MHI SC-SL2NA-E Air Conditioning Control System User Manual
- June 10, 2024
- MHI
Table of Contents
SC-SL2NA-E Air Conditioning Control System
Technical Manual: Air Conditioning Control System – Central
Control
Product Information
The Air Conditioning Control System – Central Control is a
system that allows for the centralized control of up to 64
air-conditioning units or 16 groups of units. It includes the
SC-SL2NA-E and SC-SL3NA-AE, BE central control units.
The system can be used with both New Super Link (new SL) and
Previous Super Link (previous SL) models, depending on the
compatibility of the units connected to the network.
The system offers individual, group, or batch operation and
setting, status monitoring, program setting, and administration and
control functions.
Product Usage Instructions
Connecting Units
The number of units that can be connected to each central
control unit depends on the model and combination of units being
used. Please refer to the “Number of units” table in the user
manual for more information.
When controlling the same indoor units with a plural number of
central controls, it may affect the allowable number of indoor
units for connection. Please consult your dealer for further
details.
Operation and Setting
The system offers individual, group, or batch operation and
setting for air-conditioners up to 64 units or 16 groups. Please
refer to the user manual for instructions on how to operate and set
the system.
Status Monitoring
Status monitoring may be applied in the unit of group or
air-conditioner. Please refer to the user manual for instructions
on how to use this function.
Program Setting
The operation program can be set in the unit of group. It is
possible to register the ON/OFF time or ON time + Temperature
setting at 4 times a day. Operation time can be designated in the
unit of minute. Please refer to the user manual for instructions on
how to program the system.
Administration and Control
The system offers administration and control functions. Please
refer to the user manual for instructions on how to use this
function.
Installation
When installing the system, make sure to separate the power
supply wire and signal wire to prevent malfunctions. Follow the
installation procedure outlined in the user manual, which includes
connecting the power supply wire, signal wire, and electrical
box.
TECHNICAL MANUAL
Manual No. ’10 · SC-T-154
AIR CONDITIONING CONTROL SYSTEM
CENTRAL CONTROL
SC-SL2NA-E SC-SL3NA-AE SC-SL3NA-BE
’10 · SC-T-154
CONTENTS
1 CENTRAL CONTROL SC-SL2NA-E …………………………………………………………2 2 CENTRAL CONTROL SC-
SL3NA-AE and SC-SL3NA-BE ……………………….10 3 TROUBLESHOOTING
…………………………………………………………………………..36 4 CONNECTION EXAMPLE
……………………………………………………………………..38
Number of units in combinations of SC-SL1N-E, SC-SL2NA-E and SC-SL3NA-AE, BE (per system)
In case of new SL (Super Link)
SC-SL3NA-AE, BE 0 0 0 0 0 0 1 1 1 1 1 2 2 2 2 2 2
SC-SL2NA-E
0 1 2 3 4 5~8 1 2 3 4 5~8 0 1 2 3 4 5~8
In case of previous SL
SC-SL3NA-AE, BE 0 0 0 0 1
SC-SL2NA-E
0 1 2 3 1 (3)(1)
Notes (1) In case of previous SL, since SC-SL3NA-AE, BE is for connection of 3
Super Link systems, one unit of SC-SL2NA-E can be connected to each system.
(2) Number of units in combination as shown above is applicable to when the
indoor units being controlled by each central control are not duplicated. When
controlling the same indoor units with a plural number of central controls, it
may affect the allowable number of indoor units for connection. For further
details, please consult your dealr.
Check indicator table
SL2NA-E SL3NA-AE, BE
Error code Red LED
Indoor unit control PCB Outdoor unit control PCB Location of trouble
Red LED Green LED Red LED Green LED
Description of trouble
Repair method
SL2NA-E
· Communication error (Defective communication circuit on the main unit of
Keeps flashing Stays OFF Keeps flashing Stays OFF Keeps flashing SL3NA-AE, BE SL2NA-E or SL3NA-E)
Replacement
– 1 –
1 CENTRAL CONTROL SC-SL2N-E
/
/
’10 · SC-T-154
New Super Link (new SL):
All units connected to the network are models compatible with New Super Link
(KXE6 model or later models. Central controller and I/F are from “N” models.) and
SL setting is unchanged from shipment (“New” or “AUTO”).
Previous Super Link (previous SL): Units do not meet the conditions of New SL. When even a single unit connected to
the network is an earlier model than KXE4 or the connected model is not compatible
with New SL. Setting explained in Note (5) is required.
– 2 –
PJZ000Z281
’10 · SC-T-154
– 3 –
’10 · SC-T-154
(2) Operation and setting
Operation or setting is implemented individually, in the unit of group or in a
batch for air-conditioners up to 64 units or 16 groups.
(3) Status monitor
Status monitor may be applied in the unit of group or air-conditioner.
– 4 –
’10 · SC-T-154
(4) Program setting
Operation program can be set in the unit of group. It is possible to register
the ON/OFF time or ON time + Temperature setting at 4 times a day. Operation
time can be designated in the unit of minute.
(5) Administration and control
·
(6) Outline drawing
– 5 –
’10 · SC-T-154
(7) Installation procedure
(a)
wire, signal wire, and electrical box.
Keep the power supply wire and signal wire separated to prevent malfunctions.
(b) Open the top case by following the procedure below. Grasp the indentations on the right and left sides, and pull forward to open the cover downward. Use a phillips-head screwdriver to remove the screw. (Be careful not to lose the screw.) Open the top section in the direction 4 while gently pressing the top section.
3
3
4
(c) Connect the power supply wire to the terminal. (See section (8) Electrical wiring.)
4 2 1
(d) Use the supplied pan-head screws to secure the central control to the
electrical box or control board.
(e) Use a precision screwdriver to make the control selector settings. (For
details, see section (10) Control switch selection.)
(f) Peel off the protective sheet on the screen of central control.
(g) Insert the top case back into its original location in the bottom case as before, and tighten the case mounting screws [(b), ]. This completes the installation procedure.
Important Please peel off the protective sheet on the air conditioner screen when transferring the central control to the customer. Peel off before mounting the top case.
Caution The case and power supply kit are an integrated unit. Please do not separate them.
(8) Electrical wiring
For safety reasons, please use the round crimping terminals with insulated sleeves for connecting all wires to the central control.
c Please do the grounding work. Please do not connect earth line with gas pipes, water pipes, lightning rods and grounding line of
telephone.
c Please do not turn on the power supply (local switch) until all of the work is completed.
c Please wait at least two minutes after the indoor and outdoor units are turned on before turning on the power supply.
c
lamps, etc.).
c Please be sure to build the breaker which is easily accessible with building equipment’s wiring.
c Please be sure to use the supplied round crimping terminals when connecting wires to the power supply terminal block and
Super Link terminal block.
c Please use demand input device, emergency stop input device and external timer input device comply with a relevant IEC safety
standard.
– 6 –
’10 · SC-T-154
(9) Installation work
Please install the central control after turning off the power for fear of electric shock.
Please arrange or protect the wiring so that excessive force is not applied to the electrical wires.
Control PCBs (printed circuit boards) are mounted to both the top and bottom cases.
Be careful that you do not damage the PCBs when using a screwdriver and other tools.
The PCBs can be damaged by static electricity, and so be sure to discharge any static electricity accumulated on your body before
starting the work.
(a) Installation place
Please install in an indoor location that is not exposed to electromagnetic waves, water, dust, or other foreign substances.
Install in a location where the ambient temperature remains within the operating temperature range.
However, if the operating temperature range is exceeded, be sure to implement corrective measures such as installation of a
cooling fan.
Be aware that continued usage of this of this central control outside the operating temperature range can result in operation
problems.
(b) Space required for installation
– 7 –
’10 · SC-T-154
(c) In case of installing on the control board Please be sure to lock the control board to protect persons from the electric shock. Avoid usage of heat- retaining materials and heat-insulating materials because these can result in heat buildup and adversely affect the operation of the central control.
(d) In case of embedding in a wall
central control on the control board.
Caution
Please do not install devices that can cause the ambient
temperature to rise in the same control board. Also, do
not install multiple controllers in the same control board.
These can cause heat to build up and result in false
operation. If multiple central control must be installed in
the same control board, take corrective measures to ensure
that the temperature in the control board does not rise
When performing the continued installation of multiple controllers, be sure to obtain the distance between units and service
– 8 –
’10 · SC-T-154
(10) Control switch selection
It is possible to change the setting as follows by settings of the PCB switches SW1 to SW10, J1, J2, and J3 on the central control.Please change the control on site as necessary. It is recommended to change the setting by using a precise driver.
(a) Switch
Power failure compensation function selector
(b) Jumper wires
(11) Setting the control target units
Make the settings for the units to be controlled by the central control.
For the setting procedure, see the user’s manual attached to the central contrl.
At shipping, none of the units are set as target units for control, and so the units to be controlled by this
central control must be set as control target units.
Three types of settings are available.
Units are selected as control targets for central control and controlled as a group /Group setting
Units are selected as control targets for central control but not grouped
/Individual setting
Units are not selected as control targets for central control
/Not target units for control
(or units will be controlled by another central control)
Be sure to set the current time. This is needed for the program settings and error history display.
Turn on the power and press the three buttons (MENU, RESET, GROUP No. 1
initialize the setting contents.
c Group control when using multiple units This central control can control up to 64 target units (up to 48 units when using the previous Super Link setting). Multiple central controls must be installed to control 65 or more air conditioner units.
When connecting multiple central controls on a single network, any group settings can be made for each central control.
– 9 –
’10 · SC-T-154
2 CENTRAL CONTROL SC-SL3NA-AE and SC-SL3NA-BE
/ /
(2) Operation and setting
Operation and setting is implemented in group or in a batch for the maximum
128 groups (144 for previous SL).
Note (1) Operation or setting cannot be done in block.
– 10 –
PJZ000Z284
’10 · SC-T-154
New Super Link (new SL):
All units connected to the network are models compatible with New Super Link
(KXE6 model or later models. Central controller and I/F are from “N” models.) and
SL setting is unchanged from shipment (“New” or “AUTO”).
Previous Super Link (previous SL): Units do not meet the conditions of New SL. When even a single unit connected to
the network is an earlier model than KXE4 or the connected model is not compatible
with new SL.
Use the “Function setting” screen of main unit to set new or previous Super Link (new or previous SL). When the connecting network consists of previous Super Link, it is necessary to change the selection.
(3) Control selection setting
It is possible to change the setting as follows by setting on the “Function
Setting”
– 11 –
(4) Status monitor
Status monitor can be applied in the unit of block, group or air-conditioner.
’10 · SC-T-154
(5) Schedule setting
This schedule can be set by each group every one minute. It is possible to
register the RUN/STOP time, operation mode, remote controller Lock/Unlock
setting, temperature setting at 16 times a day.(*)
(*) e.q
750
940
1000 … 2300
RUN/STOPRUN RUN/STOPSTOP RUN/STOPRUN
RUN/STOPSTOP
Lock/Unlock Lock/UnlockALL Lock Lock/UnlockALL Unlock
Lock/UnlockALL Lock
Operation modeCool Operation mode Operation mode
Operation mode
Set temp. 25 Set temp. Set temp.
Set temp.
– 12 –
(6) Management and control
·
· ·
’10 · SC-T-154
– 13 –
(7) Outline drawing
’10 · SC-T-154
(8) Installation work
Please install the central control after turning off the power for fear of electric shock.
Please arrange or protect the wiring so that excessive force is not applied to the electrical wires.
(a) Installation place
Please install in an indoor location that is not exposed to electromagnetic waves, water, dust, or other foreign substances. The
Install in a location where the ambient temperature remains within the operating temperature range. However, if the operating
temperature range is exceeded, be sure to implement corrective measures such as installation of a cooling fan. Be aware that
continued usage of this central control outside the operating temperature range can result in operation problems.
(b) Space required for installation Please choose one of two ways.
- In case of installing on the control board · Please use the control board of the size of 300mm x 400mm x 120mm or larger. · Please be sure to lock the control board to protect persons from the electric shock. Avoid usage of heatretaining materials and heat-insulating materials because these can result in heat buildup and adversely affect the operation of the central control.
Caution
Please do not install devices that can cause the
ambient temperature to risea in the same control
board. Also, do not install multiple controllers in
the same control board. These can cause heat to
build up and result in false operation. If multiple
central control must be installed in the same
control board, take corrective measures to ensure
that the temperature in the control board does not
- In case of embedding in a wall
Please be sure to use the special box, SLA3R-BX (sold
the box is unused, the central control will not work
properly because of heat buildup inside the box.
Please be sure to use for protecting persons from the
electric shock.
the wall.
When the inside of the wall is divided and have a cavity,
please create space more than 0.08m3. Refer to the table
below.
If there is no partition on the left, right, top and bottom
of the central control, please create a space that is
105mm or deeper.
When you cannot create the sufficient space or
thickness of the wall is above 15mm, please install the
central control on the control board.
– 14 –
Outline drawing of SLA3R-BX
’10 · SC-T-154
(c) Installation procedure
- Remove the upper case a) Take out two screws using a cross slot screwdriver. (Don’t lose the screws) b) Pull the upper case a little forward and push above. Then, upper case can be removed.
Caution
c Embed signal wire and power supply wire in a wall beforehand.
c Connect wires to the terminal block.
c
Please do not install facing upward or at a slant.
2) In case of installing on the control board
- In case of embedding in a wall · Please be sure to use the special box, SLA3R-BX (sold separately).
(9) Electrical wiring
For safety reasons, please use the round crimping terminals with insulated sleeves for connecting all wires to the central control.
c Please do the grounding work. Please do not connect earth line with gas pipes, water pipes, lightning rods and grounding line of
telephone.
c Please do not turn on the power supply (local switch) until all of the work is completed.
c Please wait at least two minutes after the indoor and outdoor units are turned on before turning on the power supply.
c
lamps, etc.)
c Please be sure to build the breaker which is easily accessible with building equipment’s wiring.
c Pease be sure to use the supplied round crimped terminals when connecting wires to the power supply terminal block and Super
Link terminal block.
c
block as before. The cover is used to prevent electric shock due to accidental contact.
c Please use a gas meter or wattmeter, demand input device and emergency stop input device which comply with a relevant IEC
safety Standard.
(a) Wiring outline
– 15 –
’10 · SC-T-154
(b) System wiring
-
The upper tier of terminal block (*)
-
The lower tier of terminal block
Caution Do not connect power supply wire to another terminal block.When you connect by mistake, damage and damage by fire of the electric part are caused, and it is very dangerous. Please check the wiring thoroughly again before it turns on power.
Caution
· the meter with pulse transmitter
· the meter with pulse width of 100ms or more
The energy consumption calculated by this central control
does not conform to OIML, and there are no guarantees
concerning the results of the calculations.
Notice Please choose the new or previous setting of Super Link (SL) in the
display of SL3NA-AE (SL3NA-BE). (See user’s manual) It is necessary to change
if the connection network is for previous Super Link. Whether the real
connection network is new Super Link or previous Super Link depends on the
type of connected indoor unit,outdoor unit,etc. Inquire the agents or dealers
for more information. When the new Super Link setting, 1 system can connect up
to a maximum of 128 units. Be sure to connect wiring to the Super Link
terminal 1 (A1, B1). Be careful not to connect to the Super Link system 2 or
3, as SL3NA-AE (SL3NA-BE) will not be recognized.
– 16 –
’10 · SC-T-154
(c) Reset switch There is a switch to reset the power supply when the screen
freezes. Data is never deleted with this switch. This central control will be
reset in about 1 second.
Operating method Please push the button which is the inner part of the small
hole of the underside of the upper case using the clip which is extended
straight or the tool which is similar to that.
Note Please peel off the protection sheet of the screen when you pass the central control to the customers.Before you mount the upper case, please peel off the sheet.
After checking the wiring and doing reset switch operation, when the screen is not displayed, please contact the shop where the central control was purchased. This product consists of the exclusive parts, and you can not exchange the electrical equipment. Please do not disassemble other than this instruction manual stating.
(d) Other information
· This central control is electronic and independently mounted control.
· The type of this central control is automatic action for which the manufacturing deviation and the drift of its operating value,
operating time or operating sequence have not been declared, and tested under the standard.
· The actions of this central control are full-disconnection on operation, a trip-free mechanism which cannot even momentarily
be reclosed against the fault, an action which can only be reset by the use of a tool, and an action that does not require any
external auxiliary energy source of electrical supply for its intended operation.
· The rated impulse voltage (impulse withstand voltage) is 2500V.
· The surface of touch panel and front cover produce an increase of temperature of about 15 degrees.
· The lifetime of the keying of touch panel is one million times. The lifetime of LCD is about 20,000 hours. (The brightness will
become half of the starting value.)
(10) About the accounting calculation
(a) Selection
following items.
(b) Selecting the pulse unit
-
Restrictions on the pulse input receiving side
-
Selecting the pulse unit
Calculate the total of power supply capacity required for the air-conditioners to be connected.
Maximum operating status of air-conditioner: Estimated overload condition expected in the summer season, for example:
If it is assumed to be the total power consumption @ 1.2;
Example) Provided the total power consumption status = 100 kW and the power factor = 90%
If max. operating status = 100 @ 1.2 = 120 kW, 3-phase, 200 V
I = 120 @ 1,000/(1.732 @ 200 @ 0.9) = 385A
/ The watt-hour meter needs to have a capacity of 400 A.
If we select an oscillation device from Mitsubishi’s products of 400 A:
· K11 type Select the pulse unit 100 kWh/P or 10 kWh/P
· K12 type Select the pulse unit 100 kWh/P or 10 kWh/P or 1 kWh/P
- For a further small pulse unit, consult a watt-hour meter manufacturer.
Check for when the power consumption is 120 kWh (Example)
c If 0.1 kWh/P is selected when the pulse input is the largest: 1,200 P/h = 20 P/min, which means it is 20 pulses/min, and
so this is acceptable.
c If the duty cycle decreases to 1/10 (12 kWh), for example; If 10 kWh/P is selected, 1.2 P/h = 0.02 P/min, which means
that there is no pulse within 10 minutes. It becomes 28.8 pulses for a day. If 1 kWh/P is selected, it is 12 P/h = 0.2 P/
min, which means that there are 2 pulses/10 minutes.
1 pulse a day, it is possible to use 10 kWh/P. However, since it is likely
to produce calculation errors depending on the duty cycle, it is better to use 1 kWh/P.
– 17 –
a) Maximum count number of power pulse input b) Maximum count number of gas pulse input
’10 · SC-T-154
(c) Energy consumption calculation nethod
USB memory. The base data are created on the monthly basis.
< Calculation procedure >Accumulate operation times of respective air-conditioners. (Per minute)
Obtain the amount of operation for each air-conditioner (Ki) and accumulate it on
the basis of time zone (within business hours, overtime hours) (Per minute)
Ki = Ki + KM
KM = : Amount of operation for air-conditioner per minute
Amount of operation is calculated with the following 3
of SC-SL3NA-BE.)
Amount of operation when the value converted to the rated expansion valve aperture of air-conditioner is E:
· MULTI 1
Thermostat ON indoor unit. ( Ej)
· MULTI 2
(Ej: Conversion value of indoor unit expansion valve aperture per minute)
@ E)
· RUN/STOP (Operation time): Convert the state when the remote controller is turned ON and add he value. (Operation time @ E)
(E: Conversion value of indoor unit capacity per minute)
-
Set the same watt meter (gas meter) system at the same type.
-
If it is set at MULTI 1 or MULTI 2, indoor units in the fan mode are excluded from the proportional distribution.
If you need to include the indoor units under the fan mode in the proportional distribution, set it to RUN/STOP.
- When the air-conditioning is not used in a day (Ex. Holiday), and thus there is no operating indoor unit to divide in proportion, the
portion of standby power does not match the value on the meter. It is necessary to re-calculate the accounting data using the spreadsheet
software.
attached to it.
· The accounting data can be output via the attached USB memory.
– 18 –
’10 · SC-T-154
In case of MULTI 1 setting: Conduct proportional distribution according to the results of a accumulated answer Hz. Accumulation is not performed when the thermo is OFF or during the Fan mode operation.
Indoor unit A 25Hz
Indoor unit B 40Hz
Indoor unit C 60Hz
Total value of operating volume (Total value of answer Hz)
Operating volume of indoor unit A = accumulated pulse counts @ power
consumption per pulse @ 25/125 (25 + 40 + 60) Operating volume of indoor unit
B = accumulated pulse counts @ power consumption per pulse @ 40/125 Operating
volume of indoor unit C = accumulated pulse counts @ power consumption per
pulse @ 60/125
In case MULTI 2 setting: Conduct proportional distribution according to the Hz corresponding to the air conditioner capacity
according to capacity).
Different from
is OFF and during the Fan mode operation.
Indoor unit A 30Hz
Indoor unit B 50Hz
Indoor unit C 70Hz
Total value of operating volume (capacity equivalent Hz @ thermo On time)
Operating volume of indoor unit A = accumulated pulse counts @ power
consumption per pulse @ 30/150 (30 + 50 + 70) Operating volume of indoor unit
B = accumulated pulse counts @ power consumption per pulse @ 50/150 Operating
volume of indoor unit C = accumulated pulse counts @ power consumption per
pulse @ 70/150
In case of RUN/STOP setting: Conduct proportional distribution according to the Hz corresponding to the air conditioner capacity
Same as
is also performed when the thermo is OFF and during the air supply operation.
Indoor unit A 40Hz
Indoor unit B 60Hz
Indoor unit C 70Hz
Total value of operating volume (capacity equivalent Hz @ remote controller ON
time)
Operating volume of indoor unit A = accumulated pulse counts @ power
consumption per pulse @ 40/160 (40 + 50 + 70) Operating volume of indoor unit
B = accumulated pulse counts @ power consumption per pulse @ 50/160 Operating
volume of indoor unit C = accumulated pulse counts @ power consumption per
pulse @ 70/160
.User login For owners the fee apportionment for multi machine air
conditioners is more complicated and harder to explain to customers. In many
cases it’s best to use simple explanations. In addition, consumption for multi
machines are calculated based on volume, making it easy for excessive cooling
and differences in building load to lead to discrepancies in electricity
consumption. These different values are hard to explain. Therefore, it is
easier to explain how many horsepower were used for how long.
At this point, recommend [RUN/STOP] registration Both multi machines and
single machines use [RUN/STOP] registration. Recommend that separate
electricity meters be installed for single machine and multi machine systems.
Display every unit of electricity (kW) on the electricity consumption board.
For example, register P280H as 28.0. Current operational value = electricity
volume @ time of operation, calculated according to the electricity volume
ratio.
– 19 –
’10 · SC-T-154 (d) Software overview (SL3N-BE Utility)
SL3N-BE Utility calculates the amount of energy consumption with air
conditioner’s running data saved by SC-SL3NA-BE. The amount of energy
consumption is divided proportionally day by day according to the operating
ratio of the air conditioner, and it is calculated as the group total amount
of energy consumption for every period. 1) Flow of data processing
– 20 –
’10 · SC-T-154
- Function outline
c
· The operating time and the energy (electricity and gas)consumption for each air conditioner’s group.
(Microsoft® Excel, etc.).
c
· SL3
and converts them into the CSV format.
3NA-BE via USB memory,
-
Working environment
c Operating system Microsoft® Windows® 2000 SP3, 4 Windows® XP Windows Vista® Windows® 7
c Hardware Pentium 300 MHz or greater 128 MB RAM 5 MB free hard disk space 1 USB (1.1 or 2.0) port
c The screen size of SL3N-BE Utility is optimized by the following setup. 800 2 600 resolution display Small font size -
End user agreement
This software is for using SC-SL3NA-BE. Mitsubishi Heavy Industries, Ltd. (MHI) permits you to use two or more copies of
this software on two or more computers.
This software and SC-SL3NA-BE do not warrant the contents of the calculation result.
Please be sure to use a calculation result in the customer’s responsibility.
MHI or its suppliers are not liable for any damages whatsoever (including but not limited to damages for loss of business
Moreover, whatever the cause of failure and an obstacle, MHI cannot warrant the data saved at your memory storage (hard
disk, USB memory).
- Installation instructions a) Insert the CD-ROM “Air-Conditioners Management System” into your CD-ROM drive. b) Run “setup.exe” from the CD-ROM to start the installation.
– 21 –
’10 · SC-T-154 (e) Starting and quitting the software
-
Starting the SL3N-BE Utility Double-click the short-cut icon displayed on Windows® desktop or select the program displayed on the Start menu. The Main Menu screen shown in Fig.1 will appear.
Fig.1 Main Menu screen 2) Quitting SL3N-BE Utility
Click [Exit] button, or [x] button of a title bar.
– 22 – -
Screen changes The screen changes are shown in Fig.2.
’10 · SC-T-154
Fig.2 Screen changes and operation
– 23 –
’10 · SC-T-154
- Calculating energy consumption a) Start the SL3N-BE utility Double-click the short-cut icon displayed on Windows® desktop or select the program displayed on the Start menu. The Main Menu screen shown in Fig.3 will appear.
Step 1: Click [Import Accounting Data File] button on this screen.
Step 4: Click [Calculate Energy Consumption] button on this screen.
Since SL3
there is no change in a setup, you may skip Step2 and Step3. However, we recommend that you check the contents of the
setting whenever you calculate.
When you manage two or more SC-SL3NA-BEs, don’t skip Step2 and STEP3. You need to read (“Open”) the setting of each SC-SL3NA-BE’s setteings in Step2 and Step3.
Fig.3 Main Menu screen
[Import Accounting Data File]: switches to the Import Accounting Data File screen. [Calculate Energy Consumption]: switches to the Calculate Energy Consumption screen.
– 24 –
’10 · SC-T-154
Step 1: Import Accounting Data File
(2) Insert the USB memory in your personal computer.
(3
(4) Specify the year and the month to calculate.
Fig.4 Import Accounting Data File screen
[Back]: Returns to the Main Menu screen.
c
3
– 25 –
’10 · SC-T-154
c Importing Accounting Data Files
SL3
Group name, group composition
b-1: Daily operating time (minutes), calculated value of the air conditioner for each period (the basis period and the
overtime), in the Super Link system.
· File name (in case of New Super Link system):
SL3N1costYYMM.csv, SL3N2costYYMM.csv SL3N3costYYMM.csv, SL3N4costYYMM.csv
· File name (in case of previous Super Link system):
SL1SLA3costYYMM.csv, SL2SLA3costYYMM.csv
SL3SLA3costYYMM.csv
b-2: Daily cumulative pulses from meters (PI1-PI8) for each period.
· File name (in case of New Super Link system):
PLSSL3NcostYYMM.csv
· File name (in case of previous Super Link system):
PLSSLA3costYYMM.csv
YYMM means the year and the month.
3N-BE Utility”. If you have not changed
– 26 –
’10 · SC-T-154
SL3
long as there is no change.
It is possible to assign two or more meter numbers to one air conditioner’s indoor unit. It is applicable to an air-conditioning
system like a GHP (Gas Heat Pump) system that consumes different energy. It can apply, when measuring an outdoor unit
and each indoor unit with another watt-hour meter. In this case, assign meter number of an outdoor unit to indoor units.
In case of the previous Super Link system, “Unit No.” shows the “Super Link” communication line number (1 – 3) and the indoor unit number (00-47). Input the meter number (1 – 8) without a space into “Meter No.” column.
[Save]: Push this button when you want to save the current setting. [Prev]: returns to the previous SL page. Three pages of SL1 – 3 exist in this screen. [Next]: returns to the next SL page. [Back]: returns to the Main Menu screen.
Caution Setting of this screen is important when carrying out distribution calculation of the appropriate energy consumption. It is necessary to tie in setting with an actual installation situation. Please ask your installation contractor about setting.
– 27 –
’10 · SC-T-154
c First time (1) Click [New] button and input the Meter number. (3) Click [Back] button.
c 2nd hereafter You don’t have to select this menu. However, we recommend that you check the contents of the setting whenever you calculate.
c If you manage two or more SC-SL3NA-BEs
(2) Click [Back] button.
When you click [Save] button, Fig.8
[Save] button.
– 28 –
’10 · SC-T-154
SL3
as long as there is no change.
[Save]: Push this button when you want to save the current setting. [Back]: returns to the Main Menu screen.
c Caution
Setting of this screen is important when carrying out distribution calculation of the appropriate energy consumption. It
is necessary to tie in setting with an actual installation situation. Please ask your installation contractor about setting.
c First time
(1) Click [New] button and input the pulse constant.
(3) Click [Back] button.
c 2nd hereafter
You don’t have to select this menu. However, we recommend that you check the contents of the setting whenever you
calculate.
c If you manage two or more SC-SL3NA-BEs
(2) Click [Back] button.
– 29 –
’10 · SC-T-154
Step 4: Calculate Energy Consumption
SL3N-BE Utility carries out proportional division calculation based on the Monthly Data Files that imported, the Meter
Fig.10 Calculate Energy Consumption screen
[Calculate]: calculates the energy consumption. [Back]: returns to the Main
Menu screen.
(1) Specify the period to calculate.
(3) Click [Calculate] button.
(4) Click [Back] button.
1. When you click the check box “The gas energy consumption”, Fig.11 dialog
box will appear. If you want to change the
name that you want.
– 30 –
’10 · SC-T-154
2. When you click the check box “The electric energy consumption”, Fig.12
dialog box will appear. If you want to change
that you want.
The energy consumption in basis period every Meter number: · File name:
P1ICONSUMYYMM.csv, P2ICONSUMYYMM.csv, …, P8ICONSUMYYMM.csv
The energy consumption in overtime period every Meter number: · File name:
P1OCONSUMYYMM.csv, P2OCONSUMYYMM.csv, …, P8OCONSUMYYMM.csv
The running time and energy consumption every indoor unit: · File name (in
case of New Super Link system): SL3N1CONSUMYYMM.csv, SL3N2CONSUMYYMM.csv,
SL3N3CONSUMYYMM.csv, SL3N4CONSUMYYMM.csv · File name (in case of previous
Super Link system): SL1CONSUMYYMM.csv, SL2CONSUMYYMM.csv, SL3CONSUMYYMM.csv
<Note 1>
The running time and energy (electricity and gas) consumption for every group:
· File name (in case of New Super Link system): NGRP1CONSUMYYMM.csv,
NGRP2CONSUMYYMM.csv, NGRP3CONSUMYYMM.csv, NGRP4CONSUMYYMM.csv · File name (in
case of previous Super Link system): GRPCONSUMYYMM.csv <Note 1>
YYMM means the year and the month.
3N-BE utility”. If you have not changed
<Note 1> When using Microsoft® columns. Refer to Appendix 2.
256
– 31 –
’10 · SC-T-154
*** C:¥Program Files¥SLB3EUtility¥db¥MonthE0503. csv (02/05 – 03/14)
Group No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59
Group Name 1F ENTRANCE GATE 1F ENT. HALL STH 1F ENT. HALL NRTH 1F ENT. HALL EST 2F ENTRANCE ELV. 2F PASSAGE NORTH 2F PASSAGE SOUTH 3F ENTRANCE ELV. 3F PASSAGE NORTH 3F PASSAGE SOUTH 4F ENTRANCE ELV. 4F PASSAGE NORTH 4F PASSAGE SOUTH 5F ENTRANCE ELV. 5F PASSAGE NORTH 5F PASSAGE SOUTH 6F ENTRANCE ELV. 6F PASSAGE NORTH 6F PASSAGE SOUTH 7F EMTRANCE ELV. 7F PASSAGE NORTH 7F PASSAGE SOUTH 8F ENTRANCE ELV. 8F PASSAGE NORTH 8F PASSAGE SOUTH MHIE OFFlCE #1 MHIE OFFlCE #2 MHIE OFFlCE #3 MHIE CONF. ROOM 1 MHIE CONF. ROOM 2 MHIE CONF. ROOM 3 MHlS OFFICE #1 MHlS OFFICE #2 MEE OFFICE #1 MEE OFFICE #2 MEE OFFICE #3 MEE OFFICE #4 MCFE OFFICE #1 MCFE OFFICE #2 MLP-UK OFFICE #1 MLP-UK OFFICE #2 MLP- UK OFFICE #3 MLP-UK OFFICE #4 MC OFFICE #1 MC OFFICE #2 MC OFFICE #3 MC OFFICE
4 MC CONF. ROOM 701 MC CONF. ROOM 702 MC CONF. ROOM 703 MC CONF. ROOM 710 MC
CONF. ROOM 711 unused unused unused unused uhused unused unused
Basic Period [H] 0.0 0.0 0.0
870.0 31.7
650.8 1057.4
287.1 806.7 388.2
3.2 484.2 485.4 133.2 169.3 434.6
0.0 623.4 647.5 211.5 535.8 615.0
0.0 462.1 462.1 171.0 490.0
7.7 267.8 267.9
0.1 0.4 219.3 438.4 437.3 218.7 124.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0
Overtime [H] 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
– 32 –
Basic Period [kWh] 0.000 0.000 0.000
1595.992 65.959
1119.757 1657.156
471.401 1226.261
654.044 5.689
868.573 1124.734
326.014 325.835 874.511
0.000 1129.392 1100.648
322.490 809.279 1124.523
0.000 710.040 710.040 293.380 1012.432
11.402 458.081 458.081
0.000 0.000 3.681 7.362 6.248 3.124 173.841 0.000 0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Overtime [H] 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
® Excel
’10 · SC-T-154
- Choose the “Import External Data” menu and the “Import Data…” menu in the menu bar.
– 33 –
’10 · SC-T-154 3
] button.
- Select “Comma” in the “Delimiters” section of the dialog box, and click [Next >] button.
– 34 –
- Click the head column to exclude under the “Data preview”.
’10 · SC-T-154
- Click the last column to exclude, pressing [Shift] key (on keyboard), under the “Data preview”. Click the “Do not import column (skip)” in the “Column data format”, and click [Finish] button.
– 35 –
’10 · SC-T-154
3 TROUBLESHOOTING
A malfunction has occurred with the unit. The malfunctioning unit is stopped.
Contact the shop where the unit was purchased. The shop will need the
following information: “unit icon color”, “malfunction situation”, “model name
of the malfunctioning unit”, “Error No. (E00)” etc.
A communication problem has occurred. Contact the shop where the unit was
purchased. The shop will need the following information: “unit icon color”,
“malfunction situation”, “model name of the malfunctioning unit” etc.
Clean the air filter. (See the manual attached to the air conditioning unit
for the cleaning method.) Press the filter reset button after cleaning.
Regular inspection is necessary. Contact the shop where the unit was
purchased. The shop will need the following information: “maintenance display
color”, “unit model name” etc. * The unit number and maintenance display
content can be checked on the UNIT INFORMATION screen.
It is possible that there is malfunction due to electrostatic discharge. Turn
the power off, then turn it on again (power supply reset). When it does not
operate normally with the procedure above, it can be assumed that the unit was
damaged, so contact the shop where the unit was purchased with the
“malfunction situation”.
· The backlight (illumination) is turned OFF after a fixed period of time to
preserve the screen. Touch the screen. (It may take a little time for the
display to reappear.)
· It is possible that there is malfunction due to electrostatic discharge.
Turn the power off, then turn it on again (power supply reset). When it does
not operate normally with the procedure above, it can be assumed that the unit
is damaged, so contact the shop where the unit was purchased with the
“malfunction situation”.
When multiple units are registered in a group, the settings for the
representative unit for the group are displayed. Check the status display for
each of the units. Run/Stop displays “Run” if one or more units in the group
are running, and it displays “Stop” if all units are stopped.
Check the schedule settings. The group settings that have been scheduled can
be changed.
The unit may get warm, but this is not a problem. When the room is hot, it
gets warm more readily. Use in an environment where the temperature around it
is 40°C or lower.
· If the total operating time in a day is less than 30 minutes, there has been
no operation for calculating purposes. Therefore the calculating results may
be a little low.
· Even if the air conditioner is not used all day long such as on a holiday,
standby electricity is still consumed. If power consumption is allotted to
only the operated indoor units on a pro-rated basis, standby electricity
consumed on holidays is not included in the calculation result. As a result,
the total calculation result becomes different from the actual power
consumption. On the other hand, if power consumption of standby electricity is
proportionally allotted to all indoor units including those not being
operated, the total calculation result coincides with actual power
consumption. However, in this case, the power consumption of standby
electricity is allotted to not only the tenants actually operating indoor
units but also the dummy tenants and the tenants not operating indoor units.
This may cause problems among tenants so that this method has not been
adopted. If there is any difference between the total calculation result and
the actual power consumption, try to reallocate the power consumption to the
tenants actually operating indoor units respectively by using the spreadsheet
software according to the calculation results.
It is possible that either the definition file has not been saved to the USB
memory or there is an error in specifying the folder to be read. Check again
and then perform the operation again. If this message appears again, contact
the shop where the unit was purchased.
There is a possibility that the USB memory has damaged or the files in the USB
memory have damaged. Delete all the files in the USB memory and create them
again. If this message appears again, contact the shop where the unit was
purchased.
The USB memory may not have been fully inserted. Remove the USB memory, and
reinsert it. If this message appears again, it is possible that the USB memory
is damaged or the USB memory is not the attachment. Replace it with the
bundled USB memory and try the operation again. If this message appears again,
contact the shop where the unit was purchased.
– 36 –
’10 · SC-T-154
Contact the shop where the unit was purchased. (Re-check the communications
line connections of the units.) Perform operations according to the messages
on the screen or turn the power off and then on (power supply reset). If the
message appears again, contact the shop where the unit was purchased. When the
intake-air temperature is 0°C or less, “–” is displayed. When it differs from
the display of remote controller, contact the shop where the unit was
purchased. This function can be applied to the indoor units, which are the
model KXE4 or later, and to the remote controller, which is the model RC-E1 or
later. Make sure to select “Invalid” for the Individual Lock/Unlock on the
Function setting screen. There may be inadequacy for communication line or the
setting of this center console. Please contact the shop where the unit was
purchased. This may possible that the central control or power system has
malfunction. Please contact the shop where the unit was purchased.
– 37 –
4 CONNECTION EXAMPLE
’10 · SC-T-154
– 38 –
’10 · SC-T-154
– 39 –
AIR CONDITIONING CONTROL SYSTEM
Air-Conditioning & Refrigeration Systems Headquarters 16-5, 2-chome, Kounan,
Minato-ku, Tokyo, 108-8215, Japan Fax : (03) 6716-5926
Because of our policy of continuous improvement, we reserve the right to make
changes in all specifications without notice. c Copyright MITSUBISHI HEAVY
INDUSTRIES.LTD