Reversible Heat Pumps for Split TECHNICAL BULLETIN

Omnia S 3.2 Air Water Reversible Heat Pumps for Split

Dati ERP

Dati ERP / ERP data|
---|---
Models| 4| 6| 8| 10| 12| 14| 16| 12T| 14T| 16T| UM
Seasonal space      low temperature (water outlet at 35°C)| 191| 195| 205| 204| 189| 185

A+++

| 182| 189| 185| 182| ηs (%)

class

              A++           class

SCOP

| low temperature (water outlet at 35°C)

medium temperature (water at 55°C)

| 4,85

3,31

| 4,95

3,52

| 5,21

3,36

| 5,19

3,49

| 4,81

3,45

|  | 4,72

3,47

| 4,62

3,41

| 4,81

3,45

| 4,72

3,47

| 4,62

3,41

| W/W

W/W

 | water at 7°C| 4,99| 5,34| 5,83| 5,98| 4,89|  | 4,86| 4,69| 4,86| 4,83| 4,67| W/W
 | water at 18°C| 7,77| 8,21| 8,95| 8,78| 7,10|  | 6,90| 6,75| 7,04| 6,85| 6,71| W/W

The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.
The manufacturer reserves the right to modify the products contents in this catalogue without previous notice.

ERP DATA FOR SPACE HEATING

For low – temperature application (35°C)


Mod

| Average| Colder| Warmer
Energy efficiency class| Indoor unit sound power| Outdoor unit sound power|

Prated

| Seasonal energy efficiency|

Annual energy consumption

|

Prated

| Seasonal energy efficiency|

Annual energy consumption

|

Prated

| Seasonal energy efficiency|

Annual energy consumption

OMNIA S 3.2 HI3 4| A+++| 39| 55| 5| 191| 2351| 5| 160| 2769| 5| 255| 1146
OMNIA S 3.2 HI3 6| A+++| 39| 58| 7| 195| 2845| 6| 165| 3300| 6| 260| 1244
OMNIA S 3.2 HI3 8| A+++| 39| 59| 8| 205| 3218| 7| 170| 3976| 8| 277| 1551
OMNIA S 3.2 HI3 10| A+++| 39| 60| 9| 204| 3644| 8| 170| 4423| 9| 281| 1617
OMNIA S 3.2 HI3 12| A+++| 40| 65| 12| 189| 5152| 11| 160| 6870| 11| 256| 2292
OMNIA S 3.2 HI3 14| A+++| 40| 65| 14| 185| 6012| 13| 160| 7667| 12| 260| 2457
OMNIA S 3.2 HI3 16| A+++| 40| 68| 15| 182| 6804| 14| 158| 8431| 13| 249| 2781
OMNIA S 3.2 HI6 12T| A+++| 40| 65| 12| 189| 5153| 11| 160| 6871| 11| 256| 2296
OMNIA S 3.2 HI6 14T| A+++| 40| 65| 14| 185| 6013| 13| 160| 7667| 12| 260| 2462
OMNIA S 3.2 HI6 16T| A+++| 40| 68| 15| 182| 6805| 14| 158| 8431| 13| 248| 2786
For medium – temperature application (55°C)

Mod

| Average| Colder| Warmer
Energy efficiency class| Indoor unit sound power| Outdoor unit sound power|

Prated

| Seasonal energy efficiency|

Annual energy consumption

|

Prated

| Seasonal energy efficiency|

Annual energy consumption

|

Prated

| Seasonal energy efficiency|

Annual energy consumption

OMNIA S 3.2 HI3 4| A++| 39| 55| 4| 129| 2744| 3| 102| 3158| 5| 163| 1614
OMNIA S 3.2 HI3 6| A++| 39| 58| 6| 138| 3345| 4| 111| 3680| 5| 165| 1634
OMNIA S 3.2 HI3 8| A++| 39| 59| 7| 131| 4056| 6| 112| 4948| 8| 177| 2242
OMNIA S 3.2 HI3 10| A++| 39| 60| 8| 136| 4539| 7| 116| 5539| 9| 182| 2496
OMNIA S 3.2 HI3 12| A++| 40| 65| 12| 135| 6927| 10| 118| 8419| 12| 174| 3776
OMNIA S 3.2 HI3 14| A++| 40| 65| 12| 135| 7202| 11| 119| 8866| 14| 177| 4088
OMNIA S 3.2 HI3 16| A++| 40| 68| 13| 133| 7895| 12| 122| 9309| 14| 176| 4112
OMNIA S 3.2 HI6 12T| A++| 40| 65| 12| 135| 6928| 10| 118| 8420| 12| 174| 3780
OMNIA S 3.2 HI6 14T| A++| 40| 65| 12| 135| 7203| 11| 119| 8867| 14| 176| 4092
OMNIA S 3.2 HI6 16T| A++| 40| 68| 13| 133| 7896| 12| 122| 9310| 14| 176| 4116

Product fiche 1

Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

4

| ****

6

| ****

8

| ****

10

| ****

12

---|---|---|---|---|---|---


*Unit sound pow er ()**

| Average clim ate low temperature

application (indoor / outdoor)

| [dB(A)]| 39 / 56| 39 / 58| 39 / 59| 39 / 60| 40 / 64
Average climate medium

temperature application (indoor / outdoor)

| [dB(A)]| 39 / 55| 39 / 57| 39 / 59| 39 / 60| 40 / 64
Capicity of the back-up

heater integrated in the unit

| Psup back-up heater (optional)| [kW]| 0/3| 0/3| 0/3/9| 0/3/9| 0/3/9
Space heating| Energy efficiency class 35°C (Low

temp. app.)

| –| A+++| A+++| A+++| A+++| A+++
Space heating| Energy efficiency class 55°C

(Medium temp. app.)

| –| A++| A++| A++| A++| A++
Average climate (Design temperature = –10°C)



Space heating 35°C

| P rated (declared heating capacity) @

–10°C

| [kW]| 5.5| 6.8| 8.1| 9.2| 12.0
Seasonal space heating efficiency (η

s )

| [%]| 191| 195| 205| 204| 189
Annual energy consumption| [kWh]| 2,351| 2,845| 3,218| 3644| 5,152



Space heating 55°C

| P rated (declared heating capacity) @

–10°C

| [kW]| 4.4| 5.7| 6.6| 7.7| 11.6
Seasonal space heating efficiency (η

s )

| [%]| 129| 138| 131| 136| 135
Annual energy consumption| [kWh]| 2,744| 3,345| 4,056| 4,539| 6,927
Part load conditions space heating average climate low temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 4.88| 6.03| 7.18| 8.10| 10.61
COP d (declared COP)| –| 3.19| 3.09| 3.35| 3.23| 2.88
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 3.05| 3.88| 4.65| 5.18| 6.69
COP d (declared COP)| –| 4.78| 4.85| 5.09| 5.01| 4.65
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 1.93| 2.39| 2.90| 3.32| 4.44
COP d (declared COP)| –| 6.13| 6.63| 6.82| 7.08| 6.62
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 1.48| 1.39| 1.63| 1.65| 3.74
COP d (declared COP)| –| 8.05| 7.93| 8.35| 8.58| 8.47
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90
Heat pump space heater| ****

Model

OMNIA S 3.2

| 14| ****

16

| ****

12T

| ****

14T

| ****

16T

---|---|---|---|---|---|---


*Unit sound pow er ()**

| Average clim ate low temperature

application (indoor / outdoor)

| [dB(A)]| 40 / 65| 40 / 68| 40 / 64| 40 / 65| 40 / 68
Average climate medium

temperature application (indoor / outdoor)

| [dB(A)]| 40 / 65| 40 / 67| 40 / 64| 40 / 65| 40 / 67
Capicity of the back-up

heater integrated in the unit

| Psup back-up heater (optional)| [kW]| 0/3/9| 0/3/9| 0/3/9| 0/3/9| 0/3/9
Space heating| Energy efficiency class 35°C (Low

temp. app.)

| –| A+++| A+++| A+++| A+++| A+++
Space heating| Energy efficiency class 55°C

(Medium temp. app.)

| –| A++| A++| A++| A++| A++
Average climate (Design temperature = –10°C)



Space heating 35°C

| P rated (declared heating capacity) @ –10°C| [kW]| 13.7| 15.2| 12.0| 13.7| 15.2
Seasonal space heating efficiency (η

s )

| [%]| 185| 182| 189| 185| 182
Annual energy consumption| [kWh]| 6,012| 6,804| 5,153| 6,013| 6,805



Space heating 55°C

| P rated (declared heating capacity) @ –10°C| [kW]| 12.1| 13.0| 11.6| 12.1| 13.0
Seasonal space heating efficiency (η

s )

| [%]| 135| 133| 135| 135| 133
Annual energy consumption| [kWh]| 7,202| 7,895| 6,928| 7,203| 7,896
Part load conditions space heating average climate low temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 12.14| 13.45| 10.61| 12.14| 13.45
COP d (declared COP)| –| 2.79| 2.72| 2.88| 2.79| 2.72
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 7.94| 8.56| 6.69| 7.94| 8.56
COP d (declared COP)| –| 4.52| 4.41| 4.65| 4.52| 4.41
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 5.20| 5.70| 4.44| 5.20| 5.70
COP d (declared COP)| –| 6.68| 6.56| 6.62| 6.68| 6.56
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 3.75| 3.78| 3.74| 3.75| 3.78
COP d (declared COP)| –| 8.52| 8.51| 8.47| 8.52| 8.51
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90

Product fiche 2

Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

4

| ****

6

| 8| 10| 12
---|---|---|---|---|---|---



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -10.00| -10.00| -10.00| -10.00| -10.00
P dh (declared heating capacity)| [kW]| 4.41| 5.36| 6.44| 7.40| 10.74
COP d (declared COP)| –| 2.86| 2.76| 3.04| 2.96| 2.77
WTOL (Heating w ater Operation

Lim it)

| [°C]| 60.00| 60.00| 60.00| 60.00| 60.00


(F) Tbivalent temperature

| T blv| [°C]| -7.00| -7.00| -7.00| -7.00| -7.00
P dh (declared heating capacity)| [kW]| 4.88| 6.03| 7.18| 8.10| 10.61
COP d (declared COP)| –| 3.19| 3.09| 3.35| 3.23| 2.88
Supplementary capacity at

P_design

| P sup (@Tdesignh: –10°C)| [kW]| 1.11| 1.45| 1.68| 1.76| 1.26
Part load conditions space heating average climate medium temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 3.89| 5.04| 5.84| 6.78| 10.24
COP d (declared COP)| –| 2.17| 2.17| 2.16| 2.24| 2.01
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 2.38| 3.12| 3.76| 4.28| 6.52
COP d (declared COP)| –| 3.30| 3.51| 3.30| 3.42| 3.44
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 2.94| 2.08| 2.43| 2.77| 4.36
COP d (declared COP)| –| 4.41| 4.54| 4.34| 4.52| 4.59
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 1.32| 1.28| 1.39| 1.58| 3.29
COP d (declared COP)| –| 5.66| 5.59| 5.33| 5.68| 6.05
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -10.00| -10.00| -10.00| -10.00| -10.00
P dh (declared heating capacity)| [kW]| 3.42| 4.52| 4.91| 5.38| 9.10
COP d (declared COP)| –| 1.91| 1.91| 1.84| 1.83| 1.79
WTOL (Heating w ater Operation

Lim it)

| [°C]| 60.00| 60.00| 60.00| 60.00| 60.00


(F) Tbivalent temperature

| T blv| [°C]| -7.00| -7.00| -7.00| -7.00| -7.00
P dh (declared heating capacity)| [kW]| 3.89| 5.04| 5.84| 6.78| 10.27
COP d (declared COP)| –| 2.17| 2.17| 2.16| 2.24| 2.01

ERP PRODUCT FICHE FOR SPACE HEATING

Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

14

| ****

16

| ****

12T

| ****

14T

| ****

16T

---|---|---|---|---|---|---



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -10.00| -10.00| -10.00| -10.00| -10.00
P dh (declared heating capacity)| [kW]| 11.47| 12.52| 10.74| 11.47| 12.52
COP d (declared COP)| –| 2.59| 2.48| 2.77| 2.59| 2.48
WTOL (Heating w ater Operation

Lim it)

| [°C]| 60.00| 60.00| 60.00| 60.00| 60.00


(F) Tbivalent temperature

| T blv| [°C]| -7.00| -7.00| -7.00| -7.00| -7.00
P dh (declared heating capacity)| [kW]| 12.14| 13.45| 10.61| 12.14| 13.45
COP d (declared COP)| –| 2.79| 2.72| 2.88| 2.79| 2.72
Supplementary capacity at

P_design

| P sup (@Tdesignh: –10°C)| [kW]| 2.23| 2.68| 1.26| 2.23| 2.68
Part load conditions space heating average climate medium temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 10.68| 11.52| 10.24| 10.68| 11.52
COP d (declared COP)| –| 2.01| 1.99| 2.01| 2.01| 1.99
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 6.86| 7.18| 6.52| 6.86| 7.18
COP d (declared COP)| –| 3.43| 3.34| 3.44| 3.43| 3.34
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 4.63| 4.67| 4.36| 4.63| 4.67
COP d (declared COP)| –| 4.66| 4.61| 4.59| 4.66| 4.61
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 3.31| 3.32| 3.29| 3.31| 3.32
COP d (declared COP)| –| 6.13| 6.07| 6.05| 6.13| 6.07
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -10.00| -10.00| -10.00| -10.00| -10.00
P dh (declared heating capacity)| [kW]| 9.19| 10.33| 9.10| 9.19| 10.33
COP d (declared COP)| –| 1.76| 1.80| 1.79| 1.76| 1.80
WTOL (Heating w ater Operation

Lim it)

| [°C]| 60.00| 60.00| 60.00| 60.00| 60.00


(F) Tbivalent temperature

| T blv| [°C]| -7.00| -7.00| -7.00| -7.00| -7.00
P dh (declared heating capacity)| [kW]| 10.68| 11.52| 10.27| 10.68| 11.52
COP d (declared COP)| –| 2.01| 1.99| 2.01| 2.01| 1.99
Supplementary capacity at

P_design

| P sup (@Tdesignh: –10°C)| [kW]| 2.91| 2.67| 2.50| 2.91| 2.67
Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

4

| ****

6

| 8| 10| 12
---|---|---|---|---|---|---
Supplementary capacity at

P_design

| P sup (@Tdesignh: –10°C)| [kW]| 0.98| 1.18| 1.69| 2.28| 2.50
Colder climate (Design temperature = –22°C)



Space heating 35°C

| P rated (declared heating capacity) @

–22°C

| [kW]| 4.6| 5.6| 7.0| 7.7| 11.4
Seasonal space heating efficiency (η

s )

| [%]| 160| 165| 170| 170| 160
Annual energy consumption| [kWh]| 2,769| 3,300| 3,976| 4,423| 6,870



Space heating 55°C

| P rated (declared heating capacity) @

–22°C

| [kW]| 3.4| 4.3| 5.8| 6.7| 10.3
Seasonal space heating efficiency (η

s )

| [%]| 102| 111| 112| 116| 118
Annual energy consumption| [kWh]| 3,158| 3,680| 4,948| 5,539| 8,419
Part load conditions space heating colder climate low temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 2.75| 3.42| 4.46| 4.83| 7.05
COP d (declared COP)| –| 3.49| 3.59| 3.66| 3.60| 3.48
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 1.77| 2.06| 2.69| 2.94| 4.67
COP d (declared COP)| –| 4.95| 5.21| 5.20| 5.26| 4.96
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 1.17| 1.46| 1.65| 1.92| 3.14
COP d (declared COP)| –| 5.53| 6.24| 6.53| 7.08| 6.10
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 1.43| 1.44| 1.65| 1.65| 3.57
COP d (declared COP)| –| 7.67| 7.66| 7.96| 7.96| 7.87
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -22.00| -22.00| -22.00| -22.00| -22.00
P dh (declared heating capacity)| [kW]| 2.80| 3.48| 4.06| 4.62| 7.01
COP d (declared COP)| –| 1.97| 1.96| 1.95| 1.97| 1.98
WTOL (Heating w ater Operation

Lim it)

| [°C]| 51.00| 51.00| 51.00| 51.00| 51.00


(F) Tbivalent temperature

| T blv| [°C]| -15.00| -15.00| -15.00| -15.00| -15.00
P dh (declared heating capacity)| [kW]| 3.72| 4.59| 5.69| 6.32| 9.28
COP d (declared COP)| –| 2.57| 2.53| 2.83| 2.64| 2.59
Supplementary capacity at P_design| P sup (@Tdesignh: –22°C)| [kW]| 1.76| 2.15| 2.91| 3.08| 4.40
Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

14

| ****

16

| ****

12T

| ****

14T

| ****

16T

---|---|---|---|---|---|---
Colder climate (Design temperature = –22°C)



Space heating 35°C

| P rated (declared heating capacity) @ –22°C| [kW]| 12.6| 13.7| 11.4| 12.6| 13.7
Seasonal space heating efficiency (η

s )

| [%]| 160| 158| 160| 160| 158
Annual energy consumption| [kWh]| 7,667| 8,431| 6,871| 7,667| 8,431



Space heating 55°C

| P rated (declared heating capacity) @ –22°C| [kW]| 11.0| 11.8| 10.3| 11.0| 11.8
Seasonal space heating efficiency (η

s )

| [%]| 119| 122| 118| 119| 122
Annual energy consumption| [kWh]| 8,866| 9,309| 8,420| 8,867| 9,310
Part load conditions space heating colder climate low temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 7.96| 8.31| 7.05| 7.96| 8.31
COP d (declared COP)| –| 3.44| 3.37| 3.48| 3.44| 3.37
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 5.05| 5.26| 4.67| 5.05| 5.26
COP d (declared COP)| –| 4.92| 4.86| 4.96| 4.92| 4.86
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 3.15| 3.62| 3.14| 3.15| 3.62
COP d (declared COP)| –| 6.11| 6.49| 6.10| 6.11| 6.49
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 3.57| 3.34| 3.57| 3.57| 3.34
COP d (declared COP)| –| 7.82| 7.40| 7.87| 7.82| 7.40
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -22.00| -22.00| -22.00| -22.00| -22.00
P dh (declared heating capacity)| [kW]| 7.57| 8.88| 7.01| 7.57| 8.88
COP d (declared COP)| –| 1.92| 1.97| 1.98| 1.92| 1.97
WTOL (Heating w ater Operation

Lim it)

| [°C]| 51.00| 51.00| 51.00| 51.00| 51.00


(F) Tbivalent temperature

| T blv| [°C]| -15.00| -15.00| -15.00| -15.00| -15.00
P dh (declared heating capacity)| [kW]| 10.31| 11.22| 9.28| 10.31| 11.22
COP d (declared COP)| –| 2.53| 2.43| 2.59| 2.53| 2.43
Supplementary capacity at P_design| P sup (@Tdesignh: –22°C)| [kW]| 5.03| 4.82| 4.40| 5.03| 4.82
Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

4

| ****

6

| 8| 10| 12
---|---|---|---|---|---|---
Part load conditions space heating colder climate medium temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 2.13| 2.69| 3.86| 4.27| 6.63
COP d (declared COP)| –| 2.32| 2.46| 2.48| 2.54| 2.63
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 1.28| 1.60| 2.21| 2.57| 4.06
COP d (declared COP)| –| 2.99| 3.36| 3.35| 3.51| 3.60
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 1.01| 1.02| 1.44| 1.65| 2.78
COP d (declared COP)| –| 3.86| 3.94| 4.11| 4.37| 4.54
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 1.36| 1.37| 1.47| 1.48| 3.33
COP d (declared COP)| –| 6.28| 6.35| 5.92| 5.96| 6.25
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -22.00| -22.00| -22.00| -22.00| -22.00
P dh (declared heating capacity)| [kW]| 1.64| 2.09| 2.80| 2.80| 4.19
COP d (declared COP)| –| 1.02| 1.13| 1.22| 1.22| 1.13
WTOL (Heating w ater Operation

Lim it)

| [°C]| 51.00| 51.00| 51.00| 51.00| 51.00


(F) Tbivalent temperature

| T blv| [°C]| -15.00| -15.00| -15.00| -15.00| -15.00
P dh (declared heating capacity)| [kW]| 2.74| 3.47| 4.71| 5.47| 8.41
COP d (declared COP)| –| 1.74| 1.86| 1.90| 2.00| 1.84
Supplementary capacity at

P_design

| P sup (@Tdesignh: –22°C)| [kW]| 1.72| 2.17| 2.97| 3.91| 6.12
Warmer climate (Design temperature = 2°C)



Space heating 35°C

| P rated (declared heating capacity) @

2°C

| [kW]| 5.5| 6.1| 8.1| 8.6| 11.1
Seasonal space heating efficiency (ηs)| [%]| 255| 260| 277| 281| 256
Annual energy consumption| [kWh]| 1,146| 1,244| 1,551| 1,617| 2,292



Space heating 55°C

| P rated (declared heating capacity) @

2°C

| [kW]| 5.0| 5.1| 7.6| 8.6| 12.5
Seasonal space heating efficiency (ηs)| [%]| 163| 165| 177| 182| 174
Annual energy consumption| [kWh]| 1,614| 1,634| 2,242| 2,496| 3,776
Heat pump space heater| ****

Model

OMNIA S 3.2

| 14| 16| 12T| 14T| 16T
---|---|---|---|---|---|---
Part load conditions space heating colder climate medium temperature application


(A) condition (-7°C)

| P dh (declared heating capacity)| [kW]| 6.89| 7.64| 6.63| 6.89| 7.64
COP d (declared COP)| –| 2.66| 2.65| 2.63| 2.66| 2.65
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 4.32| 4.42| 4.06| 4.32| 4.42
COP d (declared COP)| –| 3.66| 3.79| 3.60| 3.66| 3.79
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 3.06| 2.97| 2.78| 3.06| 2.97
COP d (declared COP)| –| 4.72| 4.81| 4.54| 4.72| 4.81
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 3.33| 3.43| 3.33| 3.33| 3.43
COP d (declared COP)| –| 6.25| 6.29| 6.25| 6.25| 6.29
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| -22.00| -22.00| -22.00| -22.00| -22.00
P dh (declared heating capacity)| [kW]| 4.20| 5.21| 4.19| 4.20| 5.21
COP d (declared COP)| –| 1.13| 1.23| 1.13| 1.13| 1.23
WTOL (Heating w ater Operation

Lim it)

| [°C]| 51.00| 51.00| 51.00| 51.00| 51.00


(F) Tbivalent temperature

| T blv| [°C]| -15.00| -15.00| -15.00| -15.00| -15.00
P dh (declared heating capacity)| [kW]| 8.94| 9.61| 8.41| 8.94| 9.61
COP d (declared COP)| –| 1.79| 1.86| 1.84| 1.79| 1.86
Supplementary capacity at

P_design

| P sup (@Tdesignh: –22°C)| [kW]| 6.76| 6.59| 6.12| 6.76| 6.59
Warmer climate (Design temperature = 2°C)



Space heating 35°C

| P rated (declared heating capacity) @ 2°C| [kW]| 12.1| 13.1| 11.1| 12.1| 13.1
Seasonal space heating efficiency (η

s )

| [%]| 260| 249| 256| 260| 248
Annual energy consumption| [kWh]| 2,457| 2,781| 2,296| 2,462| 2,786



Space heating 55°C

| P rated (declared heating capacity) @ 2°C| [kW]| 13.7| 13.8| 12.5| 13.7| 13.8
Seasonal space heating efficiency (η

s )

| [%]| 177| 176| 174| 176| 176
Annual energy consumption| [kWh]| 4,088| 4,112| 3,780| 4,092| 4,116
Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

4

| ****

6

| ****

8

| ****

10

| ****

12

---|---|---|---|---|---|---
Part load conditions space heating w armer climate low  temperature application


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 5.34| 5.93| 7.56| 8.44| 11.26
COP d (declared COP)| –| 3.94| 3.91| 3.98| 3.84| 3.59
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 3.56| 3.93| 5.22| 5.52| 7.14
COP d (declared COP)| –| 5.92| 5.89| 6.26| 6.18| 5.87
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 1.63| 1.79| 2.62| 2.62| 3.55
COP d (declared COP)| –| 7.91| 8.20| 9.23| 9.04| 7.94
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| 2.00| 2.00| 2.00| 2.00| 2.00
P dh (declared heating capacity)| [kW]| 5.34| 5.93| 7.56| 8.44| 11.26
COP d (declared COP)| –| 3.94| 3.91| 3.98| 3.84| 3.59
WTOL (Heating w ater Operation

Lim it)

| [°C]| 62.00| 62.00| 62.00| 62.00| 62.00


(F) Tbivalent temperature

| T blv| [°C]| 7.00| 7.00| 7.00| 7.00| 7.00
P dh (declared heating capacity)| [kW]| 3.56| 3.93| 5.22| 5.52| 7.14
COP d (declared COP)| –| 5.92| 5.89| 6.26| 6.18| 5.87
Supplementary capacity at

P_design

| P sup (@Tdesignh: 2°C)| [kW]| 0.18| 0.18| 0.55| 0.14| 0.00
Part load conditions space heating w armer climate medium temperature application


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 4.83| 5.02| 7.55| 8.06| 12.07
COP d (declared COP)| –| 2.51| 2.48| 2.59| 2.59| 2.31
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 3.22| 3.31| 4.86| 5.54| 8.04
COP d (declared COP)| –| 3.68| 3.67| 3.92| 4.10| 3.86
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 1.47| 1.59| 2.32| 2.53| 3.75
COP d (declared COP)| –| 5.15| 5.29| 5.55| 5.82| 5.70
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90
Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

14

| ****

16

| ****

12T

| ****

14T

| ****

16T

---|---|---|---|---|---|---
Part load conditions space heating w armer climate low  temperature application


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 12.04| 13.10| 11.26| 12.04| 13.10
COP d (declared COP)| –| 3.44| 3.35| 3.59| 3.44| 3.35
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 7.78| 8.41| 7.14| 7.78| 8.41
COP d (declared COP)| –| 5.84| 5.36| 5.87| 5.84| 5.36
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 3.75| 3.87| 3.55| 3.75| 3.87
COP d (declared COP)| –| 8.25| 8.11| 7.94| 8.25| 8.11
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| 2.00| 2.00| 2.00| 2.00| 2.00
P dh (declared heating capacity)| [kW]| 12.04| 13.10| 11.26| 12.04| 13.10
COP d (declared COP)| –| 3.44| 3.35| 3.59| 3.44| 3.35
WTOL (Heating w ater Operation

Lim it)

| [°C]| 62.00| 62.00| 62.00| 62.00| 62.00


(F) Tbivalent temperature

| T blv| [°C]| 7.00| 7.00| 7.00| 7.00| 7.00
P dh (declared heating capacity)| [kW]| 7.78| 8.41| 7.14| 7.78| 8.41
COP d (declared COP)| –| 5.84| 5.36| 5.87| 5.84| 5.36
Supplementary capacity at

P_design

| P sup (@Tdesignh: 2°C)| [kW]| 0.00| 0.00| 0.00| 0.00| 0.00
Part load conditions space heating w armer climate medium temperature application


(B) condition (2°C)

| P dh (declared heating capacity)| [kW]| 13.04| 13.38| 12.07| 13.04| 13.38
COP d (declared COP)| –| 2.20| 2.29| 2.31| 2.20| 2.29
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(C) condition (7°C)

| P dh (declared heating capacity)| [kW]| 8.83| 8.86| 8.04| 8.83| 8.86
COP d (declared COP)| –| 3.91| 3.84| 3.86| 3.91| 3.84
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90


(D) condition (12°C)

| P dh (declared heating capacity)| [kW]| 4.08| 4.06| 3.75| 4.08| 4.06
COP d (declared COP)| –| 5.90| 5.86| 5.70| 5.90| 5.86
Cdh(degradation coefficient)| –| 0.90| 0.90| 0.90| 0.90| 0.90
Heat pump space heater| ****

Model

OMNIA S 3.2

| ****

4

| ****

6

| ****

8

| ****

10

| ****

12

---|---|---|---|---|---|---



(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| 2.00| 2.00| 2.00| 2.00| 2.00
P dh (declared heating capacity)| [kW]| 4.83| 5.02| 7.83| 8.15| 12.07
COP d (declared COP)| –| 2.51| 2.48| 2.66| 2.61| 2.31
WTOL (Heating w ater Operation

Lim it)

| [°C]| 62.00| 62.00| 62.00| 62.00| 62.00


(F) Tbivalent temperature

| T blv| [°C]| 7.00| 7.00| 7.00| 7.00| 7.00
P dh (declared heating capacity)| [kW]| 3.22| 3.31| 4.86| 5.54| 8.04
COP d (declared COP)| –| 3.68| 3.67| 3.92| 4.10| 3.86
Supplementary capacity at

P_design

| P sup (@Tdesignh: 2°C)| [kW]| 0.18| 0.12| 0.00| 0.48| 0.43
0





Product description

| Air-to-w ater heat pump| Y/N| Yes| Yes| Yes| Yes| Yes
Water-to-w ater heat pump| Y/N| No| No| No| No| No
Brine-to-w ater heat pump| Y/N| No| No| No| No| No
Low -temperature heat pump| Y/N| No| No| No| No| No
Equipped w ith a supplementary

heater

| Y/N| Yes| Yes| Yes| Yes| Yes
Heat pump combination heater| Y/N| No| No| No| No| No
Air to w ater unit| Rated airflow| [m3/h]| 2770| 2770| 4030| 4030| 4060
Brine/w ater to w ater unit| Rated w ater/brine flow (outdoor H/E)| | /| /| /| /| /






Other

| Capacity control| –| Inverter| Inverter| Inverter| Inverter| Inverter
P off (Pow er consumption Off mode)| [kW]| 0.014| 0.014| 0.014| 0.014| 0.014
P to (Pow er consumption

Thermostat off mode)

| [kW]| 0.024| 0.024| 0.024| 0.024| 0.024
P sb (Pow er consumption Standby

mode)

| [kW]| 0.014| 0.014| 0.014| 0.014| 0.014
P CK (Pow er crankcase heater

model)

| [kW]| 0.000| 0.000| 0.000| 0.000| 0.000
Q elec (Daily electricity consum ption)| [kWh]| /| /| /| /| /
Q fuel (Daily fuel consumption)| [kWh]| /| /| /| /| /
Heat pump space heater|

Model

OMNIA S 3.2

|

14

|

16

|

12T

|

14T

|

16T

---|---|---|---|---|---|---

(E) Tol (temperature operating lim it)

| Tol (temperature operating lim it)| [°C]| 2.00| 2.00| 2.00| 2.00| 2.00
P dh (declared heating capacity)| [kW]| 13.04| 13.38| 12.07| 13.04| 13.38
COP d (declared COP)| –| 2.20| 2.29| 2.31| 2.20| 2.29
WTOL (Heating w ater Operation

Lim it)

| [°C]| 62.00| 62.00| 62.00| 62.00| 62.00

(F) Tbivalent temperature

| T blv| [°C]| 7.00| 7.00| 7.00| 7.00| 7.00
P dh (declared heating capacity)| [kW]| 8.83| 8.86| 8.04| 8.83| 8.86
COP d (declared COP)| –| 3.91| 3.84| 3.86| 3.91| 3.84
Supplementary capacity at

P_design

| P sup (@Tdesignh: 2°C)| [kW]| 0.66| 0.42| 0.43| 0.66| 0.42
0

Product description

| Air-to-w ater heat pump| Y/N| Yes| Yes| Yes| Yes| Yes
Water-to-w ater heat pump| Y/N| No| No| No| No| No
Brine-to-w ater heat pump| Y/N| No| No| No| No| No
Low -temperature heat pump| Y/N| No| No| No| No| No
Equipped w ith a supplementary

heater

| Y/N| Yes| Yes| Yes| Yes| Yes
Heat pump combination heater| Y/N| No| No| No| No| No
Air to w ater unit| Rated airflow| [m3/h]| 4060| 4650| 4060| 4060| 4650
Brine/w ater to w ater unit| Rated w ater/brine flow (outdoor H/E)| | /| /| /| /| /

Other

| Capacity control| –| Inverter| Inverter| Inverter| Inverter| Inverter
P of f (Power consumption Off mode)| [kW]| 0.014| 0.014| 0.02| 0.02| 0.02
P to (Power consumption Thermostat off mode)| [kW]| 0.024| 0.024| 0.030| 0.030| 0.030
P sb (Power consumption Standby mode)| [kW]| 0.014| 0.014| 0.02| 0.02| 0.02
P CK (Power crankcase heater model)| [kW]| 0.000| 0.000| 0.000| 0.000| 0.000
Q elec (Daily electricity consumption)| [kWh]| /| /| /| /| /
Q f uel (Daily fuel consumption)| [kWh]| /| /| /| /| /

Details and precautions on installation, maintenance and assembly can be found in the installation and or operation manuals.
Product fiche data according to energy label directive 2010/30/EC regulation (EU) 811/2013.

ERP TECHNICAL DATA SHEET FOR SPACE HEATING
OMNIA S 3.2 HI3 4Medium temperature (55°C)

Technical parameters

Model(s):| OMNIA S 3.2 HI3 4
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 4.4| kW| Seasonal space heating energy efficiency| ηs| 129| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 3.89| kW| Tj = -7℃| COPd| 2.17| –
Tj = 2℃| Pdh| 2.38| kW| Tj = 2℃| COPd| 3.30| –
Tj = 7℃| Pdh| 2.94| kW| Tj = 7℃| COPd| 4.41| –
Tj = 12℃| Pdh| 1.32| kW| Tj = 12℃| COPd| 5.66| –
Tj = bivalent temperature| Pdh| 3.89| kW| Tj = bivalent temperature| COPd| 2.17| –
Tj = operating limit| Pdh| 3.42| kW| Tj = operating limit| COPd| 1.91| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.98

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| 2770| m3/h
Sound power level, indoors/outdoors| LWA| ****

39 / 56

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 2744| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 4
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 3.4| kW| Seasonal space heating energy efficiency| ηs| 102| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 2.13| kW| Tj = -7℃| COPd| 2.32| –
Tj = 2℃| Pdh| 1.28| kW| Tj = 2℃| COPd| 2.99| –
Tj = 7℃| Pdh| 1.01| kW| Tj = 7℃| COPd| 3.86| –
Tj = 12℃| Pdh| 1.36| kW| Tj = 12℃| COPd| 6.28| –
Tj = bivalent temperature| Pdh| 2.74| kW| Tj = bivalent temperature| COPd| 1.74| –
Tj = operating limit| Pdh| 1.64| kW| Tj = operating limit| COPd| 1.02| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| -15| °C| For air-to-water heat pumps: Operation limit temperature| TOL| -22| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

1.72

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| 2770| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 3159| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 4
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 5.0| kW| Seasonal space heating energy efficiency| ηs| 162| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 4.83| kW| Tj = 2℃| COPd| 2.51| –
Tj = 7℃| Pdh| 3.22| kW| Tj = 7℃| COPd| 3.68| –
Tj = 12℃| Pdh| 1.47| kW| Tj = 12℃| COPd| 5.15| –
Tj = bivalent temperature| Pdh| 3.22| kW| Tj = bivalent temperature| COPd| 3.68| –
Tj = operating limit| Pdh| 4.83| kW| Tj = operating limit| COPd| 2.51| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| 7| °C| For air-to-water heat pumps: Operation limit temperature| TOL| 2| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.18

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| 2770| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 1621| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fu5.1el consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

  Technical parameters
Model(s): OMNIA S 3.2 HI3 6
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: NO
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Declared climate condition: AVERAGE

Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 5.7| kW| Seasonal space heating energy efficiency| ηs| 138| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 5.04| kW| Tj = -7℃| COPd| 2.17| –
Tj = 2℃| Pdh| 3.12| kW| Tj = 2℃| COPd| 3.51| –
Tj = 7℃| Pdh| 2.08| kW| Tj = 7℃| COPd| 4.54| –
Tj = 12℃| Pdh| 1.28| kW| Tj = 12℃| COPd| 5.59| –
Tj = bivalent temperature| Pdh| 5.04| kW| Tj = bivalent temperature| COPd| 2.17| –
Tj = operating limit| Pdh| 4.52| kW| Tj = operating limit| COPd| 1.91| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

1.18

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

2770

| m3/h
Sound power level, indoors/outdoors| LWA| ****

39 / 58

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 3345| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

  Technical parameters
Model(s): OMNIA S 3.2 HI3 6
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: NO
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Declared climate condition: COLDER

Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 4.3| kW| Seasonal space heating energy efficiency| ηs| 111| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 2.70| kW| Tj = -7℃| COPd| 2.46| –
Tj = 2℃| Pdh| 1.60| kW| Tj = 2℃| COPd| 3.36| –
Tj = 7℃| Pdh| 1.02| kW| Tj = 7℃| COPd| 3.94| –
Tj = 12℃| Pdh| 1.37| kW| Tj = 12℃| COPd| 6.35| –
Tj = bivalent temperature| Pdh| 3.47| kW| Tj = bivalent temperature| COPd| 1.86| –
Tj = operating limit| Pdh| 2.09| kW| Tj = operating limit| COPd| 1.13| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

5.10

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

2770

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 3681| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 6
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 5.1| kW| Seasonal space heating energy efficiency| ηs| 165| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 5.02| kW| Tj = 2℃| COPd| 2.48| –
Tj = 7℃| Pdh| 3.31| kW| Tj = 7℃| COPd| 3.67| –
Tj = 12℃| Pdh| 1.60| kW| Tj = 12℃| COPd| 5.29| –
Tj = bivalent temperature| Pdh| 3.31| kW| Tj = bivalent temperature| COPd| 3.67| –
Tj = operating limit| Pdh| 5.02| kW| Tj = operating limit| COPd| 2.48| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| 2770| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 1640| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 8
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 6.6| kW| Seasonal space heating energy efficiency| ηs| 131| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 5.84| kW| Tj = -7℃| COPd| 2.16| –
Tj = 2℃| Pdh| 3.75| kW| Tj = 2℃| COPd| 3.30| –
Tj = 7℃| Pdh| 2.42| kW| Tj = 7℃| COPd| 4.34| –
Tj = 12℃| Pdh| 1.39| kW| Tj = 12℃| COPd| 5.33| –
Tj = bivalent temperature| Pdh| 5.84| kW| Tj = bivalent temperature| COPd| 2.16| –
Tj = operating limit| Pdh| 4.90| kW| Tj = operating limit| COPd| 1.84| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

1.69

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4030

| m3/h
Sound power level, indoors/outdoors| LWA| ****

39 / 59

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 4056| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

  Technical parameters
Model(s): OMNIA S 3.2 HI3 8
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: NO
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Declared climate condition: COLDER

Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 5.8| kW| Seasonal space heating energy efficiency| ηs| 112| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 3.86| kW| Tj = -7℃| COPd| 2.48| –
Tj = 2℃| Pdh| 2.21| kW| Tj = 2℃| COPd| 3.35| –
Tj = 7℃| Pdh| 1.44| kW| Tj = 7℃| COPd| 4.11| –
Tj = 12℃| Pdh| 1.46| kW| Tj = 12℃| COPd| 5.92| –
Tj = bivalent temperature| Pdh| 4.71| kW| Tj = bivalent temperature| COPd| 1.90| –
Tj = operating limit| Pdh| 2.80| kW| Tj = operating limit| COPd| 1.22| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

2.97

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4030

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 4950| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

  Technical parameters
Model(s): OMNIA S 3.2 HI3 8
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: NO
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Declared climate condition: WARMER

Parameters are declared for medium-temperature (55°C) application.

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 7.6| kW| Seasonal space heating energy efficiency| ηs| 176| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 7.55| kW| Tj = 2℃| COPd| 2.59| –
Tj = 7℃| Pdh| 4.86| kW| Tj = 7℃| COPd| 3.92| –
Tj = 12℃| Pdh| 2.31| kW| Tj = 12℃| COPd| 5.55| –
Tj = bivalent temperature| Pdh| 4.86| kW| Tj = bivalent temperature| COPd| 3.92| –
Tj = operating limit| Pdh| 7.55| kW| Tj = operating limit| COPd| 2.59| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4030

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 2259| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 10
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 7.7| kW| Seasonal space heating energy efficiency| ηs| 136| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 6.78| kW| Tj = -7℃| COPd| 2.24| –
Tj = 2℃| Pdh| 4.28| kW| Tj = 2℃| COPd| 3.42| –
Tj = 7℃| Pdh| 2.77| kW| Tj = 7℃| COPd| 4.52| –
Tj = 12℃| Pdh| 1.58| kW| Tj = 12℃| COPd| 5.68| –
Tj = bivalent temperature| Pdh| 6.78| kW| Tj = bivalent temperature| COPd| 2.24| –
Tj = operating limit| Pdh| 5.38| kW| Tj = operating limit| COPd| 1.83| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

2.29

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4030

| m3/h
Sound power level, indoors/outdoors| LWA| ****

39 / 60

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 4539| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 10
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 6.7| kW| Seasonal space heating energy efficiency| ηs| 116| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 4.27| kW| Tj = -7℃| COPd| 2.54| –
Tj = 2℃| Pdh| 2.57| kW| Tj = 2℃| COPd| 3.51| –
Tj = 7℃| Pdh| 1.65| kW| Tj = 7℃| COPd| 4.37| –
Tj = 12℃| Pdh| 1.47| kW| Tj = 12℃| COPd| 5.96| –
Tj = bivalent temperature| Pdh| 5.47| kW| Tj = bivalent temperature| COPd| 2.00| –
Tj = operating limit| Pdh| 2.80| kW| Tj = operating limit| COPd| 1.22| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

3.91

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4030

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 5540| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 10
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 8.6| kW| Seasonal space heating energy efficiency| ηs| 180| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 8.06| kW| Tj = 2℃| COPd| 2.59| –
Tj = 7℃| Pdh| 5.54| kW| Tj = 7℃| COPd| 4.10| –
Tj = 12℃| Pdh| 2.53| kW| Tj = 12℃| COPd| 5.82| –
Tj = bivalent temperature| Pdh| 5.54| kW| Tj = bivalent temperature| COPd| 4.10| –
Tj = operating limit| Pdh| 8.15| kW| Tj = operating limit| COPd| 2.61| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.48

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4030

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 2516| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 12
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 11.6| kW| Seasonal space heating energy efficiency| ηs| 135| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 10.24| kW| Tj = -7℃| COPd| 2.01| –
Tj = 2℃| Pdh| 6.52| kW| Tj = 2℃| COPd| 3.44| –
Tj = 7℃| Pdh| 4.36| kW| Tj = 7℃| COPd| 4.59| –
Tj = 12℃| Pdh| 3.29| kW| Tj = 12℃| COPd| 6.05| –
Tj = bivalent temperature| Pdh| 10.24| kW| Tj = bivalent temperature| COPd| 2.01| –
Tj = operating limit| Pdh| 9.10| kW| Tj = operating limit| COPd| 1.79| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

1.23

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

40 / 64

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 6927| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating

Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). (**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 12
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 10.3| kW| Seasonal space heating energy efficiency| ηs| 118| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 6.63| kW| Tj = -7℃| COPd| 2.63| –
Tj = 2℃| Pdh| 4.06| kW| Tj = 2℃| COPd| 3.60| –
Tj = 7℃| Pdh| 2.78| kW| Tj = 7℃| COPd| 4.54| –
Tj = 12℃| Pdh| 3.33| kW| Tj = 12℃| COPd| 6.25| –
Tj = bivalent temperature| Pdh| 8.41| kW| Tj = bivalent temperature| COPd| 1.84| –
Tj = operating limit| Pdh| 4.19| kW| Tj = operating limit| COPd| 1.13| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

6.11

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 8419| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 12
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 12.5| kW| Seasonal space heating energy efficiency| ηs| 174| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 12.07| kW| Tj = 2℃| COPd| 2.31| –
Tj = 7℃| Pdh| 8.04| kW| Tj = 7℃| COPd| 3.86| –
Tj = 12℃| Pdh| 3.75| kW| Tj = 12℃| COPd| 5.70| –
Tj = bivalent temperature| Pdh| 8.04| kW| Tj = bivalent temperature| COPd| 3.86| –
Tj = operating limit| Pdh| 12.07| kW| Tj = operating limit| COPd| 2.31| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.43

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 3776| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 14
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 12.08| kW| Seasonal space heating energy efficiency| ηs| 135| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 10.68| kW| Tj = -7℃| COPd| 2.01| –
Tj = 2℃| Pdh| 6.86| kW| Tj = 2℃| COPd| 3.43| –
Tj = 7℃| Pdh| 4.63| kW| Tj = 7℃| COPd| 4.66| –
Tj = 12℃| Pdh| 3.31| kW| Tj = 12℃| COPd| 6.13| –
Tj = bivalent temperature| Pdh| 10.68| kW| Tj = bivalent temperature| COPd| 2.01| –
Tj = operating limit| Pdh| 9.19| kW| Tj = operating limit| COPd| 1.76| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

1.40

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

40 / 65

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 7202| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 14
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 11.0| kW| Seasonal space heating energy efficiency| ηs| 119| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 6.89| kW| Tj = -7℃| COPd| 2.66| –
Tj = 2℃| Pdh| 4.32| kW| Tj = 2℃| COPd| 3.66| –
Tj = 7℃| Pdh| 3.06| kW| Tj = 7℃| COPd| 4.72| –
Tj = 12℃| Pdh| 3.33| kW| Tj = 12℃| COPd| 6.25| –
Tj = bivalent temperature| Pdh| 8.94| kW| Tj = bivalent temperature| COPd| 1.79| –
Tj = operating limit| Pdh| 4.20| kW| Tj = operating limit| COPd| 1.13| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

6.80

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 8866| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 14
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 13.7| kW| Seasonal space heating energy efficiency| ηs| 177| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 13.04| kW| Tj = 2℃| COPd| 2.20| –
Tj = 7℃| Pdh| 8.83| kW| Tj = 7℃| COPd| 3.91| –
Tj = 12℃| Pdh| 4.08| kW| Tj = 12℃| COPd| 5.90| –
Tj = bivalent temperature| Pdh| 8.83| kW| Tj = bivalent temperature| COPd| 3.91| –
Tj = operating limit| Pdh| 13.04| kW| Tj = operating limit| COPd| 2.20| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.66

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 4088| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 16
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 13.0| kW| Seasonal space heating energy efficiency| ηs| 133| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 11.52| kW| Tj = -7℃| COPd| 1.99| –
Tj = 2℃| Pdh| 7.18| kW| Tj = 2℃| COPd| 3.34| –
Tj = 7℃| Pdh| 4.67| kW| Tj = 7℃| COPd| 4.61| –
Tj = 12℃| Pdh| 3.31| kW| Tj = 12℃| COPd| 6.07| –
Tj = bivalent temperature| Pdh| 11.52| kW| Tj = bivalent temperature| COPd| 1.99| –
Tj = operating limit| Pdh| 10.33| kW| Tj = operating limit| COPd| 1.80| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

2.68

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4650

| m3/h
Sound power level, indoors/outdoors| LWA| ****

40 / 68

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 7895| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 16
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 11.8| kW| Seasonal space heating energy efficiency| ηs| 122| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 7.64| kW| Tj = -7℃| COPd| 2.65| –
Tj = 2℃| Pdh| 4.42| kW| Tj = 2℃| COPd| 3.79| –
Tj = 7℃| Pdh| 2.97| kW| Tj = 7℃| COPd| 4.81| –
Tj = 12℃| Pdh| 3.43| kW| Tj = 12℃| COPd| 6.29| –
Tj = bivalent temperature| Pdh| 9.61| kW| Tj = bivalent temperature| COPd| 1.86| –
Tj = operating limit| Pdh| 5.21| kW| Tj = operating limit| COPd| 1.23| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

6.59

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4650

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 9309| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI3 16
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 13.8| kW| Seasonal space heating energy efficiency| ηs| 176| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 13.38| kW| Tj = 2℃| COPd| 2.29| –
Tj = 7℃| Pdh| 8.86| kW| Tj = 7℃| COPd| 3.84| –
Tj = 12℃| Pdh| 4.06| kW| Tj = 12℃| COPd| 5.86| –
Tj = bivalent temperature| Pdh| 8.86| kW| Tj = bivalent temperature| COPd| 3.84| –
Tj = operating limit| Pdh| 13.38| kW| Tj = operating limit| COPd| 2.29| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.42

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.024| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4650

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 4112| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 12T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 11.6| kW| Seasonal space heating energy efficiency| ηs| 135| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 10.24| kW| Tj = -7℃| COPd| 2.01| –
Tj = 2℃| Pdh| 6.52| kW| Tj = 2℃| COPd| 3.44| –
Tj = 7℃| Pdh| 4.36| kW| Tj = 7℃| COPd| 4.59| –
Tj = 12℃| Pdh| 3.29| kW| Tj = 12℃| COPd| 6.05| –
Tj = bivalent temperature| Pdh| 10.24| kW| Tj = bivalent temperature| COPd| 2.01| –
Tj = operating limit| Pdh| 9.10| kW| Tj = operating limit| COPd| 1.79| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

1.23

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

40 / 64

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 6928| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 12T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 10.3| kW| Seasonal space heating energy efficiency| ηs| 118| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 6.63| kW| Tj = -7℃| COPd| 2.63| –
Tj = 2℃| Pdh| 4.06| kW| Tj = 2℃| COPd| 3.60| –
Tj = 7℃| Pdh| 2.78| kW| Tj = 7℃| COPd| 4.54| –
Tj = 12℃| Pdh| 3.33| kW| Tj = 12℃| COPd| 6.25| –
Tj = bivalent temperature| Pdh| 8.41| kW| Tj = bivalent temperature| COPd| 1.84| –
Tj = operating limit| Pdh| 4.19| kW| Tj = operating limit| COPd| 1.13| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

6.11

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 8420| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 12T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 12.5| kW| Seasonal space heating energy efficiency| ηs| 174| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 12.07| kW| Tj = 2℃| COPd| 2.31| –
Tj = 7℃| Pdh| 8.04| kW| Tj = 7℃| COPd| 3.86| –
Tj = 12℃| Pdh| 3.75| kW| Tj = 12℃| COPd| 5.70| –
Tj = bivalent temperature| Pdh| 8.04| kW| Tj = bivalent temperature| COPd| 3.86| –
Tj = operating limit| Pdh| 12.07| kW| Tj = operating limit| COPd| 2.31| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.43

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 3780| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 14T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 12.08| kW| Seasonal space heating energy efficiency| ηs| 135| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 10.68| kW| Tj = -7℃| COPd| 2.01| –
Tj = 2℃| Pdh| 6.86| kW| Tj = 2℃| COPd| 3.43| –
Tj = 7℃| Pdh| 4.63| kW| Tj = 7℃| COPd| 4.66| –
Tj = 12℃| Pdh| 3.31| kW| Tj = 12℃| COPd| 6.13| –
Tj = bivalent temperature| Pdh| 10.68| kW| Tj = bivalent temperature| COPd| 2.01| –
Tj = operating limit| Pdh| 9.19| kW| Tj = operating limit| COPd| 1.76| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

1.40

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

40 / 65

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 7203| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 14T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 11.0| kW| Seasonal space heating energy efficiency| ηs| 119| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 6.89| kW| Tj = -7℃| COPd| 2.66| –
Tj = 2℃| Pdh| 4.32| kW| Tj = 2℃| COPd| 3.66| –
Tj = 7℃| Pdh| 3.06| kW| Tj = 7℃| COPd| 4.72| –
Tj = 12℃| Pdh| 3.33| kW| Tj = 12℃| COPd| 6.25| –
Tj = bivalent temperature| Pdh| 8.94| kW| Tj = bivalent temperature| COPd| 1.79| –
Tj = operating limit| Pdh| 4.20| kW| Tj = operating limit| COPd| 1.13| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

6.80

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 8867| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 14T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 13.7| kW| Seasonal space heating energy efficiency| ηs| 176| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 13.04| kW| Tj = 2℃| COPd| 2.20| –
Tj = 7℃| Pdh| 8.83| kW| Tj = 7℃| COPd| 3.91| –
Tj = 12℃| Pdh| 4.08| kW| Tj = 12℃| COPd| 5.90| –
Tj = bivalent temperature| Pdh| 8.83| kW| Tj = bivalent temperature| COPd| 3.91| –
Tj = operating limit| Pdh| 13.04| kW| Tj = operating limit| COPd| 2.20| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.66

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4060

| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 4092| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 16T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| AVERAGE
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 13.0| kW| Seasonal space heating energy efficiency| ηs| 133| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 11.52| kW| Tj = -7℃| COPd| 1.99| –
Tj = 2℃| Pdh| 7.18| kW| Tj = 2℃| COPd| 3.34| –
Tj = 7℃| Pdh| 4.67| kW| Tj = 7℃| COPd| 4.61| –
Tj = 12℃| Pdh| 3.31| kW| Tj = 12℃| COPd| 6.07| –
Tj = bivalent temperature| Pdh| 11.52| kW| Tj = bivalent temperature| COPd| 1.99| –
Tj = operating limit| Pdh| 10.33| kW| Tj = operating limit| COPd| 1.80| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-10

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 60| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

2.67

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| ****

4650

| m3/h
Sound power level, indoors/outdoors| LWA| ****

40 / 68

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 7896| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 16T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| COLDER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 11.8| kW| Seasonal space heating energy efficiency| ηs| 122| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| 7.64| kW| Tj = -7℃| COPd| 2.65| –
Tj = 2℃| Pdh| 4.42| kW| Tj = 2℃| COPd| 3.79| –
Tj = 7℃| Pdh| 2.97| kW| Tj = 7℃| COPd| 4.81| –
Tj = 12℃| Pdh| 3.43| kW| Tj = 12℃| COPd| 6.29| –
Tj = bivalent temperature| Pdh| 9.61| kW| Tj = bivalent temperature| COPd| 1.86| –
Tj = operating limit| Pdh| 5.21| kW| Tj = operating limit| COPd| 1.23| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

-15

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

-22

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 51| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.020| kW| **

Rated heat output (**)

| ****

Psup

| ****

6.59

| ****

kW

Standby mode| Psb| 0.020| kW
Thermostat-off mode| Pto| 0.030| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| 4650| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 9310| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Technical parameters

Model(s):| OMNIA S 3.2 HI6 16T
Air-to-water heat pump:| YES
Water-to-water heat pump:| NO
Brine-to-water heat pump:| NO
Low-temperature heat pump:| NO
Equipped with a supplementary heater:| NO
Heat pump combination heater:| NO
Declared climate condition:| WARMER
Parameters are declared for medium-temperature application.
Parameters are declared for medium-temperature (55°C) application.
Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated heat output (*)| Prated| 13.8| kW| Seasonal space heating energy efficiency| ηs| 176| %
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj| Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = -7℃| Pdh| –| kW| Tj = -7℃| COPd| –| –
Tj = 2℃| Pdh| 13.38| kW| Tj = 2℃| COPd| 2.29| –
Tj = 7℃| Pdh| 8.86| kW| Tj = 7℃| COPd| 3.84| –
Tj = 12℃| Pdh| 4.06| kW| Tj = 12℃| COPd| 5.86| –
Tj = bivalent temperature| Pdh| 8.86| kW| Tj = bivalent temperature| COPd| 3.84| –
Tj = operating limit| Pdh| 13.38| kW| Tj = operating limit| COPd| 2.29| –
For air-to-water heat pumps: Tj = -15℃| Pdh| –| kW| For air-to-water heat pumps: Tj = -15℃| COPd| –| –
Bivalent temperature| Tbiv| ****

7

| ****

°C

| For air-to-water heat pumps: Operation limit temperature| TOL| ****

2

| °C
Cycling interval capacity for heating| Pcych| –| kW| Cycling interval efficiency| COPcyc| –| –
Degradation co-efficient ()| Cdh| 0.9| —| Heating water operating limit temperature| WTOL| 62| °C
Power consumption in modes other than active mode| Supplementary heater
Off mode| Poff| 0.014| kW| **

Rated heat output (**)

| ****

Psup

| ****

0.42

| ****

kW

Standby mode| Psb| 0.014| kW
Thermostat-off mode| Pto| 0.029| kW| ****

Type of energy input

| ****

Electrical

Crankcase heater mode| Pck| 0.000| kW

Other items|  |
Capacity control| variable| For air-to-water heat pumps: Rated air flow rate, outdoors| –| 4650| m3/h
Sound power level, indoors/outdoors| LWA| ****

| ****

dB

| For water-or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger| ****

| ****

| ****

m3/h

Annual energy consumption| QHE| 4116| kWh

For heat pump combination heater:
Declared load profile| –|  | Water heating energy efficiency| ηwh| –| %
Daily electricity consumption| Qclec| –| kWh| Daily fuel consumption| Qfuel| –| kWh
Annual electricity consumption| AEC| –| kWh| Annual fuel consumption| AFC| –| GJ


Contact details

| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Model(s): OMNIA S 3.2 HI3 4
Outdoor side heat exchanger of chiller: Air to water
Indoor side heat exchanger chiller: Water
Type: Compressor driven vapour compression
Driver of compressor: Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 4.7| kW| Seasonal space cooling energy efficiency| ηs,c| 197| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 4.66| kW| Tj=+35℃| EERd| 3.52| –
Tj=+30℃| Pdc| 3.66| kW| Tj=+30℃| EERd| 4.76| –
Tj=+25℃| Pdc| 2.21| kW| Tj=+25℃| EERd| 5.72| –
Tj=+20℃| Pdc| 0.94| kW| Tj=+20℃| EERd| 5.72| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


2770

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 56

| dB
Emissions of nitroge oxides (if applicable)| n NOx (**)| –| mg/kWh input GCV|


For water / brine-to-water

chillers: Rated brine or water flow rate, outdoor

side heat exchanger

| ****


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 4**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 4.5| kW| Seasonal space cooling energy efficiency| ηs,c| 308| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 4.51| kW| Tj=+35℃| EERd| 5.54| –
Tj=+30℃| Pdc| 3.44| kW| Tj=+30℃| EERd| 7.23| –
Tj=+25℃| Pdc| 2.19| kW| Tj=+25℃| EERd| 8.94| –
Tj=+20℃| Pdc| 1.13| kW| Tj=+20℃| EERd| 10.48| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


2770

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 56

| dB
Emissions of nitrogen oxides (if| NOx ()| –| mg/kWh input GCV| **

For water / brine-to-water

chillers: Rated brine or water flow rate, outdoor

side heat exchanger

| ****


| ****


| ****

m3/h

applicable)

GWP of the

refrigerant

| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 6**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 6.3| kW| Seasonal space cooling energy efficiency| ηs,c| 211| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 6.35| kW| Tj=+35℃| EERd| 2.93| –
Tj=+30℃| Pdc| 4.76| kW| Tj=+30℃| EERd| 4.53| –
Tj=+25℃| Pdc| 3.02| kW| Tj=+25℃| EERd| 6.32| –
Tj=+20℃| Pdc| 1.39| kW| Tj=+20℃| EERd| 7.20| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


2770

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 58

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 6**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 6.5| kW| Seasonal space cooling energy efficiency| ηs,c| 325| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 6.55| kW| Tj=+35℃| EERd| 4.69| –
Tj=+30℃| Pdc| 4.84| kW| Tj=+30℃| EERd| 7.16| –
Tj=+25℃| Pdc| 3.26| kW| Tj=+25℃| EERd| 9.64| –
Tj=+20℃| Pdc| 1.41| kW| Tj=+20℃| EERd| 11.48| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


2770

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 58

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 8**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 7.4| kW| Seasonal space cooling energy efficiency| ηs,c| 230| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 7.38| kW| Tj=+35℃| EERd| 3.39| –
Tj=+30℃| Pdc| 5.72| kW| Tj=+30℃| EERd| 4.71| –
Tj=+25℃| Pdc| 3.62| kW| Tj=+25℃| EERd| 6.65| –
Tj=+20℃| Pdc| 1.64| kW| Tj=+20℃| EERd| 8.55| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4030

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 59

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 8**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 8.4| kW| Seasonal space cooling energy efficiency| ηs,c| 355| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 8.37| kW| Tj=+35℃| EERd| 5.09| –
Tj=+30℃| Pdc| 6.47| kW| Tj=+30℃| EERd| 7.02| –
Tj=+25℃| Pdc| 4.31| kW| Tj=+25℃| EERd| 10.67| –
Tj=+20℃| Pdc| 1.80| kW| Tj=+20℃| EERd| 13.61| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4030

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 59

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 10**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 8.7| kW| Seasonal space cooling energy efficiency| ηs,c| 236| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 8.73| kW| Tj=+35℃| EERd| 3.21| –
Tj=+30℃| Pdc| 6.68| kW| Tj=+30℃| EERd| 4.47| –
Tj=+25℃| Pdc| 4.26| kW| Tj=+25℃| EERd| 7.02| –
Tj=+20℃| Pdc| 1.94| kW| Tj=+20℃| EERd| 9.54| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4030

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 60

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 10**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 10.0| kW| Seasonal space cooling energy efficiency| ηs,c| 348| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 10.01| kW| Tj=+35℃| EERd| 4.64| –
Tj=+30℃| Pdc| 7.71| kW| Tj=+30℃| EERd| 6.45| –
Tj=+25℃| Pdc| 5.03| kW| Tj=+25℃| EERd| 10.36| –
Tj=+20℃| Pdc| 2.32| kW| Tj=+20℃| EERd| 14.98| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4030

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

39 / 60

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 12**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 11.3| kW| Seasonal space cooling energy efficiency| ηs,c| 192| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 11.31| kW| Tj=+35℃| EERd| 2.61| –
Tj=+30℃| Pdc| 8.76| kW| Tj=+30℃| EERd| 3.93| –
Tj=+25℃| Pdc| 5.81| kW| Tj=+25℃| EERd| 5.73| –
Tj=+20℃| Pdc| 2.63| kW| Tj=+20℃| EERd| 6.75| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4060

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 64

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 12**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 11.8| kW| Seasonal space cooling energy efficiency| ηs,c| 281| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 11.77| kW| Tj=+35℃| EERd| 3.87| –
Tj=+30℃| Pdc| 9.21| kW| Tj=+30℃| EERd| 5.50| –
Tj=+25℃| Pdc| 5.74| kW| Tj=+25℃| EERd| 8.66| –
Tj=+20℃| Pdc| 3.33| kW| Tj=+20℃| EERd| 10.07| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4060

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 64

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 14**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 12.2| kW| Seasonal space cooling energy efficiency| ηs,c| 191| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 12.19| kW| Tj=+35℃| EERd| 2.46| –
Tj=+30℃| Pdc| 9.41| kW| Tj=+30℃| EERd| 3.85| –
Tj=+25℃| Pdc| 6.16| kW| Tj=+25℃| EERd| 5.80| –
Tj=+20℃| Pdc| 2.63| kW| Tj=+20℃| EERd| 6.74| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4060

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 65

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 14**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 13.3| kW| Seasonal space cooling energy efficiency| ηs,c| 273| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 13.30| kW| Tj=+35℃| EERd| 3.47| –
Tj=+30℃| Pdc| 10.20| kW| Tj=+30℃| EERd| 5.26| –
Tj=+25℃| Pdc| 6.57| kW| Tj=+25℃| EERd| 8.45| –
Tj=+20℃| Pdc| 3.33| kW| Tj=+20℃| EERd| 10.07| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4060

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 65

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 16**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 14.3| kW| Seasonal space cooling energy efficiency| ηs,c| 184| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 14.31| kW| Tj=+35℃| EERd| 2.47| –
Tj=+30℃| Pdc| 10.68| kW| Tj=+30℃| EERd| 3.63| –
Tj=+25℃| Pdc| 6.76| kW| Tj=+25℃| EERd| 5.27| –
Tj=+20℃| Pdc| 3.41| kW| Tj=+20℃| EERd| 7.29| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4650

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 68

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI3 16**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 15.4| kW| Seasonal space cooling energy efficiency| ηs,c| 267| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 15.40| kW| Tj=+35℃| EERd| 3.50| –
Tj=+30℃| Pdc| 11.42| kW| Tj=+30℃| EERd| 5.14| –
Tj=+25℃| Pdc| 7.27| kW| Tj=+25℃| EERd| 7.83| –
Tj=+20℃| Pdc| 3.40| kW| Tj=+20℃| EERd| 10.35| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.014| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.014| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4650

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 68

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI6 12T**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 11.3| kW| Seasonal space cooling energy efficiency| ηs,c| 191| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 11.31| kW| Tj=+35℃| EERd| 2.61| –
Tj=+30℃| Pdc| 8.76| kW| Tj=+30℃| EERd| 3.93| –
Tj=+25℃| Pdc| 5.81| kW| Tj=+25℃| EERd| 5.73| –
Tj=+20℃| Pdc| 2.63| kW| Tj=+20℃| EERd| 6.75| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.020| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.020| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4060

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 64

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI6 12T**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 11.8| kW| Seasonal space cooling energy efficiency| ηs,c| 279| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 11.77| kW| Tj=+35℃| EERd| 3.87| –
Tj=+30℃| Pdc| 9.21| kW| Tj=+30℃| EERd| 5.50| –
Tj=+25℃| Pdc| 5.74| kW| Tj=+25℃| EERd| 8.66| –
Tj=+20℃| Pdc| 3.33| kW| Tj=+20℃| EERd| 10.07| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.020| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.020| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4060

| ****


m3/h

Sound power level, indoors / outdoors| LWA| ****

40 / 64

| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. (**) From 26 September 2018.
Model(s):|
---|---
Outdoor side heat exchanger of chiller:|
Indoor side heat exchanger chiller:|
Type:|
Driver of compressor:|

Item| Symbol| Value|
Rated cooling capacity| Prated,c| 12.2|
Declared cooling capacity for part load at given outdoor temperature Tj|
Tj=+35℃| Pdc| 12.19|
Tj=+30℃| Pdc| 9.41|
Tj=+25℃| Pdc| 6.16|
Tj=+20℃| Pdc| 2.63|

Degradation co-efficient for chillers (*)| Cdc| 0.9|
Power consumption in modes other than “active mode”
Off mode| POFF| 0.020|
Thermosat-off mode| PTO| 0.010|
Other items
Capacity control| variable|
Sound power level, indoors / outdoors| LWA| ****

-/65

|
Emissions of nitrogen oxides (if applicable)| NOx (**)| –|
GWP of the refrigerant| –| 675|


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI6 14T**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 13.3| kW| Seasonal space cooling energy efficiency| ηs,c| 271| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 13.30| kW| Tj=+35℃| EERd| 3.47| –
Tj=+30℃| Pdc| 10.20| kW| Tj=+30℃| EERd| 5.26| –
Tj=+25℃| Pdc| 6.57| kW| Tj=+25℃| EERd| 8.45| –
Tj=+20℃| Pdc| 3.33| kW| Tj=+20℃| EERd| 10.07| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.020| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.020| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4060

| ****


m3/h

Sound power level, indoors / outdoors| LWA| -/64| dB
Emissions of nitrogen oxides (if applicable)| NOx ()| –| mg/kWh input GCV| For water / brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger| **


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI6 16T**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 14.3| kW| Seasonal space cooling energy efficiency| ηs,c| 184| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 14.31| kW| Tj=+35℃| EERd| 2.47| –
Tj=+30℃| Pdc| 10.68| kW| Tj=+30℃| EERd| 3.63| –
Tj=+25℃| Pdc| 6.76| kW| Tj=+25℃| EERd| 5.27| –
Tj=+20℃| Pdc| 3.41| kW| Tj=+20℃| EERd| 7.29| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.020| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.020| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4650

| ****


m3/h

Sound power level, indoors / outdoors| LWA| -/69| dB
Emissions of nitrogen oxides (if applicable)| NOx (**)| –| mg/kWh input GCV| For water / brine- to-water chillers: Rated brine or water flow rate, outdoor side heat

exchanger

| ****


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Low temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. () From 26 September 2018.
Model(s):|
OMNIA S 3.2 HI6 16T**
---|---
Outdoor side heat exchanger of chiller:| Air to water
Indoor side heat exchanger chiller:| Water
Type:| Compressor driven vapour compression
Driver of compressor:| Electric motor

Item| Symbol| Value| Unit|  | Item| Symbol| Value| Unit
Rated cooling capacity| Prated,c| 15.4| kW| Seasonal space cooling energy efficiency| ηs,c| 265| %
Declared cooling capacity for part load at given outdoor temperature Tj| Declared energy efficiency ratio for part load at given outdoor temperature Tj
Tj=+35℃| Pdc| 15.40| kW| Tj=+35℃| EERd| 3.50| –
Tj=+30℃| Pdc| 11.42| kW| Tj=+30℃| EERd| 5.14| –
Tj=+25℃| Pdc| 7.27| kW| Tj=+25℃| EERd| 7.83| –
Tj=+20℃| Pdc| 3.40| kW| Tj=+20℃| EERd| 10.35| –

Degradation co-efficient for chillers (*)| Cdc| 0.9| –|  |  |  |  |
Power consumption in modes other than “active mode”
Off mode| POFF| 0.020| kW|  | Crankcase heater mode| PCK| 0.000| kW
Thermosat-off mode| PTO| 0.010| kW| Standby mode| PSB| 0.020| kW
Other items
Capacity control| variable|  | For air-to-water comfort chillers: air flow rate, outdoor measured| ****


| ****


4650

| ****


m3/h

Sound power level, indoors / outdoors| LWA| -/69| dB
Emissions of nitrogen oxides (if applicable)| NOx (**)| –| mg/kWh input GCV| For water / brine- to-water chillers: Rated brine or water flow rate, outdoor side heat

exchanger

| ****


| ****


| ****

m3/h

GWP of the refrigerant| –| 675| kg CO2 eq

(100years)


Standard rating conditions used

| ****

Medium temperature application

Contact details| ****

Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A – tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.com

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. (**) From 26 September 2018.
“Tw_out

°C”

| “DB/WB

°C”

| Heating Capacity [W]| COP
---|---|---|---
130%| 100%| 90%| 70%| 50%| 30%| 130%| 100%| 90%| 70%| 50%| 30%

25

| -25| 2053| 1899| 1566| 1232| /| /| 1,74| 1,78| 1,79| 1,80| /| /
-20| 3086| 2824| 2276| 1728| /| /| 2,36| 2,45| 2,48| 2,50| /| /
-15| 3602| 3260| 2989| 2718| 1682| /| 3,03| 3,17| 3,35| 3,53| 3,25| /
-10| 4465| 4001| 3414| 2828| 2241| 1654| 3,36| 3,60| 3,63| 3,65| 3,68| 3,70
-7| 5112| 4678| 3798| 2917| 2037| 1156| 3,67| 3,85| 3,89| 3,93| 3,97| 4,01
-5| 5180| 4692| 3858| 3024| 2190| 1356| 4,03| 4,22| 4,26| 4,30| 4,34| 4,38
-2| 5296| 4841| 3982| 3122| 2263| 1403| 4,55| 4,71| 4,75| 4,80| 4,84| 4,88
0| 5412| 4990| 4105| 3220| 2335| 1450| 5,06| 5,19| 5,24| 5,28| 5,33| 5,37
2| 5629| 5182| 4310| 3439| 2567| 1695| 5,28| 5,45| 5,52| 5,58| 5,65| 5,71
5| 5994| 5479| 4601| 3723| 2844| 1966| 5,83| 6,04| 6,10| 6,16| 6,22| 6,28
7| 6376| 4603| 4215| 3826| 2354| 1955| 6,67| 6,98| 7,41| 7,84| 7,28| 6,96
10| 6370| 5725| 4781| 3837| 2893| 1949| 6,68| 7,13| 7,21| 7,30| 7,38| 7,46
12| 6232| 5625| 4748| 3870| 2992| 2114| 6,69| 7,21| 7,29| 7,39| 7,48| 7,56
15| 6026| 5476| 4698| 3919| 3141| 2362| 6,71| 7,32| 7,42| 7,52| 7,62| 7,72
20| 5864| 5358| 4878| 4398| 2639| /| 7,24| 7,96| 8,48| 9,00| 8,41| /
25| 5701| 5081| 4109| 3136| /| /| 7,91| 8,75| 9,00| 9,25| /| /
30| 5776| 5177| 4249| 3321| /| /| 8,41| 9,37| 9,64| 9,90| /| /
35| 5850| 5290| 4605| 3920| /| /| 8,96| 10,05| 10,34| 10,63| /| /
40| 6298| 5777| 5030| 4282| /| /| 10,84| 12,23| 12,59| 12,94| /| /
43| 6566| 6076| 5304| 4531| /| /| 12,20| 13,87| 14,28| 14,68| /| /

30

| -25| 1796| 1652| 1384| 1115| /| /| 1,48| 1,52| 1,54| 1,55| /| /
-20| 2829| 2575| 2416| 2257| 1528| /| 1,82| 1,86| 1,96| 2,07| 1,90| /
-15| 3407| 3066| 2830| 2595| 1652| /| 2,78| 2,88| 3,04| 3,21| 2,95| /
-10| 4290| 3916| 3375| 2834| 2292| 1751| 3,23| 3,40| 3,43| 3,45| 3,48| 3,50
-7| 5034| 4607| 3751| 2895| 2038| 1182| 3,51| 3,65| 3,68| 3,71| 3,73| 3,76
-5| 5076| 4618| 3803| 2987| 2172| 1356| 3,72| 3,86| 3,89| 3,92| 3,95| 3,98
-2| 5173| 4709| 3890| 3071| 2251| 1432| 4,03| 4,16| 4,19| 4,23| 4,26| 4,29
0| 5269| 4800| 3977| 3154| 2330| 1507| 4,34| 4,46| 4,50| 4,54| 4,57| 4,61
2| 5436| 4944| 4141| 3339| 2536| 1733| 4,51| 4,70| 4,74| 4,79| 4,83| 4,87
5| 5746| 5188| 4388| 3588| 2788| 1988| 4,85| 5,03| 5,08| 5,13| 5,18| 5,23
7| 6222| 4355| 4018| 3682| 2339| 1853| 5,40| 5,65| 6,00| 6,35| 5,89| 5,60
10| 6033| 5281| 4403| 3525| 2646| 1768| 5,16| 5,41| 5,48| 5,54| 5,61| 5,67
12| 5907| 5193| 4385| 3577| 2768| 1960| 5,01| 5,30| 5,37| 5,44| 5,51| 5,57
15| 5717| 5062| 4358| 3655| 2951| 2247| 4,78| 5,13| 5,20| 5,28| 5,35| 5,42
20| 5743| 5113| 4736| 4360| 2814| /| 5,75| 6,22| 6,63| 7,04| 6,58| /
25| 5768| 5237| 4320| 3403| /| /| 7,21| 7,85| 8,08| 8,30| /| /
30| 5836| 5327| 4458| 3589| /| /| 7,48| 8,20| 8,44| 8,68| /| /
35| 5903| 5436| 4725| 4014| /| /| 7,77| 8,57| 8,83| 9,08| /| /
40| 6379| 5773| 5024| 4274| /| /| 9,51| 10,57| 10,88| 11,19| /| /
43| 6665| 6085| 5309| 4532| /| /| 10,80| 12,08| 12,44| 12,80| /| /

35

| -25| 1711| 1560| 1371| 1181| /| /| 1,29| 1,31| 1,32| 1,33| /| /
-20| 2444| 2205| 1812| 1418| /| /| 1,43| 1,48| 1,50| 1,51| /| /
-15| 3253| 2901| 2674| 2447| 1548| /| 2,39| 2,48| 2,62| 2,76| 2,54| /
-10| 4136| 3824| 3296| 2769| 2241| 1713| 2,85| 2,95| 2,97| 3,00| 3,02| 3,04
-7| 4986| 4700| 3837| 2974| 2110| 1247| 3,11| 3,10| 3,16| 3,22| 3,28| 3,34
-5| 5018| 4371| 3632| 2893| 2154| 1415| 3,27| 3,41| 3,44| 3,46| 3,49| 3,51
-2| 5058| 4387| 3645| 2903| 2161| 1419| 3,51| 3,63| 3,66| 3,69| 3,71| 3,74
0| 5098| 4403| 3658| 2913| 2167| 1422| 3,74| 3,85| 3,88| 3,92| 3,95| 3,98
2| 5280| 4400| 3712| 3024| 2335| 1647| 3,87| 4,00| 4,06| 4,12| 4,17| 4,23
5| 5677| 5080| 4291| 3502| 2713| 1924| 4,33| 4,49| 4,53| 4,58| 4,62| 4,66
**7 *| 6255| 4200| 3890| 3579| 2308| 1920| 4,96| 5,10**| 5,43| 5,77| 5,39| 5,01
10| 6067| 5355| 4496| 3636| 2777| 1917| 4,82| 4,97| 5,03| 5,09| 5,15| 5,21
12| 5941| 5267| 4463| 3659| 2855| 2050| 4,73| 4,92| 4,98| 5,05| 5,11| 5,17
15| 5753| 5136| 4414| 3693| 2971| 2249| 4,59| 4,84| 4,91| 4,98| 5,05| 5,12
20| 5774| 5094| 4775| 4456| 3007| /| 5,13| 5,46| 5,82| 6,18| 5,78| /
25| 5805| 5121| 4323| 3525| /| /| 5,85| 6,27| 6,45| 6,63| /| /
30| 5781| 5319| 4553| 3786| /| /| 6,51| 7,01| 7,22| 7,43| /| /
35| 5966| 5538| 4726| 3914| /| /| 7,27| 7,89| 8,13| 8,36| /| /
40| 6359| 5731| 5123| 4515| /| /| 8,57| 9,37| 9,65| 9,93| /| /
43| 6594| 5996| 5372| 4748| /| /| 9,50| 10,46| 10,77| 11,08| /| /

40

| -25| 1531| 1418| 1253| 1087| /| /| 1,18| 1,19| 1,20| 1,20| /| /
-20| 2166| 1984| 1685| 1386| /| /| 1,24| 1,26| 1,28| 1,29| /| /
-15| 2934| 2658| 2151| 1643| /| /| 1,97| 2,02| 2,05| 2,07| /| /
-10| 4017| 3599| 3364| 3128| 2089| /| 2,43| 2,49| 2,63| 2,78| 2,56| /
-7| 4667| 4265| 3873| 3480| 2063| /| 2,70| 2,81| 2,98| 3,16| 2,93| /
-5| 4738| 4214| 3831| 3449| 2056| /| 2,82| 2,96| 3,14| 3,32| 3,07| /
-2| 4827| 4373| 3963| 3554| 2088| /| 3,00| 3,09| 3,28| 3,47| 3,21| /
0| 4916| 4533| 4096| 3659| 2119| /| 3,18| 3,23| 3,42| 3,61| 3,34| /
2| 5183| 4772| 4339| 3906| 2329| /| 3,35| 3,44| 3,66| 3,87| 3,60| /
5| 5588| 5107| 4666| 4226| 2576| /| 3,77| 3,86| 4,09| 4,33| 4,01| /
7| 6259| 4381| 3665| 2948| /| /| 4,41| 4,64| 4,71| 4,78| /| /
10| 5912| 5241| 4843| 4445| 2841| /| 4,63| 4,83| 5,13| 5,44| 5,06| /
12| 5948| 5258| 4870| 4481| 2890| /| 4,79| 5,05| 5,37| 5,70| 5,31| /
15| 6002| 5284| 4910| 4536| 2964| /| 5,04| 5,38| 5,73| 6,08| 5,68| /
20| 6076| 5593| 4736| 3878| /| /| 5,48| 5,89| 6,06| 6,23| /| /
25| 5910| 5473| 4894| 4314| /| /| 6,06| 6,55| 6,75| 6,94| /| /
30| 5886| 5480| 4756| 4032| /| /| 6,39| 6,97| 7,17| 7,37| /| /
35| 5861| 5504| 4774| 4044| /| /| 6,77| 7,43| 7,65| 7,87| /| /
40| 6334| 5777| 5169| 4560| /| /| 7,88| 8,70| 8,96| 9,22| /| /
43| 6617| 6088| 5459| 4830| /| /| 8,63| 9,60| 9,89| 10,17| /| /

45

| -25| 1371| 1285| 1075| 864| /| /| 1,10| 1,09| 1,10| 1,10| /| /
-20| 1976| 1832| 1529| 1225| /| /| 1,13| 1,14| 1,15| 1,15| /| /
-15| 2505| 2222| 1913| 1603| /| /| 1,56| 1,59| 1,60| 1,61| /| /
-10| 3588| 3254| 2714| 2174| /| /| 2,02| 2,05| 2,07| 2,09| /| /
-7| 4538| 4300| 3905| 3510| 2081| /| 2,29| 2,35| 2,49| 2,62| 2,42| /
-5| 4627| 4195| 3844| 3494| 2157| /| 2,45| 2,54| 2,68| 2,83| 2,60| /
-2| 4833| 4327| 3956| 3584| 2190| /| 2,67| 2,77| 2,93| 3,08| 2,83| /
0| 5039| 4460| 4068| 3675| 2222| /| 2,89| 3,00| 3,17| 3,34| 3,07| /
2| 5251| 5100| 4609| 4118| 2387| /| 2,97| 3,00| 3,21| 3,43| 3,23| /
5| 5601| 4824| 4451| 4078| 2591| /| 3,27| 3,42| 3,62| 3,82| 3,52| /
7| 5962| 4300| 3760| 3219| 2800| /| 3,67| 3,80| 3,86| 3,91| 4,00| /
10| 6051| 5477| 5145| 4813| 3274| /| 3,90| 4,05| 4,30| 4,54| 4,21| /
12| 6110| 5555| 4909| 4261| /| /| 4,02| 4,18| 4,37| 4,56| /| /
15| 6199| 5673| 4554| 3434| /| /| 4,21| 4,37| 4,48| 4,58| /| /
20| 6122| 5633| 4715| 3796| /| /| 4,66| 4,88| 5,00| 5,12| /| /
25| 6045| 5668| 5010| 4352| /| /| 5,25| 5,53| 5,67| 5,81| /| /
30| 6020| 5674| 5049| 4424| /| /| 5,62| 5,97| 6,12| 6,27| /| /
35| 5994| 5698| 5067| 4436| /| /| 6,05| 6,47| 6,64| 6,80| /| /
40| 6377| 5890| 5368| 4846| /| /| 6,86| 7,38| 7,57| 7,76| /| /
43| 6606| 6154| 5654| 5153| /| /| 7,39| 8,01| 8,22| 8,42| /| /
“Tw_out

°C”

| “DB/WB

°C”

| Heating Capacity [W]| COP
---|---|---|---
130%| 100%| 90%| 70%| 50%| 30%| 130%| 100%| 90%| 70%| 50%| 30%








50

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| 1853| 1725| 1502| 1279| /| /| 1,06| 1,07| 1,08| 1,08| /| /
-15| 2197| 1957| 1737| 1516| /| /| 1,31| 1,34| 1,35| 1,36| /| /
-10| 3280| 2988| 2608| 2227| /| /| 1,81| 1,84| 1,86| 1,88| /| /
-7| 4410| 4125| 3761| 3397| 2051| /| 2,08| 2,14| 2,26| 2,38| 2,18| /
-5| 4565| 4137| 3781| 3424| 2089| /| 2,26| 2,32| 2,45| 2,58| 2,37| /
-2| 4793| 4274| 3907| 3540| 2163| /| 2,37| 2,42| 2,57| 2,72| 2,52| /
0| 5021| 4410| 4033| 3655| 2236| /| 2,48| 2,52| 2,69| 2,86| 2,68| /
2| 5191| 5027| 4553| 4079| 2389| /| 2,52| 2,56| 2,74| 2,92| 2,75| /
5| 5498| 4533| 4223| 3913| 2581| /| 2,78| 2,86| 3,03| 3,19| 2,94| /
7| 5694| 4538| 3879| 3220| /| /| 3,11| 3,32| 3,36| 3,40| /| /
10| 5797| 5195| 4195| 3194| /| /| 3,40| 3,45| 3,50| 3,54| /| /
12| 5746| 5161| 4214| 3266| /| /| 3,50| 3,60| 3,67| 3,73| /| /
15| 5669| 5109| 4242| 3374| /| /| 3,65| 3,83| 3,92| 4,01| /| /
20| 5721| 5267| 4457| 3646| /| /| 3,99| 4,23| 4,34| 4,44| /| /
25| 5683| 5300| 4806| 4312| /| /| 4,39| 4,68| 4,80| 4,92| /| /
30| 5668| 5450| 4921| 4392| /| /| 4,63| 4,97| 5,10| 5,22| /| /
35| 5586| 5416| 4943| 4469| /| /| 4,90| 5,30| 5,44| 5,57| /| /
40| 6001| 5657| 4861| /| /| /| 5,20| 5,67| 5,96| /| /| /
43| 6250| 5941| 5188| /| /| /| 5,38| 5,90| 6,20| /| /| /








55

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| 1560| 1501| 1320| 1139| /| /| 0,98| 0,99| 1,00| 1,00| /| /
-15| 1835| 1692| 1470| 1248| /| /| 1,18| 1,20| 1,23| 1,25| /| /
-10| 2629| 2398| 2109| 1819| /| /| 1,56| 1,58| 1,59| 1,60| /| /
-7| 4279| 4000| 3618| 3235| 1882| /| 1,83| 1,95| 2,04| 2,12| 1,91| /
-5| 4412| 4036| 3676| 3316| 1993| /| 1,95| 2,00| 2,11| 2,22| 2,04| /
-2| 4770| 4231| 3857| 3484| 2103| /| 2,16| 2,25| 2,37| 2,49| 2,28| /
0| 5129| 4425| 4038| 3651| 2213| /| 2,37| 2,49| 2,62| 2,75| 2,51| /
2| 5263| 5100| 4635| 4171| 2483| /| 2,42| 2,45| 2,62| 2,78| 2,61| /
5| 5536| 4562| 3678| 2793| /| /| 2,68| 2,75| 2,78| 2,81| /| /
7| 5742| 4400| 4023| 3646| /| /| 2,83| 2,95| 3,05| 3,15| /| /
10| 5699| 4963| 4280| 3596| /| /| 3,16| 3,23| 3,29| 3,35| /| /
12| 5671| 4961| 4370| 3778| /| /| 3,26| 3,35| 3,42| 3,49| /| /
15| 5628| 4957| 4505| 4052| /| /| 3,41| 3,53| 3,62| 3,70| /| /
20| 5522| 4892| 4296| 3700| /| /| 3,68| 3,84| 3,94| 4,04| /| /
25| 5416| 4893| 4391| 3889| /| /| 4,02| 4,23| 4,34| 4,44| /| /
30| 5513| 5008| 4552| 4096| /| /| 4,31| 4,56| 4,68| 4,79| /| /
35| 5610| 5141| 4376| /| /| /| 4,62| 4,92| 5,18| /| /| /
40| /| /| /| /| /| /| /| /| /| /| /| /
43| /| /| /| /| /| /| /| /| /| /| /| /








60

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| /| /| /| /| /| /| /| /| /| /| /| /
-15| 1728| 1608| 1418| 1227| /| /| 1,03| 1,03| 1,04| 1,05| /| /
-10| 2811| 2589| 2304| 2018| /| /| 1,56| 1,55| 1,57| 1,58| /| /
-7| 3561| 3149| 2686| 2222| /| /| 1,84| 1,87| 1,89| 1,91| /| /
-5| 3828| 3422| 2856| 2289| /| /| 1,92| 1,95| 1,97| 1,99| /| /
-2| 4113| 3648| 3048| 2448| /| /| 2,00| 2,02| 2,05| 2,07| /| /
0| 4397| 3874| 3241| 2607| /| /| 2,09| 2,09| 2,12| 2,14| /| /
2| 4589| 4036| 3422| 2808| /| /| 2,13| 2,16| 2,20| 2,24| /| /
5| 4902| 4279| 3667| 3054| /| /| 2,35| 2,37| 2,41| 2,44| /| /
7| 5406| 4265| 3911| 3557| /| /| 2,61| 2,65| 2,70| 2,75| /| /
10| 5267| 4841| 4185| 3529| /| /| 2,69| 2,74| 2,80| 2,85| /| /
12| 5175| 4776| 4182| 3588| /| /| 2,76| 2,83| 2,88| 2,91| /| /
15| 5036| 4679| 4178| 3676| /| /| 2,87| 2,97| 2,99| 3,00| /| /
20| 4766| 4452| 3823| 3193| /| /| 3,06| 3,07| 3,15| 3,23| /| /
25| 4495| 4278| 3780| 3281| /| /| 3,30| 3,34| 3,43| 3,52| /| /
30| 4612| 4412| 3947| 3482| /| /| 3,51| 3,57| 3,67| 3,76| /| /
35| /| /| /| /| /| /| /| /| /| /| /| /
40| /| /| /| /| /| /| /| /| /| /| /| /
43| /| /| /| /| /| /| /| /| /| /| /| /








65

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| /| /| /| /| /| /| /| /| /| /| /| /
-15| /| /| /| /| /| /| /| /| /| /| /| /
-10| /| /| /| /| /| /| /| /| /| /| /| /
-7| /| /| /| /| /| /| /| /| /| /| /| /
-5| /| /| /| /| /| /| /| /| /| /| /| /
-2| /| /| /| /| /| /| /| /| /| /| /| /
0| /| /| /| /| /| /| /| /| /| /| /| /
2| /| /| /| /| /| /| /| /| /| /| /| /
5| 4040| 3305| 2820| 2335| /| /| 1,87| 1,96| 2,00| 2,04| /| /
7| 4267| 3537| 3121| 2705| /| /| 2,04| 2,16| 2,21| 2,26| /| /
10| 4494| 3667| 3267| 2867| /| /| 2,22| 2,35| 2,40| 2,44| /| /
12| 4646| 3810| 3379| 2948| /| /| 2,36| 2,52| 2,58| 2,62| /| /
15| 4873| 4025| 3548| 3070| /| /| 2,56| 2,77| 2,84| 2,90| /| /
20| /| /| /| /| /| /| /| /| /| /| /| /
25| /| /| /| /| /| /| /| /| /| /| /| /
30| /| /| /| /| /| /| /| /| /| /| /| /
35| /| /| /| /| /| /| /| /| /| /| /| /
40| /| /| /| /| /| /| /| /| /| /| /| /
43| /| /| /| /| /| /| /| /| /| /| /| /
“Tw_out

°C”

| “DB/WB

°C”

| Heating Capacity [W]| COP
---|---|---|---
130%| 100%| 90%| 70%| 50%| 30%| 130%| 100%| 90%| 70%| 50%| 30%

25

| -25| 2053| 1899| 1566| 1232| /| /| 1,74| 1,78| 1,79| 1,80| /| /
-20| 3086| 2824| 2276| 1728| /| /| 2,36| 2,45| 2,48| 2,50| /| /
-15| 3602| 3260| 2989| 2718| 1682| /| 3,03| 3,17| 3,35| 3,53| 3,25| /
-10| 4465| 4001| 3414| 2828| 2241| 1654| 3,36| 3,60| 3,63| 3,65| 3,68| 3,70
-7| 5112| 4678| 3798| 2917| 2037| 1156| 3,67| 3,85| 3,89| 3,93| 3,97| 4,01
-5| 5180| 4692| 3858| 3024| 2190| 1356| 4,03| 4,22| 4,26| 4,30| 4,34| 4,38
-2| 5296| 4841| 3982| 3122| 2263| 1403| 4,55| 4,71| 4,75| 4,80| 4,84| 4,88
0| 5412| 4990| 4105| 3220| 2335| 1450| 5,06| 5,19| 5,24| 5,28| 5,33| 5,37
2| 5629| 5182| 4310| 3439| 2567| 1695| 5,28| 5,45| 5,52| 5,58| 5,65| 5,71
5| 5994| 5479| 4601| 3723| 2844| 1966| 5,83| 6,04| 6,10| 6,16| 6,22| 6,28
7| 6376| 4603| 4215| 3826| 2354| 1955| 6,67| 6,98| 7,41| 7,84| 7,28| 6,96
10| 6370| 5725| 4781| 3837| 2893| 1949| 6,68| 7,13| 7,21| 7,30| 7,38| 7,46
12| 6232| 5625| 4748| 3870| 2992| 2114| 6,69| 7,21| 7,29| 7,39| 7,48| 7,56
15| 6026| 5476| 4698| 3919| 3141| 2362| 6,71| 7,32| 7,42| 7,52| 7,62| 7,72
20| 5864| 5358| 4878| 4398| 2639| /| 7,24| 7,96| 8,48| 9,00| 8,41| /
25| 5701| 5081| 4109| 3136| /| /| 7,91| 8,75| 9,00| 9,25| /| /
30| 5776| 5177| 4249| 3321| /| /| 8,41| 9,37| 9,64| 9,90| /| /
35| 5850| 5290| 4605| 3920| /| /| 8,96| 10,05| 10,34| 10,63| /| /
40| 6298| 5777| 5030| 4282| /| /| 10,84| 12,23| 12,59| 12,94| /| /
43| 6566| 6076| 5304| 4531| /| /| 12,20| 13,87| 14,28| 14,68| /| /

30

| -25| 1796| 1652| 1384| 1115| /| /| 1,48| 1,52| 1,54| 1,55| /| /
-20| 2829| 2575| 2416| 2257| 1528| /| 1,82| 1,86| 1,96| 2,07| 1,90| /
-15| 3407| 3066| 2830| 2595| 1652| /| 2,78| 2,88| 3,04| 3,21| 2,95| /
-10| 4290| 3916| 3375| 2834| 2292| 1751| 3,23| 3,40| 3,43| 3,45| 3,48| 3,50
-7| 5034| 4607| 3751| 2895| 2038| 1182| 3,51| 3,65| 3,68| 3,71| 3,73| 3,76
-5| 5076| 4618| 3803| 2987| 2172| 1356| 3,72| 3,86| 3,89| 3,92| 3,95| 3,98
-2| 5173| 4709| 3890| 3071| 2251| 1432| 4,03| 4,16| 4,19| 4,23| 4,26| 4,29
0| 5269| 4800| 3977| 3154| 2330| 1507| 4,34| 4,46| 4,50| 4,54| 4,57| 4,61
2| 5436| 4944| 4141| 3339| 2536| 1733| 4,51| 4,70| 4,74| 4,79| 4,83| 4,87
5| 5746| 5188| 4388| 3588| 2788| 1988| 4,85| 5,03| 5,08| 5,13| 5,18| 5,23
7| 6222| 4355| 4018| 3682| 2339| 1853| 5,40| 5,65| 6,00| 6,35| 5,89| 5,60
10| 6033| 5281| 4403| 3525| 2646| 1768| 5,16| 5,41| 5,48| 5,54| 5,61| 5,67
12| 5907| 5193| 4385| 3577| 2768| 1960| 5,01| 5,30| 5,37| 5,44| 5,51| 5,57
15| 5717| 5062| 4358| 3655| 2951| 2247| 4,78| 5,13| 5,20| 5,28| 5,35| 5,42
20| 5743| 5113| 4736| 4360| 2814| /| 5,75| 6,22| 6,63| 7,04| 6,58| /
25| 5768| 5237| 4320| 3403| /| /| 7,21| 7,85| 8,08| 8,30| /| /
30| 5836| 5327| 4458| 3589| /| /| 7,48| 8,20| 8,44| 8,68| /| /
35| 5903| 5436| 4725| 4014| /| /| 7,77| 8,57| 8,83| 9,08| /| /
40| 6379| 5773| 5024| 4274| /| /| 9,51| 10,57| 10,88| 11,19| /| /
43| 6665| 6085| 5309| 4532| /| /| 10,80| 12,08| 12,44| 12,80| /| /

35

| -25| 1711| 1560| 1371| 1181| /| /| 1,29| 1,31| 1,32| 1,33| /| /
-20| 2444| 2205| 1812| 1418| /| /| 1,43| 1,48| 1,50| 1,51| /| /
-15| 3253| 2901| 2674| 2447| 1548| /| 2,39| 2,48| 2,62| 2,76| 2,54| /
-10| 4136| 3824| 3296| 2769| 2241| 1713| 2,85| 2,95| 2,97| 3,00| 3,02| 3,04
-7| 4986| 4700| 3837| 2974| 2110| 1247| 3,11| 3,10| 3,16| 3,22| 3,28| 3,34
-5| 5018| 4371| 3632| 2893| 2154| 1415| 3,27| 3,41| 3,44| 3,46| 3,49| 3,51
-2| 5058| 4387| 3645| 2903| 2161| 1419| 3,51| 3,63| 3,66| 3,69| 3,71| 3,74
0| 5098| 4403| 3658| 2913| 2167| 1422| 3,74| 3,85| 3,88| 3,92| 3,95| 3,98
2| 5280| 4400| 3712| 3024| 2335| 1647| 3,87| 4,00| 4,06| 4,12| 4,17| 4,23
5| 5677| 5080| 4291| 3502| 2713| 1924| 4,33| 4,49| 4,53| 4,58| 4,62| 4,66
**7 *| 6255| 4200| 3890| 3579| 2308| 1920| 4,96| 5,10**| 5,43| 5,77| 5,39| 5,01
10| 6067| 5355| 4496| 3636| 2777| 1917| 4,82| 4,97| 5,03| 5,09| 5,15| 5,21
12| 5941| 5267| 4463| 3659| 2855| 2050| 4,73| 4,92| 4,98| 5,05| 5,11| 5,17
15| 5753| 5136| 4414| 3693| 2971| 2249| 4,59| 4,84| 4,91| 4,98| 5,05| 5,12
20| 5774| 5094| 4775| 4456| 3007| /| 5,13| 5,46| 5,82| 6,18| 5,78| /
25| 5805| 5121| 4323| 3525| /| /| 5,85| 6,27| 6,45| 6,63| /| /
30| 5781| 5319| 4553| 3786| /| /| 6,51| 7,01| 7,22| 7,43| /| /
35| 5966| 5538| 4726| 3914| /| /| 7,27| 7,89| 8,13| 8,36| /| /
40| 6359| 5731| 5123| 4515| /| /| 8,57| 9,37| 9,65| 9,93| /| /
43| 6594| 5996| 5372| 4748| /| /| 9,50| 10,46| 10,77| 11,08| /| /

40

| -25| 1531| 1418| 1253| 1087| /| /| 1,18| 1,19| 1,20| 1,20| /| /
-20| 2166| 1984| 1685| 1386| /| /| 1,24| 1,26| 1,28| 1,29| /| /
-15| 2934| 2658| 2151| 1643| /| /| 1,97| 2,02| 2,05| 2,07| /| /
-10| 4017| 3599| 3364| 3128| 2089| /| 2,43| 2,49| 2,63| 2,78| 2,56| /
-7| 4667| 4265| 3873| 3480| 2063| /| 2,70| 2,81| 2,98| 3,16| 2,93| /
-5| 4738| 4214| 3831| 3449| 2056| /| 2,82| 2,96| 3,14| 3,32| 3,07| /
-2| 4827| 4373| 3963| 3554| 2088| /| 3,00| 3,09| 3,28| 3,47| 3,21| /
0| 4916| 4533| 4096| 3659| 2119| /| 3,18| 3,23| 3,42| 3,61| 3,34| /
2| 5183| 4772| 4339| 3906| 2329| /| 3,35| 3,44| 3,66| 3,87| 3,60| /
5| 5588| 5107| 4666| 4226| 2576| /| 3,77| 3,86| 4,09| 4,33| 4,01| /
7| 6259| 4381| 3665| 2948| /| /| 4,41| 4,64| 4,71| 4,78| /| /
10| 5912| 5241| 4843| 4445| 2841| /| 4,63| 4,83| 5,13| 5,44| 5,06| /
12| 5948| 5258| 4870| 4481| 2890| /| 4,79| 5,05| 5,37| 5,70| 5,31| /
15| 6002| 5284| 4910| 4536| 2964| /| 5,04| 5,38| 5,73| 6,08| 5,68| /
20| 6076| 5593| 4736| 3878| /| /| 5,48| 5,89| 6,06| 6,23| /| /
25| 5910| 5473| 4894| 4314| /| /| 6,06| 6,55| 6,75| 6,94| /| /
30| 5886| 5480| 4756| 4032| /| /| 6,39| 6,97| 7,17| 7,37| /| /
35| 5861| 5504| 4774| 4044| /| /| 6,77| 7,43| 7,65| 7,87| /| /
40| 6334| 5777| 5169| 4560| /| /| 7,88| 8,70| 8,96| 9,22| /| /
43| 6617| 6088| 5459| 4830| /| /| 8,63| 9,60| 9,89| 10,17| /| /

45

| -25| 1371| 1285| 1075| 864| /| /| 1,10| 1,09| 1,10| 1,10| /| /
-20| 1976| 1832| 1529| 1225| /| /| 1,13| 1,14| 1,15| 1,15| /| /
-15| 2505| 2222| 1913| 1603| /| /| 1,56| 1,59| 1,60| 1,61| /| /
-10| 3588| 3254| 2714| 2174| /| /| 2,02| 2,05| 2,07| 2,09| /| /
-7| 4538| 4300| 3905| 3510| 2081| /| 2,29| 2,35| 2,49| 2,62| 2,42| /
-5| 4627| 4195| 3844| 3494| 2157| /| 2,45| 2,54| 2,68| 2,83| 2,60| /
-2| 4833| 4327| 3956| 3584| 2190| /| 2,67| 2,77| 2,93| 3,08| 2,83| /
0| 5039| 4460| 4068| 3675| 2222| /| 2,89| 3,00| 3,17| 3,34| 3,07| /
2| 5251| 5100| 4609| 4118| 2387| /| 2,97| 3,00| 3,21| 3,43| 3,23| /
5| 5601| 4824| 4451| 4078| 2591| /| 3,27| 3,42| 3,62| 3,82| 3,52| /
7| 5962| 4300| 3760| 3219| 2800| /| 3,67| 3,80| 3,86| 3,91| 4,00| /
10| 6051| 5477| 5145| 4813| 3274| /| 3,90| 4,05| 4,30| 4,54| 4,21| /
12| 6110| 5555| 4909| 4261| /| /| 4,02| 4,18| 4,37| 4,56| /| /
15| 6199| 5673| 4554| 3434| /| /| 4,21| 4,37| 4,48| 4,58| /| /
20| 6122| 5633| 4715| 3796| /| /| 4,66| 4,88| 5,00| 5,12| /| /
25| 6045| 5668| 5010| 4352| /| /| 5,25| 5,53| 5,67| 5,81| /| /
30| 6020| 5674| 5049| 4424| /| /| 5,62| 5,97| 6,12| 6,27| /| /
35| 5994| 5698| 5067| 4436| /| /| 6,05| 6,47| 6,64| 6,80| /| /
40| 6377| 5890| 5368| 4846| /| /| 6,86| 7,38| 7,57| 7,76| /| /
43| 6606| 6154| 5654| 5153| /| /| 7,39| 8,01| 8,22| 8,42| /| /
“Tw_out

°C”

| “DB/WB

°C”

| Heating Capacity [W]| COP
---|---|---|---
130%| 100%| 90%| 70%| 50%| 30%| 130%| 100%| 90%| 70%| 50%| 30%

50

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| 2187| 2036| 1773| 1509| /| /| 1,07| 1,08| 1,09| 1,09| /| /
-15| 2702| 2407| 2136| 1864| /| /| 1,34| 1,37| 1,38| 1,39| /| /
-10| 4127| 3760| 3281| 2802| /| /| 1,72| 1,75| 1,77| 1,78| /| /
-7| 5287| 5068| 4635| 4202| 2572| /| 2,01| 2,07| 2,18| 2,30| 2,11| /
-5| 5440| 5114| 4676| 4237| 2590| /| 2,23| 2,27| 2,41| 2,54| 2,35| /
-2| 5659| 5235| 4824| 4413| 2788| /| 2,36| 2,40| 2,54| 2,68| 2,47| /
0| 5879| 5356| 4972| 4589| 2987| /| 2,48| 2,53| 2,67| 2,82| 2,59| /
2| 6047| 5730| 5316| 4902| 3182| /| 2,54| 2,63| 2,79| 2,95| 2,73| /
5| 6374| 5905| 5519| 5134| 3429| /| 2,81| 2,89| 3,06| 3,23| 2,98| /
7| 6868| 6133| 5196| 4258| /| /| 3,17| 3,29| 3,35| 3,41| /| /
10| 7006| 6474| 5350| 4225| /| /| 3,35| 3,44| 3,51| 3,57| /| /
12| 7098| 6588| 5455| 4321| /| /| 3,48| 3,61| 3,69| 3,76| /| /
15| 7236| 6759| 5612| 4465| /| /| 3,67| 3,86| 3,96| 4,05| /| /
20| 7284| 6840| 5788| 4735| /| /| 4,02| 4,25| 4,36| 4,46| /| /
25| 7332| 7014| 6257| 5499| /| /| 4,43| 4,72| 4,84| 4,96| /| /
30| 6909| 6644| 5999| 5354| /| /| 4,92| 5,28| 5,42| 5,55| /| /
35| 6486| 6289| 5739| 5189| /| /| 5,21| 5,63| 5,78| 5,92| /| /
40| 6928| 6530| 5612| /| /| /| 5,68| 6,19| 6,50| /| /| /
43| 7193| 6838| 5970| /| /| /| 5,96| 6,54| 6,87| /| /| /

55

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| 1841| 1771| 1558| 1344| /| /| 0,99| 1,00| 1,01| 1,01| /| /
-15| 2257| 2081| 1808| 1535| /| /| 1,20| 1,22| 1,23| 1,24| /| /
-10| 3797| 3463| 3046| 2628| /| /| 1,69| 1,71| 1,73| 1,74| /| /
-7| 5217| 5150| 4717| 4284| 2639| /| 1,96| 2,00| 2,10| 2,21| 2,01| /
-5| 5305| 5078| 4708| 4338| 2809| /| 2,01| 2,06| 2,18| 2,29| 2,11| /
-2| 5363| 5112| 4740| 4369| 2831| /| 2,05| 2,09| 2,21| 2,33| 2,14| /
0| 5421| 5146| 4772| 4399| 2852| /| 2,09| 2,11| 2,23| 2,35| 2,17| /
2| 5691| 5650| 5240| 4829| 3130| /| 2,41| 2,45| 2,59| 2,73| 2,52| /
5| 6110| 5801| 5447| 5092| 3458| /| 2,48| 2,54| 2,69| 2,84| 2,62| /
7| 6899| 6000| 5191| 4381| /| /| 2,91| 2,95| 3,03| 3,10| /| /
10| 6931| 6036| 5205| 4373| /| /| 3,04| 3,11| 3,17| 3,23| /| /
12| 6952| 6082| 5359| 4635| /|  | 3,14| 3,23| 3,30| 3,37| /|
15| 6984| 6152| 5590| 5028| /| /| 3,30| 3,42| 3,50| 3,58| /| /
20| 6808| 6031| 5296| 4561| /| /| 3,60| 3,76| 3,86| 3,95| /| /
25| 6632| 5991| 5377| 4762| /| /| 4,00| 4,20| 4,31| 4,41| /| /
30| 6603| 5998| 5452| 4906| /| /| 4,21| 4,46| 4,58| 4,69| /| /
35| 6574| 6024| 5128| /| /| /| 4,45| 4,75| 4,99| /| /| /
40| /| /| /| /| /| /| /| /| /| /| /| /
43| /| /| /| /| /| /| /| /| /| /| /| /

60

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| /| /| /| /| /| /| /| /| /| /| /| /
-15| 2125| 1978| 1744| 1509| /| /| 1,05| 1,05| 1,06| 1,07| /| /
-10| 3320| 3058| 2721| 2384| /| /| 1,44| 1,44| 1,46| 1,47| /| /
-7| 4573| 4276| 3478| 2679| /| /| 1,75| 1,79| 1,81| 1,82| /| /
-5| 4728| 4345| 3532| 2719| /| /| 1,83| 1,85| 1,88| 1,90| /| /
-2| 4896| 4453| 3657| 2861| /| /| 1,91| 1,92| 1,95| 1,97| /| /
0| 5064| 4561| 3782| 3003| /| /| 1,99| 1,99| 2,02| 2,04| /| /
2| 5334| 4991| 4128| 3264| /| /| 2,05| 2,08| 2,12| 2,16| /| /
5| 5744| 5217| 4398| 3579| /| /| 2,27| 2,29| 2,33| 2,36| /| /
7| 6424| 5644| 4936| 4227| /| /| 2,55| 2,60| 2,65| 2,69| /| /
10| 6270| 5763| 4982| 4201| /| /| 2,60| 2,65| 2,70| 2,75| /| /
12| 6167| 5693| 4984| 4276| /|  | 2,64| 2,71| 2,74| 2,78| /|
15| 6013| 5587| 4988| 4389| /| /| 2,70| 2,79| 2,81| 2,82| /| /
20| 5977| 5584| 4795| 4005| /| /| 3,06| 3,07| 3,15| 3,23| /| /
25| 5941| 5654| 4996| 4337| /| /| 3,55| 3,59| 3,69| 3,78| /| /
30| 6013| 5752| 5146| 4540| /| /| 3,83| 3,91| 4,01| 4,11| /| /
35| /| /| /| /| /| /| /| /| /| /| /| /
40| /| /| /| /| /| /| /| /| /| /| /| /
43| /| /| /| /| /| /| /| /| /| /| /| /

65

| -25| /| /| /| /| /| /| /| /| /| /| /| /
-20| /| /| /| /| /| /| /| /| /| /| /| /
-15| /| /| /| /| /| /| /| /| /| /| /| /
-10| /| /| /| /| /| /| /| /| /| /| /| /
-7| /| /| /| /| /| /| /| /| /| /| /| /
-5| /| /| /| /| /| /| /| /| /| /| /| /
-2| /| /| /| /| /| /| /| /| /| /| /| /
0| /| /| /| /| /| /| /| /| /| /| /| /
2| /| /| /| /| /| /| /| /| /| /| /| /
5| 4924| 4228| 3537| 2846| /| /| 1,84| 1,91| 1,96| 2,01| /| /
7| 5245| 4402| 3864| 3325| /| /| 2,02| 2,14| 2,19| 2,24| /| /
10| 5566| 4542| 4047| 3551| /| /| 2,21| 2,34| 2,39| 2,43| /| /
12| 6101| 5039| 4442| 3844| /| /| 2,56| 2,77| 2,84| 2,90| /| /
15| /| /| /| /| /| /| /| /| /| /| /| /
20| /| /| /| /| /| /| /| /| /| /| /| /
25| /| /| /| /| /| /| /| /| /| /| /| /
30| /| /| /| /| /| /| /| /| /| /| /| /
35| /| /| /| /| /| /| /| /| /| /| /| /
40| /| /| /| /| /| /| /| /| /| /| /| /
43| /| /| /| /| /| /| /| /| /| /| /| /