Schneider Electric A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP Concentrator Instructions

June 10, 2024
Schneider Electric

Schneider LogoPowerTag Link
A9XMWD20 PowerTag Link
A9XMWD100 PowerTag Link HD PowerTag Link User Guide
DOCA0157EN

A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP Concentrator

This instruction sheet must be kept for further use.
Visit our website at www.se.com to download the above guides and to contact Schneider Electric Customer Support.
PLEASE NOTE
b Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
b All pertinent state, regional, and local safety regulations must be observed when installing and using this product.
b The manufacturer assumes no responsibility in case of failure to follow the instructions given in this document.

Description

Schneider Electric A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP
Concentrator - Wireless concentrator t

Wireless concentrator to Modbus TCP/IP
A Power supply connector 110/230 Va Power supply (phase – neutral)
B Default IPV4 adresss
C Device status LED
D Ethernet speed LED
E Wireless communication status LED
F RJ45 Ethernet connection
G Reset button Press 10 sec for reset to factory settings

Symbols Printed on the Device

IconClass II equipment
Alternating current
Hazard live parts
Recycling: This product bears the selective sorting symbol for Waste electrical and electronic equipment (WEEE). This means thas this product must be handled pursuant to European directive 2012/19/EU in order to be recycled or dismantled to minimize its impact on the environment. User has the choice to give his product to a competent recycling organisation or to the retailer when he buys a new electrical or electronic equipment.

Communication Indicators

3.1 Device Status LED

| Initialization / Operation| Green light. The gateway operates normally
---|---|---
| Startup| Alternate green and red light every second. The gateway is starting
| Factory settings| Orange light: The gateway is in DHCP mode, but the DHCP server is not connected. So the IP adress of the gateway is the default IP adress
| Reset (level 1)| Green blink: Reset button acknowledgement (pressed between 5 to 10 seconds). IP settings are reconfigured to DHCP mode
| Reset (level 2)| Red blink (Fast, 2 blinks / per second): While pressing the Reset button for more than 10 seconds.The LED stops blinking after the Reset button is released. Do not switch off the gateway until the LED stops blinking in red for at least 30 seconds, as the reset level 2 is still in progress
| Duplicate IP address| Red blink (1 blink per second): The gateway has detected duplicate IP address. Check and change the IP address of the gateway
| Degraded| Orange blink: Power supply of the gateway is degraded
| Failure| Red light: The gateway is out of order

3.2 Ethernet LED

| Orange blink: Ethernet activity at 10 Mbps
---|---
| Green blink: Ethernet activity at 100 Mbps

3.3 Wireless Communication LED

| Initialization| Orange light: Not configured
---|---|---
| Startup| Orange blink: Looking for wireless devices
| Operating| Flash green every 5 sec: Networking complete (Normal operation)
| Degraded| Alternate green and red light every second: Downgraded while boot mode
| Disabled| Off: Wireless communication disabled

Installation

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
b Turn off all power supply sources before installing and during maintenance of this equipment.
b This equipment is intended only for installation in a restricted access location.
b Always use a voltage detection device with an appropriate rated value to make sure that the power supply is off.
Failure to follow these instructions will result in death or serious injury.

Schneider Electric A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP
Concentrator - Wireless concentrator t 1

Wiring

  DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
b Turn off all power supply sources before installing and during maintenance of this equipment.
b This equipment is intended only for installation in a restricted access location.
Failure to follow these instructions will result in death or serious injury.

Schneider Electric A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP
Concentrator - Wireless concentrator t 2

Ethernet Connection

Schneider Electric A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP
Concentrator - Wireless concentrator t3

PowerTag Link has an embedded web server.
It is used to set system parameters.

  1. Disconnect your PC from all networks.
  2. Connect an Ethernet straight cable between your PC and the Ethernet port on the PowerTag Link.
    b For Windows operating systems see section 7.1.
    b Any operating systems see section 7.2.

PowerTag Link Webpage

7.1 Windows Operating Systems

  1. Launch Windows Explorer and click Network to display the PowerTag Link gateway icon in the list of devices.
    If the PowerTag Link gateway icon does not appear, please refer to the section 7.2 of the instruction sheet.

  2. Double-click on the PowerTag Link gateway icon, the login page automatically opens in your browser.

  3. Type the user name (admin by default) and password (admin by default).
    These identifiers are case-sensitive.

  4. Then click OK.

7.2 Any Operating Systems

  1. Launch your Internet browser.
  2. In the ”Address” field, type: the IPv4 address written on the upper side of PowerTag Link and press Enter to access the login page.
  3. Type the user name (admin by default) and password (admin by default).
  4. Then click OK.

EcoStruxure Power Commission Software

The EcoStruxure Power Commission software is used to:

Operation

Access to the embedded webpages of the web server using Windows Explorer or by entering the IP address on your web browser to monitor real time values and alarms from wireless devices.

Technical Characteristics

For indoor use only

  • Power supply: 110/230 Va ±15 %
  • Frequency: 50/60 Hz
  • Maximum consumption: 5 VA
  • Operating temperature: -25 °C … +60 °C / -13 °F…140 °F
  • Relative humidity: 93 % at 40 °C / 104 °F
  • Elevation (for use): 0…2000 m / 0…6500 ft
  • Overvoltage category: III
  • Pollution degree: 2
  • Weight: 133 g / 0.29 lb
  • Size: 85x54x62 mm / 3.35×2.13×2.44 in.
  • EMC according to:
  • EN 55032:2015, Class B
  • EN 55035:2017
  • EN 61000-3-2:2014
  • EN 61000-3-3:2013
  • Degree of protection according to IEC 60529:
  • Front face IP40
  • Casing IP20
  • Ethernet network interface:
  • Ethernet T-base10/100 Mbit/s
  • Maximum cable length: 100 m / 328 ft
  • Cable type: Cat6 STP
  • DHCP, SNTP, SMTP, DPWS clients:
  • IPv6 local link
  • Email encryption SHA2
  • Radio communication:
  • ISM band 2.4 GHz (2.4 GHz to 2.4835 GHz)
  • Channels 11 to 26 (IEEE 802.15.4)
  • Equivalent isotropics Radiated Power (EIRP): 0 dBm

Radio Frequency Compliance Statements

EU Declaration of Conformity
Hereby, Schneider Electric Industries SAS, declares that this A9XMWD20/A9XMWD100: Wireless to Modbus TCP/IP Concentrator is in compliance with the essential requirements and other relevant provisions of RED-DIRECTIVE 2014/53/EU.
Declaration of conformity FD18082701 can be dowloaded on: www.se.com/docs.

  • IEEE 802.15.4 operating frequency: 2405–2480 MHz.
  • Maximum radio-frequency power transmitted: < 10 mW.

Schneider Electric Industries SAS
35, rue Joseph Monier CS 30323
F – 92506 Rued Malmaison Cedex www.se.com PHA81113-07
Schneider Electric Limited
** Stafford Park 5
Telford, TF3 3BL
United Kingdom
www.se.com/uk
© 2021 Schneider Electric – All rights reserved.
Schneider QR
PHA81113-07
www.se.com**

Documents / Resources

| Schneider Electric A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP Concentrator [pdf] Instructions
A9XMWD20, A9XMWD100, HD, A9XMWD20 PowerTag Link Wireless to Modbus TCP or IP Concentrator, PowerTag Link Wireless to Modbus TCP or IP Concentrator, A9XMWD100 PowerTag Link HD
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals