Automatic Technology O-10V3L2 GDO-10 Toro Roll Up Door Opener Instruction Manual

June 10, 2024
automatic TECHNOLOGY

O-10V3L2 GDO-10 Toro Roll Up Door Opener

Product Information: GDO-10 Toro Roll Up Door Opener

The GDO-10 Toro Roll Up Door Opener is an automatic garage door
operator designed to offer safe service provided it is installed
and operated in strict accordance with the safety rules provided in
the installation manual. The opener comes with controller input and
outputs, a 12 volts 6 Amp – Hr backup battery, and a standby
battery charger/solar connector. It can be programmed for setting
limits, coding transmitters, setting pedestrian position, and
safety obstruction force test. It also has features like Safety
Close & Auto-Close Mode, Time Clock Operation, and Accessories
Installation.

Product Usage Instructions

Before using the GDO-10 Toro Roll Up Door Opener, it is
important to carefully read the installation manual and follow all
safety rules provided. Failure to comply with the instructions and
safety warnings may result in death, serious personal injury,
and/or property damage.

Set Up Requirements

The following set up requirements should be considered before
installation:

  • Door Operation
  • Unsuitable Door Types
  • Position
  • Power Supply
  • Sideroom
  • Forks

Installation

The installation process involves:

  1. Preparation and Pinning the curtain
  2. Door prop preparation
  3. Mounting The Opener
  4. Installing The Wall Mounted Control Unit

Programming The Opener

The opener can be programmed for:

  • Setting Limits
  • Coding Transmitter
  • Remotely Coding Transmitters
  • Setting Pedestrian Position
  • Safety Obstruction Force Test
  • Safety Close & Auto-Close Mode
  • Time Clock Operation
  • Accessories Installation

Setting Limits

The limits of the opener can be set using the following
methods:

  • Setting Travel Limits
  • Code A Transmitter For Limit Setting
  • Setting Limits Via Transmitter

Coding Transmitter

The transmitter can be coded using the following methods:

  • Coding Transmitter Button
  • Selecting Function Of The Button
  • Returning To Main Screen

Remotely Coding Transmitters

The transmitter can be remotely coded using the following
methods:

  • Selecting The Function To Be Coded
  • Activate Remote Code Set Mode

Setting Pedestrian Position

The pedestrian position can be set using the following
methods:

  • Setting Pedestrian Position
  • Checking Pedestrian Position
  • Error Displays

Safety Obstruction Force Test

The safety obstruction force test can be performed using the
following methods:

  • Testing Close Cycle
  • Testing Open Cycle
  • Adjusting the Safety Obstruction Force
  • To Recalculate Force Margins

Safety Close & Auto-Close Mode

The opener has various safety close and auto-close modes
like:

  • Safety Close Mode
  • Setting Up Standard Auto-Close Mode
  • Safety Beam Triggered Auto Close
  • Pedestrian Auto-Close
  • Auto-Close After Obstruction

Time Clock Operation

The time clock operation can be performed using the following
methods:

  • Time Clock Settings
  • Day Light Saving Time Adjustment

Accessories Installation

Accessories like courtesy lights, solenoid or magnetic locks can
be installed using the instructions provided in the manual.

Battery Replacement

If required, the backup battery and transmitter batteries can be
replaced using the instructions provided in the manual.

Battery Disposal

The batteries should be disposed of properly as per the
instructions provided in the manual.

Troubleshooting

If the opener is not functioning correctly, refer to the
troubleshooting guide provided in the manual.

After Installation Care

Follow the service checklist provided in the manual for
maintaining the opener after installation.

Warranty

The opener comes with a warranty. Refer to the warranty section
in the manual for more details.

GDO-10 Tor
Roll Up Door Opener
Installation Manual
Doc # 160426_03 Released 01/09/22

2 GDO-10 Toro Installation Manual

GDO-10V3L2 ToroTM

Roll Up Garage Door Opener

Contents 1. Safety Information 2. Controller Input And Outputs 3. Operating Controls 4. Set Up Requirements 5. Pre-Installation Requirements
5.1 Door Operation 5.2 Unsuitable Door Types 5.3 Position 5.4 Power Supply 5.5 Sideroom 5.6 Forks
6. Installation
6.1 Preparation and Pinning the curtain 6.2 Door prop preparation 6.3 Mounting The Opener 6.4 Installing The Wall Mounted Control Unit
7. Programming The Opener 8. Setting Limits
8.1 Setting Travel Limits 8.2 Code A Transmitter For Limit Setting 8.3 Setting Limits Via Transmitter
9. Coding Transmitter
9.1 Coding Transmitter Button 9.2 Selecting Function Of The Button 9.3 Returning To Main Screen
10. Remotely Coding Transmitters
10.1 Selecting The Function To Be Coded 10.2 Activate Remote Code Set Mode
11. Setting Pedestrian Position
11.1 Setting Pedestrian Position 11.2 Checking Pedestrian Position 11.3 Error Displays
12. Safety Obstruction Force Test
12.1 Testing Close Cycle 12.2 Testing Open Cycle 12.3 Adjusting the Safety Obstruction Force. 12.4 To Recalculate Force Margins

3 13. Safety Close & Auto-Close Mode

15

4

13.1 Safety Close Mode

15

5

13.2 Setting Up Satndard Auto-Close Mode

15

6

13.3 Safety Beam Triggered Auto Close

15

13.4 Pedestrian Auto-Close

15

7

13.5 Auto-Close After Obstruction:

15

7

14. Time Clock

16

7

14.1 Time Clock Operation

16

7

14.2 Time Clock Settings

16

7

14.3 Day Light Saving Time Adjustment

17

7

7

15. Accessories Installation

17

8

15.1 Fitting Courtesy Lights

17

15.2 Fitting Solenoid Or Magnetic Locks

17

8

8

16. Battery Replacement

18

8

16.1 Replacing Backup Batteries

18

9

16.2 Replacing Transmitter Batteries

18

9 17. Battery Disposal

18

10 18. Specifications

19

10 19. Troubleshooting

20

11 20. After Installation Care

21

11

20.1 Service Checklist

21

12

20.2 Warranty

21

12 21. Appendix

22

12

A – Console Menu Structure

22

12

B – Viewing & Editing Logic Console Parameters

24

13

C – Control Board Adjustments

25

13

D – Diagnostic Tools

27

13

E – Memory Tools

28

13

F- Transmitter Editing

29

13

G – Transmitter Management

31

13

13

14

14

14

14

14

Automatic Technology Australia Pty Ltd to the extent that such may be lawfully excluded hereby expressly disclaims all conditions or warranties, statutory or otherwise which may be implied by laws as conditions or warranties of purchase of an Automatic Technology Australia Pty Ltd Garage Door Opener. Automatic Technology Australia Pty Ltd hereby further expressly excludes all or any liability for any injury, damage, cost, expense or claim whatsoever suffered by any person as a result whether directly or indirectly from failure to install the Automatic Technology Australia Pty Ltd Garage Door Opener in accordance with these installation instructions.

3 GDO-10 Toro Installation Manual

1. Safety Information

Please read these important safety rules
These safety alert symbols indicate a personal safety or property damage instruction exists. READ THESE INSTRUCTIONS CAREFULLY.
This automatic garage door operator is designed and tested to offer safe service provided it is installed and operated in strict accordance with the following safety rules. Failure to comply with the installation instructions and the safety warnings may result in death, serious personal injury and/or property damage.

WARNING!

BATTERY WARNING!

· To reduce the risk of injury to persons ­ Use this operator only with a rolling door. The drive must not be used with a door incorporating a wicket door, unless the drive cannot be operated with the wicket door open.
· This operator is a plug in domestic appliance and is designed for indoor use only. It must be installed in a dry position that is protected from the weather.
· Activate the operator only when the garage door is in full view, free of obstructions and with the operator properly adjusted.
· Watch the moving door and keep people away until the door is completely opened or closed.

· This product contains a lithium button/coin cell battery in the transmitters. If a new or used lithium button/coin cell battery is swallowed or enters the body, it can cause severe internal burns and can lead to DEATH in as little as 2 hours. Always completely secure the battery compartment. If the battery compartment does not close securely, stop using the product, remove the battery and keep it away from children. If you think batteries might have been swallowed or placed inside any part of the body, SEEK IMMEDIATE MEDICAL ATTENTION.
CAUTION:

ELECTROCUTION:
· Installation and wiring must be in compliance with your local building and electrical codes.
· This operator is not equipped for permanent wiring. Contact a qualified electrician to install a suitable receptacle if one is not available.
· To reduce the risk of electric shock, this equipment has a grounding type plug that has a third (grounding) pin. This plug will only fit into a grounding type outlet. If the plug does not fit into outlet, contact a qualified electrician to install the proper outlet. Do not change the plug in any way.
· If the power cord is damaged, it must be replaced by the manufacturer, its service agent or a similarly qualified person in order to avoid a hazard.
· Connect the power cord only to properly earthed mains. If an extension lead must be used, make sure it is a 3-core lead and approved to 7 amp capacity.
· This unit is not user serviceable. Unplug the power cord before removing the cover. Ensure that the power cord is attached clear of all moving parts. Ignoring these instructions can cause electric shock.
· Disconnect the power supply when cleaning or other maintenance is being carried out.

· If your garage has no pedestrian entrance door, an emergency access device should be installed. This accessory allows manual operation of the garage door from outside in case of power failure.
· Frequently examine the installation for imbalance where applicable and signs of wear or damage to springs and mounting. Do not use if repair or adjustment is necessary. Sticking or binding doors must be repaired. Garage doors, door springs, brackets and their hardware are under extreme tension and can cause serious personal injury. Do not attempt any garage door adjustment. Call for professional garage door service.
· Position the Garage Door Operator so that the power plug is accessible when inserted into the power outlet.
· Install the wall transmitter in a location where the garage door is visible, but out of the reach of children at a height of at least 5 feet (1.53m).
· To avoid serious personal injury from entanglement, remove all unnecessary ropes or chains and disable any equipment such as locks which are not needed for powered operation.
· Do not wear rings, watches or loose clothing while installing or servicing a garage door operator.
· Ensure ladder is the correct type for the job and is on flat ground. We recommend the user has 3 points of contact while on ladder.
· Activate the operator only when the garage door is in full view, free of obstructions and with the operator properly adjusted.
· The operator is not intended for use by young children or infirm persons without supervision.
· Keep transmitters away from children.
· Do not allow children to play with door controls

4 GDO-10 Toro Installation Manual
2. Controller Input And Outputs

08 07

12 11

10

01

02

09

03

06

04

Fig 2.1

01 Light Relay Output N/O, Com, N/C Contact

02 Lock Relay Output N/O, Com, N/C Contact

03 Serial Interface Connector

04 12 volts 6 Amp – Hr Batteries

05 Engage/Disengagement Handle

06 Standby Battery Charger/Solar

05

Connector

07 Solar Shunt 08 Standby Battery Shunt 09 Motor Connector 10 10 Amps Slow Blow Fuse 11 24 Volts Ac In Connector 12 Position Sensor Connector

5 GDO-10 Toro Installation Manual
3. Operating Controls

16

15

18

17

14

19

20

13

21

Fig 3.1

13 Terminal Block ( From Left To Right ) AUX OUT Receiver’s Auxiliary Output V+ Accessory Supply SB3 Third Safety Beam Input SB2 Second Safety Beam Input SB1 First Safety Beam Input 0V Common For Safety Beams 0V Common Terminal For Control Inputs FIRE N/O , N/C Input Terminal GPI N/O Input Terminal OPN N/O , N/C Input Terminal STP N/O , N/C Input Terminal CLS N/O Input Terminal

14 Programmer PG-3 Input 15 Console Previous Button 16 Liquid Crystal Display 17 Console Next Button 18 Console Open Button 19 Console Stop Button 20 Console Set Button 21 Console Close Button

6 GDO-10 Toro Installation Manual
4. Set Up Requirements

4.1 Kit Contents
ITEM DESCRIPTION
1 GDO-10V3L2 POWER DRIVE UNIT 2 COMMUNICATION CABLE 3 WALL CONTROL UNIT L2 4 TRIO-CODE 4B PTX-5 TRANSMITTER 5 LOCKING BAR COVER 6 FORK EXTENSION
ACCESSORY PACK (61480) 7 CLIP CABLE CLIPSAL NO 564/1 8 SCREW-EYE 9 SELF TAPPING SCREW 6 X 25 (1″) 10 PLASTIC WALL PLUG 6.9 X 25 (1″)

QTY
1 1 1 2 2 6

ORDER CODE 60233 61909 61565 61161 71040 61486

5

72845

2

10595

2

10672

4

11152

2

3

1 4

5

4.2 Choosing your Set up The GDO-10V3L2 can be set up in various ways and therefore may require additional items. Common Set ups are as follows;

Set Up Dead Man Set Up
Automated Set Up
Automated Set Up with Safety Beams

Items Required Drive Unit, console
Drive Unit, console and transmitter
Drive Unit, console, transmitter and safety beams (optional extra)

7 8

6

9

10

Fig 4.1

7 GDO-10 Toro Installation Manual
5. Pre-Installation Requirements

Fig 5.1 Fig 5.2 Fig 5.3

IMPORTANT SAFETY INSTRUCTIONS FOR INSTALLATION Warning: Incorrect installation can lead to severe injury. Follow ALL installation instructions.

185

NOTE: Planetary chain equipment must be removed from the door

140

prior to installation of GDO-10V3L2 ToroTM.

5.1 Door Operation The door must be in good operating condition. The maximum effort to move the door up or down, from stationary, should not exceed 150 Newtons (15 kg force) at the bottom rail.

Lift the door to about halfway. When released, the door should stay in place supported entirely by its springs. Raise and lower the door to check for binding or sticking.

The door may need to be serviced to meet these requirements ­ refer to the door manufacturer’s servicing instructions or contact an authorised dealer.

5.2 Unsuitable Door Types

182

The fitting of an opener to doors with removable mullions or doors

127

incorporating a wicket door is not recommended.

5.3 Position The opener can be installed on either the right or left hand side of the door (when viewed from inside the garage). The opener is factory set for right hand side installation. This opener must be installed in a dry position that is protected from the weather. Moisture or corrosion damage is not covered by the Warranty.

5.4 Power Supply Properly earthed 3 pin single-phase power is required.

WARNING! Using a portable power generator is not recommended. The opener may appear to malfunction due to spikes, surges and fluctuations in the generated voltage.

6

5.5 Sideroom Sideroom For Right Hand Side Installation

The minimum sideroom required from the edge of the door curtain is 140

mm to the inside of the door bracket when the opener is mounted on the

door bracket (Fig. 5.1).

1

NOTE: The door axle diameter must not exceed 35mm.

· Sideroom For Left Hand Side Installation The minimum sideroom required from the edge of the door curtain is 127 mm to the inside of the door bracket when the opener is mounted on the door bracket (Fig. 5.2).
5.6 Forks Attach and secure all six (6) forks 6 to the drive unit 1 with screws supplied (Fig. 5.3). All the six (6) forks must be used and properly engaged into the drum of the door for the opener to work effectively.

8 GDO-10 Toro Installation Manual

6. Installation

6.1.1 Preparation

a. Check the door’s operation:

i. The door must travel smoothly and be easy to operate by hand.

ii. Adjust any tight or twisted guides.

iii. Clean the guides if there is any oil or wax present using a suitable white spirit. The only lubricant suitable for use on

door guides is silicon spray. DO NOT use WD-40, RP-7, petroleum grease, or similar.

b. Install the locking bar covers 5 if there are locking bar holes in the guides.

c. Affix the warning labels supplied with this opener in a prominent place where they are clearly visible.

d. Choose the side where the opener will be installed ensuring there is sufficient sideroom.

Check that the door is still balanced and smooth to operate. If it is not, the door may require servicing (refer to door manufacturer’s instructions).

Screw into the low part of

6.1.2 Pinning the Door to the drum:

grove

Pinning the door’s curtain to its drum maintains security when the opener is

closed. If the curtain is not pinned the door can be partially opened manually.

a. Fully close the door.

b. Mark a minimum of two (2) drill holes on the drum to each end of the door.

c. Drill holes using 3.2mm (1/8″) drill bit.

d. Fit M10 x 32mm screws and washers (not supplied) to each of the four (4)

holes. This screw should be positioned as low as possible in the grove, but

make sure that it does not alter the curtain’s normal lead in to the guide

as per Fig. 6.1.

BALLOONING DOOR

Fig 6.1

FREE DOOR

PINNED DOOR

Pin Points

6.2 Door prop preparation a. At the end opposite to where the opener will be fitted, check that
each nut securing the door axle, is tightened (to a torque setting of 40Nm) to the bracket. (Fig. 6.2) b. Open the door completely and tie safety ropes around the door roll approximately 300 mm from each end. Do not tie the ropes too tight as damage to the curtain may ensue. c. At the end where the opener is to be fitted, support the door with a safe and suitable lifter.
WARNING! Make sure the door is secure in the support, is stable and will not move.
d. At the end where the opener will be fitted, use pen to mark the position of the saddle on the door bracket and the position of the door bracket on the wall to assist in reassembling.
e. Remove the bolts and saddle from the door bracket. f. Raise the door off the door bracket and secure in the support.

Fig 6.2
Tighten nuts NOTE – For minimum sideroom installations, the door may have to be taken down.

9 GDO-10 Toro Installation Manual

6.3 Mounting The Opener a. If the internal gear does not rotate freely, switch the opener to
manual by pulling the disengagement handle down (there will be a click), so the ring gear can be rotated by hand. b. Slide the opener over the door axle and into the drum of the door (Fig. 6.3). c. Ensure the internal gear is pushed in as far as possible (without interfering with the door curtain) and that all of the door drum’s wheel spokes are completely between the opener’s drive forks. d. Re-attach the door bracket using your reference marks as a guide and tighten the bolts. Ensure that the slots in the mounting bracket of the opener align with the slots in the door bracket, otherwise the door bracket may have to be relocated. If the bracket cannot be relocated, the opener may be fitted onto the axle using the opener’s saddle and bolts as follows:
i. Using your reference marks as a guide, sit the opener on the door mounting bracket and secure with the opener’s bolts and saddle and tighten firmly (Fig. 6.4).

Fig 6.4

Tighten Nuts

Fig 6.3
WARNING! · The opener must not be used with a
door incorporating a wicket door. · The doors axle must be securely clamped
otherwise the door can loose spring tension. · The door and its springs are under significant tension. Adjustments should only be carried out by experienced persons, as this function can be dangerous if not performed under strict safety procedures.

ii. Adjust the door position (if necessary) on the brackets so that the door feeds smoothly into the guides. Make sure that the centre of the door doesn’t hit the lintel and that the curtain is not pushed forward hard into the guide.
e. Remove the support and safety ropes.
NOTE – If the manual release handle is more than 1.8 metres from floor level when the opener is installed, extend the handle to a height less than 1.8 metres.
6.4 Installing The Wall Mounted Control Unit a. Remove the face cover from the wall mount control unit 3 . b. Affix the wall mount control unit 3 at a height of 1.5 metres within sight of the door but away from moving parts. Make
sure this location of the wall control unit is out of reach of children and convenient to the customer. c. Replace the face cover. d. Connect the network cable 2 from the wall control unit to the GDO-10V3L2 powerhead unit 1 and secure with p clips
7. e. Connect the power cord to a suitable power point, but DO NOT SWITCH ON. Secure the power cord away from any
moving object (e.g. the door) with the cable clips. f. With the opener still disengaged, pull the door up and down to make sure it runs freely.

10 GDO-10 Toro Installation Manual

7. Programming The Opener

The three most common programs are;

Program

Menu’s required

Dead Man Set Up

Menu 10.1

Automated Set Up

Menu 1 Menu 10.1

Automated Set Up with Safety Beams

Menu 1 Menu 6.1 Menu 10.1
Menu 1 Menu 3

Function
Setting the Limits Safety Obstruction Force Coding the Transmitter Setting the Limits Safety Obstruction Force Coding the Transmitter Safety Close Mode Setting the Limits Safety Obstruction Force Coding the Transmitter Auto Close Times

Section
11.1 12.1 and 12.2 13.1 11.1 12.1 and 12.2 13.1 16.1 11.1 12.1 and 12.2 13.1 16.3, 16.4 and 16.5

For the Dead Man Set Up and the Automated Set Up the door can not be closed by Auto-Close or by transmitters. When Safety Beams are not installed, the controller will display the following message;

ATTENTION! No Safety Beams have been detected. “Safety Close’ mode has been turned on. See Manual for details. Press SET to continue.

If the closing force as measured on the bottom of the door is over 400N (40kg), a Safety Beam must be installed. The Safety Close mode can be turned off by changing the parameter in menu 6.1 (Section 16.1).
NOTE: Fitting Safety Beams enables the Auto-Close feature to become active.

11 GDO-10 Toro Installation Manual
8. Setting Limits

8.1 Setting Travel Limits
WARNING! Use caution when operating the manual release with the door open since it may fall rapidly due to weak or broken springs, or an improperly balanced door.
WARNING! Do not disengage the opener to manual operation with children, persons or any objects including motor vehicles within the doorway.
WARNING! In setting the close limit position, do not force the door into the floor with excessive force, as this can interfere with the ease of operation of the manual release mechanism.
a. Secure the engage/disengage handle and string with the accessory supplied in such a manner so that the string is away from the moving parts.
b. Move the door to half way open. If necessary, disengage the opener by pulling the cord down (Fig.8.1). Re-engage the opener by pulling the cord down again.
c. Unscrew the screws at the bottom of the logic console cover (Fig.8.2) and remove the cover to access the PREV, NEXT and SET buttons.
d. Turn on the power to the opener. The controller will go through a start up sequence. After a short delay the MAIN SCREEN (Fig. 8.3) will be displayed. If this is the first time the GDO-10V3L2 is being used, the MAIN SCREEN should enter into limit set mode and the blue close LED will be flashing. If the display shows that an input is active, then rectify the situation before continuing with the procedure for setting the travel limits. Press and hold the CLOSE button – the door should start closing. i. If the door opens, release the CLOSE button and press the STOP button once to change the motor’s direction. Press and hold the CLOSE button until close position of the door is reached. ii. If the door overshoots press the OPEN button to move the door in the open direction.
e. When the door is at the desired close position, press the SET button to record the close limit position. The display will change and green open LED will start to flash (Fig. 8.4).
f. Press and hold the OPEN button to open the door. When the door is at the desired open position, release the OPEN button. If the door overshoots, press the CLOSE button to move the door in the CLOSE direction.
WARNING! Once the next step is performed, the door will automatically close and open to calculate force settings. Keep persons and objects clear of the door.
g. Press the SET button to store the open limit. The door will now automatically close and open to calculate the safety obstruction settings. After this, if Safety Beam is installed, the opener can be operated with the OPEN or CLOSE button on the wall control unit or from the transmitter. Otherwise, the controller will be loaded with “Safety Close Mode.” See Section 13.1 for further details.
h. Place cover back on logic console and affix with screws when unit setup is complete.

Fig 8.1
Pull Down To Engage/Disengage
WARNING! Please test the manual release mechanism to ensure that the manual release is easy to operate. No more than 15 kg of force should be required to disengage the door using the manual release cord. If excessive force is required reset the close limit position.
Fig 8.2

To Desired CLOSE Limit, SET

Fig 8.3

To Desired OPEN Limit, SET

Fig 8.4

12 GDO-10 Toro Installation Manual
8. Setting Limits: Via Transmitter

Button 1 (Inch Open)

Fig 8.5

Button 4 (Inch Close)

Button 2 (Set)

IMPORTANT NOTE: Only TrioCodeTM128 Technology Transmitters are compatible with this product.

Fig 8.6

MENU 1 Code Transmitter
PR E S S

HELPFUL TIP: To access the PREV, NEXT tip and SET buttons, unscrew the screws at
the bottom of the logic console cover and remove cover.

The GDO-10V3L2 ToroTM has the alternate ability to set travel limits using a transmitter, allowing free movement around the garage to better assess the desired limit positions. In order to use a transmitter, it must first have at least one of its buttons coded to the door controller. The function assigned to the transmitter’s buttons is of no concern here as the buttons are temporally assigned to OPEN, CLOSE and SET (Fig. 8.5).
8.2 Code A Transmitter For Limit Setting Navigating to “code transmitter” menu a. Press NEXT to navigate to Menu 1. b. Press SET to enter the code set procedure (Fig. 8.6).
Storing Transmitter Code a. Controller will prompt to press one of the transmitter’s Button. b. Press the transmitter button you wish to use to operate the door
opener (e.g. button 1) . c. Press the same transmitter button again as prompted by display. d. Press the set button to store the transmitter.
Navigating To “Set Door Travel Menu” a. Press PREV to navigate to Menu 10. b. Press SET to display MENU 10.1. c. Press SET two times to enter the limit setting procedure. The
close blue LED will start to flash.
8.3 Setting Limits Via Transmitter a. Press and hold Button 4 on the transmitter to close the door
i. If the door opens, release Button 4 and press the stop button once on the wall control unit to change the direction of the motor.
WARNING! In setting the close limit position, do not force the door into the floor with excessive force, as this can interfere with the ease of operation of the manual release mechanism.
b. Then press and hold Button 4 on the transmitter to close the door. i. If the door is closed too far, press Button 1 to “inch” the door towards open. ii. When happy with the close limit position, press Button 2 to store this in the memory. The open green LED will starts to flash.
c. Press Button 1 to open the door. i. If the door is opened too far, press Button 4 to “inch” the door towards close

WARNING: The door will automatically close and open once next step is performed. Ensure that no persons or objects are in the door’s path.

When happy with the open limit position, press Button 2 on the transmitter to store into memory. The door will now automatically close and open to calculate the safety obstruction settings. After this, if Safety Beam is installed, then the opener can be operated with the OPEN or CLOSE button on the wall control unit or from the transmitter. Otherwise, the controller will be loaded with “Safety Close Mode”. See Section 13.1 for further details.

13 GDO-10 Toro Installation Manual
9. Coding Transmitter

The GDO-10V3L2 can store up to five hundred and eleven (511) transmitters in its memory. Each transmitter can be allocated an alpha-numeric ID label up to eleven (11) characters in length and each button can be assigned to one of several control functions. The settings for a transmitter are represented in (Fig. 9.1). It shows the transmitter’s store number, ID label or serial number and the functions assigned to each of its four buttons. To toggle between ID/SN display, press UP/DOWN with the cursor on the ID/SN indicator. The procedures below code, delete, replace, edit and copy transmitter records.

IMPORTANT NOTE: Only TrioCodeTM128 Transmitters are compatible with this product.
9.1 Coding Transmitter Button

Technology

Navigating To Menu 1 “Code Transmitter” a. Press NEXT to navigate to Menu 1). b. Press SET to enter the code set procedure.

Storing Transmitter Code a. The logic console will prompt to press one of the transmitter’s
buttons. b. Press the transmitter button you wish to use to operate the
opener (e.g. button 1) (Fig. 9.2) . c. Press the same transmitter button again as prompted by the
display.

9.2 Selecting Function Of The Button The logic console will now show the transmitter’s record, with a cursor on the field for the button being coded (Fig. 9.3). Use OPEN/CLOSE to select the function for the button.

Available functions:
OSC (Open/Stop/Close) SWP (Swipe) OPN (Open) LGT (Courtesy Light) AUX (Auxiliary )

PED (Pedestrian access) CLS (Close) STP (Stop) VAC (Vacation Mode) OFF (No action)

NOTE: OSC can change to OS and CLS (Close) function, but is not available in the case where PE Beams are not installed. Press SET to save the settings or STOP to abort without saving.

9.3 Returning To Main Screen Press STOP to return to the MAIN SCREEN and test the transmitter. NOTE: To edit the other settings, refer to transmitter edit procedure in Appendix F.

Store number

ID/SN display indicator

I.D label/Serial number

123 ID Name/SN
OSCPEDLGTVAC

Fig 9.1

Button 1 function

Button 4 Button 2 Button 3 function function function

HELPFUL TIP: To access the PREV, NEXT tip and SET buttons, unscrew the screws at
the bottom of the logic console cover and remove cover.

Press Tx’er Button! List

PR E S S

Fig 9.2

1 [No Name] OSC OFF OFF OFF

PRESS
PRESS

Fig 9.3

14 GDO-10 Toro Installation Manual
10. Remotely Coding Transmitters

If a transmitter is already coded into the opener, additional transmitters

can be coded without being in direct contact with the opener’s wall

console unit.

PRESS

NOTE: Only the function of the existing transmitter button can be assigned to new transmitter. Please read instructions prior to proceeding – there is a time-out facility for security reasons.

10.1 Selecting The Function To Be Coded a. Using the existing transmitter, operate the Door with the transmitter
button which has the function to be coded (Fig. 10.1) (e.g. Button 1 has been coded with the OSC function assigned). b. If the button’s function activates the Door (PED, SWP, OSC, CLS, STP or OPN) wait for the Door to complete its cycle.

Fig 10.1

Existing transmitter

10.2 Activate Remote Code Set Mode a. Use a small pin / pen to press and hold through the Coding Hole of the
existing transmitter for 2 seconds (Fig. 10.2). b. Within 10 seconds, press the button on the new transmitter you wish
to code for 2 seconds (Fig. 10.3). c. Press the same button again (within 10 seconds) for confirmation. d. Test Operation. The new transmitter button should now function as
the existing transmitter.
NOTE: To Manage your Transmitters, refer to Transmitter Management in Appendix G.

PRESS
New transmitter
Fig 10.3

11. Setting Pedestrian Position

Existing transmitter
Fig 10.2

After completing the limit setup procedure the Pedestrian Access position is automatically set to a position which is

approximately in the middle of the door travel. The position can be manually set by following the Setting Pedestrian

Position procedure.

HELPFUL TIP: To access the PREV, NEXT

11.1 Setting Pedestrian Position

tip and SET buttons, unscrew the screws at

a. Drive and stop the door at the desired Pedestrian Access

the bottom of the logic console cover and

position by using a transmitter or wall control unit.

remove cover.

b. Press PREV to navigate to Menu 10.

c. Press SET. MENU 10.1 will be displayed.

MENU 10.3

d. Press NEXT to go to MENU 10.3

Set Pedestrian

e. Press SET on the wall control unit to save the Pedestrian

Access position (Fig. 11.1). f. Press the STOP button to exit to the main screen.

Fig 11.1

11.2 Checking Pedestrian Position When activated by a transmitter button which is coded as Ped mode, the opener drives the door to the preset position from either above or below. Ped Mode’s active status is indicated on the display (Fig. 11.2). If a Ped Mode button is pressed while the door is moving, the door will stop. If a Ped Mode button is pressed when the door is in the Ped position, then the door will close.

PR E S S

Ped’n Access FRI 11:06:44 STD

Fig 11.2

11.3 Error Displays During the above procedure many error checks are performed. If an error is detected, a message will be displayed indicating the error.

15 GDO-10 Toro Installation Manual

12. Safety Obstruction Force Test

WARNING! Take care when testing or adjusting the Safety Obstruction Force. Excessive force may cause SERIOUS PERSONAL INJURY and/or PROPERTY DAMAGE.
12.1 Testing Close Cycle a. Press the OPEN button to open the door. b. Place a piece of timber approximately 40mm high on the floor
directly under the door (Fig. 12.1). c. Press the CLOSE button to close the door. The door should strike
the object and start to re-open.
12.2 Testing Open Cycle d. Press the CLOSE button to close the door. e. Press the OPEN button to open the door. When the door reaches
the half open point, grab the bottom rail of the door firmly and the door should stop. f. If the door does not reverse readily when closing, or stop when opening, the force may be excessive and need adjusting.
WARNING! If the door fails these tests, put the opener into manual mode, only operate the door by hand and call for service.

40mwmooBdlock of

1: CLOSE Margin

(Amps)

0.7

Fig 12.1

12.3 Adjusting the Safety Obstruction Force. The Safety Obstruction Force is calculated automatically during setup. Adjusting this is normally only necessitated by environmental conditions such as windy or dusty areas, and areas with extreme temperature changes.

Fig 12.2

Force Pressure For Close Cycle.

Navigating To “Current Trips”

a. Press NEXT or PREV to navigate to Menu 2 Current Trips.

b. Press SET.

tip

c. MENU 2.1: CLOSE Margin is displayed (Fig. 12.2).

d. Press OPEN to increase or CLOSE to decrease the value.

e. Press SET to save the new value.

f. Test the force again as per “Safety Obstruction Force Test” in Section 12.1.

Force Pressure For OPEN Cycle. Navigating To “Current Trips” a. Press NEXT to navigate to the Menu 2 Current Trips. b. Press SET. c. Press NEXT. d. MENU 2.2: OPEN Margin is displayed (Fig. 12.3). e. Press OPEN to increase or CLOSE to decrease the value. f. Press SET to save the new value. g. Test the force again as per “Safety Obstruction Force Test” in Section 12.2.

HELPFUL TIP: To access the PREV, NEXT and SET buttons, unscrew the screws at the bottom of the logic console cover and remove cover.

2: OPEN Margin

(Amps)

0.9

Fig 12.3

12.4 To Recalculate Force Margins a. Reprofiling is a simplified way of re- learning the travel characteristic of a previously setup Limit Switch travel installation.
Re-profiling can be used when the travel characteristics of the door change due to mechanical adjustments etc. To initiate a re-profile, simply locate “MENU 10.2 Reprofile Travel”, press SET and follow the prompts. The door will start to move and re-calculate force margins. The door can move between the open and close limit positions up to two (2) times (depending on the position of the door and the power up condition). b. A single beep will be heard once the process is complete. c. Test the force again as per “Safety Obstruction Force Test” (Section 12.1 and 12.2).

16 GDO-10 Toro Installation Manual
13. Safety Close & Auto-Close Mode

13.1 Safety Close Mode The controller has a built in Safety Beam detection. If Safety Beams are not installed, the controller will automatically turn on the Safety Close Mode. By enabling this parameter, the Door can only be closed by holding the close button on the wall control unit. In order to facilitate an Automated Set Up and enable to Door to be closed by a transmitter proceed by;
Navigate to “Safety Close Mode (Menu 6.1)” a. Press the OPEN button. b. Warning will display.
DANGER! Read Manual before turning off Safety Close Mode. Press SET to continue.

c. Press SET to accept the warning. d. Press either the OPEN or CLOSE arrows to change to OFF. e. Press SET to Save the change.
WARNING! The Auto-Close function is not available unless Safety Beam is installed.

13.2 Setting Up Satndard Auto-Close Mode Menu 3. Auto-Close Times The Auto- Close modes automatically close the Door after it has been operated. To implement this the controller starts a timer once the Door has reached its desired open position. The timer then counts down and when it expires the controller starts to close the Door. Details about the four Auto-Close modes follow. Automatic Technology strongly recommend using a Safety Beam for added safety.
Menu 3.1 Standard Auto Close This mode is selected by entering a non-zero time for the STD Auto-Close parameter. When selected, the Door will Auto-Close after being fully opened (except when the Door has reversed to the open position after a motor obstruction or overload. Countdown is suspended by: S.B., OPN or SWP input being active. The countdown is aborted if the STP input is activated. If the Door is already open and the OPN or the SWP input is activated, then the countdown will start.

13.3 Safety Beam Triggered Auto Close Menu 3.2 (SB AC Trig) This mode is selected by entering a non-zero time for the “Safety Beam Auto-Close” parameter. This mode is used to Auto-Close the Door but only after an object has passed through the doorway and has triggered the Safety Beam input. Any Safety Beam or combination of Safety Beams can be configured to activate Safety Beam Auto-Close mode and combinations are:

One Beam only i. Safety Beam 1 ii. Safety Beam 2 iii. Safety Beam 3

Either Beam i. Safety Beam 1 or Safety Beam 2 ii. Safety Beam 1 or Safety Beam 3 iii. Safety Beam 2 or Safety Beam 3 iv. Safety Beam 1 or Safety Beam 2
or Safety Beam 3

Combination i. Safety Beam 1 and Safety Beam 2 ii. Safety Beam 1 and Safety Beam 3 iii. Safety Beam 2 and Safety Beam 3 iv. Safety Beam 1, Safety Beam 2 and Safety Beam 3
NOTE: The swipe input can be used to clear the Safety Beam triggered status so that the Safety Beam input must be activated again before the countdown will start. As with the other Safety Beam modes, the STP input will abort countdown and the OPN and SWP inputs will restart the countdown if the Door is OPEN.
Menu 3.3 Directional Auto-Close (SB Auto Close) This mode is selected by entering a non-zero time for the “S.B. Auto-Close” parameter. S.B 3 Beam must be installed and configured to EXIT WITH SB1. Sub in menu 6.5. This mode is used to Auto-Close the Door only after a vehicle has passed through the Safety Beam 3 and then through Safety Beam 1 to exit the premises . This mode is useful for fire brigade, ambulance stations etc.
13.4 Pedestrian Auto-Close Menu 3.4 Pedestrian Auto-Close This mode is selected by entering a non-zero time for the “Ped’n A/C” parameter. When selected, the door will AutoClose after being opened for pedestrian access unless it was following a reverse from an obstruction.
Menu 3.5 (Safety Beam) Pedestrian Triggered Auto-Close Any Safety Beam or combination of Safety Beams can be configured to activate Safety Beam Auto- Close mode.
Menu 3.6 (Safety Beam) Pedestrian Auto-Close This mode is selected by entering a non-zero time for the “Ped’n A/C” parameter. When selected, the door will AutoClose after being opened for pedestrian access unless it was following a reverse from an obstruction.
13.5 Auto-Close After Obstruction: Three parameters are provided to enable the Auto-Close feature to be activated after obstructions and power up. Normally the Auto-Close feature is not enabled after obstructions for safety reasons. Safety Beams must be used for these features to be activated. The three parameters are:
Menu 3.7 (Auto-Close after close overload) This mode enables the Auto-Close feature to be activated when a close overload occurs (requires Safety Beams).
Menu 3.8 (Auto-Close after open overload) This mode enables the Auto-Close feature to be activated when an open overload occurs.
Menu 3.9 (Auto-Close after power up) This mode enables Auto-Close feature after power up.

17 GDO-10 Toro Installation Manual

14. Time Clock

HELPFUL TIP: To access the PREV, NEXT and SET buttons, tip unscrew the screws at the bottom of the logic console cover
and remove cover.
The opener provides a programmable time clock which can be used to control the GDO-10V3L2 on a timed basis at various times of the week. This section details the time clock operation and configuration.

MENU 7.1 Set Time/Date
PRESS

Fig 14.1

14.1 Time Clock Operation The time clock consists of a 7 day clock and storage for 32 programs. The clock is powered by its own battery and therefore does not lose time when the GDO-10V3L2 is turned off. Each time clock program defines the time of the day and the days of the week it is to run and the output function to be executed. Any combination of the days of the week can be selected.

00:00:80 STD — 00/00/2000

14.2 Time Clock Settings The Time Clock settings are accessed by selecting the Time Clock menu (MENU 7). Press SET (Fig. 14.1) to enter the menu and then PREV or NEXT to navigate through the options.

Fig 14.2

Menu 7.1 Set Time/date This is where the current time, date and day are displayed and set (Fig. 14.2).

NOTE: The time is in a 24 hour format and the Day of the week is not automatically set with the date. To change the settings simply press UP or DOWN to display the cursor and then move to the field to be changed using the NEXT / PREV buttons. Then press OPEN/CLOSE to change the setting and then the SET or STOP buttons to save.
Menu 7.2 View Programs Select this menu to display or edit the Time Clock programs (Fig. 14.3). When selected, program number 1 is displayed and the cursor is shown on the program number field. The other fields shown include the function, time and days of operation. The example

Fig. 14.4 shows that the DOOR will OPEN at 7 am on Mondays, Tuesdays, Wednesdays, Thursdays and Fridays. Use the OPEN /CLOSE buttons to scroll though the other programs (Fig 14.5). To edit a program, simply press the NEXT / PREV buttons to move the cursor onto the required field and press the OPEN/CLOSE button to change the value. To save the program settings, press SET or to exit without saving press STOP.

The selectable functions available are:

Function

Operation

RX = Off

From the time when the program with RX = OFF is activated, all the transmitters will be disabled.

RX = On

From the time when program with RX = ON is activated, all the transmitters will be enabled.

Open Door From the time when the program with OPEN DOOR is activated, the door will open and stay open.

Stop Door

This feature will let the user activate the stop function until the next program starts. The door will not open or close while stop is activated.

Free Door Release the controls from the timer.

Off

This will temporarily disable the program.

Fig 14.5

MENU 7.2 View Programs
Fig 14.3
PRESS

P#01 OPEN DOOR 07:00:00 MTWTF–

Fig 14.4

NOTE: The most recent program that applies to an output remains active until a new program takes effect.
NOTE: If a Time Clock program does not have a day selected then it can not be executed. If a Time Clock program is taking control of the opener, then this status is displayed on the LCD. The MAIN SCREEN and clock status screen flashes alternatively.

18 GDO-10 Toro Installation Manual
14. Time Clock
Menu 7.3 Settings Under this menu, three sub menus are available: a. Run Programs. The programs of the timer can be interrupted by selecting RUN PROGRAM off. b. Configuration Of GPI Input. General Purpose Input can be configured as OSC, PED or DST setup. c. This is activated by the GPI input terminal with the N/O switch.
i. When GPI Selected As OSC: If the door is moving, the activation of GPI input or pressing a transmitter button with the OSC function assigned will cause the door to stop. The next trigger will move the door in the opposite direction to the last travelled.
ii. When GPI Input Is Configured As PED: The activation of the GPI input or by pressing a transmitter button with PED function assigned will open the door partially to allow pedestrian access but prevent vehicle access. The position the door is driven to is automatically set to halfway during setting of the travel limits, but can be adjusted to suit.
iii. When GPI Input Is Configured As DST: GPI input can be used to switch between STD time and DST (daylight savings time). The AUX input needs to be constantly active to show day light saving time.
14.3 Day Light Saving Time Adjustment The time selected is the amount of time added to STD time when DST is selected by AUX input. Options are OFF, 30, 60, 90 or 120 minutes.
15. Accessories Installation

15.1 Fitting Courtesy Lights An AC or DC courtesy light can be activated via an output on the door opener control board. Connect the light as per the diagram. (Fig. 15.1)
WARNING: A qualified electrician must perform the installation where 240V AC power is used.
Menu 4. Light/Lock Times a. Press NEXT or PREV on the wall control unit to navigate to Menu 5
Light/Lock Times. b. Press SET to select the sub menu. c. Press NEXT or PREV to navigate through the sub menu. d. Press OPEN to increase or CLOSE to decrease the time. e. Press SET to save the new time. f. Press the STOP button two times to exit. g. Test the light operation.
15.2 Fitting Solenoid Or Magnetic Locks Install the lock mechanism on the door as per the manufacturers instructions. See Fig. 15.2 for the wiring diagram.
Menu 4. Light/Lock Times Lock output can be programmed for both hold and pulse mode. The operation of the lock can be programmed to activate prior to the door and behave differently on open cycles to that on close cycles.
a. Press NEXT or PREV on the wall control unit to navigate to Menu 4 Light / Lock Times.
b. Press SET to select the sub menu. c. Press NEXT or PREV to navigate through the sub menu. d. Press OPEN to increase or CLOSE to decrease the time. e. Press SET to save the new time. f. Press the STOP button two times to exit and test the locks operation.

HELPFUL TIP: To access the PREV, tip NEXT and SET buttons, unscrew the
screws at the bottom of the logic console cover and remove cover.

LIGHT
NO COM
NC NO COM NC
LOCK

SUITABLE Fig 15.1
POWER SUPPLY
LIGHT

LIGHT
NO COM
NC NO COM NC
LOCK

SUITABLE POWER SUPPLY

Fig 15.2

LOCK

19 GDO-10 Toro Installation Manual
16. Battery Replacement

16.1 Replacing Backup Batteries a. Unplug the drive unit from mains power. b. Disengage motor using manual release cord. c. Remove the bottom cover by pressing in from sides and sliding
downward. d. Remove the two screws and slide upward the top cover upwards
to remove it. e. Remove the battery bracket by undoing the battery bracket screws. f. Remove the batteries and replace with the same type (Fig. 16.1).

Fig 16.1

16.2 Replacing Transmitter Batteries (Battery Type: 3V Lithium Battery CR2032). Use a non-metallic object (e.g. pen) to remove the battery. (Fig. 16.2).
To test the battery is working, press and hold a transmitter button; (Fig. 16.3).

Light Status Solid Flashing No light
Fig. 16.3

Battery Status OK Requires replacement Requires replacement

WARNING! Chemical Burn Hazard. Keep batteries away from children

17. Battery Disposal

Use a pen to push the battery down through the side opening to release battery
REPLACE BATTERY WITH CR2032 ONLY

Fig. 16.2

When batteries reach the end of their usual life in accordance with Australian Battery Recycling Initiative please follow the next simple steps for protecting the environment.
WARNING! The Battery shall be disposed of properly, including keeping them away from children. Even used batteries may cause injury.
DO NOT throw the batteries in municipal waste. This symbol of the crossed out wheeled bin indicates that the battery should not be placed in the municipal waste. Check your local regulations for appropriate disposal of the batteries.
Recycling all batteries will have other environmental and social benefits: · Some batteries are less toxic but hazardous for other reasons. Lithium batteries can explode or catch fire in landfill, while
button cells are dangerous if swallowed by children. Recycling offers a safe and environmentally responsible solution for end of life batteries. · Battery recycling recovers non-renewable materials such as lead, cadmium, stella, zinc, manganese, cobalt, silver, plastics and rare earth elements.
· Removal of batteries and other hazardous household products from household waste facilitates the recovery of organic materials through alternative waste technologies such as composting. Batteries and heavy metals are known contaminants in compost.
· The community supports recycling because it reduces waste to landfill and achieves environmental benefits.
WARNING! Prior to disposal, recycling, or collection, all battery terminals must be securely insulated with a non conductive material to prevent any two batteries from short circuiting and generating heat during storage or transport. Battery terminals may be insulated with electrical tape; or batteries may be individually packaged in a non conductive material (e.g., plastic bag or original packaging).

20 GDO-10 Toro Installation Manual
18. Specifications

Technical Specifications

Power supply

Standby power

Geared Motor power

Motor type

Maximum door opening:

Height: Width: Weight:

Opener Limits Travel

Maximum Rated Load

Nominal Load

Duty Cycle

Receiver type

Receiver code storage capacity

Receiver Sensitivity

Transmitter frequency

Number of code combinations

Code generation

Controller fuse

Transmitter Battery

Real Time Clock Battery

Backup Battery

230V – 240Va.c. 50Hz 2.6 Watts 150 Watts 24Vd.c. Permanent Magnet 5100mm 5500mm 270kg 5.5 turns of Door Drum Wheel 500N 150N 25 Operations/hr UHF Multi-frequency FM Receiver 511 X 4 button Transmitter Codes ­ 103 dB UHF Multi-frequency FM Transmitter Over 100 billion random codes Non-linear encryption algorithm 10 A slow blow CR – 2032 (3 Volts) CR -1220 (1.5 Volts) 12 Volts 6 Amp Hr x 2

NOTE:
1. The door must be well balanced. A person should be able to lift the door up manually with very little effort in case of an emergency.
2. Intermittent operations may occur in areas which experience very strong winds. Strong wind puts extra pressure on the door and tracks which may in turn trigger the safety obstruction detection system intermittently.
3. If the Safety Beam are not installed then the controller will automatically goes into “Safety Close” mode. Limited number of features are available in this mode please refer to Section 13.1.

21 GDO-10 Toro Installation Manual
19. Troubleshooting

Symptom Door will not operate
Door starts to close but automatically reverses to open position
Door operates from wall control unit (OPEN/CLOSE) button but not from transmitter Door does not close with transmitter Door will not close fully. Door will not open fully. Auto-Close not working

Possible cause
Mains power not switched on. Door is obstructed. Door is locked or motor jammed. Door tracks/hardware damaged. The stop function is activated The opener is in “Vacation Mode”

Remedy
Switch on mains power. Remove obstruction. Unlock door or remove jam. Door requires service/repair by qualified technician. Deactivate the stop switch/timer Turn off “Vacation Mode”(Appendix C Menu 6.16).

Adverse weather conditions (wind or cold) causing door to stiffen and become tight in the tracks.
Possible obstruction in the doorway.

Increase force margin setting (Section 12.4) Remove obstruction.

Transmitter code not stored in memory.

Code transmitter in to openers memory. (Section 9.1)

Transmitter does not contain TrioCodeTM128 Technology

Check the transmitter. It should have grey buttons and the model number should display V2. Contact dealer for support if otherwise.

Flat battery in transmitter

Replace battery (Section 16))

Safety Close Mode is on. Safety Beam not working properly.

Turn the Safety Close Mode off (Section 13.1) Make sure Safety Beam are operational.

Door limit positions need to be reset. Door obstructed and reverses.

Reset limits positions.
Clear obstruction or adjust force margin (Section 12.3)

Door limit positions need to be reset. Door obstructed.

Reset limits positions.
Clear obstruction or adjust force margin (Section 12.3)

Safety Beam not installed.

Install Safety Beam.

Safety Beam or wiring faulty.

Repair Safety Beam or replace wiring.

Safety Beam not aligned correctly.

Re-align optics.

Safety Beam is obstructed.

Remove obstruction from path of Safety Beams.

Door obstructed when closing.

Remove obstruction.

Auto-Close time not set.

Set Auto-Close times (Section 13.3).

Auto-Close mode not set

Set Auto-Close mode. (Section 13.2)

22 GDO-10 Toro Installation Manual

20. After Installation Care

20.1 Service Checklist Preventative servicing of your garage door and opener, is just as important as servicing your car. Much like the engine of your car, your garage door is made up of numerous moving parts designed to lift and lower your door safely and efficiently.
Ongoing preventative servicing ensures that your door continues to function within factory specifications, greatly reduces the risk of failure and repair bills down the track and ensures you maintain your Warranty.
Run the Safety Testing procedures MONTHLY in tip Section 12 to ensure garage door is fit for use.

WARNING! Failure to maintain your your garage door voids the warranty on your garage door opener.
DO NOT DO IT YOURSELF:
DIY Door adjustments should only be
carried out by experienced persons, as this function can be dangerous if not performed under strict safety procedures.

TECHNICIAN CHECKLIST 1. Lubrication of the critical moving parts including chain drive, tracks, wheels or cable drum. 2. Tightening of door mounting points along with door bolts, screws, cables and connectors. 3. Adjustment of spring tension to limit `spring fatigue’. 4. Adjustment of opener travel limits and force margin to ensure the door opens and closes to specification. 5. Assessment and adjustment of safety components and accessories including safety beams, Auto-Lock and Safe Lock (if
installed) 6. Assessment of the door alignment and the diagnosis of irregular operation remedies. 7. Record Cycle count at each service to establish next date of service (as per table)

DATE: BUSINESS NAME: TECHNICIAN NAME: PG3 COUNTERS STALLS OBSTRUCTIONS SENSOR FAULTS OVERLOADS / CUT-OUTS WARRANTY CYCLES FIRMWARE UPDATE AVAILABLE? IF `YES’ PLEASE UPDATE FIRMWARE CURRENT FORCE MARGIN

SERVICE 1 (12 months after installation
or 3,000 cycles)

OPEN

CLOSE

YES

NO

SERVICE 2 (3 years after installation)

OPEN

CLOSE

YES

NO

SERVICE 3 (5 years after installation)

OPEN

CLOSE

YES

NO

TECHNICAL SIGNATURE:
DATE: BUSINESS NAME: TECHNICIAN NAME: PG3 COUNTERS STALLS OBSTRUCTIONS SENSOR FAULTS OVERLOADS / CUT-OUTS WARRANTY CYCLES FIRMWARE UPDATE AVAILABLE? IF `YES’ PLEASE UPDATE FIRMWARE CURRENT FORCE MARGIN

SERVICE 4 (7 years after installation)

OPEN

CLOSE

YES

NO

SERVICE 5 (9 years after installation)

OPEN

CLOSE

YES

NO

TECHNICAL SIGNATURE:
20.2 Warranty
Warranty conditional on proper servicing as listed in 20.1 Service Checklist. Full details of the warranty are available in your Owners Opener Handbook, from your nearest ATA office or visit theATA Website ata-aust.com.au.

23 GDO-10 Toro Installation Manual

21. Appendix
A – Console Menu Structure

OPERATIONAL BUTTONS: 1. Press PREV/NEXT buttons move to Left/Right. 2. Press OPEN/CLOSE buttons to change setting. 3. Press SET button to save changes. 4. Press STOP to return to MENU without saving
NOchTaEng: eTs.he System will automatically return to the main screen after 30 secs if a menu screen is displayed and no buttons are pressed.

Parameter

Min

Max Default Step Unit Menu No. Section

Menu 1 – Code Transmitter

STORING TRANSMITTERS

0.0

511

1

13.1

Menu 2 – Current Trips

CLOSE MARGIN

0.0

2.0

0.7

0.1 AMPS 2.1

12.3

OPEN MARGIN

0.0

2.0

0.9

0.1 AMPS 2.2

12.4

REVERSE TIME AFTER CLOSE OBSTRUCTION

5.0

60

FULL

1.0 SEC

2.3

12.5

Menu 3 – Auto Close

STD AUTO-CLOSE TIME Sets and enables the standard Auto-Close time

0.0

300.0 0.0

1.0 Sec

3.1

16.2

S.B AUTO-CLOSE TRIG Selects the Safety Beam or combination of Safety Beams to enable the S.B triggered Auto-Close mode.

None

None

3.2

16.3

S.B AUTO-CLOSE TIME Sets and enables the S.B triggered Auto-Close time

0.0

60.0 0.0

1.0 Sec

3.3

16.3

PEDESTRIAN AUTO-CLOSE TIME Sets and enables the

0.0

60.0 0.0

1.0 Sec

3.4

16.4

Pedestrian Auto-Close time

S.B PEDESTRIAN AUTO-CLOSE TRIG Selects the Safety Beam or combination of Safety Beams to enable the S.B triggered Pedestrian Auto-Close mode.

None

None

3.5

16.4

S.B PEDESTRIAN AUTO-CLOSE TIME Sets and enables

0.0

60.0 0.0

1.0 Sec

3.6

16.4

the PE Pedestrian Auto-Close time

AUTO-CLOSE AFTER CLOSE OBSTRUCTION

Off

On

Off

Enables Auto-Close feature after close obstructions

(requires Safety Beams)

3.7

16.5

AUTO-CLOSE AFTER OPEN OBSTRUCTION

Off

On

Off

Enables Auto-Close feature after open obstructions

3.8

16.5

AUTO-CLOSE AFTER POWER UP Enables Auto-Close feature power up

Off

On

Off

3.9

16.5

Menu 4 – Light / Lock Times

ON AFTER CYCLE LIGHT TIME Time light remains on for after a cycle

0

255

60

1

Sec

4.1

18.1

ON BEFORE OPEN CYCLE LIGHT TIME

0

25.5 0

0.1 Sec

4.2

18.1

Minimum time light is activated for prior to opening

ON BEFORE CLOSE CYCLE LIGHT TIME

0

25.5 0

0.1 Sec

4.3

18.1

Minimum time light is activated for prior to closing

OPEN LOCK TIME Set the time the lock is activated for

0.0

Hold 0.0

0.1 Sec

4.4

18.2

on open cycles

CLOSE LOCK TIME Set the time the lock is activated for 0.0

Hold 0.0

0.1 Sec

4.5

18.2

on close cycles

PRE-OPEN LOCK TIME Time the lock is activated for prior to opening

0.0

25.5 0.0

0.1 Sec

4.6

18.2

PRE-CLOSE LOCK TIME Time the lock is activated for prior to closing

0.0

25.5 0.0

0.1 Sec

4.7

18.2

Menu 5 – Motor Settings

OPEN SPEED VOLTAGE Sets the full speed motor voltage

~12.0

~24

~22

~1 Volts 5.1

Appendix C

CLOSE SPEED VOLTAGE Sets the full speed motor voltage

~12.0

~24

~20

~1 Volts 5.2

Appendix C

24 GDO-10 Toro Installation Manual

Parameter
Menu 6 – Operating Modes
Safety Close Mode
Safety Open Mode
Safety Beam Input Response Mode Sets the S.B response mode. Options are OPEN and CLOSE cycles stop, Close cycles stop or Close cycle reverse
SB REVERSE TIME
GPI INPUT MODE configure the GPI input. Options are OSC, PED, SWP and DAY LIGHT SAVING
PED INPUT = SWIPE MODE Selects PED input functions as pedestrian access swipe input
OPN INPUT N/C OPERATION Selects operating polarity of OPN input
STP INPUT N/C OPERATION Selects operating polarity of STP input
FIRE INPUT N/C OPERATION Selects operating polarity of FIRE input
FIRE INPUT MODE configure the fire input. Options are OPN, CLS and PED
REMOTE CODE ENABLED Selects remote transmitter coding function
ACTIVITY REPORTS Select report to be output
ACTIVITY REPORT ID Selects ID for controller, sent with activity report
VACATION MODE Selects Vacation Mode – disables remote control
BATTERY/SOLAR MODE Selects Battery Backup/Solar operation
PASSWORD Selects password protection for all changes
Transmitter Grouping
Fault Auto Reset Selects Fault Auto Reset
LED Low Power Mode Selects saving the power by turning LEDs Off
Console OSC Buttons Selects to lock out the console buttons
AUX OUT O/P can be activated by either LIGHT DRIVE ,CLOCK/TXER / SB, OPEN or CLOSE status
SBFEC MODE In the event of Safety Beam failure the door can be closed by pressing and holding a button on remote or on console
Menu 7 – Time Clock
SET TIME / DATE
VIEW / EDIT PROGRAMS
SETTINGS
Menu 8 – Diagnostics
TEST INPUTS – Controls input display status
TEST TRANSMITTERS (TX’ERS)
DISPLAY HISTORY
MEMORY USAGE
SERVICE COUNTER

Min

Max

Off

On

Off

On

OPN & CLS stop CLS to stop CLS to reverse

5

FULL

OSC, PED, DST

Off

On

Off

On

Off

On

Off

On

OPN, CLS, PED

Off

On

Off

255

0

65535

Off

On

Off

On

Off

On

Off

On

Off

On

Off

On

Off

On

Off

On

Off

On

Off

On

Off

On

Default Step Unit

On
Off
CLS to reverse

FULL

1

Sec

OSC

Off

N/O

N/O

N/O

OPN

On

Off

1

0

1

Off

On

Off

Off Off

Off

On

LIGHT DRIVE
On

Off Off Off
Inactive

60,000

Menu No. Section

6.1 6.2 6.3-5

16.1 Appendix C Appendix C

6.6

Appendix C

6.7

Appendix C

6.8

Appendix C

6.9

Appendix C

6.10

Appendix C

6.11

Appendix C

6.12

Appendix C

6.13

Appendix C

6.14

Appendix C

6.15

Appendix C

6.16

Appendix C

6.17

Appendix C

6.18

Appendix C

6.19

Appendix C

6.20

Appendix C

6.21

Appendix C

6.22

Appendix C

6.23

Appendix C

6.24

Appendix C

7.1

17.1

7.2

17.2

7.3

17.3

8.1

Appendix D

8.2

Appendix D

8.3

Appendix D

8.4

Appendix D

8.5

Appendix D

25 GDO-10 Toro Installation Manual
Appendix
A – Console Menu Structure

Parameter EVENT COUNTER INSTALL DATA PARAMETERS VERSION INFO – Firmware Menu 9 – Memory Tools CLR CONTROL CLR TRANSMITTERS (TX’ERS) Menu 10 – Setup Travel SETUP LIMITS REPROFILE TRAVEL SET PEDESTRIAN

Min

Max Default Step Unit Menu No. Section

8.6

Appendix D

8.7

Appendix D

8.8

Appendix D

8.9

Appendix D

9.1

Appendix E

9.2

Appendix E

10.1

11.1

10.2

12.5

10.3

15.1

Appendix
B – Viewing & Editing Logic Console Parameters

This section illustrates how to locate, view and adjust parameters in the logic console unit.
Locating parameters Refer to MENU STRUCTURE on Page 15 or the preceding section for CONTROL BOARD ADJUSTMENTS. Locate the required parameter and note the MENU number. The example used in (Fig. B.1) displays Menu 2.2 “100% O/L Time”
Changing Settings a. Press NEXT/PREV to navigate to the required menu. b. Press SET to show the sub-menu. c. Press NEXT/PREV to go to the required sub- menu. d. Press OPEN/CLOSE to change the parameter setting. e. Holding the button down causes the parameter’s value
to change rapidly. f. The longer the button is held, the faster the value
changes. g. Press SET to SAVE the setting.
Reload Default Setting a. Press NEXT/PREV buttons to display the LOAD
DEFAULT screen. b. Press SET to load the default value.

View Mode (No cursor)

Parameter number

Parameter

in sub menu

name

2: 100% O/L Time Parameter

(sec)

10

value

Displays previous parameter in list

Displays next parameter in list

Fig B.1

Returns back to menu

Enter Edit Mode

Edit Mode (Cursor shown)

Increase value

2: 100% O/L Time

(sec)

1

Fig B.2

Return To Menu If the parameter’s value is not to be changed, press STOP to return to the sub menu. Press STOP again to return to the MAIN SCREEN.

Displays “Load

Default?” screen,

giving option of

loading default

value

Decrease value

Saves new value
Exits back to View Mode

26 GDO-10 Toro Installation Manual
Appendix
C – Control Board Adjustments
The standard operation of the opener can be altered by editing various parameters. This section describes the parameters and the effect they have. Use the VIEWING AND EDITING PARAMETER PROCEDURE (Appendix B) to make changes.
Menu 2.3 Door Reverse Time After Close Obstruction
Normally after a close obstruction, the door will fully open to its open position. After a close obstruction, the open cycle can be reduced from 5 seconds to its full open position.
Menu 5. Motor Settings Motor speed – The maximum speed the motors run at is controlled by the OPEN AND CLOSE SPEED VOLTAGE parameter. The default value is the maximum recommended for normal operation. If however the door moves too quickly for a particular installation, the voltage can be reduced to make the motors run slower.
NOTE: Altering these parameters will cause the travel limits to be cleared.
Menu 6.2 Safety Open Mode
By enabling this parameter, the user can open the door only by holding the open button on the wall control unit or by holding the open input active. The door can not be opened by the transmitters.
Menu 6.3 First (SB1) Safety Beam Response Mode The Safety Beams input can be configured to respond in one of eight modes.
i. Reverses Close Cycles In this mode, the Safety Beam input has no effect when opening but will cause the door to reverse if activated when closing.
ii. Close Cycles Stop In this mode, the Safety Beam input has no effect when opening but will stop the door when closing.
iii. Open and Close Cycles Stop In this mode, all cycles are prevented from being completed or initiated when the Safety Beam input is active.
iv. Open input In this mode, open cycle is initiated when the Safety Beam is activated. v. Swipe input In this mode, open cycle is initiated when the Safety Beam is activated. vi. Close input In this mode, close cycle is initiated when the Safety Beam is activated. vii. Ped input In this mode, ped cycle is initiated when the Safety Beam is activated. viii. Aux O/P trigger In this mode, aux output is triggered when the Safety Beam is activated. ix. Disabled In this mode, Safety Beam is disabled.
Menu 6.4 Second Safety Beam (SB2) Response Mode Same as above menu 6.3
Menu 6.5 Third Safety Beam (SB3) Response Mode Same as above menu 6.3
Menu 6.6 Safety Beam Obstruction Reverse Time Mode Normally after a Safety Beam obstruction the door will fully open to its open position. After a Safety Beam Close obstruction, the doors open cycle can be reduced from 5 sec to its full open position.
Menu 6.7 GPI Input GPI input can be configured as OSC, PED or DST setup. The GPI input terminal is activated by the N/O switch.
i. When GPI Selected As OSC: If the door is moving, the activation of the GPI input or by a transmitter button with the OSC function assigned will cause the door to stop. The next trigger will move the door in the opposite direction to the last travelled.
ii. When GPI Input Is Configured As PED: The activation of the GPI input or by a transmitter button with PED function assigned will open the door partially to allow pedestrian access but prevent vehicle access. The position the door is driven to is automatically set to halfway during setting of the travel limits, but can be adjusted to suit.
iii. When GPI Input Is Configured As SWP: Activation of GPI input in this mode will open the door. iv. When GPI Input Is Configured As MANUAL OPERATION: Activation of GPI input in this mode will disable all the transmitters. v. When GPI Input Is Configured As DST: The GPI input can be used to switch between STD time and DST (daylight savings
time). The time selected is the amount of time added to STD time when DST is selected. The Options are OFF, 30, 60, 90 or 120 minutes. The GPI input needs to be constantly active to show day light saving time.
Menu 6.8 PED Input Function If GPI or Fire Input is selected as PED then these inputs can be configured to a SWIPE type input for pedestrian access. This provides full functionality with the Safety Beam Triggered Pedestrian Auto- Close function.
Menu 6.9 Open Input Polarity The OPN input is normally configured for N/O operation. This parameter allows its operation to be changed to N/C.
Menu 6.10 STP Input Polarity The STP input is normally configured for N/O operation. This parameter allows its operation to be changed to N/C.
Menu 6.11 FIRE Input Polarity The FIRE input is normally configured for N/O operation. This parameter allows its operation to be changed to N/C.

27 GDO-10 Toro Installation Manual
Appendix
C – Control Board Adjustments
Menu 6.12 FIRE Input Configuration Fire input can be configuration as OPN ,CLS (available only if Safety Beams are installed) or PED function. Activated by FIRE input terminal with N/O or N/C (if selected) switch.
i. When Fire Input Is Configured As CLS : Activating the fire input will cause the door to close only if Safety Beams are installed. Holding the input active will prevent door from opening.
ii. When Fire Input Is Configured As PED: The activation of fire input will open the door partially to allow pedestrian access but prevent vehicle access. The position the door is driven to is automatically set to halfway during setting of the travel limits, but can be adjusted to suit.
iii. When Fire Input Is Configured As OPN : Activating the fire input will cause the door to open. Holding the input will prevent the door from closing.
6.13 Remote Code The controller supports the Remote Code Set feature. This parameter can be used to disable the feature for security or transmitter management reasons.
6.14 Activity Reports This parameter enables activity report outputs. Contact Automatic Technology for more details.
6.15 Activity Report ID This parameter sets the ID of the controller that is sent with the activity report. Contact Automatic Technology for more details.
6.16 Vacation Mode Vacation Mode can be turned on or off using this parameter.
6.17 Standby Battery Enable/Disable The controller can be instructed to turn off the Battery Backup facilities so that the control board can be shut down without having to disconnect the Battery Backup system.
6.18 Password Protection The password feature enables all parameters and configuration settings to be protected unless a password is entered. When this feature is turned on, the user is requested to enter the desired password to be used. The password protection feature has a time-out that expires after 60 seconds of inactivity. Alternatively, the user may log out manually by pressing exit when the main screen is displayed.
6.19 Transmitter Grouping The transmitter store number display format can be changed to show a grouped format. When grouping is selected, instead of displaying the store location as a number between 1 and 511, it will display as ##$ where ## is the group number and $ is a character a,b,c,d,e,f,g or h which indicates the group member.
6.20 Fault, Auto Reset When selected, the controller will reset any fault automatically.
6.21 LED Low Power Mode When LED low power mode is selected, the controller will turn the LED power off to save the power.
6.22 Console OSC Buttons Console can be locked out by selecting console OSC buttons OFF.
6.23 AUX Output Operation AUX output can be selected to be driven by:
i. Light Drive: Although the GDO10V3L2 drive unit has a light relay output, a light relay module can be connected on the console between V+ and AUX OUT terminal which will turn the courtesy light on and off.
ii. Clock/Transmitter: By selecting this option, AUX output can be triggered by programming the clock timer or by the transmitter. iii. Open Status: Selecting this option will cause the AUX output to stay active as long as the door stays open. iv. Close Status: Selecting this option will cause the AUX output to stay active as long as the door stays closed.
6.24 Safety Beam Failure Emergency Close Mode (SBFEC) When a safety beam prevents movement due to any reason other than a `real’ obstruction, the user can secure their property by pressing and holding a button on the remote control or OSC on the console. The button must be held active for more than five seconds to activate this mode and hold the button for the entire duration of close cycle.

28 GDO-10 Toro Installation Manual
Appendix
D – Diagnostic Tools

MENU 9 Diagnostics
Fig D.1
PRESS

Fig D.2

I/P:SB[—] fir osc opn stp cls

Fig D.3

PRESS TX’ER <-/-> Shows ID/SN

The controller provides several diagnostic tools from within the Diagnostics Menu (Menu 8). This section details the function of each tool and its use.
Navigating To Diagnostics Menu a. Press PREV to navigate to Menu 8 (Fig. D.1). b. Press SET to display the menu of available functions. c. Press PREV or NEXT to cycle through diagnostic tools. d. Press SET to select.
Menu 8.1 Test Inputs This tool is used to view the state of the control inputs. When selected, a screen is displayed (Fig. D.2) which indicates the state of each input. If the name of the input is in upper case or number in the bracket, then the input is active. Conversely if the input is in lower case and [—] dash in the bracket, then the input is inactive. For normal operation, all inputs should be inactive. When finished, press STOP.
Menu 8.2 Test Transmitters (Tx’ers) This tool is used to test receiver/transmitter functionality. When selected, a screen is displayed which prompts for a transmitter button to be pressed (Fig. D.3) and whether ID or serial numbers are to be displayed.
The opener will then beep each time a transmission is received. If the transmitter button is stored in the controller memory and has a function assigned to it, a second screen will be displayed that shows the transmitter details along with the button pressed (Fig. D.4). The example shows the case where transmitter number 14 is activated by button 4. Note ID is selected for display.
Menu 8.3 Display History The opener keeps a record of the last 64 events that have taken place. The events include the type of drive cycles executed, obstruction detection, various faults, power failures etc. When this tool is selected, the screen displays the last event that occurred (Fig. D.5). Press NEXT or PREV to view each event. The “EVENT#” field shows the sequence of the events, with (1) being the first and (64) being the last. The example shows that the last event was a close cycle which succeeded in closing the door. When finished viewing the events, press STOP to exit.
Menu 8.4 Memory Usage This tool displays the number of transmitter store locations used and the number free (Fig. D.6).

14 ID BB SMITH OSC PED LGT>VAC
PRESS
Fig D.4

Close Complete EVENT # 64

Used = Free =

1 510

Fig D.5

Fig D.6

29 GDO-10 Toro Installation Manual
Appendix

D – Diagnostic Tools

Menu 8.5 Service Counter The opener provides a periodic service counter which can be set to expire after a number of drive cycles. When expired, the opener will beep three times at the beginning of each drive cycle and a message will be displayed on the MAIN SCREEN (Fig. D.7). This tool displays the current value of the service counter and allows the user to set its value using the normal parameter editing techniques (See Appendix B). If the service counter is not to be used, it can be set to the maximum number (60,000).

Service Counter (Cycles) 60000

Fig D.7

Menu 8.6 Event Counters The opener keeps a count of number of times a particular event occurs. The list of event counters kept is shown below. When this tool is selected, the first event counter is shown (Fig. D.8). Press NEXT or PREV to step through the list. The example shows the OPEN CYCLE event counter with a value of 500. When finished viewing press STOP.

1: Open Cycles 3: PED Cycles 5: Warranty Cycles 7: Close O/LS 9: Close Stalls 11: Position Sensor faults 13: Position Wrap Faults 15: PCB Temp Fault 17: INV logic faults

2: Close Cycles 4: Setup Limits 6: Open O/LS 8: Open Stalls 10: Direction Faults 12: Drive Memory Faults 14: Console Volt Faults 16: Comms Compat Faults 18: Low DC Bus Volt Faults

1: Open Cycles (Cycles) 500

Fig D.8

Menu 8.7 Install Data i. Open Position: Shows the fully open position door counter. ii. PED Position: Shows the pedestrian position counter. iii. Open Time:Time taken for the opener to drive the door to open position. iv. Close Time: Time taken for the opener to drive the door to the close position.

Menu 8.8 Parameters Position of the limit counter, frequency, current used by the motor, overload graph, PCB temperature and DC bus voltage are displayed under this menu.All the parameters mentioned above can also be viewed while the opener is running. By default, the current used by the motor will be displayed on the LCD screen. This can be useful to check the condition of the Door. Scroll through other parameters by pressing NEXT or PREV buttons while the Door is running

Menu 8.9 Version Info Firmware information for the Axess® Pro 1505’s drive and console are shown here.
Appendix

E – Memory Tools

Menu 9.0 Memory Tools The Memory Tools accessed from within Menu 9 are used to clear the transmitters codes from the openers memory and clear the controller’s memory. Once selected, the PREV or NEXT buttons can be used to view the Memory Tool options. To execute the displayed option, simply press SET.
Menu 9.1 Clear Control This option will clear the door control memory and reload the factory set defaults for parameters such as the lock time, light time, Auto-Close times etc. It will also clear the travel limits.
Menu 9.2 Clear Transmitters (Tx’ers) This option will clear the transmitter storage memory.

30 GDO-10 Toro Installation Manual
Appendix
F- Transmitter Editing
Display Transmitter Record Using one of the methods below, you can display the required transmitters details.
Navigating To “Edit Transmitter” Menu a. Press NEXT to navigate to Menu 1 (Fig. F.1) . b. Press SET to enter the transmitter edit procedure. c. Press NEXT to enter transmitter list and edit mode.
Editing Button Function Field a. Press NEXT or PREV to move the cursor to the left or right and between
the top and bottom lines to select the desired field. b. Press OPEN or CLOSE to change the displayed value (Fig. F.2). The
available functions are shown below. Selecting OFF will prevent the opener responding to that button.
Available functions OSC (Open/Stop/Close) PED (Pedestrian access) SWP (Swipe) CLS (Close) OPN (Open) STP (Stop) LGT (Courtesy Light) VAC (Vacation Mode) AUX (Auxiliary ) OFF (No action)
NOTE: OSC will change to OS and CLS (Close) function is not available in the case where PE Beams are not installed.
c. Press SET to save changes or press NEXT or PREV to move to the next field. i. The example in (Fig. F.3) shows that PED is assigned to the transmitter button two. ii. The transmitter in the example is transmitter number 14 which has the ID label AB Smith.
NOTE: If all button functions are set to OFF, when SET is pressed, the opener will prompt to confirm if the transmitter is to be deleted. Press SET to delete or STOP to continue editing.

MENU 1 Code Transmitter

PR E S S

Fig F.1

14 ID A B SMITH OSC PED LGT VAC
PRESS

Fig F.2

PRESS

14 ID A B SMITH OSC PED LGT VAC

PRESS

Fig F.3

31 GDO-10 Toro Installation Manual
Appendix
F – Transmitter Editing
Editing The Store Location This feature is only available when coding the first button of a new transmitter. a. Press NEXT or PREV to move the cursor over Store No. (Fig. F.4) b. Press UP or DOWN to select new Store No. c. Press SET to confirm or NEXT/PREV to move to the next field.
This is useful when managing transmitters using a scheme which ties the store location to the transmitter’s owner.
Selection Of ID or Serial Number Display a. Press NEXT to navigate to Menu 1 “Code Transmitter” (Fig. F.5). b. Press SET to enter the transmitter edit procedure. c. Press NEXT to enter transmitter list and edit mode. d. Press NEXT/PREV to move the cursor over the ID field. e. Press NEXT to reveal the Serial Number (Fig. F.6).
The serial number display is provided for additional means of identification. The transmitter in this example has serial number 12345.
Editing A Character Field a. Press NEXT or PREV to move the cursor. (Fig. F.7) b. Press UP or DOWN to scroll through and select a new character. c. Press NEXT or PREV to move the cursor to the next character. d. Repeat step 2. e. Press SET to record changes.
The second line of the display shows a list of available characters with the current value indicated at the cursor position (Fig. F.8).

14 ID [No Name] OSC PED LGT VAC
PRESS

Fig F.4

MENU 1 Code Transmitter

PR E S S

Fig F.5

14 ID B B SMITH 56789 AB CDEFGHIJ
Fig F.6
PRESS

14 ID B B SMITH 56789 AB CDEFGHIJ
PRESS

Fig F.7

14 SN

12345

OSC PED LGT VAC

PRESS

Fig F.8

32 GDO-10 Toro Installation Manual

Appendix

G – Transmitter Management

MENU 1 Code Transmitter

Transmitter Listing Facility

The GDO-10V3L2 ToroTM provides a transmitter listing facility which enables

PRESS

the user to find a transmitter location within the memory. Once located a

stored transmitter can be replaced, deleted, edited, copied or, if the location

PRESS

is empty, a new transmitter can be coded.

Method 1 – Go To The Start Of The List Accessing The List Menu a. Press NEXT to navigate to Menu 1 (Fig. G.1). b. Press SET to enter the transmitter edit procedure. c. Press NEXT to enter the transmitter list and edit mode.
Method 2 – Use The Transmitter To Go Direct To The List Accessing The List Menu a. Press NEXT to navigate to Menu 1 (Fig. G.1). b. Press SET to enter the transmitter edit procedure. c. Press the transmitter once (Fig. G.2). d. Press NEXT to view the transmitter parameters (Fig. G.3). This method is
used for quick navigation if the transmitter is available. NOTE: “VIEW” will not be shown if the transmitter is not stored. Once the list is displayed, it can be sorted by stored number, ID Label or Serial Number. Use the NEXT or PREV buttons to select the sorting method.
NOTE: When sorting by ID label or S/N, only stored transmitters locations are displayed.
Navigating The List a. Press the OPEN or CLOSE buttons to navigate through the list (Fig. G.4). NOTE: Holding a button down will step through the list faster. b. Press SET to display the menu of available functions.
Selecting An Operation a. Press NEXT or PREV to cycle through the four menu options (Fig G.5) b. Press STOP to return to the list. Press SET to execute the menu’s operation.

Press Tx’er Button! List

PR E S S

Press Tx’er

Again

View

PRESS

Menu Option Code Operation (location used)
Delete Operation Edit Operation Copy Operation
Exiting The List

Operation
If the code operation is selected for a location that already contains a transmitter, then the storing transmitter code procedure (Section 10.1) will be initiated and the new transmitter will replace the existing one. Note the button functions and name of the existing transmitter will be transferred to the new transmitter. This procedure is of great convenience when replacing a lost transmitter.
The delete operation is used to remove a transmitter from memory along with the name and button function settings.
The edit operation displays the transmitter record for editing purposes. See TRANSMITTER EDIT PROCEDURE (Appendix B) for details.
The copy operation is used to code multiple transmitters with the same button function as that of the selected transmitter. Once selected an abbreviated code set routine is initiated which repeats steps 2 & 3 of the BASIC CODE TRANSMITTER PROCEDURE for each transmitter to be coded. Coding is terminated by pressing the STOP button.
To exit the transmitter list, simply press STOP to return to the Code menu.

12 ID B B SMITH OSC PED LGT VAC
PRESS PRESS
Fig G.5

Fig G.1 Fig G.2 Fig G.3 Fig G.4

33 GDO-10 Toro Installation Manual

Automatic Technology office location

Head Office

6-8 Fiveways Blvd, Keysborough 3073

Phone (03) 9791 0200

Prefixed trademarks are the property of Automatic Technology (Australia) Pty Ltd ABN 11 007 125 368. © 2020 Automatic Technology Australia Pty Ltd.
ata-aust.com.au

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

automatic TECHNOLOGY User Manuals

Related Manuals