tekmar IOM-T-560 Programmable Thermostat Instruction Manual
- June 10, 2024
- tekmar
Table of Contents
IOM-T-560 Programmable Thermostat
Instruction Manual IOM-T-560
Thermostat 560
Compatible With
- 1-stage heating
- Supports optional floor sensor for radiant floor heating applications
Important Safety Information
It is your responsibility to ensure that this thermostat is safely installed
according to all applicable codes and standards. tekmar is not responsible for
damages resulting from improper installation and/ or maintenance.
This is a safety-alert symbol. The safety alert symbol is shown alone or used
with a signal word (DANGER, WARNING, or CAUTION), a pictorial and/or a safety
message to identify hazards.
When you see this symbol alone or with a signal word on your equipment or in
this Manual, be alert to the potential for death or serious personal injury.
This pictorial alerts you to electricity, electrocution, and shock hazards.
WARNING
This symbol identifies hazards which, if not avoided, could result in death or
serious injury.
CAUTION
This symbol identifies hazards which, if not avoided, could result in minor
or moderate injury.
NOTICE
This symbol identifies practices, actions, or failure to act which could
result in property damage or damage to the equipment.
WARNING
Read Manual and all product labels BEFORE using the equipment. Do not use
unless you know the safe and proper operation of this equipment. Keep this
Manual available for easy access by all users. Replacement Manuals are
available at tekmarControls.com
WARNING
- It is the installer’s responsibility to ensure that this thermostat is safely installed according to all applicable codes and standards.
- Improper installation and operation of this thermostat could result in damage to the equipment and possibly even personal injury or death.
- This thermostat is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
NOTICE
Do not attempt to service the thermostat. There are no user serviceable parts
inside the thermostat. Attempting to do so voids warranty.
Installation
Preparation
Tools Required
- tekmar or jeweler screwdriver
- Wire stripper
- Drill (for wall anchor)
- 3/16″ drill bit (for wall anchor)
- Phillips head screwdriver
Materials Required
- 18 AWG LVT Solid Wire (Low Voltage Connections)
Installation Location
NOTICE
Consider the following:
- Interior Wall.
- Keep dry. Avoid potential leakage onto the control.
- Relative Humidity less than 90%. Non-condensing environment.
- No exposure to extreme temperatures beyond 32-122°F (0-50°C).
- No draft, direct sun, or other cause for inaccurate temperature readings.
- Away from equipment, appliances, or other sources of electrical interference.
- Easy access for wiring, viewing, and adjusting the display screen.
- Approximately 5 feet (1.5 m) off the finished floor.
- The maximum length of wire is 500 feet (150 m).
- Strip wire to 3/8″ (10 mm) for all terminal connections.
- Use standard 8 conductor, 18 AWG wire.
Removing The Thermostat Base While holding the base
section in one hand, pull the lower half of the display front towards you to
pivot it away from the base.
Moving The Thermostat
WARNING
To prevent the risk of personal injury and/or death, make sure power is not
applied to the thermostat until it is fully installed and ready for final
testing. All work must be done with power to the circuit being worked on
turned off. Please be aware local codes may require this thermostat to be
installed or connected by an electrician. Application 560-1
The Thermostat 560 operates a radiant floor heating system. The thermostat
uses the built-in air temperature sensor.
Mechanical
Legend
B1 = Boiler
BP = Boiler Pump
PS = System Pump
T1 = Thermostat 560
V1 = Zone Valve
ZVC1 = Zone Valve Control 304V or 306V
Electrical
Application 560-2
The Thermostat 560 operates a radiant floor heating system based upon the
floor temperature sensor. The built-in air sensor is disabled.
Mechanical
Legend
B1 = Boiler
BP = Boiler Pump
PS = System Pump
T1 = Thermostat 560
S1 = Floor Sensor 079
V1 = Zone Valve
ZVC1 = Zone Valve Control 304V or 306V
Electrical
Application 560-3
Mechanical
The Thermostat 560 operates a radiant floor heating system. The thermostat
uses both air and floor temperature sensors. The air temperature sensor can be
either built-in and/or external.
Legend
B1 = Boiler
BP = Boiler Pump
PS = System Pump
T1 = Thermostat 560
S1 = Floor Sensor 079
S2 = Optional Indoor Sensor 084
V1 = Zone Valve
ZVC1 = Zone Valve Control 304V or 306V
Electrical
Application 560-4
Mechanical
The Thermostat 560 operates a baseboard/radiator using an air temperature
sensor. The air temperature sensor can be either built-in and/or external.
Legend
B1 = Boiler
BP = Boiler Pump
PS = System Pump
T1 = Thermostat 560
S1 = Optional Indoor Sensor 084
V1 = Zone Valve
ZVC1 = Zone Valve Control 304V or 306V
Electrical
Sequence of Operation
Heating Operation
The Heat On symbol is shown on the display when the thermostat is heating.
Heating for freeze protection is provided whenever the air or floor
temperature falls below 40°F (4.5°C), regardless of operating mode.
Regular Heating
W1 relay is on when the air temperature falls 1.5°F (1°C) below the Heat To
setting. When the temperature reaches the Heat To setting, the relay turns
off.
Radiant Floor Heating
When Radiant Floor Heating is selected in the setup menu, the W1 relay
operates using Pulse Width Modulation. This improves comfort for radiant
systems with high mass floors.
- 100% on time at Heat To setting -1.5°F
- 50% on time at Heat To setting
- 0% on time at Heat To setting + 1.5°F
Room Sensor and Averaging
The room temperature can be measured using a combination of the built-in and
auxiliary sensors.
- Built-in room sensor only
- Built-in room sensor with auxiliary room sensor(s) (temperature is averaged)
- Auxiliary room sensor only
Floor Sensor for Radiant Floor Heating
If a floor sensor is connected, floor minimum and maximum settings are
available.
For a combination of air and floor temperature control, leave the internal air
sensor on in the setup menu. A floor minimum can be used to prevent a fast
drop in temperature caused by receding solar exposure. This operation is
recommended for areas heated by afternoon sun through large windows. When the
sun sets, it can take a long time for the floors to get warm again. This may
cause the room to cool off too much in the early evening. A floor minimum
setting can help with this condition by maintaining a floor minimum
temperature. Keep in mind the floor minimum temperature will override the air
temperature, and if set too high, may overheat the room.
A floor maximum is recommended for rooms with hardwood floors. Setting floor
minimum and maximum temperatures is a way of enhancing the comfort of the
living space while protecting floor coverings.
If there are more than one floor temperature sensors, the temperature is
averaged.
Warm Weather Shut Down (WWSD)
The heating system can automatically shut off based upon the outdoor
temperature and the WWSD setting. This provides a convenient way to shut off
radiant floor heating. The WWSD feature requires the installation of an
Outdoor Sensor 070.
User Interface
After 60 seconds of inactivity, the thermostat home screen displays only the
time and the temperature.
User Settings
Away
Use the Away setting to saveenergy when the building is unoccupied
Schedule
Display
Setting | Range | Default |
---|
Temperature units
Select °F or °C.| °F or °C| °F
ENERGY USE
View the number of hours the heating or cooling has operated either daily
or monthly.| 0 to 24 (daily)
0 to 744 (monthly)| 0 hours
Setting| Range|
Default
---|---|---
BRIGHTNESS ACTIVE
Select the brightness when touching the screen.| 30 to 100%| 100%
BRIGHTNESS INACTIVE
Select the brightness when not in use.| Off, 30 to 100%| 50%
BACKGROUND
Select the background color.| Light, Blue, Night, Latte, Espresso| Blue
LANGUAGE
Select the language.| English| English
SCREEN CLEAN
Locks screen for 10 seconds to allow cleaning.| N/A| N/A
INACTIVE TIME DISPLAY
Select if the time is visible when the display is inactive.| Off or On| On
INACTIVE OUTDOOR DISPLAY
Select if the outdoor temperature is visible when the display is inactive.
Requires an Outdoor Sensor 070.| Off or On| Off
Time
Setting
| Range|
Default
---|---|---
TIME FORMAT
Select the time format.| 12 or 24 hour| 12 hour
DAYLIGHT SAVING TIME
Select the brightness when not in use.| Off, On| On
Installer Settings
Setup
The Setup menu contains five sub-menus that determine how the thermostat
operates
Setup – Toolbox
Setting| Range|
Default
---|---|---
ERROR
Displays any error messages.| N/A| N/A
ACCESS LEVEL
Select between user and installer access levels. User access level
restricts access in the Setup Menu.| User, Installer| Installer
STATUS
The current status of warm weather shut down, cold weather shut down and
each of the relays.| WWSD, W1| N/A
SOFTWARE VERSION
Display the software version.| J1302-1.0.0| N/A
LOAD DEFAULTS
All settings are returned to factory defaults.| Yes, No| No
CALIBRATE TOUCHSCREEN
Recalibrate the screen after loading factory defaults.| N/A| N/A
Setup – Temp
Setting| Range|
Default
---|---|---
Screen Page 1
FLOOR MIN
Select the floor temperature minimum. Applies when there is both floor and
an air sensors and when no schedule is set.| Off, 40 to 95°F Off, 4.5 to
35.0°C| Off
FLOOR MIN – WAKE
Select the floor temperature while in the wake schedule. Applies when there
is both a floor and an air sensor.| Off, 40 to 95°F Off, 4.5 to 35.0°C| Off
FLOOR MIN – LEAVE
Select the floor temperature while in the leave schedule. Applies when
there is both a floor and an air sensor.| Off, 40 to 95°F Off, 4.5 to 35.0°C|
Off
FLOOR MIN – RETURN
Select the floor temperature while in the return schedule. Applies when
there is both a floor and an air sensor.| Off, 40 to 95°F Off, 4.5 to 35.0°C|
Off
FLOOR MIN – SLEEP
Select the floor temperature while in the sleep schedule. Applies when
there is both a floor and an air sensor.| Off, 40 to 95°F Off, 4.5 to 35.0°C|
Off
FLOOR MIN – AWAY
Select the floor temperature while in away.
Applies when there is both a floor and an air sensor.| Off, 40 to 95°F Off,
4.5 to 35.0°C| Off
Screen Page 2
FLOOR MAX
Select the maximum floor temperature. This protects the floor covering from
over heating. Applies when there is a floor sensor.|
Off, 40 to 95°F Off, 4.5 to 35.0°C
| Off
HEAT TO AWAY
Select the heating temperature when away.| Off, 40 to 95°F
Off, 4.5 to 35.0°C| 62°F
(16.5°C)
HEAT TO MIN LIMIT
Select the minimum heating temperature limit.| Off, 40 to 95°F
Off, 4.5 to 35.0°C| Off
HEAT TO MAX LIMIT
Select the maximum heating temperature limit.| Off, 40 to 95°F
Off, 4.5 to 35.0°C
| Off
WARM WEATHER SHUT DOWN
Select the outdoor temperature at which the heating is shut off. The WWSD
feature requires an Outdoor Sensor 070.| Off, 40 to 95°F Off, 4.5 to 35.0°C|
Off
Setup – Sensors
Setting| Range|
Default
---|---|---
SENSOR 1
Select the type of sensor connected to S1 and Com wiring terminals.| Off,
Room, Floor| Off
SENSOR 2
Select the type of sensor connected to S2 and Com wiring terminals.| Off,
Room, Floor, Outdoor| Off
INTERNAL ROOM SENSOR
Select if the internal room temperature sensor is on or off. Only available
when Sensor 1 or 2 is set to read a room or floor sen- sor.| Off, On| On
ROOM OFFSET
Select if the internal room temperature sensor is on or off. Only available
when Sensor 1 or 2 is set to read a room or floor sen- sor.| Off, -5 to +5°F
-3.0 to 3.0°C| Off
FLOOR OFFSET
Manual offset correction of the floor temperature measurement.| Off, -5 to
+5°F
-3.0 to 3.0°C| Off
Setup – Alerts
Setting | Range | Default |
---|
ROOM HOT WARNING
Displays error on home screen if the room exceeds this tem- perature.| Off,
40 to 100°F Off, 4.5 to 38.0°C| Off
ROOM COLD WARNING
Displays error on home screen if the room falls below this tem- perature.|
Off, 40 to 100°F Off, 4.5 to 38.0°C| Off
Setup – Relays
Setting | Range | Default |
---|
RADIANT FLOOR HEATING
Select if the first stage W1 heats a radiant floor.| No, Yes| No
Error Messages
Error icon will appear on the home screen when an error is present.
Description
MEMORY ERROR
The thermostat memory settings are corrupted. To clear, load the factory
defaults in the Toolbox menu. The thermostat will not operate any heating
equipment while this error message is present.
INTERNAL ROOM SENSOR FAULT
Due to an open or short circuit, the thermostat is unable to read the internal
room temperature sensor. If sensor 1 or 2 is set to room the thermostat
continues to operate, otherwise operation stops. The error cannot be field
repaired. Contact your tekmar sales representative for warranty or repair
procedures.
SENSOR 1 FAULT
Due to an open or short circuit, the thermostat is unable to read the sensor
wired to S1 and Com. The thermostat stops normal operation if sensor 1 is the
only active room or floor sensor or if a floor maximum temperature has been
set.
Check the auxiliary sensor wire for short circuits according to the sensor
installation manual. It may be necessary to replace the auxiliary sensor. Once
the error has been corrected, the error message automatically clears.
SENSOR 2 FAULT
Due to an open or short circuit, the thermostat is unable to read the sensor
wired to S2 and Com. The thermostat stops normal operation if sensor 2 is the
only active room or floor sensor or if a floor maximum temperature has been
set.
Check the auxiliary sensor wire for short circuits according to the sensor
installation manual. It may be necessary to replace the auxiliary sensor. Once
the error has been corrected, the error message automatically clears.
ROOM HOT WARNING
The room temperature is above the Room Hot Warning setting in the Alerts menu.
The warning will automatically clear once the room temperature falls below the
setting.
ROOM COLD WARNING
The room temperature is below the Room Cold Warning setting in the Alerts
menu. The warning will automatically clear once the room temperature rises
above the setting.
Technical Data
THERMOSTAT 560 ONE STAGE HEAT
Literature| ES-T-560, IOM-T-560, 560_J, UserManual-T-560
Control| Microprocessor control. This is not a safety (limit) control.
Packaged weight| 0.6 lb. (270 g)
Dimensions| 4-5/8″ H x 3″ W x 15/16″ D (118 x 76 x 24 mm)
Enclosure| White PVC plastic, NEMA Type 1
Approvals| Meets Class B: ICES & FCC Part 15
Ambient conditions| Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-
condensing
Power supply| 15 to 30 V (ac/dc), 2 VA standby, Class 2
Relays| 30 V (ac/dc), 2 A, Class 2 circuits
Sensor| NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
– Included| None
– Optional| tekmar type # 070, 072, 073, 076, 077, 079, 084
Warranty
Limited Warranty The liability of tekmar under this warranty is limited. The
Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges
the terms of the Limited Warranty in effect at the time of such Product sale
and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is
a manufacturer’s pass-through warranty which the Purchaser is authorized to
pass through to its customers. Under the Limited Warranty, each tekmar Product
is warranted against defects in workmanship and materials if the Product is
installed and used in compliance with tekmar’s instructions, ordinary wear and
tear excepted. The pass-through warranty period is for a period of twenty-four
(24) months from the production date if the Product is not installed during
that period, or twelve (12) months from the documented date of installation if
installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at
tekmar’s sole discretion: the cost of parts and labor provided by tekmar to
repair defects in materials and / or workmanship of the defective product; or
to the exchange of the defective product for a warranty replacement product;
or to the granting of credit limited to the
original cost of the defective product, and such repair, exchange or credit
shall be the sole remedy available from tekmar, and, without limiting the
foregoing in any way, tekmar is not responsible, in contract, tort or strict
product liability, for any other losses, costs, expenses, inconveniences, or
damages, whether direct, indirect, special, secondary, incidental or
consequential, arising from ownership or use of the product, or from defects
in workmanship or materials, including any liability for fundamental breach
of contract.
The pass-through Limited Warranty applies only to those defective Products
returned to tekmar during the warranty period. This Limited Warranty does not
cover the cost of the parts or labor to remove or transport the defective
Product, or to reinstall the repaired or replacement Product, all such costs
and expenses being subject to Purchaser’s
agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its
customers which are different from or in excess of the tekmar Limited Warranty
are the Purchaser’s sole responsibility and obligation. Purchaser shall
indemnify and hold tekmar harmless from and against any and all claims,
liabilities and damages of any kind or
nature which arise out of or are related to any such representations or
warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has
been damaged by negligence by persons other than tekmar, accident, fire, Act
of God, abuse or misuse; or has been damaged by modifications, alterations or
attachments made subsequent to purchase which have not been authorized by
tekmar; or if the Product was not installed in compliance with tekmar’s
instructions and / or the local codes and ordinances; or if due to defective
installation of the Product; or if the Product was not used in compliance with
tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH
THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT
LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY
RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF
ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION;
THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED
SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE
PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE
GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have
defects in workmanship or materials must be returned, together with a written
description of the defect, to the tekmar Representative assigned to the
territory in which such Product is located. If tekmar receives an inquiry from
someone other than a tekmar Representative, including an inquiry from
Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding
a potential warranty claim, tekmar’s sole obligation shall be to provide the
address and other contact information regarding the appropriate
Representative.
Need help?
Go to our website or contact us.
watts.com/tekmar
tekmar.customerservice@wattswater.com
1-800-438-3903
Tel: 1-800-438-3903 • Fax:
250-984-0815
watts.com/tekmar
©2021 tekmar Control Systems Ltd.
IOM-T-560 – 2145