KINGSMAN MCVP42N Millivolt Natural Gas Peninsula Fireplace Instruction Manual
- June 9, 2024
- Kingsman
Table of Contents
MCVP42N Millivolt Natural Gas Peninsula Fireplace
Product Information: Vented Gas Fireplace Heater
The Vented Gas Fireplace Heater is available in six certified
models: MCVP42N, MCVP42NE, MCVP42NE2, MCVP42LP, MCVP42LPE, and
MCVP42LPE2. It is also available in four ATRIUM models: MCVP42NH,
MCVP42NHE, MCVP42NHE2, and MCVP42LPH. This appliance is designed
for installation in an aftermarket, permanently located,
manufactured home (USA only) or mobile home (where not prohibited
by local codes).
It is essential to note that this appliance is only intended for
use with the type of gas specified on the rating plate. The
appliance is not convertible for use with other gases unless a
certified kit is used. Installation and service must be performed
by a qualified installer, service agency, or the gas supplier.
Product Usage Instructions:
Before using the Vented Gas Fireplace Heater, it is important to
follow the pre-installation instructions:
-
Fire the appliance four successive times for 10 minutes each
firing and a 5-minute cool down between each. During log and
firebox paint curing, a white deposit may develop on the inside of
the glass doors. It is vital to remove this white deposit from the
glass doors using a fireplace glass cleaner. -
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance. -
If you smell gas, do not try to light any appliance or touch
any electrical switch. Do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow
the gas supplier’s instructions. If you cannot reach your gas
supplier, call the fire department.
To install and use the Vented Gas Fireplace Heater:
-
Ensure the appliance is only used with the type of gas
indicated on the rating plate. The appliance is not convertible for
use with other gases unless a certified kit is used. -
For propane horizontal installations, the venting must be an
additional one foot above the minimum vertical rise off the flue
before going horizontal. -
Installation and service must be performed by a qualified
installer, service agency, or gas supplier. -
Leave the product manual with the appliance after installation,
and retain it for future reference. -
Do not use this appliance with solid fuel.
Troubleshooting:
If you experience any issues with the gas control system, refer
to the troubleshooting section in the product manual or contact a
qualified installer or service agency immediately.
Warranty:
The Vented Gas Fireplace Heater comes with a limited lifetime
warranty as outlined in the product manual.
Installation Instructions
Model Numbers: Certified to:
MCVP42N, MCVP42NE, MCVP42NE2, MCVP42LP, MCVP42LPE, MCVP42LPE2
ANSI Z21.88-2017 · CSA 2.33-2017, CSA 2.17-2017 Vented Gas Fireplace Heaters
ATRIUM
Model Numbers: Certified to:
MCVP42NH, MCVP42NHE, MCVP42NHE2, MCVP42LPH,
MCVP42LPHE, MCVP42LPHE2 ANSI Z21.88-2017 · CSA 2.33-2017, CSA 2.17-2017 Vented
Gas Fireplace Heaters
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING: If the information in these instructions are not followed exactly, a
fire or explosion may result causing property damage, personal injury or loss
of life.
-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. -WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch; do not
use any phone in your building. Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach
your gas supplier, call the fire department
-Installation and service must be performed by a qualified installer, service agency or the gas supplier.
For Propane Horizontal installations the venting must be an additional one foot above the minimum vertical rise off the flue before going horizontal.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual
for future reference.
VENTED GAS FIREPLACE HEATER: NOT FOR USE WITH SOLID FUEL.
A Division of R-Co. Inc. 2340 Logan Ave. Winnipeg, Manitoba Canada R2R 2V3 Ph.: 204-632-1962 Printed in Canada December 8, 2021 Part# 42MCVP-MAN17
Table of Contents
INFORMATION Table of Contents………………………………………………………………………………………………………………….. 2-3
Pre-installation Questions and Answers / Operations and Maintenance
Instructions……………………………………………. 4 Warnings, Installations and
Operations………………………………………………………………………………………………………….. 5 Installation
Requirements for the Commonwealth of Massachusetts / Carbon Monoxide (CO)
Detector…………………. 6 Mobile Home/Manufactured Housing
Installation…………………………………………………………………………………………….. 7 Fireplace Installations in
Covered Outdoor Locations………………………………………………………………………………………. 8 Recommendations
for Finishing of Clean View Linear Products………………………………………………………………………… 9
INSTALLATIONS Framing- Nailing Tab
Guide……………………………………………………………………………………………………… 10 Framing Your Gas
Fireplace…………………………………………………………………………………………………….. 11 Locating Your Appliance /
Fireplace Dimensions……………………………………………………………………………… 12 Framing
Dimensions……………………………………………………………………………………………………………… 13 Facing
Requirements…………………………………………………………………………………………………………….. 14 Basic Finishing:
MCVP42……………………………………………………………………………………………………… 15 Mantel
Clearances…………………………………………………………………………………………………………………. 16 Clearance to
Combustibles……………………………………………………………………………………………………… 17 42MCVP-TLK Tile Lip
Kit……………………………………………………………………………………………………… 18
ACCESSORIES Safety Screen
Installation……………………………………………………………………………………………………………. 19 MP42PL Porcelain
Liner Installation…………………………………………………………………………………………….. 20 MP42RL -Brick Liner
Installation- When using M42LG Log Grates……………………………………………………………………. 21 MP42RL
-Brick Liner Installation- When using MP42GT Glass
Tray………………………………………………………………….. 22 Baffle Removal (MCVP42-H Ceramic Glass
Units) / Deflector Removal (MCVP42 Tempered Glass Units)…………….. 22 Baffle
Removal (MCVP42-H Ceramic Glass Units)………………………………………………………………………………………….. 23
Deflector Removal (MCVP42 Tempered Glass
Units)……………………………………………………………………………………… 23 MP42-GT Installation /
Removal……………………………………………………………………………………………………………………. 24 M42-LG Installation /
Removal………………………………………………………………………………………………….. 25 MQ42LOG1- 8 Piece Driftwood
Log Set – For use with GT Glass Tray…………………………………………………….. 26 MQ42LOG1- 8
Piece Driftwood Log Set – For use with M42LG Log Grate………………………………………………… 27
MQ42LOG2- 7 Piece Oak Log Set – For use with GT Glass
Tray………………………………………………………….. 28 MQ42LOG2- 7 Piece Oak Log Set – For use with
M42LG Log Grate………………………………………………………. 29 M42LOG3- 6 Piece Driftwood Log Set –
For use with GT Glass Tray………………………………………………………. 30 M42LOG4- 8 Piece Oak Log
Set – For use with M42LG Log Grate…………………………………………………………. 31 UHS Box /
Component Locations………………………………………………………………………………………………. 32 ULK3 Universal
Light Kit………………………………………………………………………………………………………… 33 Split Receptacle- Switch
Control Outside of Fireplace……………………………………………………………………….. 34 RBCB1
-Cannonballs- Installation Instructions…………………………………………………………………………………. 35 MQ
Dealer Accessories for MCVST42 / MCVP42 (Glass)……………………………………………………………………. 36
MQSTONE, MQROCK, MQEMBER……………………………………………………………………………………………. 37
GENERAL INSTALLATION, USE, AND MAINTENANCE Door
Installation…………………………………………………………………………………………………………………… 38 Door and Glass
Information……………………………………………………………………………………………………… 39 Gas Line
Installation………………………………………………………………………………………………………………. 40 Millivolt System,
Lighting, and Burner Control…………………………………………………………………………………. 41 Annual
Inspection List for Determining Safe Operation of a Direct Vent Gas
Fireplace………………………………………… 42 Burner System
Maintenance……………………………………………………………………………………………………. 43 Gas Conversion Part A
MCVP42………………………………………………………………………………………………………………….. 44 Gas Conversion for Top
Convertible Pilot Part B (series 0190XYZ)………………………………………………………………… 45
2
Gas Conversion for Modulator PART C………………………………………………………………………………………………………. 46 Main Burner Removal / Burner System Removal & Installation…………………………………………………………………………. 47
PROFLAME 1 IPI Electronic Ignition System…………………………………………………………………………………………………….. 48 Remote Control Operation………………………………………………………………………………………………………. 49 IPI Electronic Ignition Parts List Standard System…………………………………………………………………………. 50 Configuration 1: Basic Manual Hi / Lo and manual Off………………………………………………………………………. 51 Configuration 2: Remote On / Off and manual Hi / Lo……………………………………………………………………….. 52 Operating the Receiver Without Batteries For GT / EGT / GTM / EGTM Remote Controls……………………………… 53 Configuration 3: Remote ON/OFF, Variable HI/LO, and Fan………………………………………………………………… 54 Electronic Ignition Lighting Instructions………………………………………………………………………………………… 55
PROFLAME 2 Proflame 2 Parts List / Basic System / Configuration GTMFL……………………………………………………………………………. Proflame 2 Module and Remote Control………………………………………………………………………………………………………… Cold Climates CPI Setting – Proflame 2 Remote Control……………………………………………………………………………….. Proflame 2 Remote Control………………………………………………………………………………………………………………………….. Proflame 2 Label Diagram……………………………………………………………………………………………………………………………………..
56 57 58 59-60 61
VENTING Vent Termination…………………………………………………………………………………………………………………. General
Vent Installation………………………………………………………………………………………………………….. Installation of
Side Wall Venting………………………………………………………………………………………………… Venting Routes And
Components………………………………………………………………………………………………. Horizontal Venting
Table………………………………………………………………………………………………………….. Z58HT Horizontal
Installations- Wall Thimble Sizing / Termination Sizing…………………………………………………
Venting Straight Up Through Roof……………………………………………………………………………………………… Glass
Safety / Termination Cap Safety…………………………………………………………………………………………………………..
Approved for Power Vent PVH58……………………………………………………………………………………………….. PVH58
Power Vent Control Module Installation…………………………………………………………………………………………….
PARTS LISTS PVH58 / PVH58FM Parts
List……………………………………………………………………………………………………………………….. MCVP42 Parts
List………………………………………………………………………………………………………………..
TROUBLESHOOTING THE GAS CONTROL SYSTEM Troubleshooting the Gas Control
System………………………………………………………………………………………………………..
62 63 64 65 65 66-67 68-69 70 71 72
73 74-75
76
WARRANTY Limited Lifetime Warranty…………………………………………………………………………………………………………. 77
3
Pre-installation Questions and Answers
About curing of the paint Your stove or fireplace has been painted with the
highest quality silicone stove paint. This paint dries quickly in 15-20
minutes when first applied at the factory. However, due to the high
temperature silicone components, the paint will cure when heat is applied to
the appliance as it is first used. The following information applies to the
curing process to get the paint fully hard and durable.
Fire the appliance four successive times for 10 minutes each firing and a 5
minute cool down between each. Be aware during log and firebox paint curing
that a white deposit may be developing on the inside of the glass doors. It is
important to remove this white deposit from the glass doors using a fireplace
glass cleaner.
· Babies, small children, pregnant women and pets should leave the area during
the cure phase.
· Ventilate well, open doors and windows.
· Do not touch during curing.
Why does my fireplace or stove give off odor? It is normal for your fireplace
to give off some odor at first. This is due to the curing of the paint,
adhesives, silicones and any undetected oil from the manufacturing process as
well as the finishing materials used with the installations (e.g. marble, tile
and the adhesives used to adhere this product to the walls can react with heat
and cause odors).
It is recommended that you burn your gas fireplace or stove for a minimum of
four hours at a time with the fan off (if a fan is present) after the curing
of the paint has been completed. These odors can last upward to 40 hours of
burn time; keep burning at a minimum of four hours per use until odors
dissipate.
Noise coming from the fireplace? Noise is caused by the expansion and
contraction of metal as the appliance heats up and cools down. This is normal
and is similar to the sounds produced by a furnace or heating duct. This noise
does not affect the operation or longevity of your fireplace. It is also
normal for the fan to make some noise when it comes on. This noise can be
reduced somewhat by turning down the speed of the fan with the variable speed
control. Be aware, however, that this will reduce the volume of heated air
circulated into the room by the fan. Note to the Installer: Be sure appliance
is working properly and its operation (including remote control operation, if
included) is fully explained to and understood by the customer.
Operations and Maintenance Instructions
For safe installation and operation note the following:
· Be sure to read and understand all the instructions in this manual before
operation of appliance. · Ensure all wiring is correct and properly enclosed
to prevent possible shock. · Check for gas leaks. · Make sure the glass door
is properly installed before operation. Never operate the appliance with the
glass door
removed. · Make sure venting and termination cap are installed and
unobstructed. · If brick or porcelain liners are used, ensure they are
installed. · Verify that the pilot can be seen when lighting the appliance. If
not, the log or rock placement is incorrect. · If the unit is turned off, you
must wait a minimum of 60 seconds before re-lighting it. · Venting systems
should be periodically examined by a qualified agency. · The flow of
combustion and ventilation air must not be obstructed. · The Burner/Log
Assembly has been engineered and permanently adjusted for proper flame
control. · Periodically remove the logs from the grate assembly and vacuum any
loose particles from the grate and burner
areas. See Log Placement page to remove logs. Vacuum burner parts and replace
logs. · Never use your gas fireplace as a cooking device. · Label all wires
prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous
operation. Verify proper operation after servicing. · Areas in and around the
Chase Vent Openings should be cleaned annually.
4
Warnings, Installations and Operations – Installation Regulations
This gas appliance must be installed by a qualified installer in accordance
with local building codes, or in the absence of local codes, with the current
CAN/CSA-B149.1 or .2 Installation Code (in Canada) or the current National
Fuel Gas Code Z223.1- NFPA 54 when installed in the United States. This
appliance, when installed, must be electrically connected and grounded in
accordance with local codes, or in the absence of local codes, with the
current CSA C22.1 Canadian Electrical Code or with the National Electrical
Code; ANSI/NFPA 70 when installed in the United States.
WARNING
FOR SAFE INSTALLATION AND OPERATION OF YOUR GAS FIREPLACE PLEASE NOTE THE
FOLLOWING:
1. Do not clean when the glass is hot. 2. Do not use abrasive cleaners. 3.
Using a substitute glass will void all product
warranties. 4. For safe operation, glass doors must be closed. 5. When purging
the gas line, the glass front must be
removed. 6. Do not strike or abuse glass. Take care to avoid
breakage. 7. Do not alter gas orifice. 8. No substitute materials may be used
other than
factory supplied components. 9. This appliance gives off high temperatures and
should
be located out of heavy traffic areas and away from furniture and draperies.
10. Children and adults should be alerted to the hazards of the high surface
temperatures of this appliance and should stay away to avoid burns or ignition
of clothing. 11. Young children should be carefully supervised when they are
in the same room as the appliance. Toddlers, young children and others may be
susceptible to accidental contact burns. A physical barrier is recommended if
there are at risk individuals in the house. To restrict access to a fireplace
or stove, install an adjustable safety gate to keep toddlers, young children
and other at risk individuals out of the room and away from hot surfaces. 12.
Under no circumstances should any solid fuels (wood, paper) be used in this
appliance. 13. Under no circumstances should this appliance be modified. Any
parts that have to be removed for servicing should be replaced prior to
operating this appliance. 14. Any safety screen, guard, or barrier removed for
servicing an appliance must be replaced prior to operating the appliance. 15.
Installation and repair should be done by a qualified service person. The
appliance should be inspected before use and at least annually by a
professional service person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, et cetera. It is imperative
that control compartments, burners and circulating air passageways of the
appliance be kept clean. Make sure that the gas valve and pilot light are
turned off before you attempt to clean this unit. 16. Clothing or other
flammable material should not be placed on or near the appliance. This
appliance should not be used as a drying rack for clothing nor should
Christmas stockings or decorations be hung from it.
17. Do not use this heater if any part has been under water. Immediately call
a qualified service technician to inspect the heater and to replace any part
of the control system and any gas control which has been under water.
18. Do not operate appliance unless completely installed as per installation
instructions.
19. Failure to position the parts in accordance with these diagrams or
failure to use only parts specifically approved with this appliance may result
in property damage or personal injury.
20. WARNING: Do not operate appliance with the glass front removed, cracked
or broken. Replacement of the glass should be done by a licensed or qualified
service person.
21. The appliance area must be kept clear and free from combustible
materials, gasoline, and other flammable vapors and liquids.
22. The front of the fireplace gives off high temperatures that could ignite
combustible material which is kept close to the front of the unit.
23. Ensure that power to the Fireplace is turned off before servicing.
24. Do not operate this Fireplace without the glass front or with a broken
glass.
25. Improper installation, adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to the owner’s information manual
provided with this appliance. For assistance or additional information consult
a qualified installer, service agency, or the gas supplier.
26. Operation of this appliance when not connected to a properly installed
and maintained venting system or tampering with the blocked vent shutoff
system can result in carbon monoxide (CO) poisoning and possible death.
27. This appliance is equipped with a three-prong (grounding) plug for your
protection against shock hazard and should be plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove the grounding prong from
this plug.
28. NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE. This appliance is tested
and approved as either supplemental room heat or as a decorative appliance. It
should not be factored as primary heat in residential heating calculations.
29. This appliance must not be connected to a chimney flue serving a separate
solid-fuel burning appliance.
5
Installation Requirements for the Commonwealth of Massachusetts
In the Commonwealth of Massachusetts, the installer or service agent shall be
a plumber or gas fitter licensed by the Commonwealth.
When installed in the Commonwealth of Massachusetts or where applicable codes;
the unit shall be installed with a CO detector per the requirements listed
below.
1. For direct-vent appliances, mechanical-vent heating appliances or domestic
hot water equipment, where the bottom of the vent terminal and the air intake
is installed below four feet above grade the following requirements must be
satisfied: A. If there is not one already present, on each floor level where
there are bedroom(s), a carbon monoxide detector and alarm shall be placed in
the living area outside the bedroom(s). The carbon monoxide detector shall
comply with NFPA 720. B. A carbon monoxide detector shall be located in the
room that houses the appliance or equipment and shall: Be powered by the same
electrical circuit as the appliance or equipment such that only one service
switch services both the appliance and the carbon monoxide detector; Have
battery back-up power; Meet ANSI./UL 2034 Standards and comply with NFPA 720;
and Have been approved and listed by a Nationally Recognized Testing
Laboratory as recognized under 527 CMR. C. A Product-approved vent terminal
must be used, and if applicable, a Product-approved air intake must be used.
Installation shall be in strict compliance with the manufacturer’s
instructions. A copy of the installation instructions shall remain with the
appliance or equipment at the completion of the installation. D. A metal or
plastic identification plate shall be mounted at the exterior of the building,
four feet directly above the location of vent terminal. The plate shall be of
sufficient size to be easily read from a distance of eight feet away, and read
“Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical-vent heating appliances or domestic
hot water equipment where the bottom of the vent terminal and the air intake
is installed above four feet above grade the following requirements must be
satisfied: A. If there is not one already present, on each floor level where
there are bedroom(s), a carbon monoxide detector and alarm shall be placed in
the living area outside the bedroom(s). The carbon monoxide detector shall
comply with NFPA 720. B. A carbon monoxide detector shall: Be located in the
room that houses the appliance or equipment; Be either hard-wired or battery
powered or both; and Shall comply with NFPA 720.
A Product-approved vent terminal must be used, and if applicable, a Product-
approved air intake must be used. Installation shall be in strict compliance
with the manufacturer instructions. A copy of the installation instructions
shall remain with the appliance or equipment at the completion of the
installation.
For the state of Massachusetts a T-handle gas shut-off valve must be used on a
gas appliance. This T-handle gas shutoff valve must be listed and approved by
the state of Massachusetts. This is in reference to the state of Massachusetts
state code CMR238.
Carbon Monoxide (CO) Detector
NOTE: It is recommended that a Carbon Monoxide (CO) Detector be installed in
or near bedrooms and on all levels of your home. Place a detector about 15ft
[4.5m] outside the room that houses your gas appliance.
Certified for installation in a bedroom or bed/sitting room. In Canada must be
installed with listed millivolt thermostat. In USA see local codes.
6
Mobile Home/Manufactured Housing Installation
This Direct Vent System Appliance must be installed in accordance with the
manufacturer’s installation instructions and the Manufactured Home
Construction and Safety Standard Title 24 CFR, Part 3280, or the current
Standard for Fire Safety Criteria for Manufactured Home Installations, Sites,
and Communities ANSI/NFPA 501A, and with CAN/CSA Z240 MH Mobile Home Standard
in Canada.
Appliance Must Be Secured To Structure Using 4 Supplied Nailing Tabs And Or
Fastened To Floor.
Use Existing Hole Or Remove Existing Screw To Mount Ground
Wire (Nailing Tab Screw).
Serrated Or Star Washer
Ground Wire From Appliance To Steel Chassis Of Mobile Home.
USE 8GA COPPER WIRE.
THE VENTED GAS FIREPLACE HEATERS IN THIS MANUAL MAY BE INSTALLED IN
MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE IN THE USA.
THE VENTED GAS FIREPLACE HEATERS IN THIS MANUAL MAY BE INSTALLED IN
MANUFACTURED (MOBILE) HOMES IN CANADA.
Please follow the current ANSI/NFPA 70 National Electrical Code in the USA and
CAN/CSA C22.1 Canadian National Electrical Code in Canada. An appliance must
be grounded to the steel chassis of the home with 8 ga. copper wire using a
serrated or star washer to penetrate paint or protective coating to insure
grounding. Use carriage bolt at the attachment point (see diagram above) to
secure the appliance to the floor.
Warning: Do not compromise the structural integrity of the manufactured home
wall, floor or ceiling, during installation of appliance or venting.
For required venting components see venting installation in appropriate
section of this manual. Certified for installation in a bedroom or bed/sitting
room. In Canada must be installed with listed millivolt thermostat. In USA see
local codes.
7
Fireplace Installations in Covered Outdoor Locations FOR BASIC MILLIVOLT
UNITS ONLY- NO FAN NO LIGHTS-
CAUTION Installation of an indoor gas fireplace with an outdoor exposure is
not covered under the (ANSI Z21.88 CSA 2.22 or ANSI Z21.50 CSA 2.33)
standard(s) used to certify the indoor gas-fired fireplace. The Intertek
safety certification will not apply to this installation method. This
installation method must be deemed acceptable by the Authority Having
Jurisdiction (AHJ) prior to the indoor gas fireplace being installed.
Kingsman and Marquis Direct Vent fireplaces may be installed into outdoor
locations provided they are suitably protected from direct water impingement.
However, all installation clearances in the appliance manual must be observed.
Framing, Clearances to Combustibles, Mantel Heights, Facing Requirements,
Venting Installation, etc. Use supplied Safety Screen.
· All wiring connections to line power shall be in accordance with outdoor
requirements of; -NECA NFPA 70 in the USA -Canadian Electrical Code, CSA C22.1
for Canada.
· The Fireplace is not to be operated in temperatures below freezing (0°C /
32°F).
· NOTE: TEMPERED GLASS WARNING: Tempered glass is vulnerable to rapid and/or
extreme changes in
temperature (thermal shock). Take care to prevent water from contacting the
fireplace, especially if it is hot.
· See-Through Units are suitable for an outdoor location, but not on the
outside wall of a house or other structure, as air flows through both sides of
the fireplace.
· A Minimum sheltering cover (overhang) of 1/2 the distance from the base of
the fireplace to the ceiling (base of roofline) is required.
EXAMPLE: The bottom of the fireplace is 84″ from the ceiling. Therefore, 42″
of sheltering cover is required above fireplace.
Glass Door
OUTDOOR AREA
Glass Door
Glass Door
Outside Wall of House
8
Recommendations for Finishing of Clean View Linear Products
When finishing the wall around the fireplace, it is critical that the wall
covering be fastened properly. It is acceptable to pre-drill holes and use
self-tapping screws which may be used to fasten a backer for tile, marble,
etc. Screws being installed through non-combustible board should be self-
tapping type with a maximum length of 2 inches. Wall covering fasteners, such
as screws or nails, are not permitted in some locations. Do not drill or
install longer screws which may penetrate into the lower cover panel area as
this may damage internal components. · Only non-combustible materials may be
used over the face of the appliance. · We recommend that CONCRETE BOARD (non-
combustible material) be tied in to the entire perimeter of the fireplace for
durability.
Finishing Recommendations (Obtained from professional construction contractors
and finishers): · Frame unit with metal studs (minimum 20 gauge).Wooden studs
may be used, but may cause drywall screws to pop
or pull due to wood studs drying out. · Minimum of 1/2″ CONCRETE BOARD cement
board (this non-combustible panel is ULC listed as a wall shield/floor
protector) and fasten to the entire perimeter framing. · Use fiberglass (mesh)
tape for all joints in area of the fireplace. · Use Yellow joint mud (contains
high amounts of glue) two coats, finishing with one coat of green topping
mud, sand
and prep for painting. · If not using a surround, a metal “L” Trim may be used
to finish perimeter of CONCRETE BOARD. · Refer to the following website for
more information on using CONCRETE BOARD Cement Board: www.cgcinc.com OTHER
NOTES: -A full single sheet of non-combustible board (no joints) above the
unit is recommended if possible. -It is preferred to attach the non-
combustible board to framing only and not directly to the unit to allow for
expansion and contraction during normal operation. -Lighter colored painted
surfaces may discolor due to heat exposure.
9
MCVP42
Framing- Nailing Tab Guide
[Qty] 4 Nailing Tabs are located on flue side of fireplace.
These Nailing Tabs can be used in two ways:
1/2″ Drywall Flush with Face of Fireplace
Framing Flush with Face of Fireplace -Fireplace to be covered
Fireplace and Combustible Wall to be covered
with Non-Combustibles (e.g. Concrete Board) for Flat Wall
with a surround or Non-Combustible Materials
appearance.
(e.g. Stone around Fireplace).
Nailing Tab Framing Stud
Drywall
Non-Combustible Material (eg. Stone)
Nailing Tab Framing Mount
Nailing Tabs Must Be Rotated 180° And Folded Back Onto Framing Stud.
Nailing Tab Framing Stud Drywall
Non-Combustible Material (eg. Stone)
Framing Stud Nailing Tab
Framing Stud
Nailing Tab Flush Surface
10
MCVP42
Framing Your Gas Fireplace
This section is intended for qualified installers only. Before beginning, make note of where the gas and electrical accesses are
located on the unit. This will streamline the construction process. Furthermore, familiarize yourself with the venting and
clearance requirements (see Venting section) for this appliance. Failure to comply with those requirements can seriously
compromise the safety and operation of the fireplace.
Specifications 1. Cold climate installation recommendation: When installing
this fireplace against non insulated exterior wall or chase,
it is recommended that the outer walls be insulated to conform to applicable
insulation codes. Drywall & vapor barrier must be installed over insulation to
prevent contact of insulation and unit. 2. Choose fireplace location and frame
in accordance with the fireplace framing dimensions specified (view diagrams).
3. Drywall or other combustible material can extend up to the Drywall Stops
located on the sides of the unit, and up to the bottom and top. 4. A Hearth is
not required for this unit.
Vertical Venting in Cold Climates
In cold climate conditions where temperatures go below -10 degrees Celsius or
14 degrees Fahrenheit, we recommend that the chase be insulated and where the
vent pipe enters into the attic space that the pipe be wrapped with an
insulated Mylar sleeve. This will increase the temperature of the vent and
help the appliance to vent properly in cold weather conditions. It is also
important in vertical vented direct vent appliances that the appliance be
operated daily during the winter months as this will help stop the termination
from freezing up. We recommend using a thermostat. Set at room temperature to
allow the unit to cycle. For IPI models it may be necessary to set the
appliance to Standing Pilot mode to maintain heat in the cavity. The purpose
of this procedure is to prevent cold air from penetrating the chimney and then
onto the living space. Therefore, when the internal temperature is slightly
elevated the fireplace is able to freely exhaust its combustion and hence
making it easier to startup.
Certified for installation in a bedroom or bedsitting room. In Canada must be
installed with listed millivolt thermostat. In USA see local codes.
Stand-off Locations
Make note of where the stand-off locations are. These stand-offs are provided
as indicators to illustrate the boundaries for framing. Therefore, no framing
material is permitted to extend beyond these stand-offs.
Caution: 4 Standoffs on top of the unit must be folded into position & screwed down Prior to installation.
2 Holes are provided in bottom of unit to secure
appliance to floor after installation.
4 Nailing Tabs
11
MCVP42
See Mantel Leg Clearances Instruction for the proper placement of fireplace.
Locating Your Appliance
PENINSULA
ISLAND
MCVP42
ALL UNITS MAY BE VENTED VERTICALLY
Fireplace Dimensions
12
MCVP42
These structures are not load bearing.
Framed fireplace opening.
Framing Dimensions
Optional- floor cutout for gas line if coming up through floor.
Vertical Venting MUST maintain 1″ clearance to combustibles.
TOP VIEW
Vent Framing (Vertical or Horizontal) 9″ Round Hole through Masonry. 12″ x 12″
Framing for Combustible.
55″ MIN for NG 79″ MIN for LP Plus Rise of ¼”
Per Foot*
55″ MIN for NG 79″ MIN for LP Plus Rise of ¼”
Per Foot*
*For Propane Horizontal installations the venting must be an additional two feet above the minimum vertical rise off the flue before going horizontal.
BOTTOM OF
FIREPLACE
13
MCVP42 Facing Requirements
Required Non-Combustible Areas If you are covering the face of the fireplace:
NOTE: MATERIALS COVERING THE FACE OF THE FIREPLACE MUST BE NON-COMBUSTIBLE
It is also recommended (but optional) to attach Non-combustible facing to
framing.
1″ May be Combustible (Carpet, Hardwood, Laminate, etc.) Note: Do not drive
excessively long screws into the face of the unit as internal parts may be
damaged.
Combustibles (i.e. Drywall) may be installed flush with top of Fireplace. Side
facing to be installed to standoffs only.
1″ May be Non-Combustible
(Carpet, Hardwood, Laminate, etc.)
14
Basic Finishing MCVP42
Step One: Frame Fireplace with nailing tabs oriented as shown.
Step Two: Use Drywall to finish face of wall. NOTE: Drywall will be flush with
fireplace face.
Drywall
Fireplace Face
Fireplace Face
Nailing Tab
Step 3: A brick, tile, or other non-combustible covering may be applied over fireplace face.
Tile
Drywall
Fireplace Face
15
MCVP42
Mantel Clearances
Before installing any mantels it is important to determine the combustibility of its material(s). There are two types of mantels to consider: Combustible and Non-Combustible.
A Combustible Mantel is one that consists of material(s) that may discolor, combust, or lose its integrity in the presence of heat. These types of mantels must strictly conform to the dimensional requirements shown.
Conversely, a Non-Combustible Mantel is one that is constructed with material(s) that will not combust. Check your local codes and regulations to determine whether your mantel is combustible or Non-Combustible.
Mantel begins 11-3/16″ above top of fireplace
opening.
The advantage of a Non-Combustible Mantel is that it can begin at the top of
the fireplace opening. Combustible mantels must adhere to the dimensional
restrictions shown.
-Combustible Objects on NonCombustible Mantel WarningCombustible objects must not be placed on a Non-combustible Mantel unless the mantel meets the dimensional requirements for a Combustible Mantel. Determine whether your mantel conforms to the requirements of a
Combustible Mantel.
Mantel Dimensions are from front face or Non-Combustible Facing Materials
covering fireplace.
Mantel Leg Clearances
Adjacent Wall must be 1-1/2″ from standoff (2″ from edge of front face frame).
Adjacent Wall
Top View
Adjacent Wall 16
MCVP42 Clearance to Combustibles
Clearance to Combustibles MCVP42
Front and Sides
24″
Back (from Stand-offs)
0″
Floor*
0″
*Note: If appliance is installed directly on carpeting or other combustible material other than wood
flooring, a metal or wood panel extending the full width and depth of the appliance must be used.
Carpet, hardwood, or laminate may extend 1 inch above the floor of the appliance.
Minimum Ceiling Height (from bottom of fireplace) 61″
Top (from Stand-offs)
0″
Top of 90° Bend in minimum Enclosure of 61″
2″
Top of 90° Bend in Enclosure over 67″
2″
VENTING SYSTEMS
Top of Horizontal Pipe
1/1/2″
Side & Bottom of Horizontal Pipe
1″ All Vent Systems
Vertical Vent Pipe
1″ All Vent Systems
1″ May be Combustible (Carpet, Hardwood, Laminate, etc.)
55″ MIN for NG 79″ MIN for LP Plus Rise of 1/4″
Per Foot
17
42MCVP-TLK Tile Lip Kit – Optional
The 42MCVP-TLK Kit may be used as a trim around the opening of the fireplace. Fasten with supplied self-tapping screws. NOTE: ONLY NON-COMBUSTIBLE MATERIALS MAY BE PLACED OVER FACE OF FIREPLACE.
ITEM NUMBER
1
QUANTITY
PART NUMBER
4
42MCVP-TLK1
DESCRIPTION Side Tile Lip 39-5/8″ Long
2
2
42MCVP-TLK2 Front Tile Lip 25-7/8″ Long
3
2
42MCVP-TLK3 Rear Tile Lip 24″ Long
4
32
530-685
8-1/2″ Self-Tapping Screw
NON-COMBUSTIBLE FACING MATERIAL
18
MCVP42
Child Safety Screen Installation
Contents of Kit:
[3] Child Safety Screens- Ready to Install
Assembly Instructions: Attach screen to fireplace as per
instructions below. NOTE: Screens are symmetrical from
top to bottom.
WARNING:
Wait until unit is COMPLETELY cool before touching glass or attempting to
install or remove
Child Safety Screens.
First install smaller end screen. Then install side screens.
Press down and push upper clip under top glass door frame.
Hook lower clip onto glass door
frame.
To install screens hook bottom clip onto glass door frame, then press down and
push upper clip under top glass door frame, then release. Clip will hook onto
frame.
Clips
Screens shown locked in place.
Clips
To remove Safety Screens
WAIT UNTIL FIREPLACE IS COMPLETELY
COOL.
Press down on upper clips and remove screen from fireplace glass door.
19
MP42PL
Porcelain Liner Installation
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only parts
specifically approved with this appliance may result in property damage or
personal injury.
Instructions: (NOTE: Porcelain Liners should be installed BEFORE Log Grates or
Glass Tray.)
Step One: Remove Main Burner (refer to Burner Removal section). If Log Grates
or Glass Tray are installed, they must be removed also.
Step Two: Bend retainer clips away from firebox wall (See below).
Step Three: Tilt and slide Liner against wall of firebox. Use caution when
moving liner over pilot area.
Step Four: Bend retainer clips back to secure liner. Step Five: Reinstall all
components.
MP42PL Consists of: [1] Pilot Side Liner
Remove 4 Screws to remove Burner Assembly.
Pilot
Pilot Side Liner
Pilot Side Liner
MCVP42-H Ceramic Glass Units
Do not remove Baffle to install Porcelain Liners.
MCVP42 Tempered Glass Units
Do not remove Glass Heat Deflectors to install Porcelain
Liners.
Baffle
Glass Heat Deflectors
Bend Retainer Clips away from firebox wall. Bend back to secure Porcelain Liner.
Bend Retainer Clips away from firebox wall. Bend back to secure Porcelain Liner.
Note: Warping and Discoloration of Porcelain or Painted Metal Liners Is Not
Covered Under Warranty.
Both Porcelain and Painted Metal Liners may discolor and warp during normal
operation of your appliance. This is normal, and not considered a defect.
20
MP42RL -Brick Liner Installation- When using M42LG Log Grates
MP42RL Consists of: [1] Back Liner
NOTE: Brick Liner must be installed BEFORE M42LG is installed.
NOTE: Either Baffle (MCVP42-H Ceramic Glass Units) or Deflectors (MCVP42
Tempered Glass Units) must be removed. Refer to Baffle Removal / Deflector
Removal sections of manual.
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only parts specifically approved with this appliance may result
in property damage or
personal injury.
1. Remove Baffle (MCVP42-H 2. Orient tabs in upper firebox as shown. Ceramic Glass Units) or Deflectors (MCVP42 Tempered Glass Units).
Refer to Baffle Removal / Deflector Removal sections of manual.
3. Insert Liner into Firebox.
Tab
Tab
4. Bend Tabs down over Brick Liner.
Tab Tab
5. Reinstall all components.
21
MP42RL -Brick Liner Installation- When using MP42GT Glass Tray
Cut Bottom of Liner as shown below.
21-1/8″
NOTE: Brick Liner MUST BE CUT and installed AFTER MP42GT is installed.
NOTE: Either Baffle (MCVST42-H Ceramic Glass Units) or Deflectors (MCVST42
Tempered Glass Units) must be removed. Refer to Baffle Removal / Deflector
Removal sections of manual.
20-13/16″
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only parts specifically approved with this appliance may result
in property damage or
personal injury.
1. Remove Baffle (MCVST42-H Ceramic 2. Orient tabs in upper firebox as shown.
Glass Units or Deflectors (MCVST42 Tempered Glass Units).
Refer to Baffle Removal / Deflector Removal sections of manual.
Tab
Tab
3. Install MP42GT. Refer to MP42GT Installation /
Removal section.
6. Bend Tabs down over Brick Liner.
4. Cut MP42RL Liner as shown above.
– Use caution as Brick Liners are Fragile. –
5. Insert Liner into Firebox.
Tab
Tab
7. Reinstall all components.
22
ZCV42MCVP
Baffle Removal (MCVP42-H Ceramic Glass Units)
To Remove Baffle:
Remove [5] DT Screws holding Baffle in place.
NOTE: Remove end screw last. See below.
To Replace Baffle: Hook Mount Tab onto ledge at top of firebox. Replace end screw first. Replace [4] remaining screws.
Mount Tab
Remove this
Screw last.
ZCV42MCVP
Deflector Removal (MCVP42 Tempered Glass Units)
To Remove Deflectors:
Remove [2] DT Screws holding each
Deflector in place.
To Replace Deflectors:
Slot
Replace [2] DT Screws holding
each Deflector in place.
Ensure that Tab engages
With Slot on small Deflector
Inside unit.
Tab 23
MP42-GT Installation / Removal
Contents of Kit: 1 Glass Tray Instructions: To Install: Place Glass Tray into
firebox as shown.
To Remove: Lift Glass Tray from one edge and carefully remove.
Use caution around pilot area.
42MCVP
NOT FOR USE WITH MP42RL.
NOTE
Pilot Area Must Not Be Covered, as delayed ignition can occur.
Pilot Shield should be visually inspected monthly for signs of deterioration due to flame exposure. Replace if necessary.
The following items can be used with the Glass Tray:
ULK3 Light Kit MQLOG1 MQLOG2 M42LOG3 RBCB1 Cannonballs VLBIT4 or VLBIT6
Decorative Glass MQSTONE MQROCK2 or MQROCK3 MQEMBER Refer to appropriate
section in manual for these items.
Pilot Area Must Not Be Covered
24
M42-LG Installation / Removal
42MCVP
Contents of Kit:
1
1. [2] Log Grates
1
2. [2] Large Bags 3/4″ Lava Rock
3. [3] 350 Embers
2
3
4 5
4. [1] Insulation Wool 5. [1] Grate Plate
3
6
6. [6] DT Screws
2
3
PILOT
Instructions: To Install: 1. Place Grate Assemblies into firebox. 2. Slide
Grate Assemblies under
slotted area of burner tray.
3. Secure with screws. 4. Secure Grate Plate to end of burner
tray with screws. To Remove: 1. Remove screws holding Grate
Assemblies in place. 2. Remove screws holding Grate Plate
in place. 3. Remove from firebox.
GRATE PLATE
Use supplied media with: · MQLOG1 · MQLOG2 · M42LOG4
25
MQ42LOG1
5
8 Piece Driftwood Log Set – For use with GT Glass Tray
8
3
4 7
6
1 2
3
WARNING:
2
Failure to
1
position the
parts in
4
accordance
PILOT
with these
diagrams or
failure to use
only parts
specifically
approved with
this appliance
5 6
may result in property
damage or
personal injury.
8 7
Do not cover more than 25% of Air Slots with media
26
MQ42LOG1
5
8 Piece Driftwood Log Set – For use with M42LG Log Grate
8
3
4 7
1 2
2 1
PILOT 6
6
3 4
Do not cover more than 25% of Air Slots with media
Place 350 Embers from
M42LG in Burner Tray
Place Insulation Wool from M42LG
in Burner Tray
5
Place Lava Rock from M42LG on Grates and
Firebox Bottom 8
7
Place Vermiculite from M42LG on Grates and
Firebox Bottom
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only
parts specifically approved with this appliance may result in property damage
or personal injury.
27
MQ42LOG2 7 Piece Oak Log Set – For use with GT Glass Tray
5 1
3
2 4
7 6
5
3
2 1
4
PILOT
7 6
Do not cover more than 25% of Air Slots with media
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only
parts specifically approved with this appliance may result in property damage
or personal injury.
28
MQ42LOG2 7 Piece Oak Log Set – For use with M42LG Log Grate
5 1
3
2 4
7 6
3
Place 350
1
Embers from
M42LG in
Burner Tray
5
4 2
PILOT
Place Insulation Wool from M42LG in Burner Tray
Place Lava Rock from M42LG on Grates and
Firebox Bottom
7 6
Do not cover more than 25% of Air Slots with media
Place Vermiculite from M42LG on Grates and Firebox
Bottom
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only
parts specifically approved with this appliance may result in property damage
or personal injury.
29
M42LOG3 6 Piece Driftwood Log Set – For use with GT Glass Tray
1
2
6
5
3
4
PILOT
1
2
6 5
4
WARNING:
Failure to
position the
parts in
accordance
with these
diagrams or
failure to use
only parts
specifically
approved with
3
this appliance
may result in
property
damage or
personal
injury.
Do not cover more than 25% of Air Slots with media
30
M42LOG4
7
8 Piece Oak Log Set – For use with M42LG Log Grate
3 5
4
8
6
2
1
4
1 3
Place Insulation Wool from M42LG in Burner Tray
Place 350 Embers from M42LG in Burner Tray
2
PILOT
5
Do not cover more than 25% of Air Slots with media
WARNING: Failure to
position the parts in
accordance with these
diagrams or failure to use
only parts specifically
approved with this
6
appliance may result in
property damage or
personal injury.
Insert Log 7 Peg into
Log 8 Hole
8
Place Lava Rock
7
from M42LG on
Grates and
Firebox Bottom
Place Vermiculite from
M42LG on Grates and Firebox Bottom
31
MCVP42
51UHS Box
Included with base model.
The 51-UHS Box is designed for millivolt and IPI units for in-unit
installation of the Remote Receiver, Fan Control Module, and the IPI Module.
51-UHS Box can be inserted & removed from beneath fireplace through access
panel opening (Remove glass door first). NOTE: When using a remote control,
the 51-UHS Box must be used. Batteries for Remote Receiver can be changed by
lifting 51-UHS up through opening.
Door
IPI Module
Remote Receiver
Fan Control Module
Access Panel
51-UHS can be inserted & removed from beneath fireplace through access panel opening (Remove glass door first).
COMPONENT LOCATIONS
(See Each Section For Connections & Wiring)
51-UHS Box
IPI System (Top View)
Millivolt System (Top View)
32
ULK3
Universal Light Kit (Optional Accent Lighting Kit) MCVP42 & MCVST42
Please follow the current ANSI/NFPA 70 National Electrical Code in the USA and CAN/CSA C22.1 Canadian National Electrical Code in Canada.
Contents of Kit: [2] 12V Halogen Lamps 12VAC Transformer with 3 prong plug &
wire connectors Light Switch & Cover Plate c/w10ft wire c/w [1] Loose
Female & [1] Loose Male wire connector
Inside Firebox
Bottom of
Firebox
INSTALLATION: Remove Glass Tray or Log Grates if installed. Refer to MP42GT, MST42GT or M42LG Installation / Removal. STEP 1: Remove cover plates and install lamps in firebox. Seal with fresh sealant (Mill-Pac).
STEP 2: Connect lamp wires to jacketed transformer leads. Connect switch wires
to black and red wires at transformer, or plug black and red transformer wires
together if 120V receptacle will be switch controlled.
REFER TO COMPONENT LOCATIONS SECTION OF MANUAL FOR TRANSFORMER PLACEMENT. 33
Split Receptacle- Switch Control Outside of Fireplace
If you wish to have a control switch outside of the fireplace for one side of
the receptacle and you require a constant source of AC power inside the unit
for another accessory such as lights or an IPI valve system, follow one of the
procedures below.
WARNING
WARNING
WARNING
A qualified electrician must connect electrical wiring to junction outlet for
built-in installation.
Follow all codes.
Electrical Grounding Instructions This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation and servicing.
Caution: Electrical installation to be done by a qualified installer. All
wires must be connected and grounded in accordance with
CSA Standard C22.1- Canadian Electrical Code part 1 or with the National
Electrical Code, ANSI /NFPA 70 (latest edition) and /or in accordance with
local codes.
Switch Controlled Split Receptacle With Switch At START Of Cable Run
Switch Controlled Split Receptacle With Switch At END Of Cable Run
34
RBCB1 -Cannonballs- Installation Instructions
*Must be used with MST42GT/ MP42GT Glass Tray
Assorted size and colors. Place randomly as desired inside fireplace.
PILOT
Can be used with MQ Glass, MQ Ember, and / or Lava Rock. Do not place
Cannonballs directly on burner ports. If sooting occurs change position of or
remove affected objects.
MQ Glass can be placed directly on Burner and on Glass Tray. MQ Ember can be
placed directly on Burner Only. Lava Rock (Supplied with Base Unit) CANNOT be
placed on Burner. Place Lava Rock in channel in front of
Glass Tray & on Glass Tray.
NOTE
Pilot Area Must Not Be Covered, as delayed ignition can occur.
Do not place Cannonballs directly on burner ports.
Pilot Area Must Not Be Covered
*Pilot Shield should be visually inspected monthly for signs of deterioration due to flame exposure. Replace if necessary.
35
MQ Dealer Accessories for MCVST42 / MCVP42
The following Accessories are available through MQ Dealers only.
ACCESSORY ITEM
DESCRIPTION
MQG5W*
Decorative Glass 1/2″ White
MQG5A*
Decorative Ember Glass Cobalt Blue
MQG5B*
Decorative Ember Glass – Black
MQG5ZG*
Decorative Glass- Zircon Glacier Ice
NOTE: All glass is sold in 5 pound bags.
MQ42LOG2
Driftwood Log Set- 8pcs.
MQROCK2*
Rock Set Natural
MQROCK3*
Rock Set Multi-Color
MQSTONE*
Decorative Stones
MQEMBER*
Glowing Embers
GLASS (MQG5W, MQG5C, MQG5A, MQG5B, MQG5ZG)
If you wish to use this media evenly spread the glass embers onto the false
bottom and burner. Ensure the glass embers do not excessively overlap as this
will affect the flame pattern. Use care when placing glass embers near the
pilot area so as not block or have the glass fall over the crossover holes
from the pilot to the burner, as delayed ignition can occur.
The following types of glass are approved: ½” Ember Glass Material from
American Fireglass.
Maximum amount: 5lbs on Burner Tube and Burner Tray 15lbs on Glass Tray (20lbs
Max. total)
Liquid Glass from Firegear. Maximum amount: 5lbs on Burner Tube and Burner
Tray
15lbs on Glass Tray (20lbs Max. total)
*Must be used with MST42GT/ MP42GT Glass Tray
Zircon Glacier Ice. Maximum amount: 10lbs on Burner Tube and Burner Tray
15lbs on Glass Tray (25lbs Max. total)
Use of any other glass can alter the performance of the unit and is not
covered under warranty.
Discoloration of glass media may occur if placed on the burner, this is not
covered under warranty.
Pilot Area Must Not Be Covered
*Pilot Shield should be visually inspected monthly for signs of deterioration due to flame exposure. Replace if necessary.
MQG5ZG Decorative Glass- Zircon Glacier Ice 10lbs on Burner Tube and Burner
Tray- 15lbs on Glass
Tray (25lbs Max. total) Must be used with MST42GT/ MP42GT Glass Tray
NOTE
Pilot Area Must Not Be Covered, as delayed ignition can occur.
36
MQ STONE / MQ ROCK- Must be used with MST42GT/ MP42GT Glass Tray
The following Accessories are available through MQ Dealers only.
MQ STONE DECORATIVE STONE SET- Must be used with MST42GT/ MP42GT Glass Tray
PILOT
MQ Stone can be placed on or around Burner.
Place Stones onto False Bottom and Burner. Do not place directly on Pilot
Area. Not all stones will be used on some installations. If sooting occurs
change position of or remove affected objects.
MQ ROCK- Must be used with MST42GT/ MP42GT Glass
NOTE
Pilot Area Must Not Be Covered, as delayed ignition can occur.
PILOT
MQ EMBER (shown) can be placed on Burner. MQ Glass can be placed on Burner and
Glass Tray. Place Rocks onto False Bottom and Burner. Do not place directly on
Pilot Area. Not all stones will be used on some installations. If sooting
occurs change position of or remove affected objects.
MQEMBER To be placed directly on Burner and Burner Ports. Place these glowing
ember chunks randomly. May be used with or without other accessories.
NOTE
Pilot Area Must Not Be Covered, as delayed ignition can occur.
NOTE
Pilot Area Must Not Be Covered, as delayed ignition can occur.
Pilot Area Must Not Be Covered
*Pilot Shield should be visually inspected monthly for signs of deterioration due to flame exposure. Replace if necessary.
37
To install Door:
ZCV39 / ZCV42 / MCVST42 / MCVP42 Door Installation
1. Remove Access Cover below Glass Door.
30° 15°
2. Engage door in lower latches at an angle of between 15 and 30 degrees.
3. Swing door up and pull top latches over door lip at each corner.
4. Replace Access Cover below Glass Door.
Door
Bottom Latch
WARNING:
Wait until unit is COMPLETELY cool before touching glass or attempting to
install or remove
Glass Door.
38
Door and Glass Information MCVP42
Glass Cleaning
It will be necessary to clean the glass periodically. During startup,
condensation, which is normal, forms on the inside of the glass, and causes
dust, lint etc. to cling to the glass surface. Also, initial paint curing can
deposit a slight film on the glass. It is therefore recommended that initially
the glass be cleaned two or three times with a fireplace glass cleaner. After
that, the glass should be cleaned two or three times a season depending on the
circumstances.
Cautions and Warnings
Do not clean when the glass is hot. The use of substitute glass will void all
product warranties (see Glass Replacement in this section). Care must be taken
to avoid breakage of the glass. Do not operate this fireplace without the
glass front or with a broken glass front. Do not strike or abuse the glass.
Glass Replacement
MCVP42N, MCVP42NE, MCVP42LP, MCVP42LPE must use tempered glass. Must be 5mm
thick.
Only Robax ceramic or coated Neoceram glass may be used for replacement for
Models MCVP42NH, MCVP42NHE, MCVP42LPH, and MCVP42LPHE. Glass must be minimum
5mm thick.
To replace glass, clean all materials from the door frame. Scrape off old
silicone all the way down to the metal. Using high-temp silicone [rated up to
500°F (260°C)] apply a continuous bead of approximately 1/8″-3/16″ to all four
[4] sides of the frame. With the frame resting on a flat surface, insert the
new glass with a new gasket. Gently press the glass into the silicone. Be
careful not to use excessive force on the glass. Let the silicone dry for
approximately 15-20minutes. Use caution when removing broken glass. Wear
gloves.
Removal of Large Glass Doors
1. Remove the door by unlatching the 2 top latches. Simply place 2 fingers in
the grooves, and pull and lift upward slightly. 2. Once the top of the door is
unlatched, pull it outward and lower it to unlatch the bottom. 3. To re-
install, place the Bottom Door Ledge into the 2 Lower Latch assemblies first.
Then swing the door closed to seal it against
the firebox cavity. Re-latch the Upper Latch assembly to secure the door to
the appliance.
Spring Replacement
*Over time, the door latch spring (Part# 33IDV-123) may need to be replaced if tension is lost. 1. To replace latch spring, remove the 2 hex screws (located in the firebox) that secure the latch assembly in place. 2. Once the screws are removed the latches will slide out of place. 3. Remove the locknut from the latch assembly and replace the spring. Re-tighten the locknut until 2 thread turns are beyond the locknut. This is critical for proper tension. Replace latch assembly.
Latch Assembly 46ZRB-123A
Removal of the Small Glass Door 1. Unlatch the two latches. 2. To remove, pull frame forward and lift from bottom door retainer.
Small Door Latch 350-P400SA
39
Gas Line Installation
This gas appliance should be installed by a qualified installer in accordance with local building codes and with current CAN/CGA –
B149.1 or .2 installation codes for Gas Burning appliances and equipment in Canada and the National Fuel Gas Code ANSI Z223 in
the U.S.A.
1. The gas pipeline can be brought in through
either the right or the left side of the appliance. A knockout is provided at either location to allow
3/8″ UNION
for the gas pipe installation and testing of any
gas connection.
2. The gas control inlet is 3/8″ NPT. Typical installation layout for rigid pipe is shown at right. 3. When using copper or flex connector, use
1/2″ X 3/8″ SHUTOFF VALVE
only approved fittings. Always provide a union
so that gas line can be easily disconnected for
burner or fan servicing. See gas specification for
pressure details and ratings.
4. When a vertical section of gas pipe is required for the installation, a condensation trap
1/2″ GAS SUPPLY
3/8″ NIPPLE
is needed. See CAN/CGA-B149.1 or .2 for code
details.
5. For natural gas, a minimum of 3/8″ iron pipe with gas minimum pressure of 4.5″ w.c. must be used for supply from the gas meter.
Consult with the local gas utility if any questions arise concerning pipe sizes.
6. A 1/8″ NPT plugged tappings are accessible for test gauge connection both on the inlet and outlet of the gas valve.
7. Turn the gas supply ON and check for leaks. DO NOT USE OPEN FLAME FOR THIS PURPOSE. Use an approved leak testing
solution.
8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure
testing of that system at test pressures in excess of 1/2 PSIG (3.5 KPa).
9. The appliance must be isolated from the gas supply piping system by closing its individual shutoff valve during any pressure
testing of the gas sup- ply piping system at test pressures equal to or less than 1/2 PSIG (3.5 KPa).
NOTE: The gas line connection may be made of 1/2″ rigid pipe or an Approved
Kingsman Flex Connector, such as FP15GC. Since some municipalities have
additional local codes, it is always best to consult your local authorities
and the current CAN/CGA –
B149.1 or .2 installation code in Canada or the National Fuel Gas code ANSI
Z223.1 in the U.S.A
For the state of Massachusetts a T-handle gas shut-off valve must be used on a gas appliance. This T-handle gas shut-off valve must be listed and approved by the state of Massachusetts. This is in reference to the state of Massachusetts state code CMR238.
Important: Always check for gas leaks with a soap and water solution. Do not
use open flame for leak testing.
Shutoff valves installed in tubing systems shall be rigidly and securely
supported independently of the
tubing.
MODELS
Gas Specifications
MCVP42N
MCVP42LP
MCVP42NH
MCVP42NE
MCVP42LPE
MCVP42NHE
MCVP42NE2 MCVP42LPE2 MCVP42NHE2
Fuel Natural
Propane
Natural
Gas Control Millivolt / IPI Millivolt / IPI
Millivolt / IPI
Maximum 30,250 BTU 28,500 BTU
31,250 BTU
Low 21,000 BTU 23,000 BTU
21,250 BTU
Orifice Size (0-4500ft)
34
51
34
Air Shutter
1/16″
Fully Open
1/16″
MCVP42LPH MCVP42LPHE MCVP42LPHE2
Propane Millivolt / IPI 29,000 BTU 23,000 BTU
51 Fully Open
Gas Inlet Size S.I.T. 820 Nova, 3/8″ NPT Gas Supply Pressure Natural Gas Propane Manifold Pressure Manifold Pressure High Manifold Pressure Low
Minimum 5.5″ 11″ Natural Gas 3.5 IN. W.C./.87 KPa 1.6 IN. W.C./.40 KPa
Normal 7″ 11″
Maximum 9″ 12″ Propane 10 IN. W.C./2.61 KPa 6.3 IN. W.C./1.57 KPa
40
Millivolt System, Lighting, and Burner Control
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property
damage, personal injury or loss of life.
BEFORE LIGHTING
A This appliance has a pilot which must be lighted by hand. When
· Immediately call your gas supplier from a neighbour’s phone. Follow the
lighting the pilot, follow these instructions exactly.
gas supplier’s instructions.
B Smell all around the appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
· Do not try to light an appliance.
· Do not touch any electrical switch; do not use any phone in your building.
· If you cannot reach your gas supplier, call the fire department.
C Use only your hand to push or turn the gas control knob. Never use tools. If
the knob will not push in or turn by hand, don’t try to repair it. Call a
qualified technician. Force or attempted repair may result in a fire or
explosion.
D Do not use the appliance if any part has been under water. Immediately call
a qualified service technician to inspect the appliance and to replace any
part of the control system which has been under water.
LIGHTING INSTRUCTIONS
1. Stop! Read the safety information above this label.
If a flame has appeared then continue to depress the control knob for 20
2. Set the thermostat to lowest setting.
seconds. If the flame did not appear then continue to depress the red
3. Turn off all electrical power to the appliance.
igniter button every 5 seconds until a flame is established. NOTE: If
4. Locate valve under the burner assembly.
5. If the control knob is not already in the off position, i.e. the word
“OFF” in the 9 o’clock position, then push in the gas control knob slightly
and turn clockwise to “OFF”. NOTE: Knob cannot be turned from “PILOT” to “OFF”
unless knob is pushed in slightly. Do
after 30 seconds a flame has not yet been established then turn the control
knob back to the off position and repeat steps 5, 6 & 7.
9. Once the pilot has been established hold the control knob in the depressed
position for approximately 25 seconds before releasing. If the flame goes out
then repeat steps 7 and 8.
not use force.
· If the knob does not pop up when released, stop and immediately call
6. Wait five [5] minutes to clear out any gas. If you then smell gas.
your service technician or gas supplier.
STOP! Follow “B” in the safety information above on this label. If
· If the pilot will not stay lit after several tries, turn the gas control to
you don’t smell gas then go to the next step.
“OFF” and call your service technician.
7. Now push in the control knob slightly and turn counter-clockwise 10. Now turn the control knob to the “ON” position. The burner will not light
to the “PILOT” position.
unless the wall switch thermostat or remote control is turned “ON” or in
8. Push in the control knob all the way and hold it. With the other
the case of the thermostat there is a call for heat.
hand push in the red igniter button until you hear a click. Now
11. Close the access door and turn all electrical power back to the
observe closely the pilot burner located on the rear center-left
appliance.
hand side of the main burner.
12. The pilot must be turned off when the unit is not in use.
TO TURN OFF THE APPLIANCE
1. Set the thermostat to lowest setting.
4. Push in the gas control knob slightly and turn clockwise to the “OFF”
2. Turn off all electric power to the appliance if service is to be
position. Do not force.
performed.
5. Replace control access panel.
3. Open the control access door.
NOTE: Only one on/off device (manual on/off, remote control, or hard wired
thermostat) should be connected to the appliance at any one time, this is most
important when installing an insert or stove as the on/off rocker switch is
installed at
the factory.
Recommended Maximum Lead Length (Double Wire) When Using Wall Switch or Thermostat
Wire Size
Max. Length
14ga
100ft [30.4m]
16ga
64ft [19.5m]
18ga
40ft [12.1m]
20ga
25ft [7.6m]
22ga
15ft [4.5m]
CAUTION: DO NOT WIRE 120V POWER TO MILLIVOLT SWITCHES OR THERMOSTAT.
To ON/OFF, Wall Switch, Thermostat*, Or Remote Receiver
Millivolt Valve Shown
41
Annual Inspection List for Determining Safe Operation of a Direct Vent Gas
Fireplace Refer to this checklist for proper maintenance, safe use, and
operation.
See each section for more specific information.
1. Inspect and operate all pressure relief mechanisms (i.e., relief dampers,
spring loaded door latches) installed on your appliance to verify relief
mechanisms are free from obstruction to operate.
Relief Dampers inside Firebox should open
and close freely.
Upper Damper
Upper Door Latch
Upper Damper
Spring loaded Door Latches should extend and return to the closed position.
Lower Damper
Lower Door Latch
2. Clean glass window with a suitable fireplace glass cleaner. Abrasive cleaners must not be used. Be careful not to scratch the glass when cleaning.
3. Inspect the operation of the Pilot. Ensure that it is working properly.
Pilot Orientation (Top View)
Burner
Inspect Pilot Flame
4. Inspect and ensure the lighting of the main burner occurs within 4 seconds
of the main gas valve opening. Visual inspection should match that outlined in
the appliance instruction manual (refer to Monthly Flame
Inspection). Inspect primary air openings for blockage.
Burner
Primary Air Opening Inspect for Blockage
5. Inspect condition of vent and vent terminal for sooting or obstruction and
correct if present.
6. Vacuum and clean any debris in the firebox that is not supposed to be
there.
7. Test and measure the flame failure response time of the flame safety
system. It must de-energize the safety shutoff in no more than 30 seconds.
Procedure for Millivolt Units: Turn on fireplace for 5 minutes. Shut off
fireplace while listening to valve. A “click” should be heard within 30
seconds. This indicates the safety shutoff is working properly. Procedure for
IPI Units: Turn on fireplace and allow main burner to come on. Then disconnect
Flame Sense wire from IPI Module (X3 Connection). The fireplace should shut
down immediately.
8. Check all accessible gas-carrying tubes, connections, pipes and other
components for leaks.
42
Burner System Maintenance- MCVST42 / MCVP42
It is recommended to annually inspect and clean the Burner System to prevent
malfunction and / or sooting. This operation should be performed by your
dealer or a qualified technician.
-CAUTION-
Before servicing the burner system ensure that the gas supply is turned OFF
and disconnect all electrical connections to the appliance. Allow the
appliance to cool to room temperature. Note that the pilot assembly may be hot
in an intermittent or standing-pilot system–even if the main burner was never
on. Exercise caution when working within the area.
-ALL WORK SHOULD BE PERFORMED BY A QUALIFIED AND CERTIFIED TECHNICIAN-
Monthly Flame Inspection
Thermocouple / Flame Sense Pilot Burner
Thermopile
It is recommended to turn on the unit at least once a month and inspect the
flame pattern to ensure there are no problems with the burner tube (Flame
should appear similar to the above picture).
The pilot flame should also be inspected monthly to ensure proper operation.
Pilot Must Maintain This Relationship With Burner.
Pilot Shield Area Must Not Be Covered With Media. *Pilot Shield should be
visually inspected monthly for signs of deterioration due to flame exposure.
Replace if necessary.
43
Gas Conversion Part A MCVP42
Models: MCVP42N, MCVP42NE, MCVP42NE2, MCVP42LP, MCVP42LPE, MCVP42LPE2, MCVP42NH, MCVP42NHE, MCVP42NHE2, MCVP42LPH, MCVP42LPHE, MCVP42LPHE2
Kit Number
Description
Pilot Orifice
Burner Orifice Brass Nipple Air Shutter Hi/Lo Regulator
Brass (1000-255)
42MP-CKLP Propane Conversion 1001-P167SI
51
1000-253
Fully Open 1001-P202SI
-Millivolt-
30 (977.167)
Closed
(0.907.202)
42MP-CKNG NG Conversion
1001-P165SI
34
1000-253
1/16″
1001-P201SI
-Millivolt-
51 (977.165)
Closed
(0.907.201)
42MP-CKLPI Propane Conversion 1001-P168SI
51
1000-253
Fully Open 1002-P014SI
-IPI-
35 (977.168)
Closed
(0.907.014)
42MP-CKLP2 Propane Conversion 1001-P168SI
51
1000-253
Fully Open 1002-P012SI
-IPI-
35 (977.168)
Closed
(907.012)
42MP-CKNGI NG Conversion
1001-P166SI
34
1000-253
1/16″
1002-P016SI
-IPI-
62 (977.166)
Closed
(0.907.016)
42MP-CKNG2 NG Conversion
1001-P166SI
34
1000-253
1/16″
1002-P013SI
-IPI-
62 (977.166)
Closed
(907.013)
IMPORTANT: Always check for gas leaks with a soap and water solution. DO NOT USE OPEN FLAME FOR LEAK TESTING.
Parts List:
· HI/LO Pressure Regulator Assembly
· Pilot Orifice · Burner Orifice · Brass Nipple · Instructions · Conversion
Kit Label
Caution:
The gas supply shall be shut off prior to disconnecting the electrical power,
before proceeding with the conversion.
1.The Burner Tube must be removed from the Burner Pan Assembly (See Burner
Tube Removal). Adjust the Air Shutter to the correct Primary Air setting as
specified in the manual or on the label plate. To adjust the Primary Air
setting, loosen screw on the side of the Air Shutter and rotate to the correct
opening using a drill bit or tape measure. Retighten screw.
2.Remove the Main Orifice using a ½” wrench and replace with the new
Conversion Orifice which came with the Conversion Kit.
3. Replace the Burner Tube. Install the new Pilot Orifice (See Pilot
Conversion) and Hi/Lo valve regulator by following instructions supplied with
the Conversion Kit.
Pilot Must Maintain This Relationship
With Burner.
Refer to “Gas Specifications Chart” for inlet pressures and input ratings. Clock meter to verify input rate. Place conversion label as close to converted gas control as possible. Refer to lighting instructions to verify the normal operating sequence of the ignition system.
– WARNING –
This conversion kit shall be installed by a qualified service agency in
accordance with the manufacturer’s instructions and all applicable codes and
requirements of the authority having jurisdiction. If the information in these
instructions is not followed exactly, a fire, explosion or production of
carbon monoxide may result causing property damage, personal injury or loss of
life. The qualified service agency is responsible for the proper installation
of this kit. The installation is not proper and complete until the operation
of the converted appliance is checked as specified in the manufacturer’s
instructions supplied with the kit.
44
Gas Conversion for Top Convertible Pilot Part B (series 0190XYZ)
Instructions for converting SIT 190 series pilot burner injector from NG to
PROPANE and from PROPANE to NG only. This information should be considered as
supplemental to the Appliance Manufacturer’s Instructions.
WARNING! The installation of this conversion kit must only be undertaken by a
qualified and certified gas appliance installer.
1. Shut-off the gas supply to the appliance. 2. Allow the pilot burner to
cool to room temperature.
WARNING: Touching a hot pilot burner can result in injury.
3. The pilot hood is held in place by spring. First remove the spring, then
remove the hood by pulling it up from the pilot bracket (fig. 1).
4. Insert a 5/32″ or 4 mm Allen wrench into the hexagonal key-way of the
injector (fig. 2), and rotate it counter-clockwise until it is free of the
injector journal.
5. Verify that the new injector is proper for the application. The injector
size is stamped on the side of the injector near the top. Propane injectors
have a groove machined around their circumference near the top, while NG
injectors do not have a groove (fig. 4). Refer to the Appliance Manufacturer’s
instruction sheet for the proper injector size.
6. Insert the Allen wrench into the end of the injector. Then, insert the
injector into injector journal, and rotate the injector clockwise until a
torque of 9 lbf in (1.0 Nm) is achieved.
7. First replace the pilot hood by aligning the tab on the base of the hood
with the slot in the side of the pilot journal, and push the hood down, onto
the pilot bracket (fig. 3). The hood must sit squarely on the bracket for
proper operation. Then replace the spring by pushing it on his seat (fig.3).
Check to insure that the hood is properly seated onto the pilot bracket and
that the spring is properly inserted onto his seat.
8. Restore the gas supply to the appliance, and ignite the pilot burner.
Verify proper ignition and operation.
WARNING!
This conversion kit must ONLY be applied as part of a conversion kit supplied
by the APPLIANCE MANUFACTURER for the specific appliance, and type of gas,
being converted.
SIT GROUP
w w w . s i t g r o u p . i t
45
Gas Conversion for Modulator PART C
46
MCVST42 / MCVP42
Main Burner Removal
If Glass Tray or Log Grates are installed, refer to MCVST42GT or MCVST42LG Installation / Removal page in this manual.
To remove burner, Lift Pilot Shield off of Pilot.
Remove four [4] screws from burner.
Slide burner away from pilot and lift to remove.
– WARNING-
Turn off Unit and allow to cool before cleaning. Only a Qualified service
technician should service and repair this appliance.
MCVP42
Burner System Removal / Installation
Removal: If Glass Tray or Log Grates are installed, refer to MCVP42GT or MCV42LG Installation / Removal page in this
manual. Then refer to Burner Removal instructions above to remove burner.
Remove fourteen [14] screws around edge of Burner Pan. Carefully work the burner pan loose & lift the assembly
upward to remove it from the firebox cavity.
Installation is the reverse of these steps. Ensure that the mounting surface is clean. Use fresh Black Mill Pac to reseal the burner pan.
Burner Pan NOTE: Pilot connections through Burner Pan
must be sealed with Red Silicone.
– WARNING-
Turn off Unit and allow to cool before cleaning. Only a Qualified service
technician should service and repair this appliance.
47
IPI Electronic Ignition System
Overview
The IPI system is an advanced burner controller that provides you with the
option of having either a StandingPilot, or an intermittent igniting system.
This alternating mode is controlled by the CPI/IPI Switch (Continuous Pilot
Ignition/Intermittent Pilot Ignition) located on the IPI System Box. The
difference between a Standing-Pilot and an Intermittent-Pilot is in whether
the pilot stays lit or shuts off:
In Standing-Pilot, the pilot assembly is lit by the IPI Main Module and
continues to stay lit until 1) the CPI/IPI Switch is switched to the IPI
position; 2) a loss of electrical power (battery and AC source), 3) the flame
sensor loses its signal, 4) the fuel supply discontinues, or 5) the IPI Main
Module malfunctions.
UHS Box Cover
Backup Battery Pack
Remote Receiver Module
CPI / IPI Switch
In the Intermittent-Pilot mode, the pilot shuts off when the appliance is not
in use. The advantage of this mode is that fuel is not consumed when the
fireplace is not operating.
NOTE: In some jurisdictions Intermittent-Pilot is required. That means the
pilot cannot remain lit when the appliance is not operating.
Components The core of the IPI system is the Main Module and the IPI Valve.
With these two components the system is able to operate a gas fireplace. There
are also other components available to complement the IPI system.
IPI Module Fan Control Module
AC Adapter Plug In
IPI System Cover: Is essential in keeping the components at
their proper operating temperatures. DO NOT OPERATE THE APPLIANCE WITHOUT THIS
COVER.
Modulating Servo Motor: Is an add-on valve component that permits HI/LO functionality to be controlled by the remote. Contrary to this feature is a Manual HI/LO Control Knob. The Modulating Servo Motor requires the Remote system to be present.
Backup Battery Pack: This component permits the IPI system to operate without the need for an external AC Adapter power source. The advantage to using the battery backup is that in the case of a power failure, the appliance is still operable.
NOTE: In certain instances the IPI Main Module requires resetting. This can occur if the system is unable to ignite the pilot or the main burner in the allotted time period. The IPI is programmed to lockout all commands. To reset this lockout you must deplete the system of all electrical power. This means to remove the batteries from the Battery Pack, remove the batteries from the Remote Receiver (if applicable), and disconnect the AC Adapter from the system. Leave the power off for approximately 25 seconds to clear its lockout.
Remote Receiver: This component provides the capability of controlling the appliance with a wireless remote transmitter.
Standing Pilot Mode for Colder Climates (Below Freezing) For IPI models it may
be necessary to set the appliance to Standing Pilot mode to maintain heat in
the cavity. The purpose of this procedure is to prevent cold air from
penetrating the chimney and then onto the living space. Therefore, when the
internal temperature is slightly elevated the fireplace is able to freely
exhaust its combustion and hence making it easier to startup.
NOTE: The pilot system for this appliance may be equipped with a Seven Day
Timer, in which case the pilot flame will be extinguished if the main burner
has not been turned ON for seven days. This Seven Day Cycle is reset every
time the main burner is cycled ON / OFF and the pilot remains lit. If more
than seven days has passed since the main burner has been cycled ON / OFF and
the pilot is also out, follow the procedures described in this manual to light
the pilot.
48
Proflame 1 -Remote Control Operation-
The Proflame GTM is configured to control the on/off main burner operation, its flame levels, and provides on/off and Smart *thermostatic control of the appliance.
Transmitter
Remote Receiver
Transmitter The Transmitter is powered by 3 AAA type batteries. A Mode Key is
provided to Index between the features and a thermostat Key is used to turn
on/off or index through thermostat functions
Remote Receiver The Receiver connects directly to the gas valve and stepper
motor with a wiring harness. The Receiver is powered by 4 AA type batteries.
The Receiver three position slider switch can be set to one of three
positions: ON (Manual Override), Remote (Remote control) or Off.
Initializing the System for the first time Install 4 AA batteries into the
receiver battery bay. Install 3 AAA type batteries in the Transmitter battery
bay. Place the 3 position slider switch in the “Remote” position. Insert the
end of a paper clip into the hole marked “PRG” on the Receiver front cover.
The Receiver will “beep” three (3) times to indicate that it is ready to
synchronize with a Transmitter. Push the On button. The Receiver will “beep”
four times to indicate the Transmitter’s command is accepted. The system is
now initialized.
Temperature indication Display With the system in the “OFF” position, press
the *thermostat Key and the Mode Key at the same time. Look at the LCD screen
on the Transmitter to verify that a C or F is visible to the right of the Room
Temperature display.
Turn the Appliance On or Off Press the ON/OFF Key on the Transmitter
Remote Flame Control The Proflame GTM has six (6) flame levels. Pressing the
Down Arrow Key once will reduce the flame height by one step until the flame
is turned off. The Up Arrow Key will increase the flame height each time it is
pressed. If the Up Arrow Key is pressed while the system is on but the flame
is off, the flame will come on in the high position.
Room thermostat ( Transmitter Operation) The Remote Control can operate as a
room thermostat. To activate this function, press the thermostat Key. The
LCD display on the Transmitter will change to show that the room thermostat
is “ON” and the set temperature is now displayed. To adjust the set
temperature, press the Up or Down Arrow Keys until the desired set temperature
is displayed on the LCD screen of the Transmitter.
Smart thermostat (Transmitter Operation) The Smart thermostat function
adjusts the flame height in accordance to the difference between the set point
temperature and the actual room temperatures. As the room temperature gets
closer to the set point the Smart Function will modulate the flame down. To
activate this function, press the *thermostat Key until the word “SMART”
appears to the right of the temperature bulb graphic. To adjust the set
temperature, press the Up or Down arrow Keys until the desired set point
temperature is displayed.
Key Lock Function This function will lock the keys to avoid unsupervised
operation. To activate this function, press the MODE and the UP Arrow Key at
the same time. To de-activate this function, press the MODE and the UP Arrow
Key at the same time.
Low Battery Detection Transmitter – When the Transmitter batteries are low, a
Battery Icon will appear on the LCD display of the Transmitter. Receiver –
When the Receiver batteries are low, No “beep” will be emitted from the
Receiver when it receives an On/Off command from the Transmitter. When the
batteries are replaced the “beep” will be emitted from the Receiver when the
ON/OFF Key is pressed (See Initializing the System for the first time).
Manual Bypass Of The Remote System If the batteries of the Receiver or
Transmitter are low or depleted, the appliance can be turned on manually by
sliding the three position slider switch on the Receiver to the ON position.
This will bypass the remote control feature and the appliance main burner will
come on if the gas valve is in the “On” position.
Wall Mount Option
10ft. Extension Harness (Part No. 1001-P904SI) required.
· The Remote Receiver can be mounted on a vertical wall stud using the DCHS as
a mounting bracket.
· Ensure that the face is protruding 1/2″ so that the face plate will be flush
on the face of the wall.
· Drywall cutout size is 2″ wide by 4-1/8″ tall. · Must be installed within
10ft of valve assembly (6ft
recommended). 49
Proflame 1
-IPI System Parts List-
PART NO. 1. 1006-P002SI 2. 1006-P003SI 3. 1002-P302SI 4. 1002-P047SI 5.
1002-P033SI 6. 1002-P850SI 7. 1002-P12BH 8. 1001-P280SI
9. 1001-P166SI
DESCRIPTION Valve IPI Hi/Lo NG Valve IPI Hi/Lo LP IPI Ignition Board Pilot
Assembly-LP -24″ Wire Pilot Assembly-NG -24″ Wire AC Wall Adapter Battery Pack
TC – Tubing W/Fittings 1/8 2.182.280
TC – Orifice Pilot NG 977.166 #62 (IPI)
10. 1001-P168SI TC – Orifice Pilot LP 977.168 #35 (IPI)
11. 1002-P012SI 12. 1002-P013SI 13. 1002-P014SI 14. 1002-P016SI 15.
1002-P017SI
16. 1002-P119SI
17. 1002-P903SI
18. 1002-P910SI
IPI Stepper Kit – LP 907.012
IPI Stepper Kit – NG 907.013 IPI Reg Kit – LP Hi-Lo 907.014
IPI Reg Kit – NG Hi-Lo 907.016 TC – Electrode Cable & Sparker IPI 915.017 24″
TC – Electrode Cable & Sparker IPI 35″ (Infinite, ZCVRB47, VRB46) TC –
Electrode Flame Sense IPI 007.253/915.903 24″
TC – Electrode Flame Sense 35″ (Infinite, ZCVRB47, VRB46)
Proflame Transmitter 1001-P023SI
NOTE: Fan and / or Light Options are not available on some fireplaces. Check
with your dealer.
4&5 8
FAN OPTION NOT AVAILABLE
1&2
3
Proflame Receiver
6
1001-P221SI
7
50
Configuration #1: Basic manual HI/LO and manual ON/OFF capabilities.
FAN OPTION NOT AVAILABLE
51
Proflame 1- Configuration #2: Remote ON/OFF and Manual HI/LO Capabilities
OPTIONAL: For units with remote HI/LO capabilities, a modulating servo is
required to be installed on the valve. The connectors to this servo must be
connected to the Remote Harness as shown.
SCHEMATIC
PICTURE
1001-P221SI
FAN OPTION NOT AVAILABLE
NOTE: Fan Option is not available on some models of fireplace. Check with your dealer.
52
Operating the Receiver Without Batteries for GT / EGT / GTM / EGTM Remote
Controls
-Wiring Harness P/N 1002-P906si required for both IPI & Millivolt systems. -Millivolt Systems will also require Power Adapter P/N 1002-P850si. The Remote Receiver & IPI or Millivolt system can be powered by the AC Adapter. This is advantageous if you do not want to use batteries. Simply connect the AC Adapter into the Remote Control Wiring Harness as per the diagrams below.
IPI System EGTM
Receiver Module 0.584.523/521/221 1001-P221SI
Millivolt System GTM
Receiver Module 0.584.523/521/221 1001-P221SI
53
Proflame 1- Configuration #3: Remote ON/OFF, variable HI/LO, and fan capabilities
Refer to the fan installation/removal section for fan installation.
SCHEMATIC
NOTE: This Configuration is not available on all models of fireplace. Check with your dealer.
FAN OPTION NOT AVAILABLE
PICTURE
FAN OPTION NOT AVAILABLE
NOTE: Fan Option is not available on some models of fireplace. Check with your dealer.
54
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which automatically
lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING smell around the appliance area for gas. Be sure to smell
next to the floor because some gas is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electric switch; do not use any phone
in your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.
C. Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and replace any
part of the control system and any gas control which has been under water.
D. If the gas valve requires repair, call a qualified service technician.
Force or attempted repair may result in a fire or explosion.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Read the owner’s manual including the section on “Remote Control”
operation if applicable.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically
lights the pilot. Do not try to light the pilot by hand.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including
near the floor. If you smell gas, STOP! Follow “B” in the safety information
above this label. If you do not smell gas, go to next step.
6. Turn on all electric power to the fireplace.
7. Turn “On” Switch that operates the Main Burner. For Remote Control units,
press the ON/OFF key on the remote control. “ON” will be displayed on the LCD
display and a “beep” will be heard at the unit to indicate the command has
been received.
8. If the appliance will not operate, follow the instructions “To Turn Off
Gas To Appliance” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting.
For Remote Control units, press the ON/OFF key on
the remote control. “OFF” will be displayed on the LCD display and a “beep”
will be heard at the unit to indicate the command has been received.
2. Turn off all electric power to the fireplace if service is to be performed.
55
Proflame 2 NE2 / LPE2
-IPI System Parts List-
IPI PROFLAME 2 – COMPONENT PARTS
PART NO.
DESCRIPTION
1. 1005-P001SI Valve IPI Proflame PF2 885.001 NG – Stepper
2. 1005-P002SI Valve IPI Proflame PF2 885.002 LP – Stepper
3. 1005-P325SI Module IPI – Proflame 2 – 584.325
4. 1005-P627SI 5. 1005-P924SI
Module IPI Proflame 2 – Basic – 584.627 Harness PF2 – 584.924
6. GTMFL
Transmitter- PF2 – 584.090 – WiFi Version
6b. 1005-P042SI Transmitter- PF2 – 584.042 – Non-WiFi Version
6c. 1005-P080SI Transmitter- PF2 – 584.080 – WiFi Version
For Replacement Transmitters, Replace with Same Part Number
7. 584-PWR-C Wire Harness PF2 Power Cord
8. 584-X4P
Terminal Block
9. 584-X10
Wire Harness PF2
10. 584-ACC01-C Wire Harness PF2 – Fan/Light
11. 584-X8-B
Wire Harness PF2 – Optional Reset Harness
12. 584-X12
Optional Power Vent Harness
6 Proflame Transmitter 0.584.090 – WiFi Current Version
13
IPI – PF1 and PF2 Common Components
PART NO.
DESCRIPTION
13. 1002-P033SI TC – Pilot Burner IPI (Assembled) NG 199.033
14. 1002-P047SI TC – Pilot Burner IPI (Assembled) LP 199.047
15. 1001-P166SI TC – Orifice Pilot NG 977.166 #62 (IPI)
16. 1001-P168SI TC – Orifice Pilot LP 977.168 #35 (IPI)
17. 1001-P280SI TC – Tubing W/Fittings 1/8 2.182.280
18. 1002-P012SI 19. 1002-P013SI
IPI Stepper Kit – LP 907.012 IPI Stepper Kit – NG 907.013
P2 CONVERSION
20. 1002-P014SI 21. 1002-P016SI
IPI Reg Kit – LP Hi-Lo 907.014 IPI Reg Kit – NG Hi-Lo 907.016
P1 CONVERSION
22. 1002-P017SI TC – Electrode Cable & Sparker IPI 915.017 24″
23. 1002-P119SI
TC – Electrode Cable & Sparker IPI 35″ (Infinite, ZCVRB47, VRB46)
24. 1002-P12BH IPI Battery Housing 12bh347-Gr
25. 1002-P903SI
TC – Electrode Flame Sense IPI 007.253/915.903 24″
26. 1002-P910SI
TC – Electrode Flame Sense 35″ (Infinite, ZCVRB47, VRB46)
NOTE: Fan and / or Light Options are not available on some fireplaces. Check with your dealer.
6b Proflame Transmitter 0.584.042 – Non-WiFi
6c Proflame Transmitter 0.584.080 – WiFi
5
7
1&2
8
10
FAN OPTION
3&4 9
NOT
11
AVAILABLE
10 12
56
IPI Proflame 2 IFC Module and Remote Control
Batteries
IFC Module
SW1 Button
Pairing Remote Control:
· Install the 3 AAA type batteries in the battery bay, located on the base of
the Remote Control. Note polarity of the batteries and insert them as
indicated.
· Connect the AC power supply to the IFC Module.
· Press the SW1 button on the IFC Module so the IFC will “beep” and a red LED
is illuminated to indicate that the IFC Module is ready to synchronize with a
Remote Control within 10 seconds. With the batteries already installed in the
Remote Control, push the ON button. The receiver will “beep” four times to
indicate the Remote Control’s command is accepted.
The system is now initialized.
Resetting Proflame 2 IFC Module for Manual Use
If the transmitter gets misplaced, is broken, or is no longer wanted the PF2
Module can be reset to a manual system. A manual on/off switch or thermostat
may be installed at the X4 connector (this connection is Jumped at the
factory) no power is required.
The following sequence must be followed to reset the PF2 Module:
· Press the Red SW1 button until you hear three beeps. · Within 10 seconds
press the SW1 button again until
you hear it beep. · The PF2 Module may now be turned on/off manually
(x4 connector) by a switch (not supplied), the pilot will
remain on CPI (continuous pilot ignition) mode, all other functions of main
burner, fan and lights will be on the high setting. Fan Startup and Shutdown
Timings: Fan setting is started with a delay of 5 minutes from the fireplace
ignition and stopped with a delay of 12 minutes from the fireplace switching
off. Low Battery Power Detection When the Remote Control’s batteries are low,
a Battery Icon will appear on the LCD display before all power is lost. When
the batteries are replaced this icon will disappear. Battery Backup The PF2
module is powered by line voltage (AC) with provision of battery backup in
case of main power loss. Fans and lighting features will not function with the
PF2 Module is powered by battery backup. It is recommended that the 4 x AA
batteries are changed before each heating season.
57
Cold Climates CPI Setting – Proflame 2 Remote Control
Use the CPI setting during cold weather, otherwise the fireplace may have a
hard time starting up and establishing a flame. The CPI (Continuous Pilot
Ignition) setting will keep the firebox and fireplace exhaust vent warm during
cold weather. When the firebox and exhaust vent are warm, exhaust gasses will
readily flow out of the firebox.
If the firebox and venting are too cold, there is resistance due to the heavy
cushion of cold air, and combustion gasses may not rise into the exhaust vent,
thus causing the fireplace to cycle or Lockout (if this happens see Lockout
Reset Procedures below).
NOTE: The pilot system for this appliance may be equipped with a Seven Day Timer, in which case the pilot flame will be extinguished if the main burner has not been turned ON for seven days. This Seven Day Cycle is reset every time the main burner is cycled ON / OFF and the pilot remains lit. If more than seven days has passed since the main burner has been cycled ON / OFF and the pilot is also out, follow the procedures described in this manual to light the pilot.
To switch from IPI to CPI Mode:
1. Turn the fireplace OFF using the ON / OFF Key.
2. Press the Mode Key. Display will appear as below.
3. Press UP on the UP / DOWN Arrow Key. Display will show CPI.
The module in the fireplace will beep once to confirm command.
TO RETURN TO IPI (INTERMITTENT PILOT) MODE:
Repeat steps one and two, and then press DOWN on the UP / DOWN Arrow Key. The
module in the fireplace will beep once to confirm command.
Lockout Reset Procedures Proflame 2
If the fireplace has cycled too many times in a short period of time, it will
shut down and become unresponsive to any new command.
The LED light on the Proflame 2 module in the fireplace will be flashing red.
This condition is a Lockout state.
Lockout Reset Procedure:
1. Disconnect power from the Proflame 2 module in the fireplace for 10
seconds. This includes removing the backup batteries.
2. Once the 10 second interval has passed, reconnect power and reinstall
backup batteries. The pilot should now try to light.
3. If the fireplace does not come on, call your fireplace technician.
58
Proflame 2 Remote Control
59
Note: When Smart Thermostat is activated, manual flame height adjustment is
disabled.
FAN OPTION NOT AVAILABLE
(Halogen lights only)
Note: This function is only
available in Room Thermostat or
Smart Thermostat Control Mode.
60
FAN OPTION NOT
AVAILABLE
61
Vent Terminal Clearances
NOTE: A HORIZONTAL VENT CERTIFIED GUARD (SAFETY CAGE) IS AVAILABLE WHEN
REQUIRED BY LOCAL CODES.
Clearances are to the edge of the terminal plate. Add 6-3/4″ to clearances to
arrive at centerline. Local codes or regulations may
require different clearances.
N
Canadian installations1
US installations2
A Clearance above grade, veranda, porch, deck, or balcony
12 in (30 cm)
12 in (30 cm)
B Clearance to window or door that may be opened
6 in (15 cm) for appliances 10,000 Btu/h (3 kW), 12 in (30 cm) for appliances
10,000 Btu/h (3 kW) and 100,000 Btu/h (30 kW), 36 in (91 cm) for appliances 100,000 Btu/h (30 kW)
6 in (15 cm) for appliances 10,000 Btu/h (3 kW), 9 in (23 cm) for appliances > 10,000 Btu/h (3 kW) and 50,000 Btu/h (15 kW), 12 in (30 cm) for appliances > 50,000 Btu/h (15 kW)
C Clearance to permanently closed window
12 inches (30cm) recommended to prevent condensation on window
12 inches (30cm). 9 inches (23cm) for appliances 50,000 Btu’s and lower
D Vertical clearance to ventilated soffit 18 inches (46cm) located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal
18 inches (46cm)
E Clearance to unventilated soffit
12 inches (30cm)
12 inches (30cm)
F Clearance to outside corner
3″ *
3″ *
G Clearance to inside corner
3″ *
3″ *
H Clearance to each side of center line 3 ft (91 cm) within a height 15 ft (4.5 m) above the 3 ft (91 cm) within a height 15 ft (4.5 m) above
extended above meter/regulator
meter/regulator assembly
the meter/regulator assembly
assembly
I Clearance to service regulator vent outlet
3 ft (91 cm)
3 ft (91 cm)*
J Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
6 in (15 cm) for appliances 10,000 Btu/h (3 kW), 12 in (30 cm) for appliances
10,000 Btu/h (3 kW) and 100,000 Btu/h (30 kW), 36 in (91 cm) for appliances 100,000 Btu/h (30 kW)
6 in (15 cm) for appliances 10,000 Btu/h (3 kW), 9 in (23 cm) for appliances > 10,000 Btu/h (3 kW) and 50,000 Btu/h (15 kW), 12 in (30 cm) for appliances > 50,000 Btu/h (15 kW)
K Clearance to a mechanical air supply 6 ft (1.83 m) inlet
3 ft (91 cm) above if within 10 ft (3 m) horizontally
L Clearance above paved sidewalk or 7 ft (2.13 m) paved driveway located on public property
*(Notes: 2)
M Clearance under veranda, porch deck, or balcony
12 in (30 cm)
12 in (30 cm) *
N Where a vent termination may cause **(Notes: 1) hazardous frost or ice accumulations on adjacent property surfaces
*(Notes: 2)
O Clearance above highest point of exit 18 in (45cm) on roof
18 in (45cm)
P Clearance to perpendicular or adjacent 24 in (60cm) wall
24 in (60cm)
Notes:
It is imperative that the vent termination be located observing the
- In accordance with the current CSA B149.1, Natural Gas and Propane Installation minimum clearances as shown. There must not be any obstruction
Code.
such as bushes, garden sheds, fences, decks or utility buildings within
- In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code. 24″ from the front of the termination plate.
- Clearance in accordance with local installation codes and the requirements of the gas supplier.
Do not locate termination where excessive snow or ice build-up may occur. Be sure to check vent termination area after snow falls and clear
** A vent shall not terminate directly above a paved sidewalk or paved
driveway that is located between two single family dwellings and serves both
dwellings. Note: This does not apply to non-condensing appliances (Province of
Ontario ONLY).
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum
of two sides beneath the floor.
to prevent accidental blockage of venting system. When using snow blowers,
make sure snow is not directed towards vent termination area.
Venting terminal shall not be recessed into a wall or siding. If finishing the
outside wall with vinyl or wood siding it is recommended that a Siding Shield
be installed, Part Number ZDVSSLR.
62
General Vent Installation Information
This gas appliance is approved to be vented either through the side wall or
vertically through the roof. Only Kingsman Flex (Z-Flex) Venting Kits and
components specifically approved and LABELED for this stove may be used. This
appliance is also approved for use with 5 x 8 M&G-Duravent Direct Vent system
(Model DV-GS Series), BDM Pro Form Direct Vent, Ameri-Vent Direct Vent Pipe
System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
Rigid or Hard Pipe When using 5 x 8 M&G-Duravent, Ameri-Vent pipe, BDM Pro
Form Direct Vent, ICC Excel Direct, Metal Fab Sure-Seal DV and or Selkirk
Direct Temp a 5 x 8 M&G Duravent hard pipe adapter must be used (part #
Z58DFA). Follow installation instructions provided by M&G-Duravent/Ameri-
Vent/Selkirk Direct Temp, ICC Excel Direct, and Metal Fab Sure-Seal DV for
installation of pipe and adhere to the clearance to combustibles provided in
this manual. Apply a bead of Mill Pac high temp sealant to all joints of
pipes, adapters and termination, when using Kingsman Flex (Z-Flex) venting and
M&G-Duravent venting. NOTE: Increase framing depth by one inch when using hard
pipe.
Flex Pipe Venting Kingsman Flex pipe is shipped in unexpanded length. When
installing pipe expand the lengths. Pipe can be expanded to twice their
lengths e.g. 4ft to 8ft. Fully expand pipe and cut off excess. Do not use more
than 2 couplers to extend short pipes. Single sections are preferred in an
installation attaching at the fireplace and termination.
Place the spring spaces provided approximately every two feet to stabilize 5″
flex in the center of 8″ flex. When forming bends place spring in bend or
before and after. (See Fig. 1). Horizontal runs require support metal straps
every 2 feet. In offset installation support straps should be used to
stabilize pipe. Expand 5″ and 8″ flex pipe to the point that the 8″ protrudes
approximately 2 to 3 inches past outer wall and the 5″ flex protrudes
approximately 2 to 3 inches past the 8″ flex. (See Fig. 1). Attach the 5″ pipe
to the termination first and secure with sealant and screws then attach the 8″
flex to the termination with caulking and screws. Termination may then be
moved back to the outer wall and attached to home screwing into the framing.
Silicone around termination to waterproof. If siding shield is going to be
used attach this using same attaching hole as the top of termination after
termination has been caulked for water proofing.
Use Hi Temp Sealant Apply a bead of Mill Pac high temp sealant to all joints
and use four screws to secure each pipe at fireplace, termination and any
joint if joining any sections of pipe.
Preventing Moisture Problems Insulate wall thimbles and support boxes for
vertical attic terminations with non-combustible mineral wool Insulation
(Roxul, Rockwool, Thermafiber UltraBatt, etc.). Attach and seal the outer
perimeter of the wall thimble or support box to the existing vapor barrier.
FRAMING DIMENSION
Combustible Wall Cut a 12″ hole through exterior wall and frame as shown. Non-
Combustible Wall Cut or drill 9″ diameter hole.
NOTE: It is critical to the proper and safe operation of this fireplace that on all connections the inner liner and the outer casing are both caulked with liberal amounts of sealant. Do not use any kind of tape or silicone other than that recommended in this manual. Use Mill Pac Sealant.
WARNING: DO NOT mix parts from different systems unless stated in the manual.
63
Installation of Side Wall Venting
1. To determine the minimum distance from the bottom of fireplace to center
of vent see the Framing Your Gas Fireplace section. Cut a hole through the
wall allowing for a 12″ x 12″ (inside diameter) in combustible walls for wall
thimble or a 9″ diameter hole in a non-combustible wall (See Figure 2).
2. For the clearance to combustible above a 90-degree bend see Clearance to
Combustibles section.
3. Select the approximate vent length, precise measurements are not needed as
your flex pipe can be expanded to twice its shipped length for ease of
installation.
4. To install wall thimble center over 12″ x 12″ (inch) framing from both
sides of wall and secure. Route flex vent pipe through wall thimble (See
Figure 1).
5. Before joining pipes, apply a bead of high temperature sealant (Mill Pac)
to end of pipe. First attach the five-inch (5″) flue pipe to the vent
termination with sealant, and secure with the four screws provided. At this
time make sure the spacer springs are attached to the (5″) flex pipe as
required. Then attach the eight-inch (8″) pipe by the same method.
6. Mount vent termination and seal to wall using caulking around the wall
thimble to weather proof. After installing the vent termination, double check
to make sure the pipe extends properly through wall thimble and into vent
termination.
7. Before joining pipes to fireplace flue, apply a bead of high temperature
sealant (Mill Pac) to end of pipe. First attach the five-inch (5″) flue pipe
to fireplace with sealant, and secure with the four screws provided. At this
time verify that the spacer springs are attached properly to the (5″) flex
pipe as required. Then attach the eight-inch (8″) pipe by the same method.
8. Support horizontal pipes every two (2) feet (61 cm) with metal strap
bands. Re-check fireplace to make sure it is levelled and properly positioned
and secured.
9. Support vertical pipes to maintain a minimum of 1″ or greater clearance to
combustibles with metal strapping bands. 10. If finishing the outside wall
with vinyl or wood siding it is recommended that a Siding Shield be installed,
Part Number
ZDVSSLR.
Note: Vent Termination must not be recessed into wall or siding.
WARNING: A HORIZONTAL VENT CERTIFIED GUARD (SAFETY CAGE) IS AVAILABLE WHEN
REQUIRED BY LOCAL CODES.
MINIMUM 1″ TO COMBUSTIBLES
MIN 55″ FOR MCVP42N MIN 79″ FOR MCVP42LP
Figure 1
12″ 12″
9″ DIA
MIN 55″ FOR MCVP42N MIN 79″ FOR MCVP42LP
THROUGH COMBUSTIBLE WALL
THROUGH NON-COMBUSTIBLE WALL
Figure 2
64
Venting Routes And Components
Venting Routes and Components Since it is very important that the vent system
maintain its balance between the combustion air intake and the flue gas
exhaust, certain limitations as to vent configurations apply and must be
strictly adhered to. The table showing the relationship between vertical and
horizontal side wall venting will help to determine the various vent lengths.
The maximum horizontal run is 20 ft/6.1 m when the vertical run is 7 ft. /
2.1m (Figure #2). Note: 1/4″ vertical rise is required for every 12″ of
horizontal run. The maximum number of 45 degree bends per side wall
installation is two (2) in the horizontal run and then you must reduce the
length of the horizontal by 18 inches for each 45 degree bend. The maximum
vertical run is 43 ft. / 13.1meters. Special Note: For each 45 degree bend
installed in the horizontal run, the length of the horizontal run must be
reduced by 18″ (45cm). This does not apply if the 45 degree bends are
installed on the vertical part of the vent system.
Example: If according to the table, the length of the horizontal run is 10
feet, and two 45 degree bends are required, the horizontal run length must be
reduced to 7 feet.
2 additional 90° bends or equals are allowed. The horizontal run must be
reduced by 36″ per each 90° bend, or 18″ per each 45° bend.
IMPORTANT: Always locate the fireplace in such a way that a minimum of offsets
and/or horizontal runs are required. 1/4″ vertical rise is required for every
12″ horizontal run.
Figure 1
12 FEET
6 FEET Plus ¼” Rise/Ft = 73-1/2″
Figure 2 7 FEET
20 FEET MAX
Support Straps Every 2 Feet
How to Use the Horizontal Vent Table 1. Determine the height of the system and
the number of
bends required. 2. Having determined the vertical distance determine the maxi-
mum horizontal section allowed. 3. Vent table has been established for 90°
horizontal/vertical
runs. With use of flex pipe distance not having 90° bends will not fall into
vent table standards. See Fig. B.
-Horizontal Venting Table from Bottom of Fireplace-
For venting to a maximum of 43ft (13.1 meters).
Total Vertical
Max Total Horizontal
Feet
Meters
Feet
Meters
55″ (MCVP42N)
1.3
5
1.5
67″
1.6
8
2.4
6
1.8
12
3.7
79″ (MCVP42LP)
2.0
12
3.7
7
2.1
20
6.1
8
2.4
20
6.1
9
1.8
20
6.1
10
3.0
20
6.1
11
3.4
20
6.1
12
3.7
20
6.1
13
4.0
20
6.1
14
4.3
20
6.1
15
4.6
20
6.1
20
6.1
20
6.1
25
7.6
15
4.6
30
9.1
10
3.0
43 (Max)
13.1
0
0
Example A:
If the vertical dimension from the floor of the fire- place is 6ft, the
horizontal run to the wall flange of the vent termination must not exceed
12ft.
12 FEET MAX
NOTE: The final location of the fireplace must be such that the horizontal vent dimensions fall within those stated on the graph. The Maximum Vertical vent run is 43ft. (13.1 meters).
Important: Minimum clearance between vent pipes and combustible materials is1 inch (25mm).
For Propane Horizontal installations the venting must be an additional two
feet above the minimum
vertical rise off the flue before going horizontal.
65
Z58HT Horizontal Installations- Wall Thimble Sizing / Termination Sizing-
NOTE: If you are installing 5/8 Termination in an existing wall, measure
diameter of both Wall Thimble and Termination.
Wall Thimble mount plate comes in two sizes: Termination Plate comes in two
sizes:
15-3/4″
Old wall thimble
13-3/4″
New wall thimble
13-5/16″
Old Termination Siding Shield (If required):
ZDVSSLR
14-5/16″
New Termination Siding Shield (If required):
Z58SSLR
In the future, Wall Thimble mount plate will be smaller than Termination Plate as a running change has been implemented.
Wall Thimble may need to be trimmed on outside mount plate to be completely
hidden by termination. See next page for possible combinations.
66
O ld Wa ll Thimble O ld Te rmina tio n
15-3/ 4″
Wa ll Thimb le
Ne w Wa ll Thimble O ld Te rmina tio n
13-3/ 4″
Wa ll Thimb le
1-3/ 16″
Te rmina tio n 13-5/ 16″
3/ 16″
Te rmina tio n 13-5/ 16″
O ld Wa ll Thimble Ne w Te rmina tio n
15-3/ 4″
Wa ll Thimb le
11/ 16″
14-5/ 16″ Te rmina tio n
Ne w Wa ll Thimble Ne w Te rmina tio n
13-3/ 4″
Wa ll Thimb le
14-3/ 8″ Te rmina tio n
67
Venting Straight Up Through Roof
An Attic Insulation Shield must be installed where the vent passes from a
lower living space into an attic space where the chimney is not enclosed. It
is designed to keep insulation materials away from the chimney. When
installing the Attic Insulation Shield where the chimney passes from a living
space to an attic space, install the shield from below and nail in place using
1″ spiral nails. A fire stop must be installed on the bottom side of the
joists when passing through a ceiling or floor. If an attic insulation shield
is to be used, a fire stop is not required.
Attic Insulation Shield
Fire Stop
Vertical Vent Framing 9″ Round Hole through Masonry. 12″ x 12″ Framing for
Combustible.
Using Flex Bends
Avoid cutting joists by offsetting the flex pipe. When using 45° bends a bend
support is required directly above the highest bend. When installing a bend in
a joist area a minimum of 4″ clearance to combustible to the top of bend must
be maintained, sides and bottom of pipe, a 1″ clearance to combustibles must
be maintained. If running horizontal through an area a 1-1/2″ minimum
clearance to the top of the horizontal pipe must be maintained. Maximum
vertical height of system should not exceed 43 feet. Use roof support and
rigid pipe at roof level. Flex pipe is not permitted within roof support. When
penetrating the roof a rigid galvanized pipe must be used. Attach flex pipe to
the rigid pipe with high temperature sealant, secure with four screws assuring
the flex pipe and rigid pipe are secured. Attach rigid pipe to termination
with sealant and screw with 4 sheet metal screws. The Inner flex pipe must be
secured with 4 screws which must penetrate both the flex pipe and inner
section of termination. Attach 8″ rigid pipe to 8″ termination with sealant
and screw with 4 sheet metal screws. Vertical termination clearance is 18″
[45.7cm] above the roof, measured from highest point of exit on the roof line.
Support vertical pipes to maintain minimum of one inch or greater clearances
to combustibles.
Roof Flashing
Ensure that you have the proper roof flashing by checking your roof pitch
using a level and two rulers, or by using a roof pitch card. Slide a Roof
Flashing suitable to your roof slope over the vent. Place the edge of the
flashing plate that will be on the higher part of the roof slope under the
shingles. Both the sides and the lower edge lay on top of the shingles. NOTE:
At the top edge of the flashing plate, lift the shingles and nail the plate to
the roof deck, then cement the shingles to the plate with a suitable
waterproof mastic. Ensure that the chimney is plumb. Square up the flashing
plate and nail in place to the roof deck. Use 12 nails with neoprene washers
or cover the heads with a suitable waterproof mastic. Wrap the storm collar
around the vent above the flashing. Secure the ends together loosely with nut
and bolt supplied. Slide the collar down the vent until it comes in contact
with the flashing. Tighten the bolt and seal the Storm Collar to the vent with
a suitable waterproof non-combustible mastic. The flashing and storm collar
should be painted to match the roof shingles. This will extend its life and
improve the appearance. Clean, prime and paint with suitable painting
products.
Vertical Venting in Cold Climates
In cold climate conditions where temperatures go below -10 degrees Celsius or
14 degrees Fahrenheit, we recommend that the chase be insulated and where the
vent pipe enters into the attic space that the pipe be wrapped with an
insulated Mylar sleeve. This will increase the temperature of the vent and
help the appliance to vent properly in cold weather conditions. It is also
important in vertical vented direct vent appliances that the appliance be
operated daily during the winter months as this will help stop the termination
from freezing up.
We recommend using a thermostat set at room temperature to allow the unit to
cycle. For IPI models it may be necessary to set the appliance to Standing
Pilot mode to maintain heat in the cavity. The purpose of this procedure is to
prevent cold air from penetrating the chimney and then onto the living space.
Therefore, when the internal temperature is slightly elevated the fireplace is
able to freely exhaust its combustion and hence making it easier to start up.
-ALSO SEE DIAGRAMS ON FOLLOWING PAGE-
68
-RestrictorRemove for Runs
Under 15 Feet
Clearances in horizontal venting.
Z58VT
Clearance to adjacent or perpendicular wall is 24 inches (60 cm). (Recommended to prevent re-circulation of exhaust products. For additional requirements check local codes.)
24″
18″ MIN Clearance above highest point of exit on roof 18 inches (45cm)
43ft
A)
B)
C)
A) Straight-through roof support configuration; B) Flex bend configuration; C) Termination mounting
69
-Glass Safety- All Units
IT IS THE RESPONSIBILITY OF THE HOME OWNER TO ENSURE THAT NO ONE TOUCHES A HOT
APPLIANCE.
If the barrier becomes damaged, the barrier shall be replaced with the
manufacturer’s barrier for this appliance. Any safety screen, guard, or
barrier removed for servicing the appliance, must be replaced prior to
operating the appliance. Children and adults should be alerted to the hazards
of the high surface temperatures of this appliance and should stay away to
avoid burns or ignition of clothing. Do not clean when the glass is hot. Young
children should be carefully supervised when they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to
accidental contact burns. A physical barrier is recommended if there are at
risk individuals in the house. To restrict access to a fireplace or stove,
install an adjustable safety gate to keep toddlers, young children and other
at risk individuals out of the room and away from hot surfaces. Do not leave
the fireplace remote control where it is accessible to children.
-Termination Cap Safety- All Units
WARNING:
A HORIZONTAL VENT CERTIFIED GUARD (SAFETY CAGE) IS AVAILABLE WHEN REQUIRED BY
LOCAL CODES.
SAFETY CAGES ARE AVAILABLE FOR ALL HORIZONTAL VENT TERMINATIONS. CHECK WITH
YOUR DEALER.
TERMINATION CAP IS HOT! Do not place flammable materials on or within 24
inches of termination caps. It is imperative that the vent termination be
located observing the minimum clearances as shown in manual. There must not be
any obstruction such as bushes, garden sheds, fences, decks or utility
buildings within 24″
from the front of the termination plate. Do not locate termination where
excessive snow or ice build-up may occur. Be sure to check vent termination
area after snow falls and clear to prevent accidental blockage of venting
system. When using snow blowers, make sure snow is not directed towards vent
termination area. Venting terminal shall not be recessed into a wall or
siding.
70
Approved for Power Vent PVH58 / PVH58FM
– This appliance is approved for use with a Kingsman PVH58 Horizontal Power
Vent A Horizontal Power Vent Termination is intended for use where standard
venting configurations are not possible.
NOTE: MODELS EQUIPPPED WITH MILLIVOLT/ STANDING PILOT IGNITION: Downward
vertical vent runs are NOT permitted. NOTE: MODELS EQUIPPPED WITH INTERMITTENT
PILOT IGNITION (Proflame 1 or Proflame 2): Downward vertical vent runs are
permitted, however, Cold Climate Switch (Standing Pilot Mode) must NOT be
used.
Maximum / Minimum Vent Lengths: Maximum Vent Length is 125 ft plus six 90°
elbows with Air Intake Shutter fully closed. Termination must not be below
unit. This power vent can be installed up to 8ft below the installed fireplace
on runs less than 100ft and not more than four 90° elbows. Minimum Vent Length
is 1 FT vertical x 3 FT horizontal x 3 FT vertical x 3 FT horizontal (See
PVH58 manual).
Seven 90° elbows are possible if the total horizontal is not more than 25ft
and the vertical does not exceed 15ft.
Refer to Power Vent Manual for proper installation and use.
71
Atrium MCVP42
Power Vent Control Module Installation
FIREPLACE IS SUPPLIED WITH ONE JUNCTION BOX. ADDITIONAL OUTLETS MAY BE REQUIRED. CONSULT A QUALIFIED ELECTRICIAN.
MAIN WIRING HARNESS
POWER VENT CONTROL MODULE
IPI SYSTEM
DOUBLE POLE SWITCH MV SYSTEMS ONLY
MAIN WIRING HARNESS
Power Vent Control Module Mounted inside fireplace.
FOLLOW EITHER MILLIVOLT OR IPI SYSTEM INSTRUCTIONS TO COMPLETE THE
INSTALLATION.
NOTE: Fireplace glass door must be removed to Install or remove Power Vent
Control Module. 72
Power Vent Parts List 5/8 Venting
NUMBER PVH58
DESCRIPTION Horizontal Power Vent Starter Kit – Exterior Mount
PVH58FM Horizontal Power Vent Kit – Flush Mount
Note: Must use a one foot section of 5/8 DV hard pipe to connect to the Power Vent Termination (not supplied)
CHOOSE CONTROL MODULE OR HARNESS DEPENDENT ON VALVE SYSTEM PVC58MV Power Vent Control Module – for Millivolt Models PVC58IPI Power Vent Control Module – for Proflame 1 – IPI Models
584-X12
Harness for Proflame 2 IPI – Deluxe Models
PVH20H
Main Wiring Harness Assembly Extension Harness (20ft)
CHOOSE VENTING TO BE USED: SECTION 1: 5/8 HARD PIPE – SECTION 2: 4×6-5/8″ HARD PIPE – SECTION 3: FLEX VENT
SECTION 1 DIRECT VENT HARD PIPE 5/8″ Used for entire installation Order Z58DFA
Z58DFA
Duravent Hard Pipe Adapter 5/8″ (Sloped Flue) Note: Only sloped flues require Z58DFA adapter.
SECTION 2 Z58DFA
ZDVRA
DIRECT VENT HARD PIPE 4 x 6-5/8″- Used for entire installation- Order ZDVDRA,
ZDVDIA
Duravent Hard Pipe Adapter 5/8″ (Sloped Flue) Note: Only sloped flues
require Z58DFA adapter.
Duravent REDUCER- 5/8″ to 4×6-5/8″ ADAPTER (used at flue of fireplace) (Models
MQVL48/60 and ZCVRB60 will require a one-foot section of MG Hard Pipe at flue
before using ZDVDRA)
ZDVDIA
Termination End Duravent Pipe Increaser- at Power Vent
SECTION 3 FLEX VENT Used for entire installation order Z58PVA
Note: Must use a one-foot section of 5/8 DV hard pipe (not supplied) to connect to the Power Vent Termination.
Z58PVA
Flex Pipe Adapter Kit – (to adapt flex pipe to power vent to hard pipe)
FLEX VENTING KITS
Z58FK5
Flex Kit (5″ & 8″ Dia.) x 2.5′ (Unexpanded) 5′ Expanded
Z58FK8 Z58FK20
Flex Kit (5″ & 8″ Dia.) x 4′ (Unexpanded) 8′ Expanded
Flex Kit (5″ & 8″ Dia.) x 10′ (Unexpanded) 20′ Expanded *Kits are complete
with spring stand-offs & silicone.
POWER VENT ACCESSORIES
ZDV5FC
Flex Connector 5″ Diameter
ZDV8FC
Flex Connector 8″ Diameter
ZDV5FCL ZDV8FCL ZDV4SS PVH58WT
Flex Clamp 5″ Flex Clamp 8″ Spring 4″ Standoff Spacer Wall Thimble for Power Vent
73
MCVP42
Parts List
Fireplace Part Numbers
MCVP42N
(Millivolt) Fireplace Heater rated, NG, Tempered Glass, Safety Screens
MCVP42NH
(Millivolt) Fireplace Heater rated, NG, Ceramic Glass, Safety Screens
MCVP42NE
(IPI) Fireplace Heater Rated NG, Tempered Glass, Safety Screens
MCVP42NE2
(IPI) Fireplace Heater Rated NG, Tempered Glass, Safety Screens, Remote Control
MCVP42NHE
(IPI) Fireplace Heater Rated NG, Ceramic Glass, Safety Screens
MCVP42NHE2
(IPI) Fireplace Heater Rated NG, Ceramic Glass, Safety Screens, Remote Control
MCVP42LP
(Millivolt) Fireplace Heater Rated LP, Tempered Glass, Safety Screens
MCVP42LPH
(Millivolt) Fireplace Heater Rated LP, Ceramic Glass, Safety Screens
MCVP42LPE
(IPI) Fireplace Heater Rated LP, Tempered Glass, Safety Screens
MCVP42LPE2
(IPI) Fireplace Heater Rated LP, Tempered Glass, Safety Screens, Remote Control
MCVP42LPHE
(IPI) Fireplace Heater Rated LP, Ceramic Glass, Safety Screens
MCVP42LPHE2
(IPI) Fireplace Heater Rated LP, Ceramic Glass, Safety Screens, Remote Control
MCVP42 Options
42MCVP-TLK
Tile Lip Kit
M42LOG3
Driftwood Log Set- 6 Pcs
(Use with GT only)
M42LOG4
Oak Log Set- 8 Pcs (Use with LG only)
Not for use with Propane
VLBIT4
Log Bits – Large Four Piece Kit
VLBIT6
Log Bits – Small Six Piece Kit
MP42GT
Glass Tray- Requires 10LBS Glass
M42LG
Log Grate Not for use with Propane
42MVB-258
Pilot Shield – for MP42GT & M42LG
ZG5C
Decorative Ember Glass Bronze 5LB
RBCB1
Cannonballs- Assorted size and colors
ULK3 Universal Light Kit
3927ZDV-P779-1
Bulb 10W 12V 64418 or [Sylvania 58691] (light bulbs NOT covered under Warranty.)
5143-P77912
Lamp Assembly 58mm (light bulbs NOT covered under Warranty.)
3927ZDV-P601 Transformer MET60-1
MCVP42 OPTIONS MQ DEALER ONLY –
MQ42LOG1
Driftwood Log Set- 8pcs
(Use with GT or LG)
MQ42LOG2
Oak Log Set- 7pcs (Use with GT or LG)
Not for use with Propane
MQSTONE
Decorative Stones
MQROCK2 MQROCK3 MQEMBER MQG5W MQG5A
MQG5B MQG5ZG
Rock Set Natural
Rock Set Multi-Color
Glowing Embers Decorative Glass 1/2″ White 5LB Decorative Ember Glass Cobalt
Blue 5LB
Decorative Ember Glass Black 5LB Decorative Glass- Zircon Glacier Ice 5LB
Refractory Liners MP42RLT
MP42PL
Refractory Liner Traditional (Use with LG only) Porcelain Reflective Liner (Use with GT or LG)
Child Safety Screens
MP42CSSL
Child Safety Screen (Large)
MP42CSSS
Child Safety Screen (Small)
Door Glass 42HB-310 42HB-311 42MCVP-315T 42MCVP-315C 46ZRB-123A
Ceramic Glass-for MCVP42-H Units Tempered Glass-for MCVP42 Units Tempered Glass-for MCVP42 Units Ceramic Glass-for MCVP42-H Units Door Latch Assembly
Replacement Burner Assembly / Burner
42MP-200A
Fireplace Burner
42MP-BLPSI
Burner Assembly- Propane c/w Valve System (MCVP42LP)
42MP -BLPSIH
Burner Assembly- Propane c/w Valve System (MCVP42LPH)
42MP -BNGSI
Burner Assembly- Natural Gas c/w Valve System (MCVP42N)
42MP-BNGSIH
Burner Assembly- Natural Gas c/w Valve System (MCVP42NH)
42MP-BLPSIE
Burner Assembly- Propane c/w Valve System (MCVP42LPE)
42MP-BLPSIHE Burner Assembly- Propane c/w Valve System (MCVP42LPHE)
42MP-BNGSIE
Burner Assembly- Natural Gas c/w Valve System (MCVP42NE)
42MP-BNGSIHE Burner Assembly- Natural Gas c/w Valve System (MCVP42NHE)
Conversion Kit 42MP-CKLP LP Conversion Kit for MCVP42 Millivolt 42MP-CKLPH LP Conversion Kit for MCVP42H Millivolt 42MP-CKNG NG Conversion Kit for MCVP42 Millivolt 42MP-CKNGH NG Conversion Kit for MCVP42H Millivolt 42MP-CKLPI LP Conversion Kit for MCVP42 IPI 42MP-CKLPHI LP Conversion Kit for MCVP42H IPI 42MP-CKNGI NG Conversion Kit for MCVP42 IPI 42MP-CKNGHI NG Conversion Kit for MCVP42H IPI
Baffle Conversion Kit 42MP-BCKNG NG Ceramic Glass / upgrade Kit for
MCVP42N / NE to MCVP42NH /NHE
74
42MP-BCKLP LP Ceramic Glass / upgrade Kit for MCVP42LP / LPE to MCVP42LPH /LPHE
Accessories Z1MT Z80PT
Thermostat Millivolt Wall Mount
Thermostat Programmable Digital Millivolt Wall Mount (1F80-40)
Valve System Parts / Millivolt
1000-P136WR
Generator / Thermopile
1001-P069SI
Electrode Sparker 915.069 TC SIT
1001-P216SI
Thermocouple 290.216 TC SIT
1001-P165SI
Orifice Pilot NG 977.165 TC SIT
1001-P167SI
Orifice Pilot LP 977.167 TC SIT
1001-P280SI
Tubing 24″
1001-P633SI
Valve Nova LP Hi/Lo 0820651
1001-P634SI
Valve Nova NG Hi/Lo 0820652
1001-P713SI
Pilot Burner LP 199.713 TC SIT
1001-P714SI
Pilot Burner NG 199.714 TC SIT
Remote Control / Millivolt
GFRC
Remote Control Millivolt / IPI On/Off
GTRC
Remote Control Millivolt – Thermostat
GTMRCN
Remote Control Millivolt Thermostat/Modulating – NG
GTMRCP
Remote Control Millivolt Thermostat/Modulating – LP
GTFRCN
Remote Control Millivolt Thermostat/Modulating/Fan – NG
GTFRCP
Remote Control Millivolt Thermostat/Modulating/Fan LP
Electronic Ignition/Remote Control IPI
EGTRC
Remote Control IPI (Thermostat)
EGTMRCN
Remote Control IPI
(Thermostat/Modulating – NG)
EGTMRCP
Remote Control IPI
(Thermostat/Modulating – LP)
EGTFRCN
Remote Control IPI
(Thermostat/Modulating/Fan – NG)
EGTFRCP
Remote Control IPI
(Thermostat/Modulating/Fan – LP)
Electronic Ignition Replacement Parts IPI 1006-P002si Valve IPI (NG; Hi/Lo)
1006-P003si Valve IPI (LP; Hi/Lo) 1002-P047si Pilot Assembly (LP)
Longer (35 “) Must be used when purchasing complete Pilot 1002-P033si Pilot Assembly (NG) Longer (35 “) Must be used when purchasing complete Pilot 1002-P119si Spark Electrode (35″) 1002-P910si Electrode Flame Sensor (35″) 1002-P302si IPI Ignition Board 1002-P850si AC Wall Adapter 1002-P12BH Battery Pack 1002-P912si Wiring Harness 1001-P166si Orifice Pilot (NG) 1001-P168si Orifice Pilot (LP) 1002-P013si Stepper Motor (NG)
1002-P012si 1002-P016si 1002-P014si 6961-P161
Stepper Motor (LP) Hi/Lo Regulator (NG) Hi/Lo Regulator (LP) 16″ Extension Cord
Miscellaneous Parts
1000-150GE Silicone GE Red IS806 #736
1000-150MP Hi-Temp Millpac Sealant 840099
1000-214
Piezo-Igniter 1244-17 MARK 21
1000-215
Pal Nut (18MMXI.5MM)BLK (1364.03)
1000-218
Switch Ivory (1451/001)
1000-227
Cover Ivory (86001/001)
1000-255
Orifice Brass – (State Size)
3600-B139
Explosion felt Gasket
2000-080
Thermodisc 2450 (For Blower)
1000-306
Thermalcord – Adhesive Back for Door Frame
1000-085
Control Variable Speed KBWC-13BV
FP15GC
Stainless Steel Gas Connector
KINGSMAN FIREPLACE VENTING
Z58DFA
M&G-Duravent Adapter (5 x 8)
Z58VT
Vertical Vent Termination
Z58HT
Horizontal Vent Termination
FDVHSCU
Safety Cage for Horizontal Termination
Z58AIS
Attic Insulation Shield
Z58AIS24
Attic Insulation Shield
ZDVVOS
Offset Support
Z58FS
Firestop Spacer
Z58RS
Roof Support
Z58SS
Siding Shield
Z58WT
Wall Thimble (Horizontal Venting)
ZDVSS
Siding Shield for FDVHT
ZDVSSLR
Siding Shield – Large Return
Z58SSLR
Siding Shield – Large Return
Z58GP
Galvanized Pipe 8″ Dia. x 48″
(Vertical Installations)
Z58AAF
Flashing 8″ c/w Storm Collar (1/12 to 7/12)
Z58AF2
Flashing 8″ c/w Storm Collar (8/12 to 12/12)
Z58AF3
Flashing 8″ c/w Storm Collar Flat
Z58SC
Storm Collar 8″
Z58FK5
Flex Kit (5″ & 8″ Dia.) x 2.5′ (Unexpanded) 5′ Expanded
Z58FK8
Flex Kit (5″ & 8″ Dia.) x 4′ (Unexpanded) 8′ Expanded
Z58FK20
Flex Kit (5″ & 8″ Dia.) x 10′ (Unexpanded) 20′ Expanded *Kits are complete with spring stand-offs & silicone.
Z58HSK5
Horizontal Round Termination Vent Starter Kit – 5/8″ X 5 FT Length, Wall Thimble Shield,
Horizontal Vent Termination, Wall Thimble, 60″ Flex Pipe, Screws, Mill Pac.
ZDV5FC
Flex Connector 5″ Diameter
ZDV8FC
Flex Connector 8″ Diameter
ZDV4SS
Spring 4” Standoff Spacer
75
Troubleshooting the Gas Control System
WARNING
BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE THE GLASS FRONT. NOTE:
Before troubleshooting the gas control system, be sure external gas shut off
is in the “On” position.
Problem
Spark igniter will not light.
Possible Causes
Defective or misaligned electrode at pilot.
Defective igniter (pushbutton).
Pilot will not stay lit after carefully following lighting instructions.
Defective thermocouple (flame switch where applicable).
Pilot burning, no gas to burner, valve knob “ON”, and wall switch “ON”.
Defective valve magnet.
Wall switch or wires defective.
Generator may not be generating sufficient voltage.
Plugged burner orifice.
Defective automatic valve operator.
Frequent pilot outage problem.
Flame lifts off burner and goes out in less than 30 seconds.
Flame lifts off burner on one side while the rest of the flame remains lit.
Pilot flame may be too low or blowing (high) causing the pilot safety to drop
out.
Inner 4″ liner has come off flue or termination, flame is starving for oxygen.
Improper installation of firebrick. Firebrick is likely leaning.
Corrective Action
Check for spark at electrode and pilot: if no spark and electrode wire is
properly connected, replace igniter.
Using a match, light pilot. If pilot lights, turn off pilot and push the red
button again. If pilot will not light – check gap at electrode and pilot
should be 1/8″ to 1/4″ to have a strong spark.
Check pilot flame. Must impinge on generator and thermocouple. Clean and/or
adjust pilot for maximum flame impingement on generator and thermocouple.
Replace thermocouple if pilot will not hold. (Hand tight 1/8 turn on
replacement)
Replace valve, if pilot won’t hold after the thermocouple is replaced.
Check wall switch and wires for proper connections. Jumper wire across
terminals at wall switch. If burner comes on, replace defective wall switch.
If okay, jumper wires, across wall switch wires at valve. If burner comes on,
wires are faulty or connections are bad.
Check generator with millivolt meter. Take reading at generator terminals of
gas valve. Should read 325 millivolts minimum while holding valve knob
depressed in pilot position and wall switch “off” Replace faulty generator if
reading is below specified minimu
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>