Industrie technik THS2 Series Room Controller Evolution Split Instruction Manual
- June 9, 2024
- industrie technik
Table of Contents
THS2 Series Room Controller Evolution Split
Product Information: Room Controller Evolution Split THS2
Series
The Room Controller Evolution Split THS2 Series is a highly
advanced and versatile HVAC controller designed for regulating
heating, cooling, and ventilation systems in various environments
such as hotels, offices, hospitals, and residential buildings. Some
of the key technical features of the THS2 series are:
- THS2 Display unit (optional)
- THS2-0MM Remote unit
- Internal and External Modbus network connectivity
- Regulation sensor for temperature control
- Automatic season changeover with water sensor
- Working setpoint, economy, and unoccupied holidays mode
- 3-point valve and mixed-use valve controls
- Supplemental modulating and on/off battery functions
- Pump and CO2-based damper control
- Dehumidifier and fan coil unit with EC motor support
Product Usage Instructions:
Before using the Room Controller Evolution Split THS2 Series, it
is important to read the instruction manual carefully and
understand the features and functionalities of the controller.
Follow these steps to use the THS2 series:
-
Mount the THS2 display unit at an appropriate location for easy
visibility and accessibility. -
Connect the THS2-0MM remote unit to the controller using an
internal or external Modbus network. -
If necessary, connect optional THS2 devices to the
controller. -
Configure the temperature regulation batteries and
heating/cooling battery logic based on the type of HVAC system
being used. Refer to the instruction manual for detailed
instructions. -
If using a 3-point valve or mixed-use valve, set the
appropriate regulation mode based on the HVAC system being
used. -
If using a supplemental battery function for modulating or
on/off control, configure the setup based on the requirements of
the HVAC system. -
If using a pump or CO2-based damper, follow the instruction
manual to configure the proper settings. -
If using a dehumidifier or fan coil unit with an EC motor,
configure the controller for automatic speed control logic based on
heating or cooling mode. -
Test the controller and make any necessary adjustments to
ensure optimal performance.
It is important to regularly check and maintain the THS2 series
to ensure proper functionality and efficiency of the HVAC system.
Refer to the instruction manual for maintenance instructions and
troubleshooting tips.
INSTRUCTION MANUAL
ROOM CONTROLLER EVOLUTION SPLIT THS2 SERIES
27/08/2021 Rev. 1.0.4
EN
INDEX
1. Technical features ………………………………………………………………………………………………..6
Display unit: THS2 (optional)
6
Remote unit: THS2-0MM
6
2. Internal Modbus network………………………………………………………………………………………7
3. External Modbus network……………………………………………………………………………………..8
4. Optional THS2 connection …………………………………………………………………………………. 10
5. THS2-0MM connected to THS2 and supervisor contemporaneously ……………………. 12
6. Regulation sensor ……………………………………………………………………………………………… 13
7. ON/OFF function on THS2-0MM………………………………………………………………………….. 16
8. Logic of digital and analogue inputs THS2-0MM …………………………………………………. 16
Digital slave inputs DI1 and DI2
16
Analogue slave inputs
17
9. Automatic season changeover with water sensor……………………………………………….. 20
10. Working setpoint, economy and unoccupied holidays mode ………………………………. 21
11. Temperature regulation batteries ……………………………………………………………………….. 24
12. Heating and cooling battery logic……………………………………………………………………….. 26
2-pipe HEATING regulation (I01=0)
26
2-pipe COOLING regulation (I01=0) without mid-season changeover (M13=0)
27
2-pipe COOLING regulation (I01=0) with mid-season changeover (M13=1)
28
4-pipe regulation (I01=1)
29
13. 3-point valve ……………………………………………………………………………………………………… 32
3-point, 2-pipe HEATING regulation (I01=0)
32
3-point, 2-pipe COOLING regulation (I01=0)
32
3-point, 4-pipe regulation (I01=1)
33
14. Mixed-use valve…………………………………………………………………………………………………. 34
15. Supplemental battery logics ………………………………………………………………………………. 35
Supplemental modulating battery function:
35
Supplemental on/off battery function:
35
16. Pump ………………………………………………………………………………………………………………… 36
17. CO2-based damper regulation ……………………………………………………………………………. 36
Use of modulating damper:
36
Use of on/off damper:
36
18. Dehumidifier ……………………………………………………………………………………………………… 38
Use of a modulating dehumidifier:
38
Use of an on/off dehumidifier:
38
19. Fan coil unit with EC motor………………………………………………………………………………… 40
Automatic speed control logic for EC motor with on/off outputs in heating mode
40
Automatic speed control logic for EC motor with on/off outputs in cooling mode
41
Automatic speed control logic for EC motor with 0..10 V or 3-point outputs in heating mode
42
Automatic speed control logic for EC motor with 0..10 V or 3-point outputs in cooling mode
43
2/128
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
20. Fan coil unit with 3-speed on/off motor ……………………………………………………………… 44
Automatic speed control logic for 3-speed on/off motors with 0..10 V or 3-point outputs in heating
mode
44
Automatic speed control logic for 3-speed on/off motors with 0..10 V or 3-point cooling outputs 45
Automatic speed control logic for 3-speed on/off motors with on/off outputs in heating mode
46
Automatic speed control logic for 3-speed on/off motors with on/off outputs in cooling mode
47
21. Manual speeds and ventilation in the absence of regulation ……………………………….. 48
22. Fan boost ………………………………………………………………………………………………………….. 48
23. Minimum thermostat ………………………………………………………………………………………….. 48
24. Destratification cycle …………………………………………………………………………………………. 49 25. Window contact…………………………………………………………………………………………………. 49
26. Frost protection function of the heating battery ………………………………………………….. 49
27. Dirty filter ………………………………………………………………………………………………………….. 50 28. Summertime changeover …………………………………………………………………………………… 50
29. Remote setpoint variator ……………………………………………………………………………………. 51
30. Restoring default parameters …………………………………………………………………………….. 51
31. Optional THS2……………………………………………………………………………………………………. 52
32. Display, keypad and icons of THS2 …………………………………………………………………….. 52
33. Setting parameters using quick access on THS2 ………………………………………………… 54
Keypad lock
54
Global on/off
54
Setting the setpoint and offset setpoint
55
Fan operating mode
55
MODE key function
56
34. Timer extension or forced presence mode………………………………………………………….. 58
35. Setting DATE and TIME………………………………………………………………………………………. 59
36. Operation and setting of TIME BANDS ……………………………………………………………….. 60
37. Duplication of TIME BANDS ………………………………………………………………………………. 62
38. Alarms ………………………………………………………………………………………………………………. 63
Communication error counter parameters
64
Resetting of internal network communication error counter parameters
65
39. Setting configuration parameters (level 1 password)…………………………………………… 66
40. Setting setpoints parameters (level 2 password)…………………………………………………. 72
41. Setting THS2 parameters (level 3 password) ………………………………………………………. 74
42. Setting CN4 communication parameters (level 4 password)………………………………… 76
43. Logic of digital inputs THS2……………………………………………………………………………….. 77
Digital THS2 inputs DI1 and DI2
77
44. Input/output status of THS2-0MM connected to THS2 …………………………………………. 77
45. Display of THS2-0MM operating by THS2 connected …………………………………………… 80
46. Monitoring status internal network (from THS2)………………………………………………….. 81 47. Restoring default parameters …………………………………………………………………………….. 83
48. Firmware version display …………………………………………………………………………………… 84
49. USB connection…………………………………………………………………………………………………. 85
50. Jumper configuration ………………………………………………………………………………………… 86
51. Forcing digital and analogue slave inputs/outputs ……………………………………………… 87
Forcing outputs
87
Forcing inputs
88
52. THS2-0MM master Modbus variables………………………………………………………………….. 90
53. Electrical connections ……………………………………………………………………………………… 113
THS2-0MM unit connection
113
THS2 unit connection
116
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
3/128
54. Networks connection diagram ………………………………………………………………………….. 117
Internal network connection diagram without supervisor on CN4
117
Internal network connection diagram with supervisor on CN4
117
External MODBUS network connection diagram with supervisor on CN5
119
Connection between optional THS2 to THS2-0MM
121
55. Dimensions ……………………………………………………………………………………………………… 122
THS2-0MM unit
122
THS2 unit
122
56. Installation requirements………………………………………………………………………………….. 123
THS2-0MM unit installation
124
THS2 unit installation
125
4/128
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
5/128
1. Technical features
· Display unit: THS2 (optional)
Power supply:
5 Vdc provided by THS2-0MM
Ambient temperature:
0…50°C
Display:
LCD display with backlight
Inputs:
2 potential-free contacts SELV (limit of voltage: 5 Vdc)
USB for configuration and software update
Communication:
external network
Dimensions:
128 x 80 x 28.5 mm
Installation:
wall mounting
Protection class:
2
CE compliance standards:
EN 60730-1
· Remote unit: THS2-0MM
Power supply: Power consumption: Ambient temperature: Inputs:
Outputs:
Connections: Communication:
Dimensions: Protection class: Mode of operation: Rated impulse voltage:
Control pollution degree: Low voltage directive LVD: CE compliance standards:
110…240 Vac, 50/60 Hz max 1.1 W (3.5 VA) THS2-0MM (with THS2 connected) 0…40°C 2 potential-free contacts SELV (limit of voltage: 4 Vdc) 2 NTC10K sensors USB for software update 3 analogue outputs 0-10 V (RL >10K) 5 SPST 240 Vac relays. K1 K2 K3 combined total 3 A (AC1), K5 K6 each 1 A (AC1) 1 SPST 240 Vac, 10 A (AC1) relay K4 max. cross-selectional area 1.5 mm2 (flexible cord conductors) one external network Modbus RTU (slave) for BMS, configuration or display. One internal network for connection up to 15 units. 140 x 121,5 x 47 mm 2 type 1 2.5 kV 2 EN 60730-1 EN 60730-1
6/128
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
2. Internal Modbus network
The internal Modbus network consists of: – a master unit which allows the operating parameters of each slave and the master itself to be set – 1 to 14 slave units: the parameter M20 is the sum of the number of slaves and master unit (on the example below M20=15) – an optional humidity and CO2 transmitter whose presence is defined by parameter M21.
CN5
MASTER SLAVE SLAVE SLAVE
THS2-0MM
GN
M +
Int Adr = 1
M
–
CN4
GND
+ M
M
120 term. JP1=ON
THS2-0MM
Int Adr = 2
CN4
GND
+ M
M
THS2-0MM
Int Adr = 3
CN4
GND
+ M
M
THS2-0MM
Int Adr = 15
CN4
GND
+ M
M
120 term. JP1=ON
The minimum configuration of the internal network consists of 1 master without
slave (M20=1). The maximum configuration of the internal network consists of 1
master unit connected to 14 slave units (M20=15).
Addresses are set for all units by means of a SW3 rotary dip switch located on
each slave card (see “53. Electrical connections” page 113)
Address A=10, B=11, C=12, D=13, E=14, F=15, address 0 is not valid and must not be selected.
Each unit, included the master unit must have an address different from other
units and different from 0. The master or slave can have any adress between 1
and F.
In case less than 15 units (14 slaves + 1 master) are used, parameter M20 must
be equal to the total of units present in the
internal network.
It is mandatory to assign an address different for each unit and on the range
from 1 to the value of parameter M20. The unit that is master must have jumper
J1 ON, the slaves jumper J1 OFF (not mounted). It is not possible to set 2
units in the same internal network as master otherwise communication could not
takes place.
J2
OFF (Ext Adr = Int Adr = SW3)
J2
ON (Ext Adr = M19)
Parameter M20 can be set either by an optional THS2 unit connected on CN5 of master unit (with password 33) or by Modbus connecting a supervisor on CN5 and setting the variable ADR_MOD_MAX_UNITS_INTERNAL_NETWORK (11150).
To connect a supervisor for the first time on CN5 connector use the address set on rotary switch of the master unit for internal network (jumper J2 must be OFF) with baud rate 19200 bit/s, parity even.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
7/128
3. External Modbus network
The external Modbus network allows the connection of a supervisor to the internal network via master unit with a second
communication port.
It is possible to connect several internal networks to the same supervisor by assigning a different address to each master in
the external network.
When jumper J2 is not mounted, the address set on rotary switch SW3 is the same for internal and external network.
(Parameter M19 is also set to this value).
Connection to supervisor system can be faster for several internal networks as it is not necessary to set external address with
parameter M19.
Ext Adr = Int Adr = SW3 [1]
Int Adr = SW3 [2]
Int Adr = SW3 [3]
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
Optional
SLAVE
120 term. JP3=ON
CN5
MASTER
120 term. JP2=ON GN
M +
M –
THS2-0MM
THS2-0MM
SLAVE
THS2-0MM
Transmitter
CN4
120 term. JP1=ON
GND
+ M
M
M20=3
CN4
GND
+ M
M
CN4
GND
+ M
M
M
GND
+ M
SLAVE
Ext Adr = Int Adr = SW3 [2] J1 J2 SW3
CN5
MASTER
GN
M
+ M
THS2-0MM
–
CN4
120 term. JP1=ON
GND
+ M
M
M20=2
Int Adr = SW3 [1] J1 J2 SW3
THS2-0MM
CN4
120 term. JP1=ON
GND
+ M
M
SLAVE SLAVE SLAVE
Supervisor
120 termination ON
GN
+ M
M
Ext Adr = Int Adr = SW3 [3] J1 J2 SW3
CN5
MASTER
GN
M
+ M
THS2-0MM
–
CN4
120 term. JP1=ON
GND
+ M
M
M20=4
CN5
MASTER
Ext Adr = 16 (M19=16) Int Adr = SW3 [1] J1 J2 SW3
GN
M
+ M
THS2-0MM
–
CN4
120 term. JP1=ON
GND
+ M
M
M20=2
Int Adr = SW3 [1] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
Int Adr = SW3 [2] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
SLAVE
120 term. JP3=ON
Int Adr = SW3 [2] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
Optional
Transmitter
M
GND
+ M
Int Adr = SW3 [4] J1 J2 SW3
THS2-0MM
CN4
120 term. JP1=ON
GND
+ M
M
8/128
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
For higher number of internal networks to connect to supervisor, external address of each master unit must be set by following procedure:
Put jumper J2 in ON position.
J2
OFF (Ext Adr = Int Adr = SW3)
J2
ON (Ext Adr = M19)
if a THS2 is connected to the master set parameter M19 to the desired address and exit parameters setting to transfert the new address to master unit. If a THS2 is not connected to the THS2-0MM master, connect supervisor on CN5 and set new address on variable ADR_ MOD_MODBUS_ADDRESS_NETWORK (11149). Before changing address the connection must be done with the address set on SW3. After the THS2-0MM master takes into consideration the new address, it is necessary for THS2 (or supervisor) to establish a
MODE
connection with the new address set. Press the keys + simultaneously, the following message appears on the dis-
Adr
play:
1
Press the key the current address is flashing. With keys or select the new address and press the the key to
save the selection, then the ESC key to exit connection address setting.
Example of assignment done for the following network:
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
9/128
Min External Address = 1
Ext Adr = 1
120 term. JP2=ON GN
M +
M –
THS2-0MM
Int Adr = 1
CN4
GND
+ M
M
120 term. JP1=ON
Ext Adr = 2
THS2-0MM
GN
M +
Int Adr = 1
M
–
CN4
GND
+ M
M
120 term. JP1=ON
Every 31 node, add a repeater!
Ext Adr = 31
THS2-0MM
GN
M +
CN5
Int Adr = 1
M
–
CN4
GND
+ M
M
120 term. JP1=ON
120 term. ON 120 term. ON
GN
M +
M –
Repeater
GN
M +
M –
CN5
MASTER
CN5
MASTER
MASTER
THS2-0MM
Int Adr = 2
CN4
GND
+ M
M
THS2-0MM
Int Adr = 2
CN4
GND
+ M
M
THS2-0MM
Int Adr = 2
CN4
GND
+ M
M
SLAVE
SLAVE
SLAVE
THS2-0MM
Int Adr = 3
CN4
GND
+ M
M
THS2-0MM
Int Adr = 3
CN4
GND
+ M
M
THS2-0MM
Int Adr = 3
CN4
GND
+ M
M
SLAVE
SLAVE
SLAVE
THS2-0MM
SLAVE
Int Adr = 15
CN4
GND
+ M
M
120 term. JP1=ON
THS2-0MM
SLAVE
Int Adr = 15
CN4
GND
+ M
M
120 term. JP1=ON
THS2-0MM
SLAVE
Int Adr = 15
CN4
GND
+ M
M
120 term. JP1=ON
Max External Address = 247
Ext Adr = 247
THS2-0MM
GN
M +
M 120 term. –
JP2=ON
Int Adr = 1
CN4
GND
+ M
M
120 term. JP1=ON
CN5
MASTER
THS2-0MM
Int Adr = 2
CN4
GND
+ M
M
SLAVE
THS2-0MM
Int Adr = 3
CN4
GND
+ M
M
SLAVE
THS2-0MM
SLAVE
Int Adr = 15
CN4
GND
+ M
M
120 term. JP1=ON
The supervisor can monitor all status of each master, and several status
variables of slaves, set the operating parameters for each internal network.
If necessary, it can sets inputs, outputs of all devices of the same internal
network indipendently from regulation. The supervisor must exchange data with
each master with a time laps lower than 10 minutes to be considered as
connected by master otherwise change of parameters done by supervisor are not
considered.
Note: in case of change of parameters for baud rate, parity on external
network, make change on master unit from supervisor or on a THS2 connected to
CN5 of master unit. Automatically all units connected to master unit will
change parameters setting for communication on external network and after the
change done, the supervisor and each THS2 connected to slaves of internal
network will have to update communication parameters to the new ones to be
able to communicate again.
4. Optional THS2 connection
If no supervisor is used an optional display THS2 can be connected to a master on the second Modbus communication port (CN5 connector) for monitoring operating mode of master unit and set all parameters. The master unit transmits the same setting to the whole slaves of internal network.
10/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
120 term. JP1=ON CN5
MASTER SLAVE SLAVE
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = SW3 [1]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
M20=3
CN4
GND
+ M
M
120 term.
JP1=ON
Int Adr = SW3 [2] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
Int Adr = SW3 [3] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
120 term.
JP1=ON
Connect GN and GND on this case.
If a supervisor is connected to the master unit, an optional display THS2 can be connected to a slave on the second Modbus communication port (CN5 connector). The optional THS2 can monitor operating mode of the slave at which it is connected and can only change some operating variables such as setpoint or offset setpoint, speed of fan, on/off. These changes will be then set on the whole internal network by the THS2-0MM master unit.
CN5
MASTER SLAVE
120 term. JP1=ON CN5
SLAVE
Supervisor
120 termination ON
GN
+ M
M
Ext Adr = Int Adr = SW3 [1]
J1 J2 SW3
120 term. JP2=ON GN M + M –
M20=3
THS2-0MM
CN4
GND
+ M
M
120 term.
JP1=ON
Int Adr = SW3 [2] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
THS2
-+ M M
GND +5V
Int Adr = SW3 [3]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
CN4
GND
+ M
M
120 term.
JP1=ON
It is also possible to connect more than one THS2 on the second Modbus communication port (CN5 connector), at maximum one per unit THS2-0MM.
120 term. JP1=ON CN5
MASTER
120 term. JP1=ON CN5
SLAVE SLAVE
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = SW3 [1]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
M20=3
CN4
GND
+ M
M
120 term.
JP1=ON
THS2
-+ M M
GND +5V
Int Adr = SW3 [2]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
CN4
GND
+ M
M
Int Adr = SW3 [3] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
120 term.
JP1=ON
By parameter M22 it is possible to define what can do THS2 when connected to a THS2-0MM slave unit (see “31. Optional THS2” page 52).
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 11/128
5. THS2-0MM connected to THS2 and supervisor contemporaneously
it is possible to create a network with several THS2-0MM slave units connected to supervisor system on CN4 and THS2 unit on CN5.
120 term. JP1=ON
120 term. JP1=ON
120 term. JP1=ON
Supervisor
120
termination ON
GND
+ M
M
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = M19 = XX SW3 [0]
120 term. GN JP2=ON
J1 J2 SW3
CN5
M +
M
–
THS2-0MM
SLAVE
+5V
CN4
GND
GND
+ M
M
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = M19 = XX SW3 [0]
120 term. GN JP2=ON
J1 J2 SW3
CN5
M +
M
–
THS2-0MM
SLAVE
+5V
CN4
GND
GND
+ M
M
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = M19 = XX SW3 [0]
120 term. GN JP2=ON
J1 J2 SW3
M +
M
–
THS2-0MM
CN5
SLAVE
+5V
CN4
GND
GND
+ M
M
120 term.
JP1=ON
To create such a network, the following settings must be done on all THS2-0MM units: – jumper J1 must be OFF (not mounted), by this way all units are slaves. – the position of SW3 must be put on 0, by default the address on CN4 and CN5 becomes 1. – jumper J2 must be ON (mounted). By parameter M19 the address of a THS2-0MM unit must be set between 1 and 247. This address is the same for CN4 (internal network) and CN5 (external Modbus connection towards display THS2) and must be different for each unit. It is advisable to connect a THS2-0MM one by one and do the settings indicated. After connection has been established write on variable STATUS_PRESENCE_MASTER (11038) the value 5555 to indicate the presence of the master unit. it is necessary for supervisor to communicate with each slave with a time lapse lower than 10 minutes otherwise a slave will consider the supervisor unconnected.
if a THS2 is connected to the THS2-0MM slave, set parameter M19 to the desired address and exit parameters setting to transfert the new address to the slave unit or connect supervisor on CN4 and set new address on variable ADR_MOD_MODBUS_ADDRESS_NETWORK (11149) (default baud rate=9600bit/s with even parity and address 1). After the THS2-0MM slave takes into consideration the new address, it is necessary for THS2 (and supervisor) to establish
MODE
the connection with the new address set. For THS2 press the keys + simultaneously, the following message appears
Adr
on the display:
1
Press the key the current address is flashing. With keys or select the new address and press the the key to
save the selection, then the ESC key to exit connection address setting.
12/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
6. Regulation sensor
A wide choice can be made when selecting the regulation sensor for a THS2-0MM. The regulation sensor of a given unit can be: – it’s own remote regulation sensor, – the internal sensor of optional THS2, – the remote regulation sensor of master unit. Selection is made writing the variable ADR_MODTYPESENSREG (11070) (parameter I02) on master unit.
If I02=0, the respective slave regulation sensor that can be sensor AI1 (or AI2): .
Ext Adr = Int Adr = SW3 [1] J1 J2 SW3
Int Adr = SW3 [2] J1 J2 SW3
Int Adr = SW3 [3] J1 J2 SW3
Int Adr = SW3 [4] J1 J2 SW3
MASTER SLAVE SLAVE SLAVE
THS2-0MM
AI1 GND
CN4
GND
+ M
M
M20=4 I02=0
120 term. JP1=ON
I11=1
S1
THS2-0MM
AI1 GND
CN4
GND
+ M
M
S2
THS2-0MM
AI1 GND
CN4
GND
+ M
M
S3
THS2-0MM
AI1 GND
CN4
GND
+ M
M
120 term. JP1=ON
S4
Write 0 on variable ADR_MODTYPESENSREG (11070) (parameter I02) on master unit. Write 1 on variable ADR_MODANAINPUT1FUN (11079) (parameter I11) to set AI1 as regulation sensor on master unit [or ADR MOD_ANAINPUT2FUN (11081) (parameter I13) to set AI2].
If I02=1 regulation with internal temperature of optional THS2 connected to master unit for whole network:
120 term. JP1=ON CN5
MASTER SLAVE SLAVE SLAVE
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = SW3 [1]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
CN4
GND
+ M
M
M20=4 I02=1
120 term. JP1=ON
Int Adr = SW3 [2] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
Int Adr = SW3 [3] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
Write 1 on variable ADR_MODTYPESENSREG (11070) (parameter I02) on master unit. On THS2 unit set parameter M22=0.
Int Adr = SW3 [4] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
120 term. JP1=ON
– regulation with internal temperature of optional THS2 connected to a slave unit for whole network
CN5
MASTER SLAVE
120 term. JP1=ON CN5
SLAVE
Ext Adr = Int Adr = SW3 [1] J1 J2 SW3
GN M
+ M
–
M20=3
THS2-0MM
CN4
GND
+ M
M
120 term.
JP1=ON
Int Adr = SW3 [2] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
THS2
-+ M M
GND +5V
Int Adr = SW3 [3]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
CN4
GND
+ M
M
120 term.
JP1=ON
Write 1 on variable ADR_MODTYPESENSREG (11070) (parameter I02) on master unit. On THS2 unit set parameter M22=0.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 13/128
– In case several THS2 units are connected to different THS2-0MM units it is possible to select the internal temperature of the THS2 that will be used for whole network (see example below):
120 term. JP1=ON CN5
MASTER 120 term. JP1=ON CN5 SLAVE SLAVE
Tint1 THS2
-+ M M
GND +5V
Ext Adr = Int Adr = SW3 [1]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
M20=3
CN4
GND
+ M
M
120 term.
JP1=ON
Tint2 THS2
-+ M M
GND +5V
Int Adr = SW3 [2]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
CN4
GND
+ M
M
Int Adr = SW3 [3] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
120 term.
JP1=ON
Tint1: internal temperature of THS2 connected to THS2-0MM with address 1 Tint2: internal temperature of THS2 connected to THS2-0MM with address 2
M22 [THS2 connected to THS2-0MM with address 1] = 0 M22 [THS2 connected to THS2-0MM with address 2] = 0 Regulation temp THS2-0MM [with address 1]=Tint1 Regulation temp THS2-0MM [with address 2]=Tint2 Regulation temp THS2-0MM [with address 3]=Tint1 (both THS2 transmit there internal temperature, units of internal network without THS2 connected use the internal temperature of the THS2 connected to the THS2-0MM with lowest internal address).
M22 [THS2 connected to THS2-0MM with address 1] = 1 M22 [THS2 connected to
THS2-0MM with address 2] = 0
Regulation temp THS2-0MM [with address 1]=Tint2 Regulation temp THS2-0MM [with
address 2]=Tint2 Regulation temp THS2-0MM [with address 3]=Tint2
M22 [THS2 connected to THS2-0MM with address 1] = 0 M22 [THS2 connected to THS2-0MM with address 2] = 1 Regulation temp THS2-0MM [with address 1]=Tint1 Regulation temp THS2-0MM [with address 2]=Tint1 Regulation temp THS2-0MM [with address 3]=Tint1
– If a supervisor is connected to master unit instead an optional display, it can send a temperature to the internal network for regulation:
Ext Adr = Int Adr = SW3 [1]
Int Adr = SW3 [2]
Int Adr = SW3 [3]
Int Adr = SW3 [4]
Supervisor
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
120 termination ON
CN5
MASTER SLAVE SLAVE SLAVE
GN
GN
M
M
THS2-0MM
M
M
–
–
120 term. JP2=ON
CN4
GND
+ M
M
M20=4 I02=1
120 term. JP1=ON
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
120 term. JP1=ON
Follow the procedure below on master unit from supervisor: – write the value 22222 to indicate presence of supervisor on variable STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) – write the value of temperature multiplied by 10 (for example 255 to transmit a temperature of 25.5°C) on variable ADRMOD STATUS_CURRENT_THS2_TEMP (11034). Do not exceed 9 minutes without sending a message from supervisor to master unit otherwise supervisor is considered not connected and temperature is forced to a value corresponding to sensor open (-200).
– If a supervisor is connected to master unit and an optional display on a THS2-0MM unit, the selection of the temperature for regulation depends on the setting done on variable STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) of master unit from supervisor and parameter M22 of THS2:
14/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
CN5
MASTER SLAVE
120 term. JP1=ON CN5
SLAVE
Supervisor
120
termination ON
GN
+ M
M
Ext Adr = Int Adr = SW3 [1]
J1 J2 SW3
120 term. JP2=ON GN M + M –
M20=3
THS2-0MM
CN4
GND
+ M
M
120 term.
JP1=ON
Int Adr = SW3 [2] J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
Tint2 THS2
-+ M M
GND +5V
Int Adr = SW3 [3]
120 term. JP2=ON GN
M +
M –
J1 J2 SW3
THS2-0MM
+5V GND
CN4
GND
+ M
M
120 term.
JP1=ON
Tint2: internal temperature of THS2 connected to THS2-0MM with address 3
->regulation of all internal network with temperature supplied by supervisor – write the value 22222 to indicate presence of supervisor on variable STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) – write the value of temperature multiplied by 10 (for example 255 to transmit a temperature of 25.5°C) on variable ADRMOD STATUS_CURRENT_THS2_TEMP (11034). Do not exceed 9 minutes without sending a message from supervisor to master unit otherwise supervisor is considered not connected and temperature is forced to a value corresponding to sensor open (-200). – set M22 [THS2 connected to THS2-0MM with address 3] = 1
->regulation of all internal network with temperature supplied by THS2: – write the value 11500 to indicate presence of supervisor on variable STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) without transmitting temperature – set M22 [THS2 connected to THS2-0MM with address 3] = 0
If I02=2 regulation with own remote regulation sensor of master unit On this case the temperature of sensor connected to AI1 (or AI2) is used for regulation by all units of the whole internal network. Write 2 on variable ADR_MODTYPESENSREG (11070) (parameter I02) on master unit. Write 1 on variable ADR_MOD_ANAINPUT1FUN (11079) (parameter I11) to set AI1 as regulation sensor on master unit.
Ext Adr = Int Adr = SW3 [1]
Int Adr = SW3 [2]
Int Adr = SW3 [3]
Int Adr = SW3 [4]
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
MASTER SLAVE SLAVE SLAVE
THS2-0MM
AI1 GND
CN4
GND
+ M
M
M20=4 I02=2
120 term. JP1=ON
I11=1
S1
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
120 term. JP1=ON
Note: for I02=0 or I02=2 if a THS2 is connected to a THS2-0MM unit it is also
possible to consider the temperature of internal THS2 together with remote
regulation sensor of THS2-0MM to obtain the regulation sensor. Example: to
regulate with a weighting of 25% of the remote sensor connected on AI1 (or
AI2) and a weighting of 75% of the internal sensor of the THS2 with I02=2, set
the following setting on THS2-0MM unit: Write 2 on variable ADR_MODTYPESENSREG
(11070) (parameter I02). Write 1 on variable ADR_MOD_ANAINPUT1FUN (11079)
(parameter I11) to set AI1 as regulation sensor. Write 25 on variable
ADR_MOD_WEIGHTREMAISENS(11094) (parameter I26) to set the weigth of remote
regulation sensor
The following formula is applied for calculation of regulation sensor:
Treg=[Ti (100 – Y) + (TA x Y)] / 100 with: Ti=internal sensor of THS2,
TA=remote sensor connected on AI1 of THS2-0MM, Y=weigth of remote sensor. For
not considering weighting set the parameter I26 to 100 (default value).
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 15/128
7. ON/OFF function on THS2-0MM
The THS2-0MM master can be switched on or off by configuring a digital input
with remote on/off function I07=2 (Input DI1) or I09=2 (Input DI2), by
connecting an optional THS2-0MM or by supervisor. On this last case to put
unit in ON write the value 1 to the address ADR_MOD_FORCEMASTERGLOBALONOFF
(11048) or 0 to put the unit in OFF. To release the control of ON/OFF from
supervisor write the value 200 on the same address. A THS2-0MM slave can be
switch on/off by THS2-0MM master or by an optional THS2 connected.
In case a remote contact is used for on/off function on THS2-0MM master it has
high priority if no supervisor sytem is connected. Even if a THS2 is connected
it is not possible to switch on/off manually or by time bands. If a supervisor
system is connected to the THS2-0MM master with a remote on/off contact set,
the supervisor has the highest priority for switching on/off internal network
by writing 0 (for switching off) or 1 (for switching on) to the address ADR
MOD_FORCE_MASTERGLOBALONOFF (11048). To let the contact on/off take the
control on master unit for on/off function the supervisor must write the value
200 on address ADR_MOD_FORCE_MASTERGLOBALONOFF (11048).
8. Logic of digital and analogue inputs THS2-0MM
· Digital slave inputs DI1 and DI2
Parameter I07=0 (Input DI1) or I09=0 (Input DI2)
Logic
Not used
I07=1 (Input DI1) or I09=1 (Input DI2)
Logic DI1 I08 = Logic DI2 I10 =
0
1
Remote contact for season changeover
Summer Winter
I07=2 (Input DI1) or I09=2 (Input DI2)
Remote On/Off (Do not use if a supervisor system is connected to master unit.
Supervisor
has higher priority and contact is not considered on this case)
Logic DI1 Logic DI2
I08 = I10 =
Off
On
0
1
I07=3 (Input DI1) or I09=3 (Input DI2) Unoccupied
Logic DI1 I08 = Logic DI2 I10 =
0
1
“Unoccupied holidays” mode
“occupied” mode
I07=4 (Input DI1) or I09=4 (Input DI2)
Logic DI1 I08 = Logic DI2 I10 =
0
1
Energy saving
No economy Economy
I07=5 (Input DI1) or I09=5 (Input DI2)
Logic DI1 I08 = Logic DI2 I10 =
0
1
Window contact
Window open Window closed
I07=6 (Input DI1) or I09=6 (Input DI2)
Logic DI1 I08 = Logic DI2 I10 =
0
1
Generic alarm
Alarm absent Alarm present
I07=7 (Input DI1) or I09=7 (Input DI2)
Logic DI1 I08 = Logic DI2 I10 =
0
1
Minimum thermostat
Open Closed
Setting is done either by setting parameters on the optional THS2 connected to master unit or by modbus of master unit and
writing the following variables:
ADR_MOD_DIGINPUT1FUN (11075) for setting I07
ADR_MOD_DIGINPUT1LOG (11076) for setting I08
ADR_MOD_DIGINPUT2FUN (11077) for setting I09
ADR_MOD_DIGINPUT2LOG (11078) for setting I10
16/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
· Analogue slave inputs
1. Analogue input 1 (AI1):
Parameter
I11=0
Sensor not used
I11=1 Remote regulation sensor
Sensor AI1 is used to obtain the final regulation temperature (for the calculation, see “6. Regulation sensor” page 13
I11=2
C16=0 or 1
Water sensor for sea-
son changeover
C16=2
0.5°C
0.5°C
Cooling
Heating
Cooling
Heating
C14
C13
Temp. water
C14
C13
Temp.water
I11=3 Minimum thermostat sensor
If the water sensor temperature at power-on is between C14 and C13, see paragraph “9. Automatic season changeover with water sensor” page 20 for season definition.
Minimum thermostat open
C15 2°C
Minimum thermostat closed
C15
Temp. water coil
I11=4 Remote contact for season changeover
If the temperature of the heating battery sensor at power-on is between C15 and C15 – 2, the minimum thermostat is considered open.
I12 =
0
1
Summer
Winter
I11=5 Remote On/Off (Do not use if a supervisor system is connected to master
unit. Supervisor has higher priority and
contact is not considered
on this case)
I12 =
I11=6
I12 =
Unoccupied holidays
Off On
“Unoccupied holidays” mode
0
1
0
1
Occupied mode
I11=7 Energy saving
I12 =
No economy mode
0
1
Economy mode
I11=8 Window contact
I12 =
Window open
0
1
Window closed
I11=9 Alarm
I12 =
Alarm absent
0
1
Alarm present
I11=10 Remote setpoint variator input
The setpoint variator SAP-NTC-02-2-EV must be connected in order to change the slave setpoint
For I11=4 to 9 configurations, analogue input 1 is used as a digital input.
The contact is considered closed, if there is a short circuit on the analogue
input. The contact is considered open, if nothing is connected. Setting is
done either by setting parameters on the optional THS2 connected to master
unit or by modbus of master unit and writing the following variables:
ADR_MOD_ANAINPUT1FUN (11079) for setting I11 ADR_MOD_ANAINPUT1LOG (11080) for
setting I12
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy
Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
17/128
2. Analogue input 2 (AI2):
Parameter
I13=0
I13=1 Remote regulation sensor
I13=2 Water sensor for sea-
son changeover
Sensor not used Sensor AI2 is used to obtain the final regulation temperature (for the calculation, see “6. Regulation sensor” page 13)
C16=0 or 1
C16=2
0.5°C
0.5°C
Cooling
Heating
Cooling
Heating
C14
C13
Temp. water
C14
C13
Temp.water
I13=3 Minimum thermostat sensor
If the water sensor temperature at power-on is between C14 and C13, see paragraph “9. Automatic season changeover with water sensor” page 20 for season definition.
Minimum thermostat open
C15 2°C
Minimum thermostat closed
C15
Temp. water coil
I13=4 Remote contact for season changeover
If the temperature of the heating battery sensor at power-on is between C15 and C15 – 2, the minimum thermostat is considered open.
I14 =
Summer
0
1
Winter
I13=5 Remote On/Off (Do not use if a supervisor system is connected to master
unit. Supervisor has higher priority and
contact is not considered on this case)
I13=6 Unoccupied holidays
I14 = I14 =
Off On
“Unoccupied holidays” mode
0
1
0
1
Occupied mode
I13=7 Energy saving
I14 =
No economy mode
0
1
Economy mode
I13=8 Window contact
I14 =
Window open
0
1
Window closed
I13=9 Alarm
I14 =
Alarm absent
0
1
Alarm present
I13=10 Remote setpoint variator input
The setpoint variator SAP-NTC-02-2-EV must be connected in order to change the slave setpoint
For I13=4 to 9 configurations, analogue input 2 is used as a digital input. The contact is considered closed, if there is a short circuit on the analogue input. The contact is considered open, if nothing is connected.
Setting is done either by setting parameters on the optional THS2 connected to
master unit or by modbus of master unit and writing the following variables:
ADR_MOD_ANAINPUT2FUN (11081) for setting I13 ADR_MOD_ANAINPUT2LOG (11082) for
setting I14
18/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
The digital inputs or analogue inputs that are common to all network such as
remote on/off, change-over season, economy, unoccupied holidays, window
contact must be connected to the master unit in order to be visible by the
whole internal network.
On the example below are indicated the connection of digital inputs that are
common to the whole internal network:
Ext Adr = Int Adr = SW3 (1)
Int Adr = SW3 (2)
Int Adr = SW3 (3)
Int Adr = SW3 (4)
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
THS2-0MM
DI1 DI2 GND
CN4
GND
+ M
M
120 term. JP1=ON
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
120 term. JP1=ON
DI1 DI2
MASTER SLAVE SLAVE SLAVE
If no master is present each unit works indipendently, it is necessary to connect a digital input or an analogue input, that is configured for a function, on each unit.
The digital contacts or analogue inputs that are local to each unit such as minimum thermostat or alarm contact must be connected to each unit. On the example below are indicated the connection of digital inputs that are not common to the whole internal network:
Ext Adr = Int Adr = SW3 (1)
Int Adr = SW3 (2)
Int Adr = SW3 (3)
Int Adr = SW3 (4)
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
THS2-0MM
DI1 DI2 GND
CN4
GND
+ M
M
120 term. JP1=ON
THS2-0MM
DI1 DI2 GND
CN4
GND
+ M
M
THS2-0MM
DI1 DI2 GND
CN4
GND
+ M
M
THS2-0MM
DI1 DI2 GND
CN4
GND
+ M
M
120 term. JP1=ON
DI1 DI2
MASTER
DI1 DI2
SLAVE
DI1 DI2
SLAVE
DI1 DI2
SLAVE
Note: If the same function is assigned to the digital and/or analogue inputs on the master and slaves and also on an optional THS2 connected to the master unit, the following priority applies in cases of similar assignment:
Priority of inputs for remote season changeover, on/off, unoccupied holidays, economy, window contact:
THS2 digital input 1 (DI1)
–
Highest priority
THS2 digital input 2 (DI2)
THS2-0MM digital input 1 (DI1)
THS2-0MM digital input 2 (DI2)
THS2-0MM analogue input 1 (AI1)
THS2-0MM analogue input 2 (AI2)
–
Lowest priority
Priority of inputs for minimum thermostat function for each slave:
THS2 digital input 1 (DI1)
–
THS2 digital input 2 (DI2)
THS2-0MM digital input 1 (DI1)
THS2-0MM digital input 2 (DI2)
THS2-0MM analogue input 1 (AI1)
THS2-0MM analogue input 2 (AI2)
–
Highest priority Lowest priority
In case of alarm function there is no priority, it is possible to have several indipendent alarm contacts for master and each slave.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 19/128
9. Automatic season changeover with water sensor
In 2-pipe systems (I01=0), if no digital input is configured for remote season
changeover, and no analogue input is configured as a remote season changeover
contact, it is possible to use a remote sensor of the THS2-0MM master unit for
the internal
network and configure it as a water sensor for automatic season changeover
(I11=2 or I13=2). The example below indicates the automatic change-over season
sensor based on AI2 of master unit:
Ext Adr = Int Adr = SW3 (1)
Int Adr = SW3 (2)
Int Adr = SW3 (3)
Int Adr = SW3 (4)
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
J1 J2 SW3
MASTER SLAVE SLAVE SLAVE
THS2-0MM
AI2 GND
CN4
GND
+ M
M
120 term. JP1=ON
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
THS2-0MM
CN4
GND
+ M
M
120 term. JP1=ON
WATER SENSOR
Write 2 on variable ADR_MOD_ANAINPUT2FUN (11081) (parameter I13).
The season changeover is implemented automatically according to the water
temperature at the inlet of the fan coil unit. Depending on the value of
parameter C16, the season changeover takes place as follows:
C16=0 or 1:
Summer C14
Winter C13
Temp. water
C13: heating setpoint for automatic season changeover sensor C14: cooling setpoint for automatic season changeover sensor
When the unit is switched on, if the water sensor temperature is between C14 and C13, the operating season is heating (if C16=0) or cooling (if C16=1). Then, if the temperature of the water sensor varies and exceeds C13, heating becomes the operating season. If the temperature of the water sensor varies and falls below C14, cooling becomes the operating season.
C16=2:
0.5°C
0.5°C
Summer C14
Winter C13
Temp. water
C13: heating setpoint for automatic season changeover sensor C14: cooling
setpoint for automatic season changeover sensor
When the unit is switched on, if the water sensor temperature is between C14
and C13, the operating season is not specified, and there is no regulation.
Then, if the temperature of the water sensor varies and exceeds C13, heating
becomes the operating season. If it falls below C13 -0.5°C again, the season
is unspecified, and regulation is stopped. If the temperature of the water
sensor varies and falls below C14, cooling becomes the operating season. If it
rises above C14 +0.5°C again, the season is unspecified, and regulation is
stopped.
Setting of parameters C13, C14, C16 is done either by setting parameters on
the optional THS2 connected to master unit or by modbus via connector CN2 of
master unit and writing the following registers: ADR_MOD_WINTERSETCO (11134)
for setting C13
20/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
ADR_MOD_SUMMERSETCO (11135) for setting C14 ADR_MOD_SEASONINBETWEENSUMWIN
(11137) for setting C16
10. Working setpoint, economy and unoccupied holidays mode
If one of the digital contacts is configured as a remote “unoccupied holidays”
contact M01=3 (DI1) or M03=3 (DI2) on the optional THS2, or if one of the
digital contacts is configured as a remote “unoccupied holidays” contact I07=3
(DI1) or I09=3 (DI2), or an analogue input is configured as an “unoccupied
holidays” contact I11=6 (AI1) or I13=6 (AI2) on a THS2-0MM master, the
“unoccupied holidays” function can be activated, if the corresponding contact
is in the appropriate position (see “8. Logic of digital and analogue inputs
THS2-0MM” page 16 and “43. Logic of digital inputs THS2” page 77).
2-pipe systems (I01=0): In “unoccupied holidays” mode, the working heating
setpoint is decreased by C09 (see 2-pipe heating diagram, WHS), the working
cooling setpoint is increased by C09 (see 2-pipe cooling diagram, WCS). 4-pipe
systems (I01=1): In “unoccupied holidays” mode, the heating trigger point is
decreased by C09 (see 4-pipe diagram, WHS), and the cooling trigger point is
increased by C09 (see 4-pipe diagram, WCS). In case of presence of optional
THS2 connected to a THS2-0MM, the icon lights up to indicate “unoccupied
holidays” mode.
If one of the digital contacts is configured as a remote “energy saving”
contact M01=4 (DI1) or M03=4 (DI2) on the optional THS2, or if one of the
digital contacts is configured as a remote “energy saving” contact I07=4 (DI1)
or I09=4 (DI2), or an analogue input is configured as an “energy saving”
contact I11=7 (AI1) or I13=7 (AI3) on a THS2-0MM master, the energy-saving
function can be activated, if the corresponding contact is in the appropriate
position (see “8. Logic of digital and analogue inputs THS2-0MM” page 16 and
“43. Logic of digital inputs THS2” page 77).
2-pipe systems (I01=0): The working heating setpoint is decreased by C08 (see
2-pipe heating diagram, WHS), and the working cooling setpoint is increased by
C08 (see 2-pipe cooling diagram, WCS) 4-pipe systems (I01=1): In “energy
saving” mode, the heating trigger point is decreased by C08 (see 4-pipe
diagram, WHS), and the cooling trigger point is increased by C08 (see 4-pipe
diagram, WCS) In case of presence of optional THS2 connected to a THS2-0MM,
the “ECO” icon is turned on to indicate “energy saving” mode. The “unoccupied
holidays” mode has priority over economy mode when both functions are
triggered.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy
Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
21/128
2-pipe diagram (analogue output, cooling)
2-pipe diagram (digital output, cooling)
OUT 100
0 C02 WCS
OUT
100
ECONOMY or HOLIDAY
0
WCS
(C08 o C09)
C02 2-pipe cooling setpoint WCS: cooling trigger point
Temp. Temp.
OUT ON
OFF
OUT
ON
ECONOMY or HOLIDAY
OFF
WCS C02
Temp.
Temp.
WCS
(C08 o C09)
C02 2-pipe cooling setpoint WCS: cooling trigger point
2-pipe diagram (analogue output, heating)
2-pipe diagram (digital output, heating)
OUT 100
0
OUT
100 ECONOMY or HOLIDAY
0
WHS C01
Temp.
WHS
Temp.
(C08 o C09)
C01: 2-pipe heating setpoint WHS: heating trigger point
OUT ON
OFF OUT
WHS C01
ON
ECONOMY or HOLIDAY
OFF
WHS
(C08 o C09)
C01: 2-pipe heating setpoint WHS: heating trigger point
Temp. Temp.
22/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
4-pipe diagram (analogue output)
OUT 100
0
OUT
100 ECONOMY or HOLIDAY
0
WHS C03 WCS
WHS
C03
WCS
(C08 o C09) (C08 o C09)
Temp. Temp.
Outputs ON
OFF
WHS
Outputs
BS4P (C03)
WCS
Temp
ON
ECONOMY or HOLIDAY
OFF
WHS
(C08 o C09)
C03: 4-pipe setpoint WCS: cooling trigger point WHS: heating trigger point
BS4P (C03)
Temp
WCS
(C08 o C09)
It is possible to display the working setpoint with an optional THS2 connected to a THS2-0MM in the I/O status menu (see paragraph “44. Input/output status of THS2-0MM connected to THS2” page 77). In this case, the value corresponding to WHS in the “WHS” submenu is displayed in heating mode, and the value corresponding to the WCS in the “WCS” submenu is displayed in cooling mode.
If none of the contacts are configured in “unoccupied holidays” or “energy
saving” mode, by an optional THS2 connected to THS2-0MM master it is possible
to program time bands in order to regulate with base setpoints within the time
bands and in
economy mode outside. To do so set Mod=tiMb on THS2, and the time band
function M10=0 (see “33. Setting parameters using quick access on THS2” page
54). If this is not the case, the status of the contact configured in
“unoccupied holidays” or “energy saving” mode takes priority, and the time
bands are not taken into account.
If none of the contacts are configured in “unoccupied holidays” or “energy
saving” mode, regulation takes place in unoccupied holidays if the operating
mode is unoccupied holidays mode (set manually via quick access parameters see
“MODE key function” page 56). If this is not the case, the status of the
contact configured in “unoccupied holidays” or “energy saving” mode overrides
the manual setting. When the timer extension function is activated manually on
THS2 connected to the THS2-0MM master it has higher priority than energy
saving, unoccupied holidays and time band modes (see “34. Timer extension or
forced presence mode” page
58).
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy
Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
23/128
11. Temperature regulation batteries
The temperature regulation batteries are configured via the parameters –
heating battery (stage 1) I03, variable ADR_MOD_TYPHEATINGCOIL (11071) –
cooling battery I04, variable ADR_MOD_TYPCOOLINGCOIL (11072) – supplemental
battery (stage 2 heating or for mid-season operation) I05,, variable
ADR_MOD_TYPADDCOIL (11073).
Battery Heating battery
Cooling battery Hot/cold mixed-use battery Supplemental heating battery
Battery type No heating battery
Modulating electrical resistance
Modulating heating valve
On/off electrical resistance
On/off heating valve No cooling battery Modulating cooling valve Cooling valve
on/off No mixed-use battery Modulating mixed-use valve Mixed-use on/off valve
No supplemental heating battery Supplemental heating battery on/off Modulating
supplemental heating battery
Set the outputs to activate the selected batteries as shown in the table below: -output DO1 I15, variable ADR_MOD_DIGOUTPUT1FUNC (11083) -output DO2 I16, variable ADR_MOD_DIGOUTPUT2FUNC (11084) -output DO3 I17, variable ADR_MOD_DIGOUTPUT3FUNC (11085) -output DO4 I18, variable ADR_MOD_DIGOUTPUT4FUNC (11086) -output DO5 I19, variable ADR_MOD_DIGOUTPUT5FUNC (11087) -output DO6 I20, variable ADR_MOD_DIGOUTPUT6FUNC (11088) -output AO1 I21, variable ADR_MOD_ANAOUTPUT1FUNC (11089) -output AO2 I22, variable ADR_MOD_ANAOUTPUT2FUNC (11090) -output AO3 I23, variable ADR_MOD_ANAOUTPUT3FUNC (11091).
Setting I03=0
I03=1
I03=2
I03=3
I03=4 I04=0 I04=1 I04=2
I03=2 and I04=1 I03=4 and I04=2
I05=0 I05=1 I05=2
Element Modulating electrical resistance
Modulating heating valve On/off electrical resistance
On/off heating valve Modulating cooling valve
Setting
I21=8 (AO1) or I22=8 (AO2) or
I23=8 (AO3)
I21=2 (AO1) or I22=2 (AO2) or
I23=2 (AO3)
I15=7 (DO1) or I16=7 (DO2) or I17=7 (DO3) or I18=7 (DO4) or I19=7 (DO5) or
I20=7 (DO6)
I15=4 (DO1) or I16=4 (DO2) or I17=4 (DO3) or I18=4 (DO4) or I19=4 (DO5) or
I20=4 (DO6)
I21=3 (AO1) or I22=3 (AO2) or
I23=3 (AO3)
24/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
Cooling valve on/off Modulating mixed-use valve
Mixed-use on/off valve Supplemental modulating resistance
Supplemental on/off resistance 3-point (open) on/off heating valve 3-point
(close) on/off heating valve 3-point (open) cooling valve on/off 3-point
(close) cooling valve on/off 3-point (open) mixed-use valve on/off 3-point
(close) mixed-use valve on/off
I15=5 (DO1) or I16=5 (DO2) or I17=5 (DO3) or I18=5 (DO4) or I19=5 (DO5) or
I20=5 (DO6)
I21=4 (AO1) or I22=4 (AO2) or
I23=4 (AO3)
I15=6 (DO1) or I16=6 (DO2) or I17=6 (DO3) or I18=6 (DO4) or I19=6 (DO5) or
I20=6 (DO6)
I21=9 (AO1) or I22=9 (AO2) or
I23=9 (AO3)
I15=8 (DO1) or I16=8 (DO2) or I17=8 (DO3) or I18=8 (DO4) or I19=8 (DO5) or
I20=8 (DO6)
I15=15 (DO1) or I16=15 (DO2) or I17=15 (DO3) or I19=15 (DO5) or
I20=15 (DO6)
I15=16 (DO1) or I16=16 (DO2) or I17=16 (DO3) or I19=16 (DO5) or
I20=16 (DO6)
I15=17 (DO1) or I16=17 (DO2) or I17=17 (DO3) or I19=17 (DO5) or
I20=17 (DO6)
I15=18 (DO1) or I16=18 (DO2) or I17=18 (DO3) or I19=18 (DO5) or
I20=18 (DO6)
I15=19 (DO1) or I16=19 (DO2) or I17=19 (DO3) or I19=19 (DO5) or
I20=19 (DO6)
I15=20 (DO1) or I16=20 (DO2) or I17=20 (DO3) or I19=20 (DO5) or
I20=20 (DO6)
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 25/128
12. Heating and cooling battery logic
The operating logic of the heating and cooling batteries depends on the following parameters: – I01: type of regulation chosen, variable ADR_MOD_TYPEREG (11069) – I03: type of heating battery (stage 1), variable ADR_MOD_TYPHEATINGCOIL (11071) – I04: type of cooling battery, variable ADR_MOD_TYPCOOLINGCOIL (11072)
· 2-pipe HEATING regulation (I01=0)
The “HEAT” icon is lit to indicate the heating function.
Modulating regulation:
·
PI-type regulation operates as follows for modulating regulation:
OUT I26
100%
Treg 0
WHS
Treg: regulation sensor WHS: calculated heating setpoint OUT: modulated
output:
– modulating valve if I03=2 and I21=2 (AO1) or I22=2 (AO2) or I23=2 (AO3) –
modulating electrical resistance if I03=1 and I21=8 (AO1) or I22=8 (AO2) or
I23=8 (AO3) – modulating mixed-use valve if I03=2 and I04=1 and I21=4 (AO1) or
I22=4 (AO2) or I23=4 (AO3) I27: proportional heating band
If the operating temperature drops below the WHS, the valve begins to open, or
the modulating electrical resistance begins to be modulated. The icon lights
up, if a valve is being controlled; the icon lights up for the modulating
resistance. The valve or modulating resistance can be regulated with PI
action, if the integral heating time I28 does not equal 0, or with
proportional action only, if I28=0. The (or ) icon turns off, if the
modulating valve closes or the electrical resistance is interrupted (no longer
powered).
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
On/off regulation:
·
On/off-type regulation operates as follows:
OUT I30
ON
Treg 0FF
WHS
Treg: regulation sensor WHS=calculated heating setpoint OUT: on/off output:
– on/off valve if I03=4 and I15=4 (DO1) or I16=4 (DO2) or I17=4 (DO3) or I18=4
(DO4) or I19=4 (DO5) or I20=4 (DO6) – on/off electrical resistance, if I03=3
and I15=7 (DO1) or I16=7 (DO2) or I17=7 (DO3) or I18=7 (DO4) or I19=7 (DO5) or
I20=7 (DO6) – mixed-use valve on/off if I03=4, I04=2, I15=6 (DO1) or I16=6
(DO2) or I17=6 (DO3) or I18=6 (DO4) or I19=6 (DO5) or I20=6 (DO6) I31:
hysteresis for on/off heating output
26/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
If Treg < (WHS – I31) the valve (or electrical resistance) is activated. The
(or ) icon lights up.
If Treg >= WHS, the valve (or electrical resistance) is deactivated. The (or )
icon turns off. Note: the icons indicated are present on an optional THS2
connected to the THS2-0MM.
· 2-pipe COOLING regulation (I01=0) without mid-season changeover (M13=0)
The “COOL” icon lights up to indicate the cooling function.
Modulating regulation:
·
PI-type regulation operates as follows for modulating regulation:
OUT I28
100%
Treg 0
WCS Treg: regulation sensor WCS: calculated cooling setpoint OUT: modulated
output:
– modulating valve if I04=1 and I21=3 (AO1) or I22=3 (AO2) or I23=3 (AO3) –
modulating mixed-use valve if I03=2 and I04=1 and I21=4 (AO1) or I22=4 (AO2)
or I23=4 (AO3) I29: proportional cooling band
If the operating temperature rises above the WCS, the modulating valve begins
to open. The icon lights up. The valve can be regulated with PI action, if the
cooling integral time I30 does not equal 0, or with proportional action only,
if I30=0. The icon turns off, if the valve closes.
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
On/off regulation:
·
On/off-type regulation operates as follows:
OUT I31
ON
0FF WCS
Treg
Treg: regulation sensor
WCS: calculated cooling setpoint OUT: on/off output:
– on/off valve if I04=2 and I15=5 (DO1) or I16=5 (DO2) or I17=5 (DO3) or I18=5
(DO4) or I19=5 (DO5) or I20=5 (DO6) – mixed-use valve on/off if I03=4, I04=2,
I15=6 (DO1) or I16=6 (DO2) or I17=6 (DO3) or I18=6 (DO4) or I19=6 (DO5) or
I20=6 (DO6) I32: hysteresis for on/off cooling output
If Treg > (WCS + I32), the valve is activated. The icon lights up. If Treg <= WCS , the valve is deactivated, and the icon turns off.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 27/128
· 2-pipe COOLING regulation (I01=0) with mid-season changeover (M13=1)
The “COOL” icon lights up to indicate the cooling function. Mid-season
operation allows heating via an electrical resistance that can be modulating
or on/off in event of a sudden drop in temperature during the summer.
Mid-season operation with modulating electrical resistance:
OUT
100%
0% I26
WCS C11
Treg
Treg: regulation sensor WCS: calculated cooling setpoint C11: heating insertion differential during summer I27: proportional heating band OUT: supplemental modulating electrical resistance if I05=2 and I21=9 (AO1) or I22=9 (AO2) or I23=9 (AO3)
If Treg < WCS – C11, the supplemental modulating electrical resistance begins to be activated, and the icon lights up and remains on until the temperature rises above this threshold. The supplemental modulating resistance can be regulated with PI action, if the integral heating time I28 does not equal 0, or with proportional action only, if I28=0.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
Mid-season operation with on/off electrical resistance:
OUT I30
100%
Treg 0%
WCS C11
Treg: regulation sensor WCS: calculated cooling setpoint C11: heating
insertion differential during summer I31: hysteresis for on/off heating output
OUT: supplemental on/off electrical resistance, if I05=1 and I15=8 (DO1) or
I16=8 (DO2) or I17=8 (DO3) or I18=8 (DO4) or I19=8 (DO5) or I20=8 (DO6)
If Tref < (WCS – C11 – I31), the supplemental electrical resistance is
activated. The icon lights up. If Treg >= (WCS – C11), the supplemental
electrical resistance is deactivated, and the icon turns off.
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
28/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
· 4-pipe regulation (I01=1)
In 4-pipe mode, the operating season is automatically selected according to
the regulation temperature, the 4-pipe room setpoint C03 and the neutral zone
C10. Depending on the regulation selected, two setpoints are calculated:
– WHS: heating setpoint=C03 – (C10/2) – WCS: cooling setpoint=C03 + (C10/2)
If the temperature rises above the WCS, the operating season is considered to
be cooling, and the “COOL” icon lights up. If the temperature drops below the
WHS, the operating season is considered to be heating, and the “HEAT” icon
lights up.
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
C10
HEATING
COOLING
Treg
WHS
WCS
Treg: regulation sensor WHS: calculated heating setpoint WCS: calculated cooling setpoint C10: neutral zone
Note: when the unit is switched on, if the Treg temperature is in the neutral zone, the season is considered heating. The mid-season activation parameter M13 has no influence on 4-pipe regulation and is not taken into account.
Modulating heating and cooling regulation:
·
PI-type regulation operates as follows for modulating regulation:
OUTH
OUTC
100% C10
Treg
0
I26
WHS WCS I28
Treg: regulation sensor WHS: calculated heating setpoint WCS: calculated
cooling setpoint C10: neutral zone I27: proportional heating band I29:
proportional cooling band OUTH: heating modulating output:
– modulating valve if I03=2 and I21=2 (AO1) or I22=2 (AO2) or I23=2 (AO3) –
modulating electrical resistance if I03=1 and I21=8 (AO1) or I22=8 (AO2) or
I23=8 (AO3) OUTC: cooling modulating output: – modulating valve if I04=1 and
I21=3 (AO1) or I22=3 (AO2) or I23=3 (AO3)
If the operating temperature drops below the WHS, the heating valve begins to
open, or the modulating electrical resistance begins to be modulated. The icon
lights up, if a valve is being controlled; the icon lights up for the
modulating resistance. The valve or modulating resistance can be regulated
with PI action, if the integral heating time I28 does not equal 0, or with
proportional action only, if I28=0. The (or ) icon turns off, if the
modulating heating valve closes or the electrical resistance is turned off (no
longer powered) when Treg >= WHS.
If the operating temperature rises above the WCS, the modulating cooling valve begins to open. The icon lights up. AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 29/128
The valve can be regulated with PI action, if the integral time I30 does not equal 0, or with proportional action only, if I30=0. The icon turns off, if the valve closes when Treg <= WCS.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
Modulating heating regulation and on/off cooling:
·
PI-type regulation operates as follows for modulating regulation:
OUTH 100%
OUTC
C10
ON
0FF Treg
0
I26
WHS WCS I31
Treg: regulation sensor WHS: calculated heating setpoint WCS: calculated
cooling setpoint C10: neutral zone I32: hysteresis for on/off cooling output
I27: proportional heating band OUTH: heating modulating output:
– modulating valve if I03=2 and I21=2 (AO1) or I22=2 (AO2) or I23=2 (AO3) –
modulating electrical resistance if I03=1 and I21=8 (AO1) or I22=8 (AO2) or
I23=8 (AO3) OUTC: on/off cooling output: – on/off valve if I04=2 and I15=5
(DO1) or I16=5 (DO2) or I17=5 (DO3) or I18=5 (DO4) or I19=5 (DO5) or I20=5
(DO6)
If the operating temperature drops below the WHS, the heating valve begins to
open, or the modulating electrical resistance
begins to be modulated. The icon lights up, if a valve is being controlled;
the icon lights up for the modulating electrical resistance. The valve or
modulating resistance can be regulated with PI action, if the integral heating
time I28 does not equal 0, or with proportional action only, if I28=0. The (or
) icon turns off, if the modulating heating valve closes or the electrical
resistance is turned off (no longer powered) when Treg >= WHS.
If Treg > (WCS + I32), the cooling valve is activated. The icon lights up. If Treg <= WCS the cooling valve is deactivated, and the icon turns off.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
On/off heating and cooling regulation:
·
PI-type regulation operates as follows for modulating regulation:
OUTH ON
OUTC
I30
C10
I31
Treg
0FF
WHS
WCS
Treg: regulation sensor WHS: calculated heating setpoint WCS: calculated
cooling setpoint C10: neutral zone I31: hysteresis for on/off heating output
I32: hysteresis for on/off cooling output OUTH: on/off heating output:
– on/off valve if I03=4 and I15=4 (DO1) or I16=4 (DO2) or I17=4 (DO3) or I18=4
(DO4) or I19=4 (DO5) or
I20=4 (DO6)
30/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
– on/off electrical resistance, if I03=3 and I15=7 (DO1) or I16=7 (DO2) or I17=7 (DO3) or I18=7 (DO4) or I19=7 (DO5) or I20=7 (DO6) OUTC: on/off cooling output: – on/off valve if I04=2 and I15=5 (DO1) or I16=5 (DO2) or I17=5 (DO3) or I18=5 (DO4) or I19=5 (DO5) or I20=5 (DO6)
If Treg < (WHS – I31), the heating valve (or electrical resistance) is activated. The (or ) icon lights up. If Treg >= WHS, the heating valve (or electrical resistance) is deactivated. The (or ) icon turns off.
If Treg > (WCS + I32), the cooling valve is activated. The icon lights up. If Treg <= WCS the cooling valve is deactivated, and the icon turns off.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
On/off heating and modulating cooling regulation:
·
PI-type regulation operates as follows for modulating regulation:
OUTH
OUTC
I30
C10
I28
100% ON
0FF
0 Treg
WHS
WCS
Treg: regulation sensor WHS: calculated heating setpoint WCS: calculated
cooling setpoint C10: neutral zone I31: hysteresis for on/off heating output
I29: proportional cooling band OUTH: on/off heating output:
– on/off valve if I03=4 and I15=4 (DO1) or I16=4 (DO2) or I17=4 (DO3) or I18=4
(DO4) or I19=4 (DO5) or I20=4 (DO6) – on/off electrical resistance, if I03=3
and I15=7 (DO1) or I16=7 (DO2) or I17=7 (DO3) or I18=7 (DO4) or I19=7 (DO5) or
I20=7 (DO6) OUTC: modulating output: – modulating valve if I04=1 and I21=3
(AO1) or I22=3 (AO2) or I23=3 (AO3)
If Treg < (WHS – I31), the heating valve (or electrical resistance) is activated. The (or ) icon lights up. If Treg >= WHS, the heating valve (or electrical resistance) is deactivated. The (or ) icon turns off.
If the operating temperature rises above the WCS, the modulating cooling valve
begins to open. The icon lights up. The cooling valve can be regulated with PI
action, if the integral time I30 does not equal 0, or with proportional action
only, if I30=0.
The icon turns off, if the cooling valve closes.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 31/128
13. 3-point valve
A slave is capable of controlling 3-point valves for 2-pipe or 4-pipe systems.
· 3-point, 2-pipe HEATING regulation (I01=0)
The “HEAT” icon is lit to indicate the heating function.
Define the following settings to use a 3-point heating valve: – Select digital
output for controlling the opening of the 3-point on/off heating valve I03=4
and I15=15 (DO1) or I16=15 (DO2) or I17=15 (DO3) or I19=15 (DO5) or I20=15
(DO6), – Select digital output for controlling the closure of the 3-point
on/off heating valve I15=16 (DO1) or I16=16 (DO2) or I17=16 (DO3) or I19=16
(DO5) or I20=16 (DO6), – Set the valve stroke time with parameter I52.
The PI-type regulation in heating mode takes place as follows for 3-point
on/off regulation:
OUT I26
100%
0
Treg: regulation sensor WHS: calculated heating setpoint OUT: 3-point on/off
heating output I27: proportional heating band
WHS
Treg
If the operating temperature drops below the WHS, the valve begins to open. The icon lights up. The on/off 3-point valve can be regulated with PI action, if the integral heating time I28 does not equal 0, or with proportional action only, if I28=0. The icon turns off, if the 3-point valve closes.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
When the controller is switched on, the valve runs through a reset cycle (valve closure) for 120% of the stroke time of the I52 valve before executing the regulation and every 24 hours. The valve runs through a reset cycle every day at 01:00 a.m. before resuming regulation if a THS2 is connected to the THS20MM.
· 3-point, 2-pipe COOLING regulation (I01=0)
The “COOL” icon lights up to indicate the cooling function.
Define the following settings to use a 3-point cooling valve: – Select digital
output for controlling the opening of the 3-point on/off cooling valve I04=2
and I15=17 (DO1) or I16=17 (DO2) or I17=17 (DO3) or I19=17 (DO5) or I20=17
(DO6), – Select digital output for controlling the closure of the 3-point
on/off cooling valve I15=18 (DO1) or I16=18 (DO2) or I17=18 (DO3) or I19=18
(DO5) or I20=18 (DO6),
– Set the valve stroke time with parameter I52.
32/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
OUT I28
100%
Treg 0
WCS Treg: regulation sensor WCS: calculated cooling setpoint OUT: 3-point
on/off cooling output I29: proportional cooling band
If the operating temperature rises above the WCS, the 3-point valve begins to
open. The icon lights up. The valve can be regulated with PI action, if the
integral time I30 does not equal 0, or with proportional action only, if
I30=0. The icon turns off, if the 3-point valve closes.
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
When the controller is switched on, the valve runs through a reset cycle
(valve closure) for 120% of the stroke time of the I52 valve before executing
the regulation and every 24 hours. The valve runs through a reset cycle every
day at 01:00 a.m. before resuming regulation if a THS2 is connected to the
THS20MM.
· 3-point, 4-pipe regulation (I01=1)
Define the following settings to specify a 3-point heating valve: – Select
digital output for controlling the opening of the 3-point on/off heating valve
I03=4 and I15=15 (DO1) or I16=15 (DO2) or I17=15 (DO3) or I19=15 (DO5) or
I20=15 (DO6), – Select digital output for controlling the closure of the
3-point on/off heating valve I15=16 (DO1) or I16=16 (DO2) or I17=16 (DO3) or
I19=16 (DO5) or I20=16 (DO6). Define the following settings to specify a
3-point cooling valve: – Select digital output for controlling the opening of
the 3-point on/off cooling valve I04=2 and I15=17 (DO1) or I16=17 (DO2) or
I17=17 (DO3) or I19=17 (DO5) or I20=17 (DO6), – Select digital output for
controlling the closure of the 3-point on/off cooling valve I15=18 (DO1) or
I16=18 (DO2) or I17=18 (DO3) or I19=18 (DO5) or I20=18 (DO6), – Set the valve
stroke time with parameter I52.
PI-type regulation operates as follows for 3-point regulation:
OUTH
OUTC
100% C10
Treg
0
I26
WHS WCS I28
Treg: regulation sensor WHS: calculated heating setpoint WCS: calculated cooling setpoint C10: neutral zone I27: proportional heating band I29: proportional cooling band OUTH: 3-point on/off heating output OUTC: 3-point on-off cooling output
If the operating temperature drops below the WHS, the 3-point heating valve begins to open. The icon lights up. The 3-point valve can be regulated with PI action, if the integral heating time I28 does not equal 0, or with proportional action
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 33/128
only, if I28=0. The icon turns off, if the 3-point heating valve closes when
Treg >= WHS. If the operating temperature rises above the WCS, the 3-point
cooling valve begins to open. The icon lights up. The 3-point valve can be
regulated with PI action, if the integral heating time I30 does not equal 0,
or with proportional action only, if I30=0. The icon turns off, if the 3-point
valve closes when Treg <= WCS. Note: the icons indicated are present on an
optional THS2 connected to the THS2-0MM. When the controller is switched on,
the valves run through a reset cycle (valve closure) for 120% of the stroke
time of the I52 valve before executing the regulation and every 24 hours. The
valves run through a reset cycle every day at 01:00 a.m. before resuming
regulation if a THS2 is connected to the THS20MM.
14. Mixed-use valve
The mixed-use valve can be regulated only in 2-pipe mode (I01=0). To specify a
mixed-use modulating valve, set parameters I03=2 and I04=1 and choose the
modulating output configured as a mixed-use modulating valve I21=4 (AO1) or
I22=4 (AO2) or I23=4 (AO3). To specify an on/off mixed-use valve, set
parameters I03=4 and I04=2 and choose the digital output configured as mixed-
use on/off valve I15=6 (DO1) or I16=6 (DO2) or I17=6 (DO3) or I18=6 (DO4) or
I19=6 (DO5) or I20=6 (DO6). Regulation in 2-pipe heating mode (I01=0) is
performed according to the logic of paragraph “2-pipe HEATING regulation
(I01=0)” page 26 and in cooling mode, according to the logic of paragraph
“2-pipe COOLING regulation (I01=0) without mid-season changeover (M13=0)” page
27. To specify a 3-point mixed-use valve, set parameters I03=4 and I04=2 and –
select digital output for controlling the opening of the 3-point on/off mixed-
use valve I15=19 (DO1) or I16=19 (DO2) or I17=19 (DO3) or I19=19 (DO5) or
I20=19 (DO6), – select digital output for controlling the closure of the
3-point on/off mixed-use valve I15=20 (DO1) or I16=20 (DO2) or I17=20 (DO3) or
I19=20 (DO5) or I20=20 (DO6). – set the valve stroke time with parameter I52.
Regulation in 2-pipe heating mode (I01=0) is performed according to the logic
of paragraph “3-point, 2-pipe HEATING regulation (I01=0)” page 32 and in
cooling mode, according to the logic of paragraph “3-point, 2-pipe COOLING
regulation (I01=0)” page 32.
34/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
15. Supplemental battery logics
The supplemental battery is used as an additional heating stage and can be a
modulating resistance (I05=2), or an on/off resistance (I05=1). The
supplemental battery uses the regulation sensor and the current working
setpoint for regulation. Regulation is proportional if the battery is
modulating, and on/off in other cases. Parameter I27 represents the
proportional band and parameter I31 the hysteresis of the supplemental heating
stage.
· Supplemental modulating battery function:
– Integrative stage with electrical resistance: I05=2 and I21=9 (AO1) or I22=9
(AO2) or I23=9 (AO3).
100%
0% I26
Treg WHS I32
Treg: regulation temperature
WHS: calculated heating setpoint I33: differential between stages I27:
proportional heating band
During regulation, the icon lights up, if the signal applied to the
supplemental modulating resistance is not equal to 0:
Tsup < WHS – I33. The icon turns off, if the signal applied to the
supplemental modulating resistance is equal to 0: Tsup >= WHS – I33. If the
main heating stage is an electrical resistance and is still activated, the
icon remains on.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
· Supplemental on/off battery function:
– Integrative stage with electrical resistance: I05=1 and I15=8 (DO1) or I16=8 (DO2) or I17=8 (DO3) or I18=8 (DO4) or I19=8 (DO5) or I20=8 (DO6).
I30 100%
Treg
0%
WHS
I32
Treg: regulation temperature WHS: calculated heating setpoint I33: differential between stages I31: hysteresis for on/off heating output
If Treg < WHS -I33 – I31 , the supplemental stage in heating mode is activated, and the icon lights up. If Treg >= WHS – I33, the supplemental stage in heating mode is deactivated. The icon turns off, but if the main heating stage is an electrical resistance and is still activated, the icon remains on.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 35/128
16. Pump
In 2-pipe systems, the pump, that deliver water to the fan coil units, can be
controlled directly by any unit by selecting a dedicated digital output I15=10
(DO1) or I16=10 (DO2) or I17=10 (DO3) or I18=10 (DO4) or I19=10 (DO5) or
I20=10 (DO6). If there is a regulation request for any valve, the pump will be
activated. If, on the other hand, there is no valve regulation request, the
pump will be deactivated.
17. CO2-based damper regulation
It is possible to regulate a modulating or on/off damper according to the CO2
level in order to implement a renewal of the ambient air. The CO2 level is
controlled by a remote CO2 transmitter with 0..10 V output connected on the
internal network, or it can be a value provided by the supervisor (virtual
transmitter).
· Use of modulating damper:
To use a modulating damper that is regulated according to the CO2 level
detected by an air quality transmitter, set up as follows: – connect a remote
transmitter TCO2A(-D)-M to the internal network with address=20, baud
rate=9600 bit/s, even parity, – select the dedicated modulating output for
this mode I21=5 (AO1) or I22=5 (AO2) or I23=5 (AO3), – CO2 setpoint C17, – CO2
proportional band C18. – transmitter present M21=1
To use a modulating damper that is regulated according to the CO2 level
provided by the supervisor, input the following settings: – write the value
22222 to indicate presence of supervisor on variable
STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) – write the value of CO2 in
variable ADR_MOD_FORCE_TRASM_CO2 (11047) between 0 and 2000 (a value of -200
excludes the presence of virtual transmitter). – select the dedicated
modulating output for this mode I21=5 (AO1) or I22=5 (AO2) or I23=5 (AO3), –
CO2 setpoint C17, – CO2 proportional band C18.
The air renewal signal is calculated according to the curve below:
Val_damper C18
C19
CO2 0
C17
CO2: level of CO2 detected by the remote CO2 air quality transmitter or value
forced by the supervisor Val_damper: theoretical percentage of air renewal
C17: CO2 setpoint C18: proportional band or CO2 hysteresis C19: minimum
opening of modulating damper
When the signal applied to the CO2 > C17 , the damper is regulated proportionally according to the proportional band C18 and
the
icon lights up.
If the CO2 <= C17, the damper takes the position of the minimum opening, and the
icon turns off.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
· Use of on/off damper:
To use an on/off damper that is regulated according to the CO2 level detected
by an air quality transmitter, input the following 36/128 AB Industrietechnik
srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39
0472/830626 info@industrietechnik.it www.industrietechnik.it
settings: – connect a remote transmitter TCO2A(-D)-M to the internal network
with address=20, baud rate=9600 bit/s, even parity, – select the dedicated
on/off output for this function I15=11 (DO1) or I16=11 (DO2) or I17=11 (DO3)
or I18=11 (DO4) or I19=11 (DO5) or I20=11 (DO6), – CO2 setpoint C17, – CO2
proportional band C18. – transmitter present M21 =1 To use an on/off damper
adjusted according to the CO2 level provided by the supervisor, input the
following settings: – write the value 22222 to indicate presence of supervisor
on variable STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) – write the value of
CO2 in variable ADR_MOD_FORCE_TRASM_CO2 (11047) between 0 and 2000 (a value of
-200 excludes the presence of virtual transmitter) – select the dedicated
on/off output for this function I15=11 (DO1) or I16=11 (DO2) or I17=11 (DO3)
or I18=11 (DO4) or I19=11 (DO5) or I20=11 (DO6), – CO2 setpoint C17, – CO2
proportional band C18. The air renewal signal is calculated according to the
curve below:
Val_damper C18
C19 CO2
0 C17
CO2: level of CO2 detected by the remote CO2 air quality transmitter or value
forced by the supervisor Val_damper: theoretical percentage of air renewal
C17: CO2 setpoint C18: proportional band or CO2 hysteresis If the CO2 signal >
C17, the damper opens, and the icon lights up . If the CO2 signal <= C17 – C18
, the damper closes, and the icons turns off . Note: the icons indicated are
present on an optional THS2 connected to the THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy
Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
37/128
18. Dehumidifier
Dehumidification can be achieved with – an on/off dehumidifier – a modulating
dehumidifier
The humidity can be controlled with the humidity sensor inside the optional
THS2 connected to a THS2-0MM controller, by a remote humidity transmitter with
a 0..10 V output connected to the internal network or with a value supplied by
the supervisor (virtual transmitter).
· Use of a modulating dehumidifier:
To use a modulating dehumidifier that is regulated according to the humidity
detected by the internal humidity sensor of THS2 connected to a THS2-0MM
controller, define the following settings: – select the dedicated modulating
output for this mode I21=6 (AO1) or I22=6 (AO2) or I23=6 (AO3), – humidity
setpoint C20, – humidity proportional band C21. – set M22=0 on THS2.
To use a modulating dehumidifier that is regulated according to the humidity
detected by a remote transmitter, define the following settings: – connect a
remote transmitter TUA(-D)-M to the internal network with address=20, baud
rate=9600 bit/s, even parity, – select the dedicated modulating output for
this mode I21=7 (AO1) or I22=7 (AO2) or I23=7 (AO3), – humidity setpoint C20,
– humidity proportional band C21, – transmitter present M21 =1.
To use a modulating dehumidifier that is regulated according to the humidity
provided by the supervisor, input the following settings: – write the value
22222 to indicate presence of supervisor on variable
STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) – write the value of humidity in
variable ADR_MOD_FORCE_TRASM_HUM (11046) – select the dedicated modulating
output for this mode I21=7 (AO1) or I22=7 (AO2) or I23=7 (AO3), – humidity
setpoint C20, – humidity proportional band C21.
The dehumidify signal is calculated according to the curve below:
% dehum C21
100
0
H
C20
H: humidity level detected by the internal or remote humidity sensor or provided by the supervisor % dehum: theoretical percentage dehumidification C20: humidity setpoint C21: proportional band or humidity hysteresis
Regulation is implemented at humidity setpoint C20 and is proportional. When the signal applied to the dehumidifier is not equal to 0, the icon lights up.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
· Use of an on/off dehumidifier:
To use an on/off dehumidifier that is regulated according to the humidity
detected by the internal humidity sensor of THS2 connected to a THS2-0MM
controller, input the following settings: – select the dedicated on/off output
for this mode I15=12 (DO1) or I16=12 (DO2) or I17=12 (DO3) or I18=12 (DO4) or
I19=12 (DO5) or I20=12 (DO6), – humidity setpoint C20,
38/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
– humidity proportional band C21. – set M22=0 on THS2.
To use a on/off dehumidifier that is regulated according to the humidity
detected by a remote transmitter, input the following settings: – connect a
remote transmitter TUA(-D)-M to the internal network with address=20, baud
rate=9600 bit/s, even parity, – select the dedicated on/off output for this
mode I15=13 (DO1) or I16=13 (DO2) or I17=13 (DO3) or I18=13 (DO4) or I19=13
(DO5) or I20=13 (DO6), – humidity setpoint C20, – humidity proportional band
C21, – transmitter present M21 =1.
To use an on/off dehumidifier that is regulated according to the humidity
provided by the supervisor, input the following settings: – write the value
22222 to indicate presence of supervisor on variable
STATUS_PRESENCE_SUPERVISOR_DISPLAY (11033) – write the value of humidity in
variable ADR_MOD_FORCE_TRASM_HUM (11046) – select the dedicated on/off output
for this mode I15=13 (DO1) or I16=13 (DO2) or I17=13 (DO3) or I18=13 (DO4) or
I19=13 (DO5) or I20=13 (DO6), – humidity setpoint C20, – humidity proportional
band C21.
The dehumidify signal is calculated according to the curve below:
% dehum C21
100
0
H
C20
H: humidity level detected by the internal or remote humidity sensor or provided by the supervisor % dehum: theoretical percentage dehumidification C20: humidity setpoint C21: proportional band or humidity hysteresis
Regulation is implemented at the humidity setpoint C20 and is on/off. If the detected humidity > C20 + C21, the dehumidifier is activated, and the If the detected humidity <= C20, the dehumidifier is deactivated, and the
icon lights up. icon turns off.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 39/128
19. Fan coil unit with EC motor
The slave units are able to control EC motor via 0..10 V analogue output, with
or without a relay for the EC motor. If there is an EC motor relay, the relay
output is activated first when the motor is started, while the analogue output
remains at 0 V. After 1 second, the analogue output is activated. To control
an EC motor, input the following settings: -I06=2 (modulating fan coil unit),
– select the analogue output to control the motor I21=1 (AO1) or I22=1 (AO2)
or I23=1 (AO3), – for EC motor with auxiliary relay, select the digital output
to control the EC motor relay I15=9 (DO1) or I16=9 (DO2) or I17=9 (DO3) or
I18=9 (DO4) or I19=9 (DO5) or I20=9 (DO6), Set the EC motor parameters as
follows: – set the voltage corresponding to the minimum speed of the EC motor
using parameter I37. – set the voltage corresponding to the maximum speed of
the EC motor using parameter I38. – set parameters I41, I42 and I43 to specify
speeds 1, 2 and 3, respectively. Example: If I37=1V, I38=8V and I41=10%, speed
1 is 1.7V [I41 x (I38 – I37) + I37] Automatic speed regulation occurs linearly
between speeds 1 and 3, while manual speed regulation is at the fixed speed
selected manually (see “33. Setting parameters using quick access on THS2”
page 54). To match speed 1 to the minimum EC motor speed, set I41 to 0. To
match speed 3 to the maximum EC motor speed, set I43 to 100. To have speed 2
in the centre between speeds 1 and 3 of the EC motor, set I42 to 50.
· Automatic speed control logic for EC motor with on/off outputs in heating
mode
Output I31
ON
OFF Fan
ECM speed 3
WHS
Temp.
ECM speed 1
Temp.
I40
H1 0%
Temp: operating temperature WHS: calculated heating setpoint H1: fan starting
point, H1=I31 I31: heating hysteresis I40: EC fan coil unit proportional band
The activation and deactivation of the fan coil unit at speed 1 corresponds to
the activation and deactivation of the heating stage.
If Temp < WHS – I31, the fan coil unit activates at speed 1 and, as the
temperature decreases, the speed increases linearly (if Temp rises, the fan
stops, if Temp >= WHS). If Temp < WHS – I31 – I40, the fan coil unit reaches
the maximum speed 3. If Temp >= WHS, heating stage is off. The fan coil unit
stops after the minimum switch-off delay I45 has elapsed. If I45=0, a minimum
delay of 30 s is applied.
When the fan coil unit is activated at speed 1, the icon lights up. When the
speed exceeds the threshold corresponding to the percentage of valve opening
defined by parameter I42 (EC motor speed 2), the icons light up.
40/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
When the speed exceeds the threshold corresponding to the percentage of valve
opening defined by parameter I43 (EC motor speed 3), the icons light up. Note:
If there is a supplemental modulating heating stage (stage 2) with I33 < H1,
the starting point of the fan at speed 1 becomes WHS – I33.
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
· Automatic speed control logic for EC motor with on/off outputs in cooling
mode
Output I32
ON
OFF Fan
ECM speed 3
WCS
Temp.
ECM speed 1
H1
I40
Temp.
Temp: operating temperature WCS: calculated cooling setpoint H1: fan starting point, H1=I32 I32: cooling hysteresis I40: EC fan coil unit proportional band
The activation and deactivation of the fan coil unit at speed 1 correspond to the activation and deactivation of the cooling stage.
If Temp > WCS + I32 the fan coil unit activates at speed 1 and, as the temperature increases, the speed increases linearly, (if Temp drops, the fan stops, if Temp <= WCS) If Temp > WCS + I32 + I40 , the fan coil unit reaches the maximum speed 3. If Temp <= WCS, cooling stage is off. The fan coil unit stops after the minimum switch-off delay I45 has elapsed.
When the fan coil unit is activated at speed 1, the icon lights up. When the speed exceeds the threshold corresponding to the percentage of valve opening defined by parameter I42 (EC motor speed 2), the icons light up. When the speed exceeds the threshold corresponding to the percentage of valve opening defined by parameter I43 (EC motor speed 3), the icons light up.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 41/128
· Automatic speed control logic for EC motor with 0..10 V or 3-point outputs
in heating mode
Output I27
100
0 Fan ECM speed 3
Temp. WHS
ECM speed 1
% opening valve
100%
I39 0%
Temp: operating temperature WHS: calculated heating setpoint I27: proportional heating band I39: starting point of EC fan coil unit (%), if the heating outlet is a valve. If the heating output is an electrical resistance, the starting point for the EC fan coil unit becomes the WHS
Set parameter I39 to specify when to start the motor with respect to the opening percentage of the heating valve. This allows the fan coil unit to be started when the water is already circulating in the fan coil unit battery and has already heated the heating battery.
If the valve opens by the percentage defined by parameter I39, the fan coil unit is activated at speed 1. If the valve continues to open, the speed of the fan coil unit increases to speed 3, when the heating valve is fully open (Temp < WHS – I27). If Temp rises, the valve starts to close, and the fan stops when Temp >=WHS after the minimum switch-off delay I45 has elapsed. If I45=0, a minimum delay of 30 s is applied.
Example: If I39=5%, the motor starts when the modulating output of the valve exceeds 0.5V [I39x10 V]. The fan coil unit is stopped, when the valve closes.
When the fan coil unit is activated at speed 1, the icon lights up. When the speed exceeds the threshold corresponding to the percentage of valve opening defined by parameter I42 (EC motor speed 2), the icons light up. When the speed exceeds the threshold corresponding to the percentage of valve opening defined by parameter I43 (EC motor speed 3), the icons light up.
Notes: – The icons indicated are present on an optional THS2 if connected to the THS2-0MM. – If an electrical resistance is being controlled instead of the valve, parameter I39 is no longer considered. If the signal applied to the modulating electrical resistance is not equal to 0, the fan coil unit is started at speed 1 and increases as the signal applied to the electrical resistance increases. If the electrical resistance signal goes to 0, the fan coil unit stops after the minimum switch-off delay I45 has elapsed. If I45=0, a minimum delay of 30 s is applied. If there is a supplemental modulating heating stage (stage 2), and if WHS – I33 corresponds to a higher opening than the minimum valve opening I39, the starting point of the fan at speed 1 becomes WHS – I33.
42/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
· Automatic speed control logic for EC motor with 0..10 V or 3-point outputs
in cooling mode
Output I29
100
0 Fan ECM speed 3
WCS
Temp.
ECM speed 1
0% I39 Temp: operating temperature WCS: calculated cooling setpoint I29:
proportional cooling band I39: starting point of EC fan coil unit (%)
% opening valve. 100%
Set parameter I39 to specify when to start the motor relative to the opening percentage of the cooling valve. This allows the fan coil unit to be started when water is already circulating in the fan coil unit and has already cooled the cooling battery.
If the valve opens by the percentage defined by parameter I39, the fan coil unit is activated at speed 1. If the valve continues to open, the speed of the fan coil unit increases to speed 3, when the cooling valve is fully open (Temp
WCS + I29). If Temp decreases, the valve starts to close, and the fan stops when Temp <= WCS after the minimum switch-off delay I45 has elapsed.
Example: If I39=5%, the motor starts when the modulating output of the valve exceeds 0.5V [I39x10 V]. The fan coil unit is stopped, when the valve closes. Once the fan coil unit has started, if the modulating output of the valve continues to increase, the fan coil unit speed increases to speed 3 when the cooling valve is fully open.
When the fan coil unit is activated at speed 1, the icon lights up. When the speed exceeds the threshold corresponding to the percentage of valve opening defined by parameter I42 (EC motor speed 2), the icons light up. When the speed exceeds the threshold corresponding to the percentage of valve opening defined by parameter I43 (EC motor speed 3), the icons light up.
Note: the icons indicated are present on an optional THS2 connected to the THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 43/128
20. Fan coil unit with 3-speed on/off motor
The slave units can handle 3-speed on-off type fan coil units. To control a
3-speed motor, input the following settings: -I06=1 (3-speed, on/off fan coil
unit), – select digital output to control speed 1 I15=1 (DO1) or I16=1 (DO2)
or I17=1 (DO3) or I18=1 (DO4) or I19=1 (DO5) or I20=1 (DO6), – select digital
output to control speed 2 I15=2 (DO1) or I16=2 (DO2) or I17=2 (DO3) or I18=2
(DO4) or I19=2 (DO5) or I20=2 (DO6), – select digital output to control speed
3 I15=3 (DO1) or I16=3 (DO2) or I17=3 (DO3) or I18=3 (DO4) or I19=3 (DO5) or
I20=3 (DO6). Automatic speed regulation takes place between speeds 1, 2 and 3,
while manual speed regulation is at the fixed speed selected manually (see
“33. Setting parameters using quick access on THS2” page 54).
· Automatic speed control logic for 3-speed on/off motors with 0..10 V or
3-point outputs in heating mode
Output I27
100
Temp. 0
WHS
Fan speed 3
H
H
speed 2
speed 1
100% I43
% opening
0% I39
valve
I42
Temp: operating temperature WHS: calculated heating setpoint I27: proportional heating band I39: starting point of fan coil unit corresponding to the opening I39(%) of the valve, if the heating output at stage 1 is a valve. If the heating output is an electrical resistance, the starting point for the fan coil unit is the WHS. I42: activation of speed 2 at I42(%) valve opening I43: activation of speed 3 at I43(%) valve opening H: hysteresis corresponding to 20% of full valve opening
– Set parameter I39 to specify the valve opening (%) at which speed 1 of the
fan coil unit begins. This allows the fan coil unit to be started when the
water is already circulating in the fan coil unit battery and has already
heated the heating battery.
– Set parameters I42 and I43 to specify the valve opening (%) at which speeds
2 and 3 of the fan coil unit begin. The hysteresis of speeds 2 and 3 is fixed
and corresponds to 20% of the full valve opening. The hysteresis of speed 1
corresponds to parameter I39.
Example: If I39=10%, I42=65%, I43=100% Speed 1 is activated at 10% of full
valve opening and is deactivated when the valve closes. Speed 2 is activated
at 65% and deactivated at 45% of full valve opening. Speed 3 is activated at
100% and deactivated at 80% of full valve opening.
44/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
When speed 1 is on, the icon is lit if display terminal THS2 is connected When
speed 3 is on, the icons are lit if display terminal THS2 is connected When
speed 3 is on, the icons are lit if display terminal THS2 is connected
Notes: – Verify that the parameters are properly defined I39 < I42 and I42 <
I43. – The icons indicated are present on an optional THS2 if connected to the
THS2-0MM. – If an electrical resistance is being controlled instead of the
valve, parameter I39 is no longer considered. If the signal applied to the
modulating electrical resistance is not equal to 0, the fan coil unit is
started at speed 1, and the speed increases as the signal applied to the
electrical resistance increases according to the previously defined activation
points. If the electrical resistance signal goes to 0, the fan coil unit stops
after the minimum switch-off delay I45 has elapsed. If I45=0, a minimum delay
of 30 s is applied. If there is a supplemental modulating heating stage (stage
2), and if WHS – I33 corresponds to a higher opening than the minimum valve
opening I39, the starting point of the fan at speed 1 becomes WHS – I33.
· Automatic speed control logic for 3-speed on/off motors with 0..10 V or
3-point cooling outputs
Output valve I29
100
0 WCS
Fan speed 3
H
H
Temp.
speed 2
speed 1
0% I39 I42
100% I43
Temp: operating temperature WCS: calculated cooling setpoint I29: proportional cooling band I39: fan coil unit starting point at valve opening I39(%) I42: activation of speed 2 at I42(%) valve opening I43: activation of speed 3 at I43(%) valve opening H: hysteresis corresponding to 20% of full valve opening
% opening valve
– Set parameter I39 to specify the valve opening (%) at which speed 1 of the
fan coil unit begins. This allows the fan coil unit to be started when the
water is already circulating in the fan coil unit battery and has already
cooled the cooling battery.
– Set parameters I42 and I43 to specify the valve opening (%) at which speeds
2 and 3 of the fan coil unit begin. The hysteresis of speeds 2 and 3 is fixed
and corresponds to 20% of the full valve opening. The hysteresis of speed 1
corresponds to parameter I39.
Example: If I39=10%, I42=65%, I43=100% Speed 1 is activated at 10% of full valve opening and is deactivated when the valve closes. Speed 2 is activated at 65% and deactivated at 45% of full valve opening. Speed 3 is activated at 100% and deactivated at 80% of full valve opening. Note: verify that the parameters are properly defined I39 < I42 and I42 < I43
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 45/128
When speed 1 is on, the icon is lit if display terminal THS2 is connected When
speed 2 is on, the icons are lit if display terminal THS2 is connected When
speed 3 is on, the icons are lit if display terminal THS2 is connected
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
· Automatic speed control logic for 3-speed on/off motors with on/off outputs
in heating mode
Output I31
ON
OFF
WHS
Temp.
Fan speed 3
I34
I34
speed 2
speed 1
I36
I35
H1
Temp.
Temp: operating temperature WHS: calculated heating setpoint I31: heating
hysteresis H1: fan coil unit starting point at speed 1:
H1=max(I31,I34), if stage 1 heating output is a valve H1=I31, if stage 1
heating output is an electrical resistance I34: on/off speed hysteresis I35:
differential between speeds 1->2 I36: differential between speeds 2->3
– Select the common I34 hysteresis at speeds 2 and 3 (temperature difference
between switching on and off at the same speed).
If I31 <= I34 the hysteresis of speed 1 is I34.
If I31 > I34 the hysteresis of speed 1 is I31. – Set the differential between
speeds 1->2 I35. – Set the differential between speeds 2->3 I36. Speed 1
starts up if Temp < WHS – H1 and turns off if Temp >= WHS. Speed 2 starts up
if Temp < WHS – H1 – I35 and turns off is Temp >= WHS – H1 – I35 + I34.. Speed
3 starts up if Temp < WHS – H1 – I35 – I36 and turns off if Temp >= WHS – H1 –
I35 – I36 + I34.
When speed 1 is on, the icon is lit if display terminal THS2 is connected When speed 2 is on, the icons are lit if display terminal THS2 is connected When speed 3 is on, the icons are lit if display terminal THS2 is connected
Notes: – The icons indicated are present on an optional THS2 if connected to the THS2-0MM. – If there is a supplemental modulating heating stage (stage 2) with I33 < H1, the starting point of the fan at speed 1 becomes WHS – I33.
46/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
· Automatic speed control logic for 3-speed on/off motors with on/off outputs
in cooling mode
Output I32
ON
OFF
WCS
Temp.
Fan
I34
I34
speed 3
speed 2
speed 1
Temp.
I35
I36
H1
Temp: operating temperature WCS: calculated cooling setpoint I32: cooling
hysteresis H1: fan coil unit starting point at speed 1: H1=max(I32 and I34)
I34: on/off speed hysteresis I35: differential between speeds 1->2 I36:
differential between speeds 2->3
– Select the common I34 hysteresis at speeds 2 and 3 (temperature difference
between switching on and off at the same speed). If I32 <= I34 the hysteresis
of speed 1 is I34. If I32 > I34 the hysteresis of speed 1 is I32. – Set the
differential between speeds 1->2 I35. – Set the differential between speeds
2->3 I36. Speed 1 starts up if Temp > WCS + H1 and turns off if Temp <= WCS.
Speed 2 starts up if Temp > WCS + H1 + I35 and turns off if Temp <= WCS + H1 +
I35 – I34. Speed 3 starts up if Temp > WCS + H1 + I35 + I36 and turns off if
Temp <= WCS + H1 + I35 + I36 – I34.
When speed 1 is on, the icon is lit if display terminal THS2 is connected When
speed 2 is on, the icons are lit if display terminal THS2 is connected When
speed 3 is on, the icons are lit if display terminal THS2 is connected
Note: the icons indicated are present on an optional THS2 connected to the
THS2-0MM.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 47/128
21. Manual speeds and ventilation in the absence of regulation
Automatic speed or manual speeds 1, 2 or 3 can be selected for the regulation.
See “19. Fan coil unit with EC motor” page 40 or “20. Fan coil unit with
3-speed on/off motor” page 44 for how to select the type of ventilation. If
the regulation speed is manual, it remains constant at the set speed once it
has been started during the regulation phase. When the setpoint is reached,
the fan is stopped, if parameter I47=0. It is possible to maintain speed 1,
regardless of the type of speed used for regulation, or one of the manual
speeds selected, even if the regulation does not require it. Continuous
ventilation is thus maintained to allow the air to circulate. To keep speed 1
active in the absence of regulation in cooling mode, set parameter I47 to 2.
To keep speed 1 active in the absence of regulation in heating mode, set
parameter I47 to 3. To keep speed 1 active regardless of the operating season
and in the absence of regulation, set parameter I47 to 1. To keep the selected
manual speed active in the absence of regulation in cooling mode, set
parameter I47 to 5. To keep the selected manual speed active in the absence of
regulation in heating mode, set parameter I47 to 6. To keep the selected
manual speed active regardless of the operating season and in the absence of
regulation, set parameter I47 to 4. To turn the ventilation off when the
setpoint is reached, set parameter I47 to 0.
22. Fan boost
The boost function eliminates the problem of faulty engine start-up at low
speeds. With parameter I46=1, the motor always starts at maximum speed for 1
second and then reaches the speed required by the regulation. If this function
is not desired, set parameter I46 to 0. With parameter I46=0, the motor starts
directly at the speed requested by the regulation.
23. Minimum thermostat
For all operations in heating mode, if a digital input is used on the optional
THS2 connected to the THS2-0MM master M01=7 or M03=7 or on the THS2-0MM I07=6
or I09=6 configured as minimum thermostat or a remote sensor configured as
minimum thermostat I11=3 or I13=3, ventilation does not start until the
minimum thermostat is considered closed. The contact position and the logic of
the digital contact are considered in determining the closure of the minimum
thermostat for digital contacts (see “8. Logic of digital and analogue inputs
THS2-0MM” page 16 and “43. Logic of digital inputs THS2” page 77). The logic
for analogue inputs is as follows:
Minimum thermostat open
C15 2°C
Minimum thermostat closed
C15
Temp. water coil
Temp water coil: heating coil temperature
If the temperature of the heating battery sensor at power-on is between C15 and C15 – 2, the minimum thermostat is considered open. In the absence of electrical resistance, the , and icons light up in sequence, when the minimum thermostat is open during regulation in heating mode.
Notes: – The icons indicated are present on an optional THS2 if connected to the THS2-0MM. – If there is electrical resistance, the minimum thermostat function is not taken into account. The fan is activated immediately when the electrical resistance is activated, even if the minimum thermostat is considered open. In the absence of regulation or in cooling mode, the minimum thermostat is not taken into account.
48/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
Setting done on optional THS2 connected to THS2-0MM master for minimum thermostat has higher priority than setting done locally on a THS2-0MM. So if a digital contact on THS2 connected to THS2-0MM master has the function of minimum thermostat, this contact set the position of minimum thermostat for whole internal network. If no digital contact is used on THS2 connected to THS2-0MM master with the function of minimum thermostat, the setting done locally on a THS2-0MM defines the position of minimum thermostat for that unit only. So for each THS2-0MM there must be a contact with minimum thermostat connected to use this function.
24. Destratification cycle
This function facilitates the prevention of air stratification and a better
reading of the temperature of the remote sensor placed on the fan intake. In
the absence of regulation, if the fan is off (I47=0), it is possible to start
the air destratification function taking the operating season into account. To
start the destratification function in both heating and cooling mode, set
parameter I48 to 1. To start the destratification function in heating mode
only, set parameter I48 to 2. To start the destratification cycle in cooling
mode only, set parameter I48 to 3. With the destratification cycle activated,
the fan starts at speed 1, and the icon flashes on an optional THS2 connected
to a THS2-0MM for a length of time equal to parameter I49 with every time
interval set with parameter I50.
25. Window contact
In all operations, if a digital input is used as a window contact on the optional THS2 connected to the THS2-0MM master:
M01=5 or M03=5, or on the THS2-0MM master I07=5 or I09=5, or an analogue input is configured as window contact I11=8 or I13=8, the outputs are all disabled if the window contact is opened.
The icon
flashes when the window contact is considered open.
If an electrical resistance has been activated, the ventilation is stopped after delay I45 has elapsed in order to evacuate the
calories produced by the electrical resistance. If I45=0, a minimum delay of 30 s is applied.
26. Frost protection function of the heating battery
The frost protection function of the heating battery is conducted by means of
a regulation sensor. If a THS2-0MM goes into frost protection mode, the
heating outputs and the fan coil speed are forced to maximum.
Anti Frost 2°C
ON
OFF C12
Treg
Anti Frost: frost alarm Treg: regulation sensor C12: frost protection setpoint
If the Treg < C12, the frost protection alarm is activated, the and icons
flash, and the ALF message appears on the alarm page. If a relay output is
configured on a slave with alarm function I15=14 (D01) or I16=14 (D02) or
I17=14 (D03) or I18=14 (D04) or I19=14 (D05) or I20=14 (D06), the relay is
activated for the duration of the frost protection state.
If Treg >= (C12 + 2°C), the frost protection alarm is deactivated, and the and
icons turn off. If a relay output is configured on a slave with alarm function
I15=14 (D01) or I16=14 (D02) or I17=14 (D03) or I18=14 (D04) or I19=14 (D05)
or I20=14 (D06), the relay is deactivated. Note: the icons indicated are
present on an optional THS2 connected to the THS2-0MM. If the regulation
sensor on a THS2-0MM is in error, the frost protection function on that unit
is deactivated.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 49/128
27. Dirty filter
For each THS2-0MM, the dirty filter function facilitates counting the hours of
operation of the connected fan and the issuance of a warning message with the
icon once the count has exceeded the maximum number of hours defined by
parameter I51. In this case, the fan filter is considered clogged and must be
changed. Note: the icon indicated is present on an optional THS2 connected to
the THS2-0MM. To activate the dirty filter function on a slave, set the
maximum number of hours to be counted with parameter I51 to a value other than
0. To disable this function, set I51, the maximum number of hours to count, to
0. With the function activated, the counter for hours of fan operation is
stored in memory every 2 hours. To reset the counter of a slave, set parameter
I53 to 1. The counter is reset, and parameter I53 automatically changes to 0,
and the icon stops flashing until the counter exceeds the value of parameter
I51 again. Note: With the function deactivated, the hours of fan operation are
not counted.
28. Summertime changeover
The unit is designed to automatically change to and from summertime for some
areas of the world. In order to use this function: – Set parameter M08 to 1 if
the controller is used in the Europe zone, For all zones other than Europe,
set parameter M08 to 0. Summertime cannot be updated automatically in this
case. Update summertime based on information from the country concerned.
50/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
29. Remote setpoint variator
On a local THS2-0MM, it is possible to change the setpoint by a shift of ±x °C
from the main setpoint by connecting the SAPNTC10-02-2-EV setpoint variator to
an analogue input configured as a setpoint variator input: I11=10 for AI1 or
I13=10 for AI2. The range of variation ±x °C is defined by parameter M12.
Slave THS2-0MM
CN2
AI1 AI2 GND
12345
12345
10K 10K
POT.
SAP-NTC10-02-2-EV
POT.
SAP-NTC10-02-2-EV
The heating and cooling working setpoint value obtained after changing the remote setpoint can be displayed on the I/O status if an optional THS2 is connected to the THS2-0MM. By Modbus it is possible to see the value of variation of setpoint directly on variable ADR_MOD_STATUS_CURRENT_OFFSET_VARIATOR (11032).
30. Restoring default parameters
It is possible to reset all parameters excluded parameters for comunication
(M17, M18, M19). Writing the value 1 to variable
ADR_MOD_RESET_PARAM_TO_DEFAULT (11153) to reset all parameters to default
value or press the key SW3 for around 5 s till the red led that is normally
flashing stops flashing and remain lit on. Release then the key.
It is possible to reset all parameters included parameters for comunication
(M17, M18, M19). Press the key SW3 for around 5 s till the red led that is
normally flashing stops flashing and remain lit on. Continue to maintain
pressed the key SW3 for other 5 s till the red led lit off continuously.
Release then the key.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 51/128
31. Optional THS2
The optional THS2 can be connected with each THS2-0MM master or slave of an internal network using connector CN5. If it is connected to a master, it is possible to control all parameters of internal network if M22=0 or 1.
120 term. JP1=ON
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = SW3 [1]
CN5
MASTER
120 term. JP2=ON GN M
+ M
–
+5V GND
J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
If it is connected to a slave, it is possible to control only few parameters if M22=0 or 1:
120 term. JP1=ON
THS2
-+ M M
GND +5V
Ext Adr = Int Adr = SW3 [1]
CN5
SLAVE
120 term. JP2=ON GN M
+ M
–
+5V GND
J1 J2 SW3
THS2-0MM
CN4
GND
+ M
M
– setpoint,
– offset setpoint if comfort function is activated, – on/off, – speed of
ventilator,
Any modification done on these parameters are then transmitted on the whole
network by the THS2-0MM master unit.
if THS2 is connected to a THS2-0MM unit the values of internal temperature and humidity of THS2 can be considered for regulation on whole internal network or locally on THS2-0MM unit at which it is connected (see “6. Regulation sensor” page 13). THS2 can also be used as a simple visualizer of the THS2-0MM status if M22=2. The first time THS2 is connected it is necessary for THS2 to establish a connection with the address set.
Adr
Press the keys + simultaneously, the following message appears on the display:
1
Press the key the current address is flashing. With keys or select the address (set on rotary switch SW3 if J2 is off
or set on parameter M19 if J2 ON) and press the the key to save the selection, then the ESC key to exit connection address setting. If connection is established, the screen displays operating mode.
32. Display, keypad and icons of THS2
MOD E
MODE
888 ESC 8 88:88 Display A
52/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ)
Italy Tel: +39 0472/830626 info@industrietechnik.it
www.industrietechnik.it
MODE
flashing steady on with one flash every 5 seconds steady on
flashing
flashing
ON
sequence 1
sequence 2
sequence 3
Keypad
sequence 4
ESC
Display B
On/Off Timer extension on Operation within the time band (normal/eco
operation) Setting the clock Economy operation on Alarm condition Alarm
communication Configuration, setpoints or THS2 parameters menu Operating
season THS2-0MM fan hours of operation exceeded alarm Cooling on Frost
protection on Dehumidifier on Air exchange on Heating on Electrical resistance
on Unoccupied holidays mode
Window open Fan speed M=manual speed selection A=automatic speed selection
Display C Displayed slave number on I/O menu and letter `C’ when communication
takes place between THS2 and THS2-0MM.
M=manual speed selection A=automatic speed selection Minimum thermostat
trigger, power sequencing 1, 2, 3, 4, 1.
On/Off key, navigation and confirmation Setpoint change, navigation and value
change keys Speed type key and ESC function in navigation
Key for manually changing season, task or operating mode (see “MODE key
function” page 56)
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 53/128
33. Setting parameters using quick access on THS2
The controller provides the following functions at the touch of a key: ·
On/Off switch · setting the setpoint and offset setpoint · fan operating mode
· setting the MODE key function
It is possible to associate one quick access function and two normal access functions to the MODE key, depending on parameter M07 (see “MODE key function” page 56) M07=0: season changeover (if local, for 2-pipe systems) M07=1: timer extension M07=2: operating mode (without time bands only if M10=0, with time bands, unoccupied holidays)
· Keypad lock
MODE
To lock the keypad, press the ESC
keys simultaneously; the message LK appears on the display for one second.
The parameters can no longer be accessed by pressing any key, and the message LK appears on the display.
MODE
To unlock the keypad, press the ESC
keys again; the message NLK appears on the display for one second.
· Global on/off
The unit can be switched on and off in four different ways: – by external
contact connected on the THS2-0MM master, – by time bands (lower priority) if
M10=1 and M14=0,
– manually, using the keypad. To turn the unit on or off manually, press the
key until the message ON or OFF appears. – by Modbus via supervisory system
(highest priority). The external contact has the highest priority. When it is
used, manual on/off and time bands on/off are not considered.
On/off switching via Modbus has the same priority as manual on/off or time bands on/off. This means that unit can be switched off by supervisor and switch on by time bands or manually (if M14=0) or only manually (if M14=1). If unit has been switched off manually it is possible to switch it on by supervisor, manually or by time bands (if M14=0). If unit has been switched off manually it is possible to switch it on by supervisor, or manually (if M14=1).
To use the external contact as on or off, set “remote On/Off” on the THS2-0MM
master. Configure I07=2 (DI1) or I09=2 (DI2) or I11=5 (AI1 used as remote DI
on/off) or I13=5 (AI2 used as remote DI on/off) using an optional THS2
connected to it or write the corresponding address (see “52. THS2-0MM master
Modbus variables” page 90). For instance to
configure I07=2 write the value 2 in address ADR_MOD_DIGINPUT1FUN (11075).
To switch on and off from time bands, configure parameter M10=1, and set the
time bands for switch-on (see “36. Operation and setting of TIME BANDS” page
60).
To switch on and off via Modbus write 0 or 1 on variable
ADR_MOD_FORCE_MASTERGLOBALONOFF (11048).
If the unit is switched off, the display shows how it was switched off.
OFF
MA
MA = manual shutdown using keypad
OFF
rEM
reM = remote contact shutdown
OFF MOD
MOD = Modbus shutdown
OFF
tiMb
tiMb = shutdown by time bands (if M10=1)
If the unit is switched off, all outputs except the main regulation output in heating mode are deactivated when the frost protection heating function (see “26. Frost protection function of the heating battery” page 49) is triggered.
54/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
· Setting the setpoint and offset setpoint
For 2-pipe regulation, the main setpoint is C01 in heating mode and C02 in
cooling mode. For 4-pipe regulation, the main setpoint is C03. The setpoint
can be changed on the THS2 unit by pressing the keys or if M11=0. The “set”
icon flashes while the setpoint is being changed. If M11=1 (active COMFORT
mode used when the application needs to set a setpoint that is not accessible
to the user) a change of ±x °C from the setpoint can be set by pressing the
key or the key; the “°C” icon flashes. The setpoint can then only be changed
by accessing the setpoint parameters using password 22. The maximum setpoint
variation for ±x °C is defined by parameter M12. Each change made with the or
keys is saved automatically. It is possible to change the setpoint locally on
a slave by a shift of ±x °C from the main setpoint by connecting the
SAPNTC10-02-2-EV setpoint variator to an analogue input configured as a
setpoint variator input: I11=10 for AI1 or I13=10 for AI2. To exit the
setpoint setting menu, wait 4 seconds or press the ESC key.
· Fan operating mode
Press the ESC key; the icon flashes along with the operating mode indicator of
the fan coil unit on display B. Press the ESC key one or more times to select
the operating mode of the fan coil unit:
AUtO = automatic regulation, SPE1 = regulation at speed 1, SPE2 = regulation
at speed 2, SPE3 = regulation at speed 3,
The value is saved automatically. To exit the menu, wait 4 seconds until
display B stops flashing.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy
Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
55/128
· MODE key function
MODE
The quick access function is selected by pressing the MODE key based on the value of parameter M07. The other 2 functions can still be accessed by pressing the ESC keys.
Access the quick function with the MODE key:
MODE
· If M07=0 (quick access to local season changeover setting, if no contact is
configured as remote season changeover on master and slave units)
Press the key; the “HEAT” (for heating) or “COOL” (for cooling) icon flashes
according to the current setting, and the same flashing message appears on
display B.
Press the key to change the setting. The value is saved automatically. To exit
the menu, wait 4 seconds or press the
ESC key.
MODE
· If M07=1 (quick access to timer extension setting) The timer extension
function extends operation with the base setpoint, excluding the economy
function and the “unoccu-
pied holidays” function, for a time corresponding to parameter M09 if the time
band function parameter M10=0. With M10=1 (time bands for switching on and
off), the timer extension function extends the ON operation by excluding the
bands for a time corresponding to parameter M09.
MODE
noOC OC Press the key; the message
flashes on display B (to stop the timer extension, if it has started) or the message
on display B and the icon flashes (to activate the timer extension).
MODE
Press the key to change the setting. The value is saved automatically.
To exit the menu, wait 4 seconds or press the ESC key.
· If M07=2 (quick access to operation mode setting) The operating mode function allows for the selection of regulation either with or without time bands (if the parameter M10=0, regulation is with time bands, see “36. Operation and setting of TIME BANDS” page 60) or in “unoccupied holidays” mode (see “10. Working setpoint, economy and unoccupied holidays mode” page 21).
MODE
If M10=0, time band function for normal/economy operation:
press the key; the following message flashes:
nOrM on display B (to regulate without time bands) or tiMb on display B and
the icon (to regulate with normal/economy time bands) or HOLY on display B and
the icon (to regulate in “unoccupied holidays” mode).
If M10=1, time band function for switching the unit off and on:
press the key; the following message flashes:
nOrM on display B (to regulate with time bands) or HOLY on display B and the
icon (to regulate in “unoccupied holidays” mode).
MODE
MODE
Press the key one or more times to select the regulation mode. The value is saved automatically.
To exit the menu, wait 4 seconds or press the ESC key.
56/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
MODE MODE
Access to non-quick functions with the ESC keys:
If the quick access function of the MODE key is set to local season changeover
(M07=0), to access the other functions, press the ESC and keys simultaneously
to enter the menu for modifying the timer extension and operating mode
functions:
Parameter Description
Timer extension
noOC=without timer extension
OC=with timer extension (for the duration corresponding to parameter
MOC
M09):
-The economy function and the unoccupied holidays function are ex-
cluded if M10=0.
– The unit stays on, if M10=1.
Operating mode with M10=0:
nOrM=operation without time bands
tiMb=operation with time bands
MOD
HOLY=unoccupied holidays operation
Operating mode with M10=1:
nOrM=time band mode HOLY=unoccupied holidays operation
Default
Min
Max
noOC noOC OC
nOrM nOrM, tIMb, HOLY nOrM nOrM, HOLY
Press the or key to select a parameter and the value of the parameter. Press the or key to change the setting.
key to enter edit mode; display B flashes with the current
Press the key to save the settings, or the ESC key to exit without saving the changes.
To exit the menu, press the ESC key again or wait approximately 10 seconds.
If the timer extension function is on, the icon flashes for the duration of parameter M09. If the timer extension function has been turned off, the icon is off.
If the quick access function of the MODE key is set to timer extension (M07=1), to access the other functions, press the
MODE
and ESC keys simultaneously to enter the menu for modifying the operating mode and season changeover functions:
Parameter Description
Default
Min
Max
Local season changeover (local season changeover setting for 2-pipe
SEA
systems):
HEAT=heating mode
HEAT HEAT COOL
COOL=cooling mode
Operating mode with M10=0:
nOrM=operation without time bands
tiMb=operation with time bands
MOD
HOLY=unoccupied holidays operation
nOrM nOrM, tIMb, HOLY
Operating mode with M10=1:
nOrM=time band mode HOLY=unoccupied holidays operation
nOrM nOrM, HOLY
Press the or key to select a parameter and the value of the parameter. Press the or key to change the setting.
key to enter edit mode; display B flashes with the current
Press the key to save the settings, or the ESC key to exit without saving the changes.
To exit the menu, press the ESC key again or wait approximately 10 seconds.
AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it 57/128
MODE
If the quick access function of the MODE key is set to operating mode (M07=2), to access the other functions, press the and ESC keys simultaneously to enter the menu for modifying the season changeover and timer extension functions:
Parameter Description
Local season changeover (local season changeover setting for 2-pipe
SEA
systems):
HEAT=heating mode
COOL=cooling mode
Timer extension
noOC=without timer extension
OC=with timer extension (for the duration corresponding to parameter
MOC
M09):
– The economy function and the unoccupied holidays function are ex-
cluded, if M10=0.
– The unit stays on, if M10=1.
Default
Min
HEAT HEAT
noOC noOC
Max
COOL
OC
Press the or key to select a parameter and the value of the parameter. Press the or key to change the setting.
key to enter edit mode; display B flashes with the current
Press the key to save the settings, or the ESC key to exit without saving the changes.
To exit the menu, press the ESC key again or wait approximately 10 seconds.
34. Timer extension or forced presence mode
This function can only be used using a THS2 connected to a THS2-0MM master in
the internal network. If time bands are used for the “energy saving” function
(M10=0) when the “energy saving” or “unoccupied holidays” function is used,
the working setpoints are calculated taking parameters C08 (economy offset)
and C09 (“unoccupied holidays” operating mode offset) into account. These
functions can be bypassed while continuing regulation with the basic setpoints
for a specified time (parameter M09). To bypass these functions, set the timer
extension manually using the MODE key (see “33. Setting parameters using quick
access on THS2” page 54).
If, on the other hand, time bands are used to switch the unit on or off M10=1,
if the timer extension function is activated by the MODE key, the unit does
not take the time bands into account and keeps the unit on for the time
corresponding to parameter M09, if the extension function has been set using
the keypad. To activate the timer extension function manually, set parameter
OC MOC to (see “MODE key function” page 56). Once activated, the time defined
by parameter M09 elapses before returning
to normal operation.
If the timer extension function is on, the icon flashes for the duration of
parameter M09. If the timer extension function has been turned off, the icon
is off.
58/128 AB Industrietechnik srl Via Julius Durst, 50 39042 BRESSANONE (BZ) Italy Tel: +39 0472/830626 info@industrietechnik.it www.industrietechnik.it
35. Setting DATE and TIME
CLK
yMdH
y-r
2012
Press the and keys simultaneously. The message CLK appears on display A and yMdH on display B. Press the key to enter the date and time setting menu.
M-h
11
day
29
Hr.
11:37
Parameter Description
CLk
Date and time setting menu
Y-r
Year
M-h
Month
day
Day
Hours
Hr.
Minutes
Min Max
2012 1 1 0 0
2100 12 31 23 59
Press the or key to select a parameter to modify and the value of the parameter. Press the or key to change the setting.
key to enter edit mode; display B flashes with the current
Press the key to save the settings or the ESC key to exit without saving the changes
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>