aube technologies AC146-410 Temperature Sensor User Manual

June 9, 2024
aube technologies

aube technologies AC146-410 Temperature Sensor User Manual
aube technologies AC146-410 Temperature Sensor

Introduction

The AC146-410 sensor is designed to be used with Aube thermostats and controllers to measure the temperature inside an air duct or air chamber. It can be also used in various other applications.

Technical Specifications

Temperature range: -70 to 120°C (-94 to 248°F) Output signal: resistive Sensing device: thermistor (10 kΩ @ 25°C or 77°F) Cable length: 3 m (10 ft)

Installation

  • Use twisted pair cable for the sensor connection.
  • The maximum allowable distance between the sensor and Aube’s controller is 50 feet (15 m).
  • The sensor must be installed so the reading hole is facing the air flow direction.
  1. Drill a 19-mm (0.75-in.) hole for inserting the sensor.
  2. Install the sensor using # 12 self-tapping screws.
  3. Wire the sensor to the controller (no polarity).

NOTE: Do not submerge in liquid.

NOTE: Dimensions are expressed in INCHES [MM] Installation

Warranty

AUBE TECHNOLOGIES INC. ONE (1) YEAR LIMITED WARRANTY This product is guaranteed against workmanship defects for a one-year period following the initial date of purchase. During this period, AUBE Technologies Inc. will repair or replace, at our option and without charge, any defective product which has been used under normal conditions.

The warranty does not cover delivery costs and does not apply to products poorly installed or randomly damaged following installation. This warranty cancels and replaces any other manufacturer’s express or implied warranty as well as any other company commitment.

AUBE Technologies Inc. cannot be held liable for related or random damages following the installation of this product.

The defective product as well as the purchase invoice must be returned to the place of purchase or mailed, prepaid and insured, to the following address:

705 Montrichard
Saint-Jean-sur-Richelieu, Quebec
J2X 5K8

Canada
Tel.: 450-358-4600
1-800-831-AUBE (2823)
Fax: 450-358-4650
service@aubetech.com

10 rue Ampère
95500 Gonesse
France

Tel. : 33 (0) 1 34 07 99 00
Fax : 33 (0) 1 34 07 99 19
advaube@comintes.com

For more information on our products, visit us at: www.aubetech.com

Resistance Curve

°C W °F °C W °F
120 388 248 20 12 493 68
115 444 239 15 15 714 59
110 510 230 10 19 903 50
105 587 221 5 25 395 41
100 678 212 0 32 651 32
95 787 203 -5 42 317 23
90 916 194 -10 55 304 14
85 1 070 185 -15 72 911 5
80 1 256 176 -20 97 007 -4
75 1 480 167 -25 130 308 -13
70 1 752 158 -30 176 805 -22
65 2 082 149 -35 242 430 -31
60 2 487 140 -40 336 103 -40
55 2 985 131 -45 471 401 -49
50 3 601 122 -50 669 262 -58
45 4 367 113 -55 962 410 -67
40 5 325 104 -60 1 402 728 -76
35 6 530 95 -65 2 073 705 -85
30 8 056 86 -70 3 111 810 -94
25 10 000 77

Resistance Curve

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals