aube technologies AC146-410 Temperature Sensor User Manual
- June 9, 2024
- aube technologies
Table of Contents
aube technologies AC146-410 Temperature Sensor User Manual
Introduction
The AC146-410 sensor is designed to be used with Aube thermostats and controllers to measure the temperature inside an air duct or air chamber. It can be also used in various other applications.
Technical Specifications
Temperature range: -70 to 120°C (-94 to 248°F) Output signal: resistive Sensing device: thermistor (10 kΩ @ 25°C or 77°F) Cable length: 3 m (10 ft)
Installation
- Use twisted pair cable for the sensor connection.
- The maximum allowable distance between the sensor and Aube’s controller is 50 feet (15 m).
- The sensor must be installed so the reading hole is facing the air flow direction.
- Drill a 19-mm (0.75-in.) hole for inserting the sensor.
- Install the sensor using # 12 self-tapping screws.
- Wire the sensor to the controller (no polarity).
NOTE: Do not submerge in liquid.
NOTE: Dimensions are expressed in INCHES [MM]
Warranty
AUBE TECHNOLOGIES INC. ONE (1) YEAR LIMITED WARRANTY This product is guaranteed against workmanship defects for a one-year period following the initial date of purchase. During this period, AUBE Technologies Inc. will repair or replace, at our option and without charge, any defective product which has been used under normal conditions.
The warranty does not cover delivery costs and does not apply to products poorly installed or randomly damaged following installation. This warranty cancels and replaces any other manufacturer’s express or implied warranty as well as any other company commitment.
AUBE Technologies Inc. cannot be held liable for related or random damages following the installation of this product.
The defective product as well as the purchase invoice must be returned to the place of purchase or mailed, prepaid and insured, to the following address:
705 Montrichard
Saint-Jean-sur-Richelieu, Quebec
J2X 5K8
Canada
Tel.: 450-358-4600
1-800-831-AUBE (2823)
Fax: 450-358-4650
service@aubetech.com
10 rue Ampère
95500 Gonesse
France
Tel. : 33 (0) 1 34 07 99 00
Fax : 33 (0) 1 34 07 99 19
advaube@comintes.com
For more information on our products, visit us at: www.aubetech.com
Resistance Curve
°C | W | °F | °C | W | °F |
---|---|---|---|---|---|
120 | 388 | 248 | 20 | 12 493 | 68 |
115 | 444 | 239 | 15 | 15 714 | 59 |
110 | 510 | 230 | 10 | 19 903 | 50 |
105 | 587 | 221 | 5 | 25 395 | 41 |
100 | 678 | 212 | 0 | 32 651 | 32 |
95 | 787 | 203 | -5 | 42 317 | 23 |
90 | 916 | 194 | -10 | 55 304 | 14 |
85 | 1 070 | 185 | -15 | 72 911 | 5 |
80 | 1 256 | 176 | -20 | 97 007 | -4 |
75 | 1 480 | 167 | -25 | 130 308 | -13 |
70 | 1 752 | 158 | -30 | 176 805 | -22 |
65 | 2 082 | 149 | -35 | 242 430 | -31 |
60 | 2 487 | 140 | -40 | 336 103 | -40 |
55 | 2 985 | 131 | -45 | 471 401 | -49 |
50 | 3 601 | 122 | -50 | 669 262 | -58 |
45 | 4 367 | 113 | -55 | 962 410 | -67 |
40 | 5 325 | 104 | -60 | 1 402 728 | -76 |
35 | 6 530 | 95 | -65 | 2 073 705 | -85 |
30 | 8 056 | 86 | -70 | 3 111 810 | -94 |
25 | 10 000 | 77 |