Q CELLS Q.PEAK DUO ML-G10.X Solar Module User Manual
- June 4, 2024
- Q CELLS
Table of Contents
Q CELLS Q.PEAK DUO ML-G10.X Solar Module
INTRODUCTION
With solar modules from Hanwha Q CELLS America Inc. (hereafter referred to as “Q CELLS”) you can directly transform the sun’s limitless energy into environmentally-friendly solar electricity. In order to ensure the maximum performance of your Q CELLS solar modules, please read the following instructions completely and carefully and observe all guidelines. Non- compliance may result in damage and/or physical injury. This installation manual provides instructions for the safe installation and operation of crystalline solar modules.
- Please read these instructions carefully before proceeding with your installation.
- Please retain these instructions for the life of the solar modules.
- Please ensure that this installation manual is available to the operator at all times.
- This installation manual should be given to all subsequent owners or users of the solar modules.
- All supplements received from the manufacturer should be included.
- Please observe all other applicable documents.
- If your questions are not satisfactorily answered in the manual, please contact your system supplier.
Additional information can be found on our website at www.q-cells.us.
Intended Use
This manual is valid in North America for Q CELLS solar modules. These
instructions contain information regarding the safe handling and use of
quality crystalline solar modules from Q CELLS and their installation,
mounting, wiring, and maintenance.
Symbols and Labels
The following symbols and labels are used throughout the installation
manualfor ease of use.
SYMBOL: DESCRIPTION
- Procedure with one or more steps.
- Lists of items.
- Ensure that when carrying out a procedure, you check the results of said procedure.
- Prohibited.
Beware of possible danger or damage.
Categories:
- Danger: Risk of fatal injury
- Attention: Risk of serious injury or damage to property
- Note: Risk of damage to the product
Units
Where both Imperial and U.S. units (for example inches) are shown, metric
units are definitive. References to “Data Sheet” or “Module Data Sheet” refer
to the Module Data Sheet applicable to the module being used.
Safety Regulations
The installer and solar module operator are responsible for compliance with
all applicable statutory requirements and regulations. Ä The following
regulations and standards must be upheld at all times during the installation,
operation, and maintenance of the solar modules:
- Installation and Operation Manual.
- Other applicable documents (such as country-specific regulations for pressure equipment, operational safety, hazardous goods, and environmental protection).
- Regulations and requirements are specific to the system.
- Applicable country-specific laws, regulations, and provisions governing the planning, installation, and operation of solar power systems and work on roofs.
- Any valid international, national and regional regulations governing work with direct current, especially those applicable to the installation of electrical devices and systems, and regulations issued by the respective energy provider governing the parallel operation of solar power systems.
- Accident-prevention regulations.
Certified Personnel
Both, the operator and installer are responsible for ensuring that the
installation, maintenance, connection to the grid, and dismantling are carried
out by trained and qualified electricians and engineers with approved training
certificates (issued by a state or federal organization) for the respective
specialist trade. Electrical work may only be performed by an officially
certified tradesperson in accordance with the applicable safety standards,
accident prevention regulations, and the regulations of the local energy
provider.
Validity
These instructions are only valid for crystalline solar modules from the
company Q CELLS as specified at chapter „2.1 Technical Specifications“. Q
CELLS assumes no liability for damage resulting from failure to observe these
instructions.
- Please observe the wiring and dimensioning of the system.
- The installer of the system is responsible for compliance with all necessary safety regulations during set-up and installation. Q CELLS assumes no liability on the basis of these instructions. Q CELLS is only liable in the context of contractual agreements or in the context of accepted guarantees. Q CELLS accepts no other responsibility for the functionality and safety of the modules.
- Please observe the instructions for any other system components that may be part of the complete solar power system. It may be necessary to carry out a structural analysis for the entire project.
- If your questions are not satisfactorily answered in the manual, please contact your system supplier. Additional information can be found on our website at www.q-cells.us.
Information for the Operator
- Please keep this installation manual for the entire life of the solar power system.
- Please contact your system supplier for information concerning the formal requirements for solar power systems.
- Please be sure to contact the relevant local authorities and energy providers regarding regulations and permit requirements prior to installation of the solar power system. Your financial success depends on the fulfillment of these requirements.
Other applicable documents
This installation manual is only valid in combination with the following
technical information.
DOCUMENT TYPE
Product data sheet
Packaging and transport information
MISUSE OR INCORRECT USE OF SOLAR MODULES VOIDS THE LIMITED WARRANTY AND MAY CREATE A SAFETY HAZARD AND RISK PROPERTY DAMAGE. THIS INCLUDES IMPROPER INSTALLATION OR CONFIGURATION, IMPROPER MAINTENANCE, UNINTENDED USE, AND UNAUTHORIZED MODIFICATION.
PLANNING
TECHNICAL SPECIFICATIONS
For additional information see the relevant datasheet of the module provided at www.q-cells.us.
PRODUCT LINE| Q.PEAK DUO ML-G10 Q.PEAK DUO ML-G10+ Q.PEAK DUO ML-G10.a Q.PEAK
DUO ML-G10.a+| Q.PEAK DUO BLK ML-G10 Q.PEAK DUO BLK ML-G10+ Q.PEAK DUO BLK
ML-G10.a Q.PEAK DUO BLK ML-G10.a+
---|---|---
Type| Q.ANTUM DUO Z| Q.ANTUM DUO Z
Length [in]| 74.0 (1879 mm)| 74.0 (1879 mm)
Width [in]| 41.1 (1045 mm)| 41.1 (1045 mm)
Frame height [in]| 1.26 (32 mm)| 1.26 (32 mm)
Area [yd²]| 2.34 (1.96 m²)| 2.34 (1.96 m²)
Weight [lbs]| 48.5 (22.0 kg)| 48.5 (22.0 kg)
Max. system voltage V SYS| 1000 V| 1000 V
Max. series fuse rating| 20 A| 20 A
Permissible temperature range| –40 °F to +185 °F (–40 °C to +85
°C)
Junction box protection class| IP67 with bypass diode
Connector protection class| IP68
Fire rating based on ANSI / UL 61730| TYPE 2| TYPE 2
Max. test load Push / Pull 1 **[lbs/ft²]| 113 / 84
(5,400 Pa / 4,000 Pa)| 113 / 84 (5,400 Pa / 4,000 Pa)
Max. design load Push / Pull 1 ****[lbs/ft²]| 75 / 55 (3,600 Pa
/ 2,660 Pa)| 75 / 55 (3,600 Pa / 2,660 Pa)
Certificates**| Quality Controlled PV by TÜV Rheinland; CE-compliant; IEC
61215:2016; IEC 61730:2016; PV module classification: Class II; UL 61730
1 Test and design load in accordance with IEC 61215:2016, depending on
mounting options
Fig. 1: External dimensions (in inch (mm)) and components for
- Q.PEAK DUO ML-G10, Q.PEAK DUO ML-G10+,
- Q.PEAK DUO BLK ML-G10, Q.PEAK DUO BLK ML-G10+,
- Q.PEAK DUO ML-G10.a, Q.PEAK DUO ML-G10.a+,
- Q.PEAK DUO BLK ML-G10.a and Q.PEAK DUO BLK ML-G10.a+
PRODUCT LINE | Q.PEAK DUO ML-G10.2 | Q.PEAK DUO ML-G10.4 |
---|---|---|
Type | Q.ANTUM DUO Z | Q.ANTUM DUO Z |
Length [in] | 74.0 (1879 mm) | 74.0 (1879 mm) |
Width [in] | 41.1 (1045 mm) | 41.1 (1045 mm) |
Frame height [in] | 1.26 (32 mm) | 1.26 (32 mm) |
Area [yd²] | 2.34 (1.96 m²) | 2.34 (1.96 m²) |
Weight [lbs] | 48.5 (22.0 kg) | 48.5 (22.0 kg) |
Max. system voltage V SYS | 1500 V | 1000 V |
Max. series fuse rating | 20 A | 20 A |
Permissible temperature range | –40 °F to +185 °F (–40 °C to +85 °C) | |
Junction box protection class | IP67 with bypass diode | |
Connector protection class | IP68 | |
Fire rating based on ANSI / UL 61730 | TYPE 1 | TYPE 2 |
Max. test load Push / Pull 1 **[lbs/ft²]** | 113 / 84 (5,400 Pa / | |
4,000 Pa) | 113 / 84 (5,400 Pa / 4,000 Pa) | |
Max. design load Push / Pull 1 **[lbs/ft²]** | 75 / 55 (3,600 Pa | |
/ 2,660 Pa) | 75 / 55 (3,600 Pa / 2,660 Pa) | |
Certificates | Quality Controlled PV by TÜV Rheinland; CE-compliant; IEC |
61215:2016; IEC 61730:2016; PV module classification: Class II; UL 61730
1 Test and design load in accordance with IEC 61215:2016, depending on
mounting options
Fig. 2: External dimensions (in inch (mm)) and components for
- Q.PEAK DUO ML-G10.2 and Q.PEAK DUO ML-G10.4
Installation Site
Please note the following guidelines that apply to the installation site:
- Solar modules are not explosion-proof and are not suitable for use in explosive environments.
- Do not operate solar modules near highly flammable gas and vapors (e.g. gas tanks, gas stations).
- Do not install modules in enclosed space.
- Do not install modules in locations where they may be submerged in water (e.g. floodplains).
- Do not use modules as a substitute for the normal roofing (e.g. modules are not watertight).
- Do not install modules in close proximity to air conditioning systems.
- Do not install modules above 13,120ft (4,000m) altitude above sea level.
- Contact with saline water (e.g. spray water from the sea) and salt aggregation on the modules must be avoided.
- Do not bring any chemical substance (e.g. oil, solvent etc.) into contact with any part of the panel. Only substances, which are released by Q CELLS, are allowed to be used during installation, operation and maintenance.
- Any installation of modules on surfaces of water is prohibited. This includes installations on floating as well as pile-based platforms. Q CELLS may extend the coverage of its warranty to such installations, based on a case by case assessment of the system design and location. A prior written consent by the warrantor is required in any case.
Prevention of Shadowing Effects
Optimal solar irradiation leads to maximum energy output:
- For this reason, install the modules so that they face the sun.
- Avoid shadowing (due to objects such as buildings, chimneys or trees).
- Avoid partial shading (for example through overhead lines, dirt, snow).
Limitations
The solar modules are designed for the following applications:
- Operating temperatures from –40°F to +185°F.
- Pull loads and push loads according to chapter 2.3 (‘Test Load’ in accordance with IEC 61215 and ‘Design Load ×1.5’ in accordance with UL 61730).
- Installation using a mounting structure for solar modules.
Mounting Structure Requirements
Requirements for the mounting structure:
- Conform to the necessary structural requirements.
- Compliant with local snow and wind loads.
- Properly fastened to the ground, the roof, or the façade.
- Forces acting on the module are relayed to the mounting substructure.
- Ensures sufficient rear ventilation of the module.
- Avoid the usage of different metals to prevent contact corrosion.
- Allows for stress-free expansion and contraction due to temperature fluctuations.
- Ensure that no additional forces are applied through the mounting system into the module except for the wind and snow loads. Additional forces and moments of torque at the mounting positions caused by torsions, displacements or vibrations in the mounting system are not allowed.
- Ensure that the clamps and the mounting frame are compatible.
Clamp System Recommendations
Use customary clamps that satisfy the following requirements:
- Clamp width: ≥1.5in (38mm).
- Clamp height compliant with a 1.26in (32mm) frame height.
- Clamp depth: 0.28-0.47 in (7-12 mm). (applicable for all CL clamping mounting options at section „2.3 Mounting Options“)
- Clamps are not in contact with the front glass.
- Clamps do not deform the frame.
- Clamps that satisfy the structural requirements based on the conditions of the installation site according to the applicable regulations and technical standards.
- Long-term stable clamps that securely affix the module to the mounting frame.
Module Orientation Requirements
- Vertical or horizontal installation is permitted.
- Ensure that rain and melting snow can run off freely. No water accumulation.
- Ensure that the drainage holes in the frame are not covered. No sealing.
MOUNTING OPTIONS
The module is considered to be in compliance with UL 61730 only when the module is either mounted in the manner specified by the mounting instructions, or when the mounting means has been evaluated with this PV module to UL 2703. A module with exposed conductive parts is considered to be in compliance with UL 61730 only when it is either electrically grounded in accordance with the manufacturer’s instructions and the requirements of the National Electrical Code, ANSI/NFPA 70 (2014-2017), or when the bonding means has been evaluated with this module to UL 2703.
Fig. 3: Installation options for crystalline Q CELLS modules. All dimensions are given in inch (mm in brackets). Also observe the maximum test loads and clamping range as specified on the following page. The illustrated installation options apply for both horizontal and vertical module orientation.
Specifications
MODULE TYPE| MOUNTING OPTION| POSITION OF CLAMPS* [IN (MM)]| TEST LOAD PUSH /
PULL [PA]| DESIGN LOAD PUSH / PULL [PA]| SAFETY FACTOR|
---|---|---|---|---|---|---
Q.PEAK DUO ML-G10|
CL1a
| 5.12 – 13.8 (130 – 350)| 5400 / 4000| 3600 / 2660| |
Q.PEAK DUO ML-G10+| |
Q.PEAK DUO ML-G10.2| |
0.79 – 19.7 (20 – 500)| 5400 / 3600| 3600 / 2400|
Q.PEAK DUO ML-G10.4| |
Q.PEAK DUO BLK ML-G10| |
0.79 – 25.6 (20 – 650)| 2400 / 2400| 1600 / 1600|
Q.PEAK DUO BLK ML-G10+| |
Q.PEAK DUO ML-G10.a| |
Q.PEAK DUO ML-G10.a+| |
CL1b| 11.8 – 19.7 (300 – 500)| 2400 / 2400| 1600 / 1600|
Q.PEAK DUO BLK ML-G10.a| |
Q.PEAK DUO BLK ML-G10.a+| |
CL3| 9.45 – 13.8 (240 – 350)| 4000 / 4000| 2660 / 2660|
| FB1| 15.6 (395.5)| 5400 / 4000| 3600 / 2660| 1.5|
| FB2| 15.6 (395.5)| 4000 / 4000| 2660 / 2660| |
| IP1| –| | | |
|
CL5
| short side: 0.79 – 3.94
(20 – 100)
long side: 11.8 – 17.7
|
3600 / 3300
|
2400 / 2200
| |
| | (300 – 450)| | | |
| | outer clamps: 0.79 – 19.7| | | |
| CL6c| (20 – 500)
middle clamps: 25.2 –
| 3600 / 3600| 2400 / 2400|
| | 48.8 (640 – 1240)**| | |
| | short side: 0.79 – 9.7| | | |
| CL6d**| (20 – 250)
long side: 25.2 – 48.8
| 4000 / 3600| 2660 / 2400|
| | (640 – 1240)****| | |
- The below mounting options are only possible under certain conditions.
MODULE TYPE| MOUNTING OPTION| POSITION OF CLAMPS* [IN (MM)]| TEST LOAD
PUSH / PULL*** [PA]
| DESIGN LOAD
PUSH / PULL*** [PA]
| SAFETY FACTOR|
---|---|---|---|---|---|---
Q.PEAK DUO ML-G10| | 0.79 – 3.94 (20 – 100)****| 2400 / 2000| 1600 /
1330|
1.5
|
Q.PEAK DUO ML-G10+| CL2a|
Q.PEAK DUO ML-G10.2 Q.PEAK DUO ML-G10.4|
(with rails)|
0.79 – 11.8 (20 – 300)**| 2400 / 1800| 1600 / 1200|
Q.PEAK DUO BLK ML-G10| |
| 0.79 – 7.87 (20 – 200)| 2000 / 2000| 1330 / 1330|
Q.PEAK DUO BLK ML-G10+| |
Q.PEAK DUO ML-G10.a Q.PEAK DUO ML-G10.a+ Q.PEAK DUO BLK ML-G10.a| CL2b
(with- out rails)**|
0.79 – 11.8 (20 – 300)
|
1800 / 1800
|
1200 / 1200
|
Q.PEAK DUO BLK ML-G10.a+| |
* Distance between outer edge of module and middle of the clamp; consider further details below.
** Loads according to IEC 61215-2:2016 and UL 61730.
*** Test procedure according to IEC 61215-2:2016 and UL 61730. Mounting options do not fulfill the requirements of the standards.
**** Rails must not be under the junction box.
|
MOIUNTING OPTIONS| REQUIREMENTS
---|---
All| The loads in the table are related to the mechanical stability of the
solar modules. The mechanical stability of the mounting system including
clamps has to be evaluated by the system supplier. The listed test load values
have been determined with the following clamp parameters: clamp width =
1.57 in (40 mm) and clamp depth = 0.39 in (10 mm).
The system installer is responsible for the determination of location-specific load requirements.
Ensure that the connection cables of the junction box do not run between laminate and mounting rails.
Modules bend under load. Therefore, sharp objects (e.g. screws, ballast stones, rail ends, rails with burrs or sharp corners) must not be placed near the module backside so as not to touch the laminate under load.
Ensure that the junction boxes do not touch the mounting structure (e.g. shorts rails, ballast, etc.) or the rooftop under load. Clamps or insertion profiles etc. must not touch the glass (even under load).
Unbalanced loads (e.g. snow overhangs, snowdrifts) which result in locally significantly increased loads must be removed or avoided by technical measures.
CL1a, CL2a, CL3, FB1, FB2| Ensure that module frame is fixed directly on the
rail of the substructure (no spacer allowed between the module and
substructure).
CL1a| With push test loads of 5400 Pa: The clamp position is variable in the
given range but the distance between the clamps along the long side of the
module (span) must not be larger than 55.12 in (1400 mm).
CL1b| Using of short mounting rails are permissible, if they overlap under
the module less than 8.27 in (210 mm). Minimum clearance between frame bottom
edge and roof top must be ≥ 1.38 in (35 mm).
CL1b, CL2b, CL3, FB2, CL6c, CL6d| A minimum support depth of 0.59 in (15 mm)
is required on the back side of the module.
CL5| The minimum required support depth on the module backside is 0.39 in
(10 mm) on long frame side and 0.59 in (15 mm) on short frame side.
IP1| Ensure minimum support depth of 0.59 in (15 mm) on the backside and
0.39 in (10 mm) on the front side of the module.
FB1, FB2| Use M8 corrosion-proof screws and washers (diameter ≥ 0.62 in
(15.8 mm)) for mounting slots (Detail A, Fig.1). Mounting screws and washers
should have the same material properties.
CL6c, CL6d| Use of short mounting rails under the modules are permissible,
if they do not touch the laminate under load.
ELECTRICAL LAYOUT
Module Selection
For detailed key electrical data, please refer to the product data sheet for
the respective product. (available at www.q-cells.us)
- For maximum energy yields, mismatches of specified electric current (IMPP) of more than 5% should be avoided for all modules connected in series.
Safety Factor
During normal operation, a module may generate a greater current and/or higher
voltage than that determined under standardized test conditions. Accordingly,
the values of ISC and VOC marked on the module should be multiplied by a facot
of 1.25 when determining:
- the component voltage ratings,
- conductor ampacities,
- fuse sizes,
- size of controls connected to the PV output.
Refer to Section 690-8 of the National Electrical Code for an additional multiplying factor of 125 percent (80 percent derating) which might be applicable.
- Please follow the valid national guidelines for the installation of electrical systems (refer to section 690-8 of the NEC for an additional multiplying factor of 125 percent [80 percent derating] which may be applicable).
Series Connection
Connection of modules in series is only permitted up to the maximum system
voltage as listed in the applicable datasheet.
- Take into account all possible operating situations and all relevant technical norms and regulations when designing the system. This will ensure that the maximum system voltage, including all necessary safety margins, is not exceeded.
- Take the voltage limit of the inverter into account when determining the maximum number of modules in the string.
Parallel Connection
Modules may be damaged by the occurrence of reverse currents (caused by module
defects, ground leaks, or defective insulation).
- Ensure that the maximum reverse current load capacity indicated in the data sheet is met.
In order to limit reverse currents that may occur, we recommend using the
following safety options:
Layout with a limited number of parallel connected strings:
Without undertaking further current blocking measures, a maximum of two module
strings may be operated in parallel on a single inverter or MPP tracker.
Layout with string fuses:
Use overcurrent devices (e.g. fuses) according to the relevant standards in
each string. Use PV-fuses according to IEC 60269-6. Observe the maximum
permitted number of strings as indicated in the specifications provided by the
respective string fuse manufacturer and the technical guidelines.
NOTE!
When installing different product versions, the lowest minimum permitted
reverse current load capacity applies.
Inverters
Inverters with or without transformers may be used.
INSTALLATION
SAFETY AND TRANSPORT
PREPARATION OF INSTALLATION
MODULE INSTALLATION
ELECTRICAL CONNECTION
SAFETY
DANGER!
Risk of fatal injury due to electric shock!
When disconnecting an electric circuit carrying direct current, electric arcs
can occur that may result in life-threatening injuries.
- Do NOT unplug the cable when under load.
- Do NOT connect any exposed cable ends.
- Electrical work may only be performed by qualified and skilled personnel (see page 3).
A solar module generates electrical current and voltage even at a low intensity of illumination. Sparks and electric arcs may result from the separation of a closed circuit. These can result in life-threatening injuries. The danger increases when several modules are connected in series.
- Please be aware of that the entire open circuit voltage is active even at low levels of solar irradiation.
- Please follow the valid national regulations and safety guidelines for the installation of electrical devices and systems.
- Please make sure to take all necessary safety precautions. With module or phase voltages of more than 120V, the safety extralow voltage range is exceeded.
- Carry out work on the inverter and the wiring with extreme caution.
- Ensure that the modules are disconnected at the inverter prior to separation.
- Be sure to observe the time intervals specified by the inverter manufacturer after switching off the inverter.
- Make sure that the plugs can not be connected unintentionally.
- Before working on the contacts, check them for safety extra-low voltage
ELECTRICAL INSTALLATION SAFETY
CONNECTION OF MODULES
AFTER INSTALLATION
GROUNDING
Protective Grounding
In order to prevent electrical shock or fire, the frame of the module as well
as any non-current-carrying metal parts of the system must be grounded. While
this section provides some information about grounding the Q CELLS frames and
modules, reference should be made to local statutes and regulations for
specific requirements on grounding. The U.S. National Electrical Code
addresses these issues in Article 250. A module with exposed conductive parts
is considered to be in compliance with this standard only when it is either
electrically grounded in accordance with the manufacturer’s instructions and
the requirements of the National Electrical Code, ANSI/NFPA 70 (2014-2017), or
when the bonding means has been evaluated with this module to UL 2703. Proper
grounding is achieved by bonding all exposed non-current carrying metal
equipment to the appropriately sized equipment grounding conductor (EGC) or
racking system that can be used for integrated grounding. Q CELLS frames are
protected from corrosion with an anodized coating, which has to be penetrated
in order to ensure proper bonding. The different methods listed below are
suggested methods for an appropriate bond between the frame and the EGC or
racking system (that will have to be properly grounded). The method
appropriate for any individual installation will depend on multiple factors.
Option A: Use of a grounding lug
A listed grounding lug can be bonded to the frame using the grounding
holes pre-drilled in the frame. These holes are marked with a ground symbol,
as shown below on the frame section drawing: To install the grounding lug,
follow the specified instructions of the manufacturer. The grounding lug
should be made of stainless steel or tin plated metals such as aluminum to
avoid corrosion. The grounding lug should be attached to the frame grounding
hole using a stainless steel screw, toothed lock washer or KEPS nut (in order
to penetrate the anodized layer) and backing nut. Care should be taken to
avoid the use of grounding hardware of dissimilar metals, which may lead to
corrosion.
Option B: Integrated grounding methods
The Q CELLS modules can be bonded with the racking system using UL1703 or
UL2703 certified integrated grounding methods.The racking system will then
have to be grounded so that the overall system is properly grounded. The
listed racking system and grounding device should be installed in accordance
with the manufacturer’s instructions. An example of such an integrated
grounding method is the use of a WEEB clip or Schletter plate between the
module and the racking system, when mounting the module. The WEEB washers are
generally compatible with Q CELLS modules, however each combination
module/racking system requires a specific WEEB washer size. Note that WEEB
clips are intended for single use only; they must not be reused after removal
or loosening. Refer to Wiley’s installation instructions for the specific use
of WEEB washers. An example of such integrated grounding method is the use of
a washer recognized as meeting UL2703 requirements between the module and the
racking system, when mounting the module. For example, WEEB washers are
generally compatible with Q CELLS modules, however each combination
module/racking system requires a specific WEEB washer size. Note that WEEB
washers are intended for single use only; they must not be reused after
removal or loosening. Refer to Wiley’s installation instructions for the
specific use of WEEB washers.
FAULTS AND DEFECTS
DANGER!
Risk of fatal injury due to electric shock!
- Do not attempt to fix any problems yourself (e.g. glass cracks, damaged cables).
- Please contact an installer or Q CELLS Technical Customer Service Department.
DISPOSAL
- Do not disconnect modules yourself.
- Please commission a trade specialist.
- Dispose of modules in accordance with the local disposal regulations.
MAINTENANCE AND CLEANING
Q CELLS solar modules are known for a long operating life and
minimal maintenance effort and expense. Dirt and grime are usually
washed away by rain. If the module is fully or partially shaded by
dirt or debris (e.g., plants, bird droppings), it needs to be cleaned
to prevent a loss of performance.
Maintenance
- The PV system has to be inspected regularly by certified personnel.
- The time intervals and extent of the inspection can depend on local circumstances (e.g. salt, ammonia content in the air, high humidity etc.). The customer /operator must inform himself about time intervals and extend of necessary inspections.
- Inspections have to be performed especially after extraordinary events (e.g. storm, hail, high snow loads etc.)
- During the inspections, it has to be checked that the components are secure, undamaged and clean.
Cleaning
WARNING!
Risk of injury due to hot and live modules!
- Only clean modules that have cooled down.
- Do not carry or wear any electrically conductive parts.
WARNING!
Risk of falling due to unsecured access!
- Never access the installation area alone or without taking adequate security precautions.
- Please commission a trade specialist.
NOTE!
Module surface damage may occur!
- Remove snow and ice carefully without force (e.g. with a very soft broom).
- Do not scratch off dirt.
- Module cleaning has to be done by qualified personnel according to the state of the art and taking into account all relevant safety issues and general product properties, e.g., but not restricted to:
- electrical safety
- mechanical stability (load limits depending on the actual mounting options)
- chemical suitability (no effect to any of the module’s components, e.g. cable, connector, silicone)
- no abrasive materials
NOTE!
Dust and dirt are abrasive materials!
- The situation for each individual project (or type of dirt) must always be professionally evaluated.
- Wrong cleaning may cause damages such as, but not limited to, damages to the glass surface (e.g. scratches) and AR coating, power loss, delamination, loss of frame-to-laminate bond, reduced snow and wind load capability etc.
Apart from the above, each customer is free to choose the method of cleaning.
However, possible damages, caused by the cleaning or related to the cleaning
tools or agents shall not be covered by the module’s Product and Performance
Warranty. Therefore it is recommended to use only the tools and agents which
have already been successfully tested and used with PV modules, to prevent
possible damage.
Isopropyl alcohol (IPA) can be used selectively to remove stubborn dirt and
stains within one hour after emergence.
- Please follow the safety guidelines provided by the IPA manufacturer.
- Do not let IPA run down between the module and the frame or into the module edges.
NOTE! Module damage may occur!
- Do not clean modules with water if there is a risk of frost.
- Free the substructure from any dirt and debris (leaves, bird nests, etc.).
HANWHA Q CELLS AMERICA INC.
400 Spectrum Center Drive
Suite 1400
Irvine, CA 92618
USA
TEL +1 949 748 59 69
EMAIL inquiry@us.q-cells.com
WEB www.q-cells.us
Subject to change without notice. © Q CELLS Installation manual solar modules Q.PEAK DUO ML-G10.X_2021-09_Rev03_NA DOCUMENT REVISION 03 This installation manual is valid for North America as of September 1st 2021 for Q.PEAK DUO ML-G10, Q.PEAK DUO ML-G10+, Q.PEAK DUO ML-G10.2, Q.PEAK DUO ML-G10.4, Q.PEAK DUO BLK ML-G10, Q.PEAK DUO BLK ML-G10+, Q.PEAK DUO ML-G10.a, Q.PEAK DUO ML-G10.a+, Q.PEAK DUO BLK ML-G10.a and Q.PEAK DUO BLK ML-G10.a+ solar modules, and replaces all earlier versions. This manual is subject to change. The data sheets and customer information valid at the point in time when the relevant module was manufactured apply to the installation, mounting, and maintenance procedures for the respective solar modules, as far as no updated document is provided.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>