL Lock Lock/UnlockALL Unlock
Lock/UnlockALL Lock

Operation modeCool Operation mode­ Operation mode­
Operation mode­

Set temp. 25 Set temp. ­ Set temp. ­
Set temp. ­

– 12 –

(6) Management and control
·
· ·

’10 · SC-T-154

– 13 –

(7) Outline drawing

’10 · SC-T-154

(8) Installation work

Please install the central control after turning off the power for fear of electric shock.

Please arrange or protect the wiring so that excessive force is not applied to the electrical wires.

(a) Installation place

Please install in an indoor location that is not exposed to electromagnetic waves, water, dust, or other foreign substances. The

Install in a location where the ambient temperature remains within the operating temperature range. However, if the operating

temperature range is exceeded, be sure to implement corrective measures such as installation of a cooling fan. Be aware that

continued usage of this central control outside the operating temperature range can result in operation problems.

(b) Space required for installation Please choose one of two ways.

  1. In case of installing on the control board · Please use the control board of the size of 300mm x 400mm x 120mm or larger. · Please be sure to lock the control board to protect persons from the electric shock. Avoid usage of heatretaining materials and heat-insulating materials because these can result in heat buildup and adversely affect the operation of the central control.

Caution

Please do not install devices that can cause the

ambient temperature to risea in the same control

board. Also, do not install multiple controllers in

the same control board. These can cause heat to

build up and result in false operation. If multiple

central control must be installed in the same

control board, take corrective measures to ensure

that the temperature in the control board does not

  1. In case of embedding in a wall

Please be sure to use the special box, SLA3R-BX (sold

the box is unused, the central control will not work

properly because of heat buildup inside the box.

Please be sure to use for protecting persons from the

electric shock.

the wall.

When the inside of the wall is divided and have a cavity,

please create space more than 0.08m3. Refer to the table

below.

If there is no partition on the left, right, top and bottom

of the central control, please create a space that is

105mm or deeper.

When you cannot create the sufficient space or

thickness of the wall is above 15mm, please install the

central control on the control board.

– 14 –

Outline drawing of SLA3R-BX

’10 · SC-T-154

(c) Installation procedure

  1. Remove the upper case a) Take out two screws using a cross slot screwdriver. (Don’t lose the screws) b) Pull the upper case a little forward and push above. Then, upper case can be removed.

Caution

c Embed signal wire and power supply wire in a wall beforehand.

c Connect wires to the terminal block.

c

Please do not install facing upward or at a slant.
2) In case of installing on the control board

  1. In case of embedding in a wall · Please be sure to use the special box, SLA3R-BX (sold separately).

(9) Electrical wiring

For safety reasons, please use the round crimping terminals with insulated sleeves for connecting all wires to the central control.

c Please do the grounding work. Please do not connect earth line with gas pipes, water pipes, lightning rods and grounding line of

telephone.

c Please do not turn on the power supply (local switch) until all of the work is completed.

c Please wait at least two minutes after the indoor and outdoor units are turned on before turning on the power supply.

c

lamps, etc.)

c Please be sure to build the breaker which is easily accessible with building equipment’s wiring.

c Pease be sure to use the supplied round crimped terminals when connecting wires to the power supply terminal block and Super

Link terminal block.

c

block as before. The cover is used to prevent electric shock due to accidental contact.

c Please use a gas meter or wattmeter, demand input device and emergency stop input device which comply with a relevant IEC

safety Standard.

(a) Wiring outline

– 15 –

’10 · SC-T-154

(b) System wiring

  1. The upper tier of terminal block (*)

  2. The lower tier of terminal block

Caution Do not connect power supply wire to another terminal block.When you connect by mistake, damage and damage by fire of the electric part are caused, and it is very dangerous. Please check the wiring thoroughly again before it turns on power.

Caution

· the meter with pulse transmitter

· the meter with pulse width of 100ms or more

The energy consumption calculated by this central control

does not conform to OIML, and there are no guarantees

concerning the results of the calculations.

Notice Please choose the new or previous setting of Super Link (SL) in the display of SL3NA-AE (SL3NA-BE). (See user’s manual) It is necessary to change if the connection network is for previous Super Link. Whether the real connection network is new Super Link or previous Super Link depends on the type of connected indoor unit,outdoor unit,etc. Inquire the agents or dealers for more information. When the new Super Link setting, 1 system can connect up to a maximum of 128 units. Be sure to connect wiring to the Super Link terminal 1 (A1, B1). Be careful not to connect to the Super Link system 2 or 3, as SL3NA-AE (SL3NA-BE) will not be recognized.
– 16 –

’10 · SC-T-154

(c) Reset switch There is a switch to reset the power supply when the screen freezes. Data is never deleted with this switch. This central control will be reset in about 1 second.
Operating method Please push the button which is the inner part of the small hole of the underside of the upper case using the clip which is extended straight or the tool which is similar to that.

Note Please peel off the protection sheet of the screen when you pass the central control to the customers.Before you mount the upper case, please peel off the sheet.

After checking the wiring and doing reset switch operation, when the screen is not displayed, please contact the shop where the central control was purchased. This product consists of the exclusive parts, and you can not exchange the electrical equipment. Please do not disassemble other than this instruction manual stating.

(d) Other information

· This central control is electronic and independently mounted control.

· The type of this central control is automatic action for which the manufacturing deviation and the drift of its operating value,

operating time or operating sequence have not been declared, and tested under the standard.

· The actions of this central control are full-disconnection on operation, a trip-free mechanism which cannot even momentarily

be reclosed against the fault, an action which can only be reset by the use of a tool, and an action that does not require any

external auxiliary energy source of electrical supply for its intended operation.

· The rated impulse voltage (impulse withstand voltage) is 2500V.

· The surface of touch panel and front cover produce an increase of temperature of about 15 degrees.

· The lifetime of the keying of touch panel is one million times. The lifetime of LCD is about 20,000 hours. (The brightness will

become half of the starting value.)

(10) About the accounting calculation

(a) Selection

following items.

(b) Selecting the pulse unit

  1. Restrictions on the pulse input receiving side

  2. Selecting the pulse unit

Calculate the total of power supply capacity required for the air-conditioners to be connected.

Maximum operating status of air-conditioner: Estimated overload condition expected in the summer season, for example:

If it is assumed to be the total power consumption @ 1.2;

Example) Provided the total power consumption status = 100 kW and the power factor = 90%

If max. operating status = 100 @ 1.2 = 120 kW, 3-phase, 200 V

I = 120 @ 1,000/(1.732 @ 200 @ 0.9) = 385A

/ The watt-hour meter needs to have a capacity of 400 A.

If we select an oscillation device from Mitsubishi’s products of 400 A:

· K11 type ­ Select the pulse unit 100 kWh/P or 10 kWh/P

· K12 type ­ Select the pulse unit 100 kWh/P or 10 kWh/P or 1 kWh/P

  • For a further small pulse unit, consult a watt-hour meter manufacturer.

Check for when the power consumption is 120 kWh (Example)

c If 0.1 kWh/P is selected when the pulse input is the largest: 1,200 P/h = 20 P/min, which means it is 20 pulses/min, and

so this is acceptable.

c If the duty cycle decreases to 1/10 (12 kWh), for example; If 10 kWh/P is selected, 1.2 P/h = 0.02 P/min, which means

that there is no pulse within 10 minutes. It becomes 28.8 pulses for a day. If 1 kWh/P is selected, it is 12 P/h = 0.2 P/

min, which means that there are 2 pulses/10 minutes.

1 pulse a day, it is possible to use 10 kWh/P. However, since it is likely

to produce calculation errors depending on the duty cycle, it is better to use 1 kWh/P.

– 17 –

a) Maximum count number of power pulse input b) Maximum count number of gas pulse input

’10 · SC-T-154

(c) Energy consumption calculation nethod

USB memory. The base data are created on the monthly basis.

< Calculation procedure >

Accumulate operation times of respective air-conditioners. (Per minute)

Obtain the amount of operation for each air-conditioner (Ki) and accumulate it on

the basis of time zone (within business hours, overtime hours) (Per minute)

Ki = Ki + KM

KM = : Amount of operation for air-conditioner per minute

Amount of operation is calculated with the following 3

of SC-SL3NA-BE.)

Amount of operation when the value converted to the rated expansion valve aperture of air-conditioner is E:

· MULTI 1

Thermostat ON indoor unit. ( Ej)

· MULTI 2

(Ej: Conversion value of indoor unit expansion valve aperture per minute)

@ E)

· RUN/STOP (Operation time): Convert the state when the remote controller is turned ON and add he value. (Operation time @ E)

(E: Conversion value of indoor unit capacity per minute)

  • Set the same watt meter (gas meter) system at the same type.

  • If it is set at MULTI 1 or MULTI 2, indoor units in the fan mode are excluded from the proportional distribution.

If you need to include the indoor units under the fan mode in the proportional distribution, set it to RUN/STOP.

  • When the air-conditioning is not used in a day (Ex. Holiday), and thus there is no operating indoor unit to divide in proportion, the

portion of standby power does not match the value on the meter. It is necessary to re-calculate the accounting data using the spreadsheet

software.

attached to it.

· The accounting data can be output via the attached USB memory.

– 18 –

’10 · SC-T-154

In case of MULTI 1 setting: Conduct proportional distribution according to the results of a accumulated answer Hz. Accumulation is not performed when the thermo is OFF or during the Fan mode operation.

Indoor unit A 25Hz

Indoor unit B 40Hz

Indoor unit C 60Hz

Total value of operating volume (Total value of answer Hz)
Operating volume of indoor unit A = accumulated pulse counts @ power consumption per pulse @ 25/125 (25 + 40 + 60) Operating volume of indoor unit B = accumulated pulse counts @ power consumption per pulse @ 40/125 Operating volume of indoor unit C = accumulated pulse counts @ power consumption per pulse @ 60/125

In case MULTI 2 setting: Conduct proportional distribution according to the Hz corresponding to the air conditioner capacity

according to capacity).

Different from

is OFF and during the Fan mode operation.

Indoor unit A 30Hz

Indoor unit B 50Hz

Indoor unit C 70Hz

Total value of operating volume (capacity equivalent Hz @ thermo On time)
Operating volume of indoor unit A = accumulated pulse counts @ power consumption per pulse @ 30/150 (30 + 50 + 70) Operating volume of indoor unit B = accumulated pulse counts @ power consumption per pulse @ 50/150 Operating volume of indoor unit C = accumulated pulse counts @ power consumption per pulse @ 70/150

In case of RUN/STOP setting: Conduct proportional distribution according to the Hz corresponding to the air conditioner capacity

Same as

is also performed when the thermo is OFF and during the air supply operation.

Indoor unit A 40Hz

Indoor unit B 60Hz

Indoor unit C 70Hz

Total value of operating volume (capacity equivalent Hz @ remote controller ON time)
Operating volume of indoor unit A = accumulated pulse counts @ power consumption per pulse @ 40/160 (40 + 50 + 70) Operating volume of indoor unit B = accumulated pulse counts @ power consumption per pulse @ 50/160 Operating volume of indoor unit C = accumulated pulse counts @ power consumption per pulse @ 70/160

.User login For owners the fee apportionment for multi machine air conditioners is more complicated and harder to explain to customers. In many cases it’s best to use simple explanations. In addition, consumption for multi machines are calculated based on volume, making it easy for excessive cooling and differences in building load to lead to discrepancies in electricity consumption. These different values are hard to explain. Therefore, it is easier to explain how many horsepower were used for how long.
At this point, recommend [RUN/STOP] registration Both multi machines and single machines use [RUN/STOP] registration. Recommend that separate electricity meters be installed for single machine and multi machine systems. Display every unit of electricity (kW) on the electricity consumption board. For example, register P280H as 28.0. Current operational value = electricity volume @ time of operation, calculated according to the electricity volume ratio.

– 19 –

’10 · SC-T-154 (d) Software overview (SL3N-BE Utility)
SL3N-BE Utility calculates the amount of energy consumption with air conditioner’s running data saved by SC-SL3NA-BE. The amount of energy consumption is divided proportionally day by day according to the operating ratio of the air conditioner, and it is calculated as the group total amount of energy consumption for every period. 1) Flow of data processing
– 20 –

’10 · SC-T-154

  1. Function outline

c

· The operating time and the energy (electricity and gas)consumption for each air conditioner’s group.

(Microsoft® Excel, etc.).

c

· SL3

and converts them into the CSV format.

3NA-BE via USB memory,

  1. Working environment
    c Operating system Microsoft® Windows® 2000 SP3, 4 Windows® XP Windows Vista® Windows® 7
    c Hardware Pentium 300 MHz or greater 128 MB RAM 5 MB free hard disk space 1 USB (1.1 or 2.0) port
    c The screen size of SL3N-BE Utility is optimized by the following setup. 800 2 600 resolution display Small font size

  2. End user agreement

This software is for using SC-SL3NA-BE. Mitsubishi Heavy Industries, Ltd. (MHI) permits you to use two or more copies of

this software on two or more computers.

This software and SC-SL3NA-BE do not warrant the contents of the calculation result.

Please be sure to use a calculation result in the customer’s responsibility.

MHI or its suppliers are not liable for any damages whatsoever (including but not limited to damages for loss of business

Moreover, whatever the cause of failure and an obstacle, MHI cannot warrant the data saved at your memory storage (hard

disk, USB memory).

  1. Installation instructions a) Insert the CD-ROM “Air-Conditioners Management System” into your CD-ROM drive. b) Run “setup.exe” from the CD-ROM to start the installation.

– 21 –

’10 · SC-T-154 (e) Starting and quitting the software

  1. Starting the SL3N-BE Utility Double-click the short-cut icon displayed on Windows® desktop or select the program displayed on the Start menu. The Main Menu screen shown in Fig.1 will appear.
    Fig.1 Main Menu screen 2) Quitting SL3N-BE Utility
    Click [Exit] button, or [x] button of a title bar.
    – 22 –

  2. Screen changes The screen changes are shown in Fig.2.

’10 · SC-T-154

Fig.2 Screen changes and operation
– 23 –

’10 · SC-T-154

  1. Calculating energy consumption a) Start the SL3N-BE utility Double-click the short-cut icon displayed on Windows® desktop or select the program displayed on the Start menu. The Main Menu screen shown in Fig.3 will appear.

Step 1: Click [Import Accounting Data File] button on this screen.

Step 4: Click [Calculate Energy Consumption] button on this screen.

Since SL3

there is no change in a setup, you may skip Step2 and Step3. However, we recommend that you check the contents of the

setting whenever you calculate.

When you manage two or more SC-SL3NA-BEs, don’t skip Step2 and STEP3. You need to read (“Open”) the setting of each SC-SL3NA-BE’s setteings in Step2 and Step3.

Fig.3 Main Menu screen

[Import Accounting Data File]: switches to the Import Accounting Data File screen. [Calculate Energy Consumption]: switches to the Calculate Energy Consumption screen.

– 24 –

’10 · SC-T-154

Step 1: Import Accounting Data File

(2) Insert the USB memory in your personal computer.

(3

(4) Specify the year and the month to calculate.

Fig.4 Import Accounting Data File screen

[Back]: Returns to the Main Menu screen.

c

3

– 25 –

’10 · SC-T-154

c Importing Accounting Data Files

SL3

Group name, group composition

b-1: Daily operating time (minutes), calculated value of the air conditioner for each period (the basis period and the

overtime), in the Super Link system.

· File name (in case of New Super Link system):

SL3N1costYYMM.csv, SL3N2costYYMM.csv SL3N3costYYMM.csv, SL3N4costYYMM.csv

· File name (in case of previous Super Link system):

SL1SLA3costYYMM.csv, SL2SLA3costYYMM.csv

SL3SLA3costYYMM.csv

b-2: Daily cumulative pulses from meters (PI1-PI8) for each period.

· File name (in case of New Super Link system):

PLSSL3NcostYYMM.csv

· File name (in case of previous Super Link system):

PLSSLA3costYYMM.csv

YYMM means the year and the month.

3N-BE Utility”. If you have not changed

– 26 –

’10 · SC-T-154

SL3

long as there is no change.

It is possible to assign two or more meter numbers to one air conditioner’s indoor unit. It is applicable to an air-conditioning

system like a GHP (Gas Heat Pump) system that consumes different energy. It can apply, when measuring an outdoor unit

and each indoor unit with another watt-hour meter. In this case, assign meter number of an outdoor unit to indoor units.

In case of the previous Super Link system, “Unit No.” shows the “Super Link” communication line number (1 – 3) and the indoor unit number (00-47). Input the meter number (1 – 8) without a space into “Meter No.” column.

[Save]: Push this button when you want to save the current setting. [Prev]: returns to the previous SL page. Three pages of SL1 – 3 exist in this screen. [Next]: returns to the next SL page. [Back]: returns to the Main Menu screen.

Caution Setting of this screen is important when carrying out distribution calculation of the appropriate energy consumption. It is necessary to tie in setting with an actual installation situation. Please ask your installation contractor about setting.

– 27 –

’10 · SC-T-154

c First time (1) Click [New] button and input the Meter number. (3) Click [Back] button.

c 2nd hereafter You don’t have to select this menu. However, we recommend that you check the contents of the setting whenever you calculate.

c If you manage two or more SC-SL3NA-BEs

(2) Click [Back] button.

When you click [Save] button, Fig.8

[Save] button.

– 28 –

’10 · SC-T-154

SL3

as long as there is no change.

[Save]: Push this button when you want to save the current setting. [Back]: returns to the Main Menu screen.

c Caution

Setting of this screen is important when carrying out distribution calculation of the appropriate energy consumption. It

is necessary to tie in setting with an actual installation situation. Please ask your installation contractor about setting.

c First time

(1) Click [New] button and input the pulse constant.

(3) Click [Back] button.

c 2nd hereafter

You don’t have to select this menu. However, we recommend that you check the contents of the setting whenever you

calculate.

c If you manage two or more SC-SL3NA-BEs

(2) Click [Back] button.

– 29 –

’10 · SC-T-154

Step 4: Calculate Energy Consumption

SL3N-BE Utility carries out proportional division calculation based on the Monthly Data Files that imported, the Meter

Fig.10 Calculate Energy Consumption screen
[Calculate]: calculates the energy consumption. [Back]: returns to the Main Menu screen.

(1) Specify the period to calculate.

(3) Click [Calculate] button.

(4) Click [Back] button.

1. When you click the check box “The gas energy consumption”, Fig.11 dialog box will appear. If you want to change the
name that you want.

– 30 –

’10 · SC-T-154
2. When you click the check box “The electric energy consumption”, Fig.12 dialog box will appear. If you want to change
that you want.

The energy consumption in basis period every Meter number: · File name: P1ICONSUMYYMM.csv, P2ICONSUMYYMM.csv, …, P8ICONSUMYYMM.csv
The energy consumption in overtime period every Meter number: · File name: P1OCONSUMYYMM.csv, P2OCONSUMYYMM.csv, …, P8OCONSUMYYMM.csv
The running time and energy consumption every indoor unit: · File name (in case of New Super Link system): SL3N1CONSUMYYMM.csv, SL3N2CONSUMYYMM.csv, SL3N3CONSUMYYMM.csv, SL3N4CONSUMYYMM.csv · File name (in case of previous Super Link system): SL1CONSUMYYMM.csv, SL2CONSUMYYMM.csv, SL3CONSUMYYMM.csv <Note 1>
The running time and energy (electricity and gas) consumption for every group: · File name (in case of New Super Link system): NGRP1CONSUMYYMM.csv, NGRP2CONSUMYYMM.csv, NGRP3CONSUMYYMM.csv, NGRP4CONSUMYYMM.csv · File name (in case of previous Super Link system): GRPCONSUMYYMM.csv <Note 1>

YYMM means the year and the month.

3N-BE utility”. If you have not changed

<Note 1> When using Microsoft® columns. Refer to Appendix 2.

256

– 31 –

’10 · SC-T-154

*** C:¥Program Files¥SLB3EUtility¥db¥MonthE0503. csv (02/05 – 03/14)

Group No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

Group Name 1F ENTRANCE GATE 1F ENT. HALL STH 1F ENT. HALL NRTH 1F ENT. HALL EST 2F ENTRANCE ELV. 2F PASSAGE NORTH 2F PASSAGE SOUTH 3F ENTRANCE ELV. 3F PASSAGE NORTH 3F PASSAGE SOUTH 4F ENTRANCE ELV. 4F PASSAGE NORTH 4F PASSAGE SOUTH 5F ENTRANCE ELV. 5F PASSAGE NORTH 5F PASSAGE SOUTH 6F ENTRANCE ELV. 6F PASSAGE NORTH 6F PASSAGE SOUTH 7F EMTRANCE ELV. 7F PASSAGE NORTH 7F PASSAGE SOUTH 8F ENTRANCE ELV. 8F PASSAGE NORTH 8F PASSAGE SOUTH MHIE OFFlCE #1 MHIE OFFlCE #2 MHIE OFFlCE #3 MHIE CONF. ROOM 1 MHIE CONF. ROOM 2 MHIE CONF. ROOM 3 MHlS OFFICE #1 MHlS OFFICE #2 MEE OFFICE #1 MEE OFFICE #2 MEE OFFICE #3 MEE OFFICE #4 MCFE OFFICE #1 MCFE OFFICE #2 MLP-UK OFFICE #1 MLP-UK OFFICE #2 MLP- UK OFFICE #3 MLP-UK OFFICE #4 MC OFFICE #1 MC OFFICE #2 MC OFFICE #3 MC OFFICE

4 MC CONF. ROOM 701 MC CONF. ROOM 702 MC CONF. ROOM 703 MC CONF. ROOM 710 MC

CONF. ROOM 711 unused unused unused unused uhused unused unused

Basic Period [H] 0.0 0.0 0.0
870.0 31.7
650.8 1057.4
287.1 806.7 388.2
3.2 484.2 485.4 133.2 169.3 434.6
0.0 623.4 647.5 211.5 535.8 615.0
0.0 462.1 462.1 171.0 490.0
7.7 267.8 267.9
0.1 0.4 219.3 438.4 437.3 218.7 124.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Overtime [H] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

– 32 –

Basic Period [kWh] 0.000 0.000 0.000
1595.992 65.959
1119.757 1657.156
471.401 1226.261
654.044 5.689
868.573 1124.734
326.014 325.835 874.511
0.000 1129.392 1100.648
322.490 809.279 1124.523
0.000 710.040 710.040 293.380 1012.432
11.402 458.081 458.081
0.000 0.000 3.681 7.362 6.248 3.124 173.841 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

Overtime [H] 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

® Excel

’10 · SC-T-154

  1. Choose the “Import External Data” menu and the “Import Data…” menu in the menu bar.

– 33 –

’10 · SC-T-154 3

] button.

  1. Select “Comma” in the “Delimiters” section of the dialog box, and click [Next >] button.

– 34 –

  1. Click the head column to exclude under the “Data preview”.

’10 · SC-T-154

  1. Click the last column to exclude, pressing [Shift] key (on keyboard), under the “Data preview”. Click the “Do not import column (skip)” in the “Column data format”, and click [Finish] button.

– 35 –

’10 · SC-T-154
3 TROUBLESHOOTING
A malfunction has occurred with the unit. The malfunctioning unit is stopped. Contact the shop where the unit was purchased. The shop will need the following information: “unit icon color”, “malfunction situation”, “model name of the malfunctioning unit”, “Error No. (E00)” etc.
A communication problem has occurred. Contact the shop where the unit was purchased. The shop will need the following information: “unit icon color”, “malfunction situation”, “model name of the malfunctioning unit” etc.
Clean the air filter. (See the manual attached to the air conditioning unit for the cleaning method.) Press the filter reset button after cleaning.
Regular inspection is necessary. Contact the shop where the unit was purchased. The shop will need the following information: “maintenance display color”, “unit model name” etc. * The unit number and maintenance display content can be checked on the UNIT INFORMATION screen.
It is possible that there is malfunction due to electrostatic discharge. Turn the power off, then turn it on again (power supply reset). When it does not operate normally with the procedure above, it can be assumed that the unit was damaged, so contact the shop where the unit was purchased with the “malfunction situation”.
· The backlight (illumination) is turned OFF after a fixed period of time to preserve the screen. Touch the screen. (It may take a little time for the display to reappear.)
· It is possible that there is malfunction due to electrostatic discharge. Turn the power off, then turn it on again (power supply reset). When it does not operate normally with the procedure above, it can be assumed that the unit is damaged, so contact the shop where the unit was purchased with the “malfunction situation”.
When multiple units are registered in a group, the settings for the representative unit for the group are displayed. Check the status display for each of the units. Run/Stop displays “Run” if one or more units in the group are running, and it displays “Stop” if all units are stopped.
Check the schedule settings. The group settings that have been scheduled can be changed.
The unit may get warm, but this is not a problem. When the room is hot, it gets warm more readily. Use in an environment where the temperature around it is 40°C or lower.
· If the total operating time in a day is less than 30 minutes, there has been no operation for calculating purposes. Therefore the calculating results may be a little low.
· Even if the air conditioner is not used all day long such as on a holiday, standby electricity is still consumed. If power consumption is allotted to only the operated indoor units on a pro-rated basis, standby electricity consumed on holidays is not included in the calculation result. As a result, the total calculation result becomes different from the actual power consumption. On the other hand, if power consumption of standby electricity is proportionally allotted to all indoor units including those not being operated, the total calculation result coincides with actual power consumption. However, in this case, the power consumption of standby electricity is allotted to not only the tenants actually operating indoor units but also the dummy tenants and the tenants not operating indoor units. This may cause problems among tenants so that this method has not been adopted. If there is any difference between the total calculation result and the actual power consumption, try to reallocate the power consumption to the tenants actually operating indoor units respectively by using the spreadsheet software according to the calculation results.
It is possible that either the definition file has not been saved to the USB memory or there is an error in specifying the folder to be read. Check again and then perform the operation again. If this message appears again, contact the shop where the unit was purchased.
There is a possibility that the USB memory has damaged or the files in the USB memory have damaged. Delete all the files in the USB memory and create them again. If this message appears again, contact the shop where the unit was purchased.
The USB memory may not have been fully inserted. Remove the USB memory, and reinsert it. If this message appears again, it is possible that the USB memory is damaged or the USB memory is not the attachment. Replace it with the bundled USB memory and try the operation again. If this message appears again, contact the shop where the unit was purchased.
– 36 –

’10 · SC-T-154
Contact the shop where the unit was purchased. (Re-check the communications line connections of the units.) Perform operations according to the messages on the screen or turn the power off and then on (power supply reset). If the message appears again, contact the shop where the unit was purchased. When the intake-air temperature is 0°C or less, “–” is displayed. When it differs from the display of remote controller, contact the shop where the unit was purchased. This function can be applied to the indoor units, which are the model KXE4 or later, and to the remote controller, which is the model RC-E1 or later. Make sure to select “Invalid” for the Individual Lock/Unlock on the Function setting screen. There may be inadequacy for communication line or the setting of this center console. Please contact the shop where the unit was purchased. This may possible that the central control or power system has malfunction. Please contact the shop where the unit was purchased.
– 37 –

4 CONNECTION EXAMPLE

’10 · SC-T-154

– 38 –

’10 · SC-T-154
– 39 –

AIR CONDITIONING CONTROL SYSTEM
Air-Conditioning & Refrigeration Systems Headquarters 16-5, 2-chome, Kounan, Minato-ku, Tokyo, 108-8215, Japan Fax : (03) 6716-5926
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. c Copyright MITSUBISHI HEAVY INDUSTRIES.LTD

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals