nVent RAYCHEM NGC-40-PTM Power and Termination Module Instruction Manual

June 10, 2024
nVent RAYCHEM

RAYCHEM
NGC-40-PTM Power and Termination Module

Instruction ManualnVent RAYCHEM NGC 40 PTM Power and Termination
Module

NGC-40-PTM
Power and Termination Module for use with nVent RAYCHEM NGC-40 system
Installation Instructions

DESCRIPTION

The invent RAYCHEM NGC-40-PTM accepts a primary and redundant power supply input, accepts CAN bus inputs, and provides for termination of the CAN bus. The  NGC-40-PTM then distributes both power and Can bus signals to other NGC-40 modules. Each NGC-40-PTM can provide power for a maximum of 10 NGC-40 modules.

TOOLS REQUIRED
• Small flat-blade screwdriver
ADDITIONAL MATERIALS

  • Custom built CAN cables with RJ-45 connections
  • CAN Termination Resistor

KIT CONTENTS

Item Qty Description
A 1 NGC-40-PTM module

APPROVALS AND CERTIFICATIONS

Hazardous Locations

Class I, Div. 2, Groups A,B,C,D T4
Class I, Zone 2, Apex nab IIC T4 IP20
Ex nab IIC T4 X
–40˚C ≤ Ta ≤ +65˚C

Conforms to:
FM Class Number 3600 (11/98)
FM Class Number 3611 (10/99)
ANSI/UL STD. 60079-15-2009
UL STD. 61010-1
Certified to:
CAN/CSA STD. C22.2 No. 213-M1987 (R2004)
CAN/CSA STD. C22.2 No. 61010-1:2004
EN 61010-1 (2001)
CAN/CSA STD. E60079-15:02 (R2006)

IEC Ex Markings:
IECEx ETL 17.0062x
EX ed IIC T4 Go
ATEX Markings:
ITS17ATEX402833X
II 3 G Ex ed IIC T4 Go

Special conditions of use for IEC Ex and ATEX :

  • The overall equipment is evaluated to type of protection “ed”.
  • For full connection details see these installation instructions.
  • The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/EN 60664-1.
  • The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP54 in accordance with IEC/EN 60079-0.
  • Transient protection shall be provided which is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.

WARNUNG:
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire.
For technical support, call invent at 800-545-6258.

GENERAL

Supply voltage 24 Vdc ± 10%
Internal power consumption 1 W per NGC-40-PTM
Output current 1.5 Amps @ 24 V
Ambient operating temperature –40ºC to 65ºC (–40ºF to 149ºF)
Ambient storage temperature –55ºC to 75ºC (–67ºF to 167ºF)
Environment PD2, CAT III
Max. altitude 2,000 m (6,562 ft)
Humidity 5 – 90% noncondensing
Mounting Din Rail – 35 mm

ELECTROMAGNETIC COMPATIBILITY

Emissions| EN 61000-6-3  Emission standard for residential, commercial and light industrial environments
---|---
Immunity| EN 61000-6-2 Immunity standard for industrial environments

CAN NETWORKING PORT

Type 2-wire isolated CAN-based peer-peer network. Isolated to 300 V.
Connection Two 8-pin RJ-45 connectors (both may be used for Input or Output

connections)
Topology| Daisy chain
Length| 10 m (33 ft) maximum
Quantity| Up to 10 CAN nodes per PTM module

CONNECTION TERMINALS

Wiring terminals Cage clamp, 0.5 to 2.5 mm2 (24 to 18 AWG).
  As the current to the modules require up to 2.05 A @ 24Vdc (20 modules–see

CAN Bus connection  diagrams) the minimum wire size to the module shall be 1.0 mm2 (AWG18)
CAN networking and module power| Two RJ-45 connectors, one each IN and OUT. Provides CAN bus signals and 24 Vdc power.

HOUSING

Size 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep

SYSTEM POWER SUPPLY REQUIREMENTS

Output voltage 24 Vdc ±10%
Approval NRTL approved device for use in nonhazardous or hazardous locations

as appropriate
Overcurrent protection| Must have an automatic disconnect upon a single fault condition

System Components

A. WIRING TERMINALS

TERMINALS FUNCTION
1 Primary 24 Vdc In (+)
2 Primary 24 Vdc In (–)
3 Primary 24 Vdc Out (+)
4 Primary 24 Vdc Out (–)
5 Redundant 24 Vdc In (+)
6 Redundant 24 Vdc In (–)
7 Redundant 24 Vdc Out (+)
8 Redundant 24 Vdc Out (–)

B. STATUS LEDS

STATUS:

24 Vdc Primary
Off No power
Green Power on
24 Vdc Redundant
Off No power
Green Power on

C. CAN / TERM
D. CAN / 24 VDC

Mounting the NGC-40-PTM

Each NGC-40-PTM mounts on a DIN 35 rail.
MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up and inwards to engage the clip.

REMOVAL: Push the module upwards to disengage the clip, then rotate the module toward you.

24 Vdc Connection (In)

Note: Power supply should have a means for disconnect from line voltage.nVent RAYCHEM NGC 40 PTM Power and Termination Module -
Vdc

Note: Assemble, lock and mount power supply per manufacturer’s instructions.

24 Vdc Connection (Out)

nVent RAYCHEM NGC 40 PTM Power and Termination Module - Vdc
Connection

Note: The primary and redundant 24 Vdc outputs each support only one additional NGC-40 PTM module

CAN Networking Port
The CAN termination device must be installed in the unused port of the last module.nVent RAYCHEM NGC 40 PTM Power and Termination Module - CAN
Networking

Provide Suitable Panel Enclosure and Determine Locations for NGC-40-PTM Assembly in Panel

  1. Provide suitable panel enclosure
    The NGC-40-PTM must be mounted in an enclosure to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements.
    Note: The NGC-40-PTM is designed for operation in ambient temperatures from –40°C to 65°C (–40°F to 149°F). If the ambient temperature is outside this range, a  space heater and/or cooling fan will be required in the panel.

  2. Determine locations for the NGC-40-PTM assembly in the electrical panel.
    The NGC-40-PTM should be located in the rear of the panel. The NGC-40PTM assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or  excessive vibration.

nVent RAYCHEM NGC 40 PTM Power and Termination Module - Assembly in
Panel

Alarm Relay

The NGC-40-PTM contains no user serviceable parts. Contact your invent representative for service and an RMA number if required.
WARNING–EXPLOSION HAZARD–SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2 HAZARDOUS AND  NONHAZARDOUS LOCATIONS WARNING–EXPLOSION HAZARD–DO NOT REPLACE NGC-40-PTM UNLESS POWER HAS BEEN SWITCHED OFF OR  THE AREA IS KNOWN TO BE NONHAZARDOUS WARNING–EXPLOSION HAZARD–DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS  BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS

NGC-40 CAN Bus Connections for Up to 10 Modules

nVent RAYCHEM NGC 40 PTM Power and Termination Module - 10
Modules

NGC-40 CAN Bus Connections for Up to 20 ModulesnVent RAYCHEM NGC 40 PTM
Power and Termination Module - 20 Modules

NGC-40 CAN Bus Connections for Up to 40 Modules

nVent RAYCHEM NGC 40 PTM Power and Termination Module - 40
Modules

North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com| Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com| Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
cn.thermal.info@nVent.com| Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nVent.com
---|---|---|---

©2022 invent. All invent marks and logos are owned or licensed by
invent Services GmbH or its affiliates.
All other trademarks are the property of their respective owners.
invent reserves the right to change specifications without notice.
RAYCHEM-IM-H58119-NGC40PTM-EN-2202
nVent.com/RAYCHEM