TRANE RT-SLB039 Rooftops High Performance Proven Reliability Installation Guide

June 9, 2024
Trane

TRANE RT-SLB039 Rooftops High Performance Proven Reliability

TRANE-RT-SLB039-Rooftops-High-Performance-Proven-Reliability-
product

Product Information

Airfinity Rooftops

The Airfinity Rooftops from Trane provide high performance and proven reliability with easy installation features. These units are available in Airfinity AFD, Airfinity XL, IC, and IH models. The rooftop units are designed with an integrated plug-and-play solution that can be customized to meet exact needs. Trane solutions also offer compatibility with multiple roof curbs, without the need for expensive adapters or other modifications, making it the perfect choice for replacement applications. The units are environmentally friendly and offer superior indoor air quality for real comfort. The capacity range varies from 30 kW to 270 kW.

AirfinityTM AFD option

The AirfinityTM AFD option is designed with Adaptive FrequencyTM Drive technology that adapts cooling and heating outputs to your building’s demand. These rooftop units have a heat recovery module with an enthalpy wheel and integrated exhaust fan, ensuring maximum efficiency with minimal impact on the unit’s footprint and installation time. Other features include EC plug fans with variable speed technology, indoor air filtration, economizer for fresh air and free cooling, high efficiency axial outdoor fans, variable speed scroll compressor with intermediate discharge valve and permanent magnet motor, embedded Trane controller, pre-wired and pre-configured from the factory for quick start-up and commissioning, and auxiliary heat options like gas heater, electric heater, and hot water coil.

Product Usage Instructions

Before installing the Airfinity Rooftops, make sure to read the user manual completely. The units come with an integrated control solution, making it easy to install and operate. The rooftop units are designed in such a way that customization can be done as per the user’s specific requirements. In case of replacement applications, Trane solutions allow compatibility with multiple roof curbs, without the need for expensive adapters or other modifications. The units are environmentally friendly and offer superior indoor air quality, making them a suitable choice for comfortable and economical air conditioning. To ensure maximum efficiency and reduce operating costs, the Airfinity rooftops can be equipped with a heat recovery system. Heat recovery systems are ideal for climates with significant differences between outdoor and indoor air temperatures, especially during winter months. For more detailed instructions, refer to the user manual provided with the product.

Airfinity Rooftops

Comfort and economy

When it comes to installing and maintaining an HVAC system, every cent counts. From your initial capital investment to utility and maintenance expenses, operating HVAC equipment can have a significant impact on your bottom line. This is why a Trane® Airfinity™ rooftop unit can be a perfect choice. Trane delivers a product that is easy to install while providing exceptional reliability, meets stringent performance requirements and is competitively priced. Trane rooftop solutions deliver real value for you and real comfort for your customer.

The performance you need at the lowest cost of ownership

With a strong legacy of proven reliability, Airfinity rooftops can deliver high seasonal efficiency standards capable of meeting even the most stringent European regulations. By reducing energy and maintenance costs, you can save money on HVAC expenditure and invest it where it matters most: your business.

Integrated plug & play solution

Thanks to its compact design and integrated control solution, installing and operating a rooftop has never been so easy. Every Airfinity unit can be customized to meet your exact needs, so you don’t have to compromise.

Rapid, easy unit replacement

Trane plug & play solutions allow compatibility with multiple roof curbs, without the need for expensive adapters or other modifications. Maximum adaptability for faster, easier, less expensive installations makes Trane the perfect choice for replacement applications.

Key features and benefits

of the Trane Airfinity™ solution

Energy savings

  • High-efficiency scroll compressors operate in tandem for optimum performance under part load
  • Adaptive Frequency Drive option
  • Electronically Commutated (EC) supply plug fan with modulating airflow for better adaptability to the building load
  • Intelligent Trane controller with embedded energy-saving features
  • Free cooling technology to reduce annual energy costs
  • Electronic Expansion Valve for tighter system control
  • Market-leading modular and fully integrated heat recovery solutions for lower energy consumption.

Easy installation, operation and maintenance

  • Light and compact for easy transportation and lifting
  • Remote unit management with alarms and notifications
  • EC plug fan requiring zero maintenance
  • Innovative rail system for easy access to key components.

Superior Indoor Air Quality for real comfort

  • Adaptive Frequency Drive option
  • Filtration level up to F9, with easy-to-replace filters
  • Double wall panel provided as standard for improved insulation and indoor air quality
  • Dynamic defrost cycles to ensure comfort is never compromised
  • Complete offering of exhaust options to prevent overpressure in the building
  • Advanced design for up to 100% fresh air management.

Environmentally friendly

  • Low-GWP R454B or R410A HFC refrigerant for zero Ozone impact
  • Optimized packaging for minimal waste.

Wide capacity range

Capacity in kW

TRANE-RT-SLB039-Rooftops-High-Performance-Proven-Reliability-
fig-14

  • With or without Adaptive Frequency™ Drive

Airfinity™

  • 40 to 135 kW heating and cooling capacity
  • 7 800 to 25 000 m3/h airflow range
  • Free cooling operation in summer
  • Heat recovery operation in winter and summer mode
  • Heat pump operation domw to -15° C
  • Hybrid version available for cold climates
  • Eurovent-certified and ErP-compliant
  • Available in single and dual circuit configurations.

Airfinity™ AFD option

Rooftop units with Adaptive Frequency™ Drive

To run efficiently, buildings need to be capable of adapting to indoor and outdoor conditions. That’s why Trane Airfinity™ rooftop air sourced heat pumps can be equipped with variable speed technology and intelligent control that adapt cooling and heating outputs to your building’s demand. It’s that simple.

  • 20 to 65 kW heating and cooling capacity
  • 3 860 to 12 000 m3/h airflow range
  • Exceeds ErP Tier 2 (2021) thresholds
  • Free cooling operation in summer
  • Heat recovery wheel optional
  • Heat pump operation down to -15°C
  • Hybrid version available for cold climates.

TRANE-RT-SLB039-Rooftops-High-Performance-Proven-Reliability-
fig-6

  1. EC plug fans with variable speed technology
  2. Indoor air filtration: G4+F7 (65% isoCoarse + ePM1 55%), F5+F7 (85% isoCoarse + ePM1 55%), G4+F9 (65% isoCoarse + ePM1 80%)
  3. Economizer for fresh air and free cooling with optional EC exhaust fan
  4. Dual skin panels with 25mm thickness insulation
  5. High efficiency axial outdoor fans (EC available as an option)
  6. Variable speed scroll compressor with intermediate discharge valve and permanent magnet motor (Adaptive Frequency™ Drive)
  7. Embedded Trane controller, pre-wired and pre-configured from the factory for quick start-up and commissioning
  8. Auxiliary heat options (not shown): gas heater, electric heater, hot water coil
  9. Optimized heat exchanger to improve efficiency in heating mode
  10. Heat recovery module with enthalpy wheel (including purge function to avoid dirty air mixing) and integrated exhaust fan

Energy recovery solutions

To enhance energy savings and reduce operating costs, Airfinity rooftops can be equipped with a heat recovery system. Heat recovery systems are ideal for climates in which there is a significant difference between outdoor and indoor air temperature, for example during winter months. Trane design ensures maximum efficiency with minimal impact on unit footprint and installation time.

Energy Recovery Module (ERM)TRANE-RT-SLB039-Rooftops-High-Performance-
Proven-Reliability-fig-7

The Energy Recovery Module is a pre-packaged system that transfers both sensible and latent heat contained in the exhaust air to the fresh air introduced into the building, through use of an enthalpy wheel. The fully packaged assembly reduces total installation cost and time by avoiding the need for special roof curbs to manage the exhaust air in applications with low to medium external static pressure. A micro-inverter also manages the rotation speed of the wheel in especially cold ambients, in order to avoid ice formation on the wheel.

ERM General data

Size| 038/040| 049/050| 058/060| 063/065| 074/075| 084/085| 100| 110| 130
---|---|---|---|---|---|---|---|---|---
Dry efficiency, ε                           %| 81| 80| 78| 77| 75| 73| 71| 76| 74
Wheel diameter| (mm)| 1200| 1200| 1200| 1200| 1200| 1200| 1200| 1500| 1500
---|---|---|---|---|---|---|---|---|---|---
Airflow through the wheel*| (m3/s)| 2340| 2740| 3310| 3820| 4400| 4850| 5700| 6560| 7600

  • Considering 30% of fresh air

Energy Recovery Circuit (ERC)

The Energy Recovery Circuit features a dedicated high-efficiency refrigeration circuit which uses exhaust air to pre-heat or pre-cool the fresh air introduced into the building. By recovering the heat in the exhaust air, the overall capacity of the machine can be increased by up to 25% in typical working conditions, without significantly impacting power consumption*. As a result, the overall efficiency of the rooftop unit increased considerably, especially at part load conditions.

The ERC is fully integrated into the unit, therefore having zero impact on the installation footprint. Moreover, an exhaust module is provided as standard and mounted directly under the fresh air damper, avoiding the need of additional equipment to manage the exhaust air for applications with low to medium static pressure requirements. Thanks to the additional refrigeration circuit and tighter control of the exhaust air, Trane ERC system guarantees superior performance when compared to alternative systems which utilize the outdoor coil.

Increases overall capacity by up to 25% thanks to thermodynamic heat recovery on the exhaust air.

  • Capacity gain with thermodynamic heat recover depends on the volume of fresh air intake, outdoor and conditions and building load.
  • For a detailed selection, please contact your Trane Sales Representative.

General data

Airfinity™

Models IC (Cooling only)|  | IC038| IC039| IC040| IC048| IC049| IC050| IC058| IC059| IC060
---|---|---|---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 7800| 8300| 8700| 9000| 10100| 10600| 11100| 11300| 12100
Net cooling capacity (1)| (kW)| 44,8| 44,3| 46,1| 53,8| 53,8| 55,8| 63,6| 59,4| 63,1
Total power input (1)| (kW)| 13,3| 14,0| 14,2| 15,9| 18,2| 18,7| 19,6| 20,3| 19,7
Net EER (1)|  | 3,38| 3,16| 3,25| 3,39| 2,95| 2,99| 3,25| 2,93| 3,2
Seasonal energy efficiency (ηs,c) (2)| (%)| 188,6| 148,6| 184,6| 173,4| 139,4| 177,4| 169,4| 138,2| 161,8
SEER (2)|  | 4,79| 3,79| 4,69| 4,41| 3,56| 4,51| 4,31| 3,51| 4,12
Outdoor sound power level (3)| (dB(A))| 81| 85| 84| 84| 85| 84| 85| 85| 85
Length| (mm)| 2830| 3020| 3020| 2830| 3020| 3020| 2830| 3020| 3020
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 1575| 1575| 1575| 1575| 1575| 1575| 1575| 1575| 1575
Operating weight (4)| (kg)| 914| 1020| 1132| 985| 1037| 1144| 985| 1048| 1148

Models IC (Cooling only)|  | IC063| IC064| IC065| IC074| IC075| IC084| IC085| IC100| IC110| IC130
---|---|---|---|---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 12600| 12700| 14000| 15700| 16100| 17100| 17300| 20200| 22200| 26000
Net cooling capacity (1)| (kW)| 72,9| 66,9| 73,8| 82,6| 84,6| 90,2| 91,7| 110,6| 125,1| 137,8
Total power input (1)| (kW)| 23,8| 24,5| 23,4| 26,1| 26,6| 30,1| 29,5| 34,8| 42,1| 49,7
Net EER (1)|  | 3,06| 2,73| 3,15| 3,16| 3,18| 3| 3,11| 3,18| 2,97| 2,77
Seasonal energy efficiency (ηs,c) (2)| (%)| 172,2| 138,2| 164,2| 143| 167,8| 143,8| 169| 169| 160,2| 152,2
SEER (2)|  | 4,38| 3,53| 4,18| 3,65| 4,27| 3,67| 4,3| 4,3| 4,08| 3,88
Outdoor sound power level (3)| (dB(A))| 85| 85| 85| 86| 85| 86| 85| 85| 85| 91
Length| (mm)| 2830| 3020| 3020| 3900| 3900| 3900| 3900| 3900| 3900| 3900
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 1575| 1575| 1575| 1595| 1595| 1595| 1595| 1900| 1900| 1900
Operating weight (4)| (kg)| 985| 1048| 1185| 1333| 1374| 1347| 1380| 1598| 1602| 1602

Models IH (Heat pump)|  | IH038| IH040| IH050| IH060| IH065| IH075| IH085| IH100| IH110| IH130
---|---|---|---|---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 7800| 8700| 10600| 12100| 13700| 15700| 16700| 19800| 21600| 25500
Net cooling capacity (1)| (kW)| 40,2| 44,5| 54,3| 62,6| 69,7| 80,9| 85,3| 106,2| 119,3| 133,8
Total power input (1)| (kW)| 13,4| 13,0| 16,9| 19,9| 24,5| 28,0| 30,1| 35,1| 42,0| 49,4
Net EER (1)|  | 3| 3,42| 3,21| 3,15| 2,84| 2,89| 2,83| 3,03| 2,84| 2,71
Seasonal energy efficiency (ηs,c) (2)| (%)| 157,4| 213,4| 203,8| 186,2| 173| 172,6| 169,8| 175,4| 165,8| 161
SEER (2)|  | 4,01| 5,41| 5,17| 4,73| 4,4| 4,39| 4,32| 4,46| 4,22| 4,1
Net heating capacity (1)| (kW)| 37,1| 42,0| 53,3| 59,8| 68,7| 76,2| 80,6| 102,7| 114,8| 131,6
Total power input (1)| (kW)| 10,8| 11,4| 14,7| 17,2| 19,8| 21,7| 23,6| 27,3| 31,7| 37,8
Net COP (1)|  | 3,43| 3,69| 3,63| 3,47| 3,47| 3,51| 3,41| 3,76| 3,62| 3,48
Seasonal energy efficiency (ηs,h) (2)| (%)| 125,8| 125,4| 129,4| 125,4| 129,4| 140,6| 133| 135,4| 141| 135,8
SCOP (2)|  | 3,22| 3,21| 3,31| 3,21| 3,31| 3,59| 3,4| 3,46| 3,6| 3,47
Outdoor sound power level (3)| (dB(A))| 81| 84| 84| 85| 85| 85| 85| 85| 85| 91
Length| (mm)| 2830| 3010| 3010| 3010| 3010| 3890| 3890| 3890| 3890| 3890
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 1565| 1565| 1565| 1565| 1565| 1585| 1585| 1890| 1890| 1890
Operating weight (4)| (kg)| 859| 1102| 1114| 1114| 1139| 1305| 1311| 1511| 1515| 1515

Airfinity™ AFD

Model IH (Heat pumps with AFD option)|  | IH021| IH031| IH041| IH051| IH061| IH071
---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 3860| 5790| 7720| 9650| 11580| 11966
Net cooling capacity (1)| (kW)| 19,8| 30,2| 39,8| 50,2| 60,3| 64,2
Total power input (1)| (kW)| 4,6| 8,0| 10,6| 14,7| 20,2| 23,0
Net EER (1)|  | 4,28| 3,76| 3,76| 3,41| 2,99| 2,79
Seasonal energy efficiency (ηs,c) (2)| (%)| 205,8| 211,4| 190,6| 199,4| 177| 169
SEER (2)|  | 5,22| 5,36| 4,84| 5,06| 4,5| 4,3
Net heating capacity (1)| (kW)| 19,9| 29,7| 40,4| 49,6| 58,6| 58,8
Total power input (1)| (kW)| 5,3| 7,9| 11,4| 14,6| 18,3| 18,3
Net COP (1)|  | 3,78| 3,75| 3,53| 3,4| 3,21| 3,22
Seasonal energy efficiency (ηs,h) (2)| (%)| 125| 131,8| 125,4| 131| 126,2| 125,4
SCOP (2)|  | 3,2| 3,37| 3,21| 3,35| 3,23| 3,21
Outdoor sound power level (3)| (dB(A))| 81| 82| 85| 86| 88| 87
Length| (mm)| 2830| 2830| 2830| 2830| 2830| 2830
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 1565| 1565| 1565| 1565| 1565| 1565
Operating weight (4)| (kg)| 858| 858| 926| 927| 937| 937

  1. According to EN14511:2018 nominal conditions (cooling: outdoor 35°C DB, Indoor 27°C DB/19°C WB; heating: 7°C DB.6°C WB, indoor 20°C DB)
  2. Seasonal efficiency according to EN 14825:2018 (average climate)
  3. Sound power level according to ISO 9614
  4. Includes G4 filters, economizer and the full refrigerant charge

Airfinity™ XL

Efficient. Flexible. Reliable. Stronger

Designed for medium to large commercial and industrial buildings, Airfinity™XL rooftop units are easy and cost-effective to install, operate and maintain. Airfinity™rooftop units integrate the latest technology available on the market to deliver high efficiency and reliability all-year around. Every model can be equipped with additional options to deliver free cooling in summer, free heating in winter and a wider operating map thanks to integrated auxiliary heat sources.

  1. EC plug fans with high available static pressure
  2. Indoor air filtration: G4+F7 (65% isoCoarse + ePM1 55%), F5+F7 (85% isoCoarse + ePM1 55%), G4+F9 (65% isoCoarse + ePM1 80%)
  3. Economizer for fresh air and free cooling with optional EC exhaust fan
  4. Lightweight dual-skin aluminum panels with 50mm thickness insulation
  5. High-efficiency axial outdoor fans (EC available as an option)
  6. Trane outdoor heat exchanger designed for efficiency and shorter defrost cycles
  7. Scroll compressors with intermediate discharge valves for higher seasonal efficiency
  8. Embedded Trane controller, pre-wired and preconfigured from the factory for quick start-up and commissioning
  9. Auxiliary heat options (not shown): gas heater, electric heater, hot water coil
  10. Heat recovery module with enthalpy wheel (including purge function to avoid dirty air mixing) and integrated exhaust fan

Airfinity™ XL

Models IC XL (Cooling only)|  | IC140| IC150| IC170| IC190| IC 220 (5)| IC250 (5)| IC270 (5)
---|---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 24000| 26000| 28000| 33000| 36000| 42000| 44000
Net cooling capacity (1)| (kW)| 140.0| 153.9| 170.5| 194.1| 211.6| 233.3| 247.2
Total power input| (kW)| 41.0| 47.4| 53.9| 65.4| 76.2| 82.6| 89.4
Net EER|  | 3.41| 3.25| 3.16| 2.97| 2.78| 2.82| 2.77
Seasonal energy efficiency (ηs.c) (2)| (%)| 196.4| 188.0| 179.8| 165.7| 149.1| 147.3| 142.1
SEER (2)|  | 4.99| 4.78| 4.57| 4.22| 3.80| 3.76| 3.63
Outdoor sound power level (3)| (dB(A))| 85| 85| 86| 91| 91| 92| 92
Length| (mm)| 5618| 5618| 5618| 5618| 5618| 6518| 6518
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 2275| 2275| 2275| 2275| 2275| 2275| 2275
Operating weight (4)| (kg)| 2393| 2401| 2519| 2630| 2703| 2918| 2922

Models IH XL (Heat pump)|  | IH140| IH150| IH170| IH190| IH220| IH250 (5)| IH270 (5)
---|---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 24000| 26000| 28000| 33000| 36000| 42000| 44000
Net cooling capacity (1)| (kW)| 137.6| 150.6| 161.5| 184.9| 200.0| 222.9| 239.3
Total power input| (kW)| 42.2| 48.7| 55.5| 67.1| 79.2| 89.0| 96.7
Net EER|  | 3.26| 3.09| 2.91| 2.76| 2.52| 2.50| 2.47
Seasonal energy efficiency (ηs.c) (2)| (%)| 187.9| 182.6| 170.3| 160.5| 145.4| 142.3| 138.1
SEER (2)|  | 4.77| 4.64| 4.33| 4.09| 3.71| 3.63| 3.53
Net heating capacity (1)| (kW)| 135.9| 152.0| 166.8| 194.7| 217.8| 248.7| 267.5
Total power input| (kW)| 38.1| 43.1| 47.5| 59.0| 68.4| 85.6| 94.0
Net COP|  | 3.57| 3.52| 3.51| 3.30| 3.18| 2.91| 2.84
Seasonal energy efficiency (ηs.h) (2)| (%)| 135.1| 137.0| 140.1| 133.8| 126.6| 127.2| 125.1
SCOP (2)|  | 3.45| 3.50| 3.58| 3.42| 3.24| 3.26| 3.20
Outdoor sound power level (3)| (dB(A))| 85| 85| 86| 91| 91| 92| 92
Length| (mm)| 5618| 5618| 5618| 5618| 5618| 6518| 6518
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 2275| 2275| 2275| 2275| 2275| 2275| 2275
Operating weight (4)| (kg)| 2335| 2503| 2561| 2672| 2744| 2939| 2942

  1. According to EN14511:2018 nominal conditions (cooling: outdoor 35°C DB, Indoor 27°C DB/19°C WB; heating: 7°C DB.6°C WB, indoor 20°C DB)
  2. Seasonal efficiency according to EN 14825:2018 (average climate)
  3. Sound power level according to ISO 9614
  4. Includes G4 filters, economizer and the full refrigerant charge
  5. Excluded from Eurovent certification scope

Models IC XL (Cooling only)|  | IC140| IC150| IC170| IC190| IC 220 (5)| IC 250 (5)| IC 270 (5)
---|---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 24000| 26000| 28000| 33000| 36000| 42000| 44000
Net cooling capacity (1)| (kW)| 141.5| 155.5| 172.9| 196.4| 212.9| 233.7| 247.0
Total power input (1)| (kW)| 42.6| 49.9| 57.1| 69.7| 81.3| 87.4| 94.0
Net EER (1)|  | 3.32| 3.12| 3.03| 2.82| 2.62| 2.67| 2.63
Seasonal energy efficiency (ηs.c) (2)| (%)| 191| 181.8| 175| 161.4| 147.2| 147.2| 138.2
SEER (2)|  | 4.85| 4.62| 4.45| 4.11| 3.76| 3.76| 3.53
Outdoor sound power level (3)| (dB(A))| 85| 85| 86| 91| 91| 92| 92
Length| (mm)| 5618| 5618| 5618| 5618| 5618| 6518| 6518
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 2275| 2275| 2275| 2275| 2275| 2275| 2275
Operating weight (4)| (kg)| 2393| 2401| 2519| 2630| 2703| 2918| 2922

Models IH XL (Heat pump)|  | IH140| IH150| IH170| IH190| IH 220 (5)| IH 250 (5)| IH 270 (5)
---|---|---|---|---|---|---|---|---
Nominal airflow| (m3/h)| 24000| 26000| 28000| 33000| 36000| 42000| 44000
Net cooling capacity (1)| (kW)| 139.8| 153.6| 162.7| 187.2| 201.8| 221.0| 236.8
Total power input (1)| (kW)| 42.7| 50.2| 57.5| 69.6| 82.0| 90.9| 98.3
Net EER (1)|  | 3.27| 3.06| 2.83| 2.69| 2.46| 2.43| 2.41
Seasonal energy efficiency (ηs.c) (2)| (%)| 183| 182.6| 171| 162.6| 145| 142.04| 138.63
SEER (2)|  | 4.65| 4.64| 4.35| 4.14| 3.7| 3.626| 3.54
Net heating capacity (1)| (kW)| 136.6| 152.9| 170.0| 195.7| 218.4| 254.1| 272.6
Total power input (1)| (kW)| 38.4| 44.6| 49.9| 61.0| 71.6| 92.0| 100.5
Net COP (1)|  | 3.56| 3.43| 3.41| 3.21| 3.05| 2.76| 2.713
Seasonal energy efficiency (ηs.h) (2)| (%)| 131.8| 131.8| 135.8| 128.2| 126.2| 127.1| 125.6
SCOP (2)|  | 3.37| 3.37| 3.47| 3.28| 3.18| 3.22| 2.98
Outdoor sound power level (3)| (dB(A))| 85| 85| 86| 91| 91| 92| 92
Length| (mm)| 5618| 5618| 5618| 5618| 5618| 6518| 6518
Width| (mm)| 2250| 2250| 2250| 2250| 2250| 2250| 2250
Height| (mm)| 2275| 2275| 2275| 2275| 2275| 2275| 2275
Operating weight (4)| (kg)| 2335| 2503| 2561| 2672| 2744| 2939| 2942

  1. According to EN14511:2018 nominal conditions (cooling: outdoor 35°C DB, Indoor 27°C DB/19°C WB; heating: 7°C DB.6°C WB, indoor 20°C DB)
  2. Seasonal efficiency according to EN 14825:2018 (average climate)
  3. Sound power level according to ISO 9614
  4. Includes G4 filters, economizer and the full refrigerant charge
  5. Excluded from Eurovent certification scope

Trane by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy-efficient indoor environments through a broad portfolio of heating, ventilating and air conditioning systems and controls, services, parts and supply. For more information, please visit trane.eu or tranetechnologies.com.

© 2022 Trane. All Rights Reserved.
RT-SLB039-GB January 2022

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals