THERMON PN50136U PETK Power and End Termination Kit Instruction Manual

June 9, 2024
THERMON

THERMON PN50136U PETK Power and End Termination Kit

INSTALLATION PROCEDURES

The following installation procedures are guidelines for the installation of the Power and End
Termination Kit. For translations other than English and local language translation provided here, please contact Thermion. The English language installation procedure shall govern.

Receiving, Storing and Handling
  1. Inspect materials for damage incurred during shipping.
  2. Report damages to the carrier for settlement.
  3. Identify parts against the packing list to ensure the proper type and quantity has been received.
  4. Store in a dry location.
PETK Power and End Termination Kits (per cable)
  • PETK-1 for BSX, VSX-HT, RSX
  • PETK-2 for HTSX, KSX, KSR, USX
  • PETK-3 for HPT, FP
  • PETK-3-ECM for HPT, FP
  • PETK-3-ZT for HPT, FP
Kit Contents

Item| Qty.|

Description

---|---|---

1

|

1

| RTV Tube

2

|

1

| Power Connection Boot

3

|

1

| End Cap

4

|

1

| Tape Strip (PETK-3 Only)

5

|

1

| End Termination Caution Label

6

|

1

| Grommet (For PETK-3 Terminator kits only)

7

|

1

| Ground Sleeve

Note:
Wire pins may be required as per client/project specification (order separately).

Warnings
  • Due to the risk of electrical shock, arcing and fire caused by product damage or improper usage, installation or maintenance, a ground-fault protection device is required.
  • Installation must comply with Thermon requirements (including form PN 50207U for Ex systems) and be installed in accordance with the regulations as per the norm EN IEC 60079-14 for hazardous areas (where applicable), or any other applicable national and local codes.
  • Component approvals and performance ratings are based on the use of Thermon specified parts only.
  • De-energize all power sources before opening enclosure.
  • Keep ends of heating cable and kit components dry before and during installation.
  • Minimum bending radius of heating cable is 32 mm (except HPT is 57 mm and FP is 19 mm).
  • Individuals installing these products are responsible for complying with all applicable safety and health guidelines. Proper Personal Protective Equipment (PPE) should be utilized during installation. Contact Thermon if you have any additional questions.
  • Avoid electrostatic charge. Clean only with a damp cloth.
Tools Required

Tools Required

PETK Certifications/Approvals1

Note:

  1. Certifications vary by cable type. See heating cable installation procedures for additional information

IMPORTANT!
Heating cable must be properly installed within expediter assembly and mounted to pipe prior to terminating with PETK kit.

See Terminator Installation Instructions for expediter mounting details.

Terminator: Route cable through base entry and mount expediter to pipe using pipe band. Do not band over cable.

For HPT and FP cable exchange grommet supplied in Terminator kit with:
GRW-G provided in PETK-3
GRW-GT2 provided in PETK-3-ECM
GRW-G/Tstat provided in PETK-3-ZT

Step 1: Remove Heating Cable Over jacket and Separate Metallic Braid to Form Pigtail
a. Cut and remove heating cable over jacket.
Do not cut metallic braid.

1b. Separate braid strands at edge of over jacket and pull cable through opening in braid.

1c. Twist braid into a pigtail. Trim ends of braid.

Step 2: Matrix Removal for BSX, VSX-HT, HTSX, RSX, KSX, KSR, USX Cables

2a. Cut and remove primary insulation jacket (BSX and RSX cables only).

2b. Cut a 4 mm strip of conductive matrix between the conductors.
Do not cut bus wire strands.

2c. Cut and remove the 4 mm matrix strip.

Step 2: Heating Element Removal for HPT and FP Cables

2a. Cut and remove primary insulation jacket.
NOTE: Bus connection must be no more than 50 mm (2”) from pipe as addressed in connection kit instructions.
Installation Procedures

2b. Cut and remove fiberglass overlay and heating element. Push any remaining heating element wire under the primary insulation jacket.
Installation Procedures

2c. Cut and remove pairing jacket.
Do not cut bus wire insulation.
Installation Procedures

Step 3: Install Power Boot on Heating Cables

3a. Apply RTV sealant to cable to cover distance of at least 3 mm and slide boot onto the end of the cable.

3b. Slide boot onto the end of the cable and green ground sleeve over twisted braid. Expose 13 mm (0.5”) of bus wire

3c. Crimp conductor wire pins on each conductor and on twisted braid if required as per client/project specification (order separately).

Step 4: End Termination for BSX, VSX-HT HTSX, RSX, KSX, KSR, USX Cables

4a. Cut and remove heating cable over jacket.
Installation Procedures

4b. Trim away exposed braid from cable.
Installation Procedures

4c. Fill the end cap with RTV sealant and apply a circumferential bead to cable [minimum of 3 mm (0.12”) wide]. Slide end cap onto end of cable.
Installation Procedures

Step 4: End Termination for HPT and FP

4a. Trim the cable 75 mm (3”) from the bus connection.
Installation Procedures

4b. Cut and remove overjacket and trim away exposed braid from cable.
Installation Procedures

4c. Cut and remove primary insulation jacket.
Installation Procedures

4d. Cut and remove fiberglass overlay and heating element. Push any remaining heating element wire under the primary insulation jacket.
Installation Procedures

4e. Cut and remove pairing jacket. Stagger cut one of the bus wires.
Do not cut bus wire strands.
Installation Procedures

4f. Tape bus wires individually and then together. Continue taping to cover overjacket. Fill the end cap with RTV sealant and apply a circumferential bead to cable [minimum of 3 mm (0.12”) wide]. Slide end cap onto end of cable.
Installation Procedures

Cable Take-off for BSX, RSX, HTSX, KSX, KSR, USX and VSX-HT

Installation Procedures
Installation Procedures
Installation Procedures
Installation Procedures

European Headquarters: Boezemweg 25 • PO Box 205 • 2640 AE Pijnacker • The Netherlands • Phone: +31 (0) 15-36 15 370
Corporate Headquarters: 100 Thermon Dr • PO Box 609 San Marcos, TX 78667-0609 • Phone:512-396-5801 • 1-800-820-4328
For the Thermon office nearest you visit us at . . .www.thermon.com

THERMON-Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

THERMON User Manuals

Related Manuals