THERMON CPD1058U Frost Protection Flx Heat Tracing User Guide

June 9, 2024
THERMON

THERMON LOGO FROST PROTECTION FLX HEAT TRACING
SELECTION GUIDE

Frost Protection

While an insulated pipe can withstand cold temperatures longer than an uninsulated pipe, the contents of the pipe will cool to the temperature of the surrounding environment. When the ambient temperature is below freezing, the results can be both costly and inconvenient. FLX self-regulating heat trace is designed to provide freeze protection of metallic and nonmetallic pipes, tanks and equipment by replacing the heat lost through the thermal insulation into the air.

Select the Proper FLX Heating Cable
Using the pipe diameter, pipe material, insulation thickness and minimum expected ambient, find the recommended heat trace using the Design Selection Chart.
All heat trace selection is based on fiberglass insulation. Closed-cell flexible foam insulation of the same thickness may also be used. If the pipe size or insulation information does not appear, contact Thermon or a Thermon representative.

  1. Find the section headed by a low ambient temperature which is equal to or lower than that expected.
  2. Use the row which corresponds to the pipe material and pipe insulation thickness shown in the minimum insulation thickness column.
  3. Based on the pipe diameter(s) for the application, read across the table to the low ambient temperature and note the FLX heat trace recommended for that set of conditions.
  4. Note that larger pipe sizes and lower ambient temperatures may require multiple passes of heat trace. Contact Thermon for more information.
  5. On piping 25 mm in diameter and smaller, the insulation must be one pipe size larger to accommodate the heat trace.
  6. For non-metallic pipes use a parallel pass of AL20L tape to fix/totally cover the FLX heat trace.
  7. For more information refer to the planning instructions or contact Thermon.
  8. Simple low costs thermostats are available.
  9. For temperature maintenance applications other than 5°C, contact Thermon for assistance.

Design Selection Chart-Frost Protection

THERMON CPD1058U Frost Protection Flx Heat Tracing -
Chart

Note
Heat loss calculations are based on IEC/IEEE 60079-30-2 Annex E, with the following provisions:

  • Piping insulated with glass fiber, k = 0,036 W/m.K
  • A 10% safety factor has been included.

European Headquarters: Boezemweg 25 • PO Box 205 • 2640 AE Pijnacker • The Netherlands • Phone: +31 (0) 15-36 15 370
United States: 100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609 • Phone: 512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at www.thermon.com

© Thermon, Inc. • Printed in U.S.A.
Information subject to change.
Form CPD1058U-0222

Documents / Resources

| THERMON CPD1058U Frost Protection Flx Heat Tracing [pdf] User Guide
CPD1058U Frost Protection Flx Heat Tracing, CPD1058U, Frost Protection Flx Heat Tracing, Flx Heat Tracing, Heat Tracing
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

THERMON User Manuals

Related Manuals