YORK YD360 Split System Air Cooled Condensing Units User Manual
- June 9, 2024
- YORK
Table of Contents
- YORK YD360 Split System Air Cooled Condensing Units
- Product Information
- Technical
- Product Nomenclature
- Warranty
- Product Usage Instructions
- Specifications
- Field-installed options
- Physical data
- Unit limitations
- Cooling ratings
- Capacity performance
- Electrical data
- Typical Wiring Diagrams
- Weight and dimensions
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
YORK YD360 Split System Air Cooled Condensing Units
Product Information
Description
The YD360, 480, and 600 models are split-system air-cooled condensing units that have a cooling capacity of 30-50 tons. These units are delivered fully assembled, wired, and piped at the factory, allowing for easy shipping and rigging. The fan guards are vinyl-coated for rust protection and to enhance the unit’s appearance. The compressors are mounted on rubber isolators to reduce noise and vibration transmission. The condenser fans direct sound upward and away from surrounding structures. All sheet metal parts are made from commercial-grade galvanized steel and coated with powder paint to maintain a quality finish for years.
- These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of nitrogen for storage or shipping.
- The compact design, clean styling, low silhouette, and quiet operation make these condensing units suitable for almost any outdoor location. They are suitable for rooftops, because they weigh much less than a single package unit of similar capacity and are much easier to rig and support and also can be located at ground level, because their ample sub-cooling capacity allows them to be located three or more stories below the evaporator coil.
- Every condenser coil is pressurized with air to 325 psig and leak tested. After assembly, the unit is pressure tested to 450 psig and additional leak testing is done. During this pressure test, the operation of the high pressure control is checked. As the unit is being evacuated and dehydrated, the operation of the low pressure control is checked.
- Every compressor, condenser fan motor, crankcase heater, and elec-trical control circuit is checked to assure a trouble-free start-up and years of reliable operation.
- The condenser fan guards are vinyl-coated to provide additional rust protection and to enhance the appearance of the unit.
- Compressors are mounted on rubber isolators to reduce the transmis-sion of vibration. Vertical discharge condenser fans direct sound upward and away from any surrounding structures.
- All sheet metal parts are constructed of commercial grade galvanized steel. After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces.
- The external parts are coated with a powder paint to assure a quality finish for many years. This UL approved coating system has passed the 750-hour, 20% salt spray test per ASTM Standard B117.
- All models include a 1-year limited warranty on the complete unit. An additional 4-year extended compressor warranty is available as an option on all models.
- A matching line of evaporator blower units is also offered to meet your precise capacity and air handling requirements.
Technical
-
Split-system
Air-cooled condensing units -
YD360, 480 and 600
30 – 50 tons
Product Nomenclature
Configured split condenser model number nomenclature
The product nomenclature is as follows:
- Product Category: Y = Split system, condenser, AC, R-410A
- Product Style: A = Style A
- Product Identifier: D = Standard efficiency, 4-pipe, R-410A
- Nominal Cooling Capacity – MBH: 360 = 30 ton, 480 = 40 ton, 600 = 50 ton
- Heat Type and Nominal Heat Capacity: C00 = Cooling only
- Product Generation: 2 = Second generation
- Installation Options: A = None, B = Option 1, E = Option 3
- Options: 1 = Disconnect, 3 = BACnet MS/TP on Smart EquipmentTM, AA = None, AB = Phase monitor, EA = E-coat condenser coil, EB = E-coat condenser coil and phase monitor
- Voltage: 2 = 208/230-3-60, 4 = 460-3-60, 5 = 575-3-60
- Airflow: A = Standard motor
Condensing unit features and benefits
- Meets or exceeds ASHRAE 90.1 standards.
- Scroll compressors provide both high efficiency and reli-ability.
- Smart Equipment™ Controls
- Dual refrigerant circuits.
- Condenser coils are constructed of copper tubes and aluminum fins for durability and long lasting efficient operation.
- Crankcase heaters that will be de-energized when the compressor is operating.
- Both high and low pressure controls. Since these con-trols are self-contained, there are no capillary lines to be damaged.
- Solid state or internal line break compressor motor pro-tection.
- Class 2, 24-volt thermostat control circuit.
- Factory installed service valves are standard.
- Two filter-driers are shipped in the unit’s control box for field installation in the liquid line near the condensing unit.
- Copper stub-outs are factory mounted on the suction and liquid line service valves to simplify the field piping connections.
- Multiple controls to provide stable system operation at ambient temperatures down to 40ºF with kits available for operation to 0ºF.
- Capacity staging for more economical operation and more even temperature levels within the conditioned space.
- A lockout circuit to prevent the unit from cycling on safety control.
- Pump-out on unit startup to prevent liquid refrigerant returning to the compressor is standard on all models.
- Inherently protected condenser fan motors.
- V-Coil Design with exterior service port connections.
- Five-minute anti-short cycle timer and minimum com-pressor run time.
- Factory installed disconnect and Technicoat coils option.
- Self contained high and low pressure controls.
Condensing unit accessories
- Low ambient VFD control to 0° F.
- Phase Monitors – Designed to prevent unit damage. The phase monitor will shut the unit down and out-of phase condition.
- Hot Gas Bypass Kit – That will provide a metered flow of compressor discharge gas to the system’s evaporator coil during reduced load operation.
- Optional skid for fork truck handling (requires 96” length forks).
Warranty
All models come with a 1-year limited warranty on the complete unit. An optional 4-year extended compressor warranty is also available on all models.
Product Usage Instructions
- Inspect the unit to ensure it meets performance, specification, power requirement, dimension, operation, and appearance standards.
- Be sure to install the unit according to the installation instructions in the user manual.
- Do not modify or alter the unit without consulting a qualified technician.
- Familiarize yourself with the maintenance requirements for the unit and perform regular maintenance to ensure optimal performance.
- If you experience any issues or problems with the unit, refer to the troubleshooting section in the user manual or contact a qualified technician for assistance.
By following these instructions, you can ensure that your YD360, 480, or 600 split-system air-cooled condensing unit operates safely and efficiently for years to come.
Specifications
Split system cooling only condensing units Models YD360, YD480 AND YD600
The installer shall:
- Furnish York® air-cooled condensing units or equivalent in accordance with the performance schedule shown on the plans, and
- Install each unit as shown on the plans in accordance with:
- The manufacturers recommendations and
- All applicable national and local codes
Each unit shall be:
- CSA approved.
- Completely assembled for one-piece shipping and rig-ging.
- Leak pressure and functionally tested at the factory to assure a trouble-free start-up after installation.
- Covered by a 1-year limited parts warranty on the com-plete unit.
- In current production with published literature available to check performance, limitations, specifications, power requirements, dimensions, operation and appearance.
Each unit shall have:
- A steel angle frame to provide the rigid support required for shipping, rigging and years of dependable operation.
- Zinc-coated steel that has been finished by a powder paint process to provide a long lasting, quality appear-ance.
- Removable panels for easy access to all internal compo-nents during maintenance and service.
The dimensions of each unit shall:
- Not exceed those specified on the plans.
Each compressor shall:
- Be mounted on isolators to minimize the transmission of vibration.
All condenser coils shall:
- Be draw through design.
- Be constructed of copper tubes arranged in staggered rows and mechanically expanded into aluminum fins.
The condenser fan motors shall:
- Be directly connected to the condenser fans.
- Have permanently lubricated ball bearings.
- Have inherent overload protection.
- Motors shall be three phase.
- The propeller-type condenser fans shall be arranged for vertical discharge of the condenser air.
The wiring for each unit shall include:
- A crankcase heater (one per compressor)
- All 24-volt temperature control circuit.
- Both high and low pressure cutouts.
- Solid-state or internal line break compressor motor pro-tection.
- Condenser fan motor control to assure stable operation
Field-installed options
Field-installed accessories – Electrical
Model| Voltage| Description| Nominal tons| Weight
(lb)
---|---|---|---|---
2LA04713925
| ****
208/230-3-60
| LOW AMBIENT TO 0° F:
This kit includes one VFD68 (Variable Frequency Drive) control to vary condenser fan speed to maintain stable head pressure. The 30-50 ton Models may require two low ambient kits if both refrigerant systems are to be operated below 40°F.
| ****
30
| ****
20
2LA04713946| 460-3-60| | 30| 20
2LA04713958| 575-3-60| | 30| 20
2HG04700824
| ****
All
| HOT GAS BYPASS KIT
Includes discharge bypass valve and Copper pipe fittings for field installation. Used to modulate capacity at low load conditions.
| ****
30
| ****
15
2PM04700124
| | PHASE MONITOR KIT
Includes control and all associated wiring. This accessory provides protection against phase reversal, loss or unbalance.
| ****
ALL
| ****
5
2LA04714025
| ****
208/230-3-60
| LOW AMBIENT TO 0° F:
This kit includes one VFD68 (Variable Frequency Drive) control to vary condenser fan speed to maintain stable head pressure. The 30-50 ton Models may require two low ambient kits if both refrigerant systems are to be operated below 40°F.
| ****
40
| ****
20
2LA04714046| 460-3-60| | 40| 20
2LA04714058| 575-3-60| | 40| 20
2HG04700824
| ****
All
| HOT GAS BYPASS KIT
Includes discharge bypass valve and Copper pipe fittings for field installation. Used to modulate capacity at low load conditions.
| ****
40
| ****
15
2PM04700124
| | PHASE MONITOR KIT
Includes control and all associated wiring. This accessory provides protection against phase reversal, loss or unbalance.
| ****
ALL
| ****
5
2LA04714025
| ****
208/230-3-60
| LOW AMBIENT TO 0° F:
This kit includes one VFD68 (Variable Frequency Drive) control to vary condenser fan speed to maintain stable head pressure. The 30-50 ton Models may require two low ambient kits if both refrigerant systems are to be operated below 40°F.
| ****
50
| ****
20
2LA04714046| 460-3-60| | 50| 20
2LA04714058| 575-3-60| | 50| 20
2HG04700824
| ****
All
| HOT GAS BYPASS KIT
Includes discharge bypass valve and Copper pipe fittings for field installation. Used to modulate capacity at low load conditions.
| ****
50
| ****
15
2PM04700124
| | PHASE MONITOR KIT
Includes control and all associated wiring. This accessory provides protection against phase reversal, loss or unbalance.
| ****
ALL
| ****
5
Physical data
YD360 – 600 Physical data
Component | M ODELS |
---|---|
YD360 | YD480 |
Nominal tonnage | 30 |
Refrigerant | |
Refrigerant type | R-410A |
Operating charge (lb)1
| System #1| 35.0| 47.0| 51.0
System #2| 35.0| 47.0| 51.0
Holding charge| Nitrogen
Dimensions (in.)| | |
Length| 128.5| 128.5| 128.5
Width| 88.5| 88.5| 88.5
Height| 37.5| 57.7| 57.7
Weights (lb)| | |
Shipping| 1875| 2315| 2345
Operating| 1895| 2347| 2381
Compressors| | |
Type| Tandem scroll| Tandem scroll| Tandem scroll
Quantity| 2| 2| 2
Cooling| | |
Nominal capacity (ton)
| System #1| 15| 20| 25
System #2| 15| 20| 25
Capacity stages
| System #1| 2| 2| 2
System #2| 2| 2| 2
System data| | |
Number of refrigeration circuits| 2| 2| 2
Suction line OD (in.)| 1 5/8| 1 5/8| 1 5/8
Liquid line OD (in.)| 7/8| 7/8| 7/8
Outdoor coil data| | |
Face area (sq. ft.) System #1| 32.5| 45.5|
52.0
System #2| 32.5| 45.5| 52.0
Rows| 2| 2| 2
Fins per in.| 16| 16| 16
Tube diameter (in.)| 3/8| 3/8| 3/8
Circuitry type| Interlaced| Interlaced| Interlaced
Refrigerant control| —| —| —
Condenser fan data| | |
Number of fans / diameter (in.)| 4/30| 4/30| 4/30
Type| Axial| Axial| Axial
Drive type| Direct| Direct| Direct
No. speeds| 1| 1| 1
Number of motors
| System #1| 2| 2| 2
System #2| 2| 2| 2
Motor hp (ea.)| 1 1/2| 1 1/2| 1 1/2
Rotation2| CW| CW| CW
rpm| 1140| 1140| 1140
Nominal cfm
| System #1| 15400| 19400| 19900
System #2| 15400| 19400| 19900
- Includes matched evaporator unit with 25 ft of piping.
- When viewing the shaft end of the motor.
Commercial splits factory provided match-ups – 30 to 50 ton
Product | AHU | |
---|---|---|
Tonnage | 30 | 40 |
Product | Tonnage | Outdoor unit / indoor units |
ND480 | ND600 |
AC
| 30| YD360| X| —| —
40| YD480| —| X| —
50| YD600| —| —| X
Unit limitations
Condenser unit limitations
Model
| ****
Nominal tonnage
| ****
Unit voltage
| Applied voltage 1| Outdoor DB temp cooling (°F)| Indoor DB temp
cooling (°F)
---|---|---|---|---|---
Min 2| Max| Max| Min †| Max| Min
YD360
| ****
30
| 208/230-3-60
460-3-60
575-3-60
| 187
432
540
| 252
504
630
| ****
125
| ****
40
| ****
86
| ****
68
YD480
| ****
40
| 208/230-3-60
460-3-60
575-3-60
| 187
432
540
| 252
504
630
| ****
125
| ****
40
| ****
86
| ****
68
YD600
| ****
50
| 208/230-3-60
460-3-60
575-3-60
| 187
432
540
| 252
504
630
| ****
125
| ****
40
| ****
86
| ****
68
- Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage.
- Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.
Cooling ratings
Outdoor unit
| ****
Condensing unit only
---|---
Gross Capacity 1 (MBH)| ****
kW
| ****
EER
YD360| 333| 29.9| 11.1
YD480| 469| 37.4| 12.5
YD600| 576| 50.0| 11.5
Condensing unit only ratings are at 45 F SST and 95 F entering-air
temperature.
EER = Energy Efficiency Ratio at full load – the cooling capacity in
Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh
per watt (Btuh/watt).
EER ; condensing unit only ratings based on 45º F SST and 95ºF entering
outdoor air temperature.
Legend
EER = Energy Efficiency Ratio
SST = Saturated Suction Temperature
Capacity performance
Condenser only cooling capacities
Model
| ****
Suction press. & corresponding temp. @ saturation
| Temperature of air on condenser coil, °F
---|---|---
65
| ****
75
| ****
85
| ****
95
| ****
105
| ****
115
PSIG| °F| MBH| kW| EER| MBH| kW| EER|
MBH| kW| EER| MBH| kW| EER| MBH| kW|
EER| MBH| kW| EER
| 104| 35| 275.4| 28.5| 9.6| 264.0| 27.4| 9.6| 250.0| 26.4| 9.5| 238.2| 28.8|
8.3| 231.8| 32.0| 7.2| 228.5| 35.1| 6.5
| 117| 40| 327.9| 29.2| 11.2| 316.0| 28.1| 11.3| 302.0| 27.0| 11.2| 285.8|
29.4| 9.7| 273.0| 32.5| 8.4| 263.3| 35.6| 7.4
YD360| 129| 45| 380.4| 29.8| 12.8| 368.0| 28.7| 12.8| 354.0| 27.5| 12.9|
333.5| 29.9| 11.1| 314.2| 33.0| 9.5| 298.1| 36.2| 8.2
| 142| 50| 432.9| 30.4| 14.3| 420.0| 29.3| 14.3| 406.0| 28.1| 14.4| 381.1|
30.5| 12.5| 355.4| 33.6| 10.6| 332.9| 36.7| 9.1
| 154| 55| 485.4| 31.0| 15.7| 472.0| 30.0| 15.8| 458.0| 28.7| 16.0| 428.8|
31.0| 13.8| 396.6| 34.1| 11.6| 367.7| 37.2| 9.9
| 105| 35| 418.0| 33.2| 12.6| 408.0| 32.4| 12.6| 399.2| 32.4| 12.3| 397.3|
36.2| 11.0| 389.6| 40.4| 9.6| 389.2| 45.0| 8.6
| 117| 40| 461.0| 34.4| 13.4| 451.0| 33.5| 13.5| 441.6| 33.1| 13.3| 433.0|
36.8| 11.8| 419.2| 40.9| 10.3| 410.8| 45.2| 9.1
YD480| 130| 45| 504.0| 35.6| 14.1| 494.0| 34.6| 14.3| 484.1| 33.8| 14.3|
468.8| 37.4| 12.5| 448.9| 41.3| 10.9| 432.4| 45.4| 9.5
| 142| 50| 547.0| 36.9| 14.8| 537.0| 35.7| 15.0| 526.5| 34.5| 15.3| 504.5|
38.0| 13.3| 478.5| 41.8| 11.5| 454.0| 45.6| 9.9
| 155| 55| 590.0| 38.1| 15.5| 580.0| 36.8| 15.8| 569.0| 35.2| 16.2| 540.3|
38.5| 14.0| 508.2| 42.2| 12.0| 475.6| 45.8| 10.4
| 105| 35| 489.4| 45.3| 10.8| 487.2| 44.1| 11.0| 482.6| 43.4| 11.1| 442.2|
48.4| 9.1| 391.3| 54.4| 7.2| 334.0| 60.7| 5.5
| 118| 40| 561.4| 46.2| 12.1| 558.7| 45.2| 12.4| 554.6| 44.4| 12.5| 509.2|
49.4| 10.3| 456.8| 55.1| 8.3| 400.0| 61.1| 6.5
YD600| 130| 45| 633.4| 47.2| 13.4| 630.2| 46.3| 13.6| 626.6| 45.4| 13.8|
576.2| 50.5| 11.4| 522.3| 55.9| 9.3| 466.0| 61.5| 7.6
| 142| 50| 705.4| 48.2| 14.6| 701.7| 47.4| 14.8| 698.6| 46.4| 15.1| 643.2|
51.3| 12.5| 587.8| 56.6| 10.4| 532.0| 62.0| 8.6
| 154| 55| 777.4| 49.2| 15.8| 773.2| 48.5| 15.9| 770.6| 47.4| 16.2| 710.2|
52.3| 13.6| 653.3| 57.4| 11.4| 598.0| 62.4| 9.6
Sound performance
Outdoor sound power levels (dB), 60 Hz
Model
| Nominal tonnage| ****
dB(A) 1
| Octave bands (Hz)
---|---|---|---
63| 125| 250| 500| 1000| 2000| 4000|
8000
YD360| 30| 92| 90| 93| 91| 89| 87| 83| 79| 74
YD480| 40| 92| 90| 93| 91| 89| 87| 84| 80| 75
YD600| 50| 93| 91| 94| 92| 90| 87| 84| 80| 75
Rated in accordance with AHRI 270 Standard.
Electrical data
YD360 through YD600 electrical data
Model
| Compressors| Outdoor fan motor| Minimum circuit ampacity|
Maximum fuse size (A)
---|---|---|---|---
Power supply| Qty| RLA
(each)
| MCC
(each)
| LRA
(each)
| Power supply| HP| Qty| FLA
(each)
YD360
| 208/230-3-60| 4| 25.0| 39| 164| 208/230-3-60| 1 1/2| 4| 5.8| 129.5| 150
460-3-60| 4| 12.2| 19| 100| 460-3-60| 1 1/2| 4| 2.9| 63.5| 70
575-3-60| 4| 9.0| 14| 78| 575-3-60| 1 1/2| 4| 2.2| 47.1| 50
YD480
| 208/230-3-60| 4| 30.1| 47| 225| 208/230-3-60| 1 1/2| 4| 5.8| 151.1| 175
460-3-60| 4| 16.7| 26| 114| 460-3-60| 1 1/2| 4| 2.9| 82.6| 90
575-3-60| 4| 12.2| 19| 80| 575-3-60| 1 1/2| 4| 2.2| 60.7| 70
YD600
| 208/230-3-60| 4| 48.1| 75| 245| 208/230-3-60| 1 1/2| 4| 5.8| 227.6| 250
460-3-60| 4| 18.6| 29| 125| 460-3-60| 1 1/2| 4| 2.9| 90.7| 100
575-3-60| 4| 14.7| 23| 100| 575-3-60| 1 1/2| 4| 2.2| 71.3| 80
Typical Wiring Diagrams
Typical 208/230 Volt, YD360/480/600 Condensing Unit Wiring Diagram
Typical 460/575 Volt, YD360/480/600 Condensing Unit Wiring Diagram
Typical Field Wiring Diagram ND360/480 Evaporator Units, ND600 Air Handler and M1CZ600A Evaporator Coil when Matched with YD360, 480, 600 Condenser
Note : Typical field wiring when OD unit is matched with ND air handler.
When matching condensing unit with models other than ND an additional control
transformer is required on the Indoor unit.
Note : For applications on air handlers/evaporator DX coils other than
ND360-600 certified matchups liquid line solenoids may be required for proper
operation and refrigerant system dump out.
Typical ND360/480 & M1CZ600A Liquid Line Solenoid Wiring
Weight and dimensions
Unit model
| Unit weight (lb)| Unit dimensions
(in.)
| ****
A
| ****
B
| ****
C
| ****
D
| ****
Dim X
| ****
Dim Y
| Weight A to B| Weight D to C
---|---|---|---|---|---|---|---|---|---|---
Shipping| Operation| Length| Width
YD360| 1875| 1895| 128.5| 88.5| 404| 537| 533| 401| 55.2| 44.1| 934| 941
YD480| 2315| 2347| 128.5| 88.5| 486| 675| 671| 483| 53.8| 44.1| 1154| 1161
YD600| 2345| 2381| 128.5| 88.5| 486| 693| 685| 481| 53.0| 44.0| 1166| 1179
Corner weights and center of gravity
YD Unit Dimensions
Model | A | B | C | D | E | F | G | H |
---|---|---|---|---|---|---|---|---|
YD360 | 128.5 | 88.5 | 37.5 | 41.8 | 40.0 | 46.1 | 37.1 | 23.6 |
YD480 | 128.5 | 88.5 | 57.7 | 41.8 | 40.0 | 46.1 | 37.1 | 23.6 |
YD600 | 128.5 | 88.5 | 57.7 | 41.8 | 40.0 | 46.1 | 37.1 | 23.6 |
- Piping And Electrical Connections
- Piping connections are made from the rear of the unit. Connections can be made directly to the suction and liquid line service valves.
- Piping can be routed to the unit from the left or right side.
- Electrical connections for power and control wiring is made from the front of all units, left of the electrical control box access. See piping sizes and electrical knockout details.
Unit clearances
Location | Dimensions |
---|---|
Overhead (Top) 1 | 120 in. |
Front access panels | 36 in. |
Left Side | 30 in. |
Right Side | 30 in. |
Rear | 36 in. |
Bottom 2 | 0 in. |
- Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge.
- Adequate snow clearance must be provided if winter operation is expected
Piping And Electrical Connection Sizes (30/40/50T)
Connection entry | Size |
---|---|
Suction Line Sys #1 | 1-5/8 in. OD |
Liquid Line Sys #1 | 7/8 in. OD |
Suction Line Sys #2 | 1-5/8 in. OD |
Liquid Line Sys #2 | 7/8 in. OD |
Power Wiring Knockout | See below |
Control Wiring | 7/8 in. HOLE |
Electrical Power Knockout Sizes
Connection Entry | 30-40-50T/230V | 30-40-50T/460-575V |
---|---|---|
Power Wiring | 2-1/2 in. | 1-1/2 in. |
30 Ton Piping Connections
40 & 50 Ton Power and Control Wiring Connections
40 & 50 Ton Piping Connections
30 Ton Power And Control Wiring Connections
Subject to change without notice. Printed in U.S.A. 628770-YTG-I-1222
Copyright © 2022 by Johnson Controls, Inc. All rights reserved. Supersedes:
628770-YTG-H-1019
York International Corporation 5005 York Drive Norman, OK 73069
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>