HK INSTRUMENTS DPT-Dual-MOD-AHU Differential Pressure Transmitters Instruction Manual
- June 9, 2024
- HK INSTRUMENTS
Table of Contents
- INTRODUCTION
- APPLICATIONS
- SPECIFICATIONS
- SCHEMATICS
- DIMENSIONAL DRAWINGS
- INSTALLATION
- STEP 1: MOUNTING THE DEVICE
- STEP 2: WIRING DIAGRAMS
- STEP 3: CONFIGURATION
- STEP 4: ZERO POINT ADJUSTMENT
- STEP 5: INPUT SIGNAL CONFIGURATION
- STEP 6: MODBUS REGISTERS
- RECYCLING/DISPOSAL
- WARRANTY POLICY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-Dual-MOD-AHU
INSTALLATION INSTRUCTIONS
INTRODUCTION
Thank you for choosing an HK Instruments DPT-Dual-MOD-AHU series differential
pressure transmitter. DPT-Dual-MOD-AHU is especially designed for air handling
units, combining two differential pressure transmitters into one device. It
offers a possibility to measure pressure from two different points. One of the
measurements can be set to show the air flow rate. DPT-Dual-MOD-AHU has a
Modbus interface and an Input terminal.
The Input terminal enables reading of multiple other signals such as
temperature or control relays over Modbus. The Input terminal has two input
channels designed to accept 0-10 V, NTC10k, Pt1000, Ni1000/(-LG), and BIN IN
(potential free contact) signals.
APPLICATIONS
DPT-Dual-MOD-AHU series devices are commonly used in HVAC/R systems for:
- air flow monitoring across centrifugal fans and blowers
- in-duct air flow monitoring
- VAV applications
- fan, blower and filter monitoring
- pressure and flow monitoring
- valve and damper control
- pressure monitoring in cleanrooms
WARNING
- READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
- Failure to observe safety information and comply with instructions can result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
- To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.
- To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.
- Retain these instructions for future reference.
- This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by HK Instruments. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced and knowledgeable technicians to install this device.
SPECIFICATIONS
Performance
Accuracy (from applied pressure):
Sensor A (-700…7000 Pa):
Pressure < 125 Pa = 1.5 % + ±2 Pa
Pressure > 125 Pa = 1.5 % + ±1 Pa
Sensor B (-250…2500 Pa):
Pressure < 125 Pa = 1 % + ±2 Pa
Pressure > 125 Pa = 1 % + ±1 Pa
(Including: general accuracy, linearity, hysteresis, long term stability and
repetition error)
Input accuracy: <0.5%
Response time: 1…20 s selectable via menu
Overpressure:
Proof pressure: 25 kPa
Burst pressure: 30 kPa
Communication
Protocol: MODBUS over Serial Line
Transmission Mode: RTU
Interface: RS485
Byte format (11 bits) in RTU mode:
Coding System: 8-bit binary
Bits per Byte:
1 start bit
8 data bits, least significant bit sent first
1 bit for parity
1 stop bit
Baud rate: selectable in configuration
Modbus address: 1-247 addresses selectable in configuration menu
Zero point calibration options:
- Manual pushbutton
- Via Modbus write coil
Technical Specifications
Media compatibility: Dry air or non-aggressive gases
Measuring units on display (Selectable via menu):
Pressure: Pa, kPa, mbar, inchWC, mmWC, psi
Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
Measuring element: MEMS, no flow-through
Environment:
Operating temperature: -20…50 °C
Temperature compensated range 0…50°C
Storage temperature: -40…70 °C
Humidity: 0 to 95 % rH, non-condensing
Physical
Dimensions:
Case: 102.0 x 71.5 x 36.0 mm
Weight: 150 g
Mounting: 2 each 4.3 mm screw holes, one slotted
Materials:
Case: ABS
Lid: PC
Pressure inlets: Brass
Tubing: Silicone
Protection standard: IP54
Display:
2-line display (12 characters/line)
Line 1: active measurement, inlet A
Line 2: active measurement, inlet B
If inputs are selected, the lines show also input information (for example
temperature)
Electrical Connections:
4+4 spring load terminals, max 1.5 mm2
Cable Entry: M20
Pressure fittings:
Male ∅5.2 mm
+ High pressure
– Low pressure
Electrical
Supply voltage: 24 VAC or VDC ± 10 %
Power consumption: < 1.3 W
Output signal: via Modbus
Input signals: 2 x input (0…10 V, NTC10k, Pt1000, NI1000/(-LG), or BIN
IN)
Conformance
Meets requirements for:
EMC:
RoHS:
WEEE:| CE:
2014/30/EU
2011/65/EU
2012/19/EU| UKCA:
S.I. 2016/1091
S.I. 2012/3032
S.I. 2013/3113
---|---|---
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
- Mount the device in the desired location (see step 1).
- Open the lid and route the cable through the strain relief and connect the wires to the terminal block(s) (see step 2).
- The device is now ready for configuration.
WARNING! Apply power only after the device is properly wired.
STEP 1: MOUNTING THE DEVICE
- Select the mounting location (duct, wall, panel).
- Use the device as a template and mark the screw holes.
- Mount with appropriate screws.
Flow
The pressure tubes are connected to a flow measurement probe (i.e. FloXact),
or to the measurement ports specified by the fan manufacturer. Please see the
FloXact installation guide or the fan manufacturer’s technical specifications
for more information.
Air handling unit
In a typical Air Handling Unit application, connect the pressure inlet A to
measure air flow and pressure inlet B to measure the differential pressure
across the filter.
Pressure inlet A can be used for pressure or flow measurement.
Pressure inlet B can be used only for pressure measurement.
STEP 2: WIRING DIAGRAMS
For CE compliance, a properly grounded shielding cable is required.
- Unscrew the strain relief and route the cable(s).
- Connect the wires as shown in figure 2a and 2b.
- Tighten the strain relief.
Figure 2b – Wiring diagram example for input signals
Input 1 Pt1000 temperature:
Function 04 – Read input register 3×0005
Input 2 NTC10k temperature:
Function 04 – Read input register 3×0013
STEP 3: CONFIGURATION
-
Activate the device Menu by pushing the the select button for 1 second.
-
Select the functioning mode of the device:
• Select Manufacturer when connecting DPT-Dual-MOD-AHU to a fan with pressure measurement points
• Select Common probe when using DPT-Dual-MOD-AHU with a common measurement probe that follows the formula:
q = k ∙ (i.e. FloXact) -
If common probe is selected, select measurement unit used in the formula: m3/s, m3/h, cfm, l/s, m/s or f/min.
Note: When using the FloXact probe, select the formula unit l/s.
For other probe models, check the manufacturer’s datasheet for the correct unit. -
Select K-value
Each application has a specific K-value. Select the K-value from the manufacturer’s specifications.
Available K-value range: 0.001…9999.000 -
Select pressure unit for display:
Pa, kPa, mbar, mmWC, inWC or psi -
Select flow unit for display:
Flow volume: m3/s, m3/h, cfm, l/s
Velocity: m/s, f/min (selectable only if a common probe is used withm/s or f/min unit) -
Select the address for Modbus: 1*…247.
-
Select the baud rate: 9600*/19200/38400.
-
Select the parity bit: None*/Even/Odd.
-
Select the response time: 1…20 s (factory setup 4 s)
-
Select the the type of sensor for input 1:
NTC10k, Ni1000-LG, Ni1000, Pt1000,
VINPUT (voltage 0–10 V), none -
Select the the type of sensor for input 2:
NTC10k, Ni1000-LG, Ni1000, Pt1000,
VINPUT (voltage 0–10 V), none -
Push the select button to save settings and exit menu.
- Factory setup
STEP 4: ZERO POINT ADJUSTMENT
NOTE! Always zero the device before use.
Supply voltage must be connected one hour before the zero point adjustment is
carried out. Access via Modbus or by pushbutton.
- Loose both tubes from the pressure inlets + and -.
- Press the select button for 1 sec to enter the menu and select zero sensors.
- Wait until the LED turns off and then install tubes again for the pressure inlets.
STEP 5: INPUT SIGNAL CONFIGURATION
Input signals can be read over Modbus via DPT-MOD RS485 interface.
Signals | Accuracy for measurement | Resolution |
---|---|---|
0…10V | < 0,5 % | 0,1% |
NTC10k | < 0,5 % | 0,1% |
Pt1000 | < 0,5 % | 0,1% |
Ni1000/(-LG) | < 0,5 % | 0,1% |
BIN IN (potential free contact) |
The jumpers should be set according to the instructions below and the value should be read from the right register. Both inputs can be configured independently.
Figure 3 – Input signal configuration
STEP 6: MODBUS REGISTERS
Function code 04 – Read input register
Register| Parameter description| Data Type| Value|
Range
---|---|---|---|---
3×0001| Program version| 16 bit| 0…1000| 0,00…99,00
3×0002| Pressure reading A| 16 bit| -700…7000| -700…7000 (Pa)
3×0003| Pressure reading B| 16 bit| -250…2500| -250…2500 (Pa)
3×0004| Input 1: 0…10 V| 16 bit| 0…1000| 0…100 %
3×0005| Input 1: Pt1000| 16 bit| -500…500| -50…+50 °C
3×0006| Input 1: Ni1000| 16 bit| -500…500| -50…+50 °C
3×0007| Input 1: Ni1000-LG| 16 bit| -500…500| -50…+50 °C
3×0008| Input 1: NTC10k| 16 bit| -500…500| -50…+50 °C
3×0009| Input 2: 0…10 V| 16 bit| 0…1000| 0…100 %
3×0010| Input 2: Pt1000| 16 bit| -500…500| -50…+50 °C
3×0011| Input 2: N i1000| 16 bit| -500…500| -50…+50 °C
3×0012| Input 2: Ni1000-LG| 16 bit| -500…500| -50…+50 °C
3×0013| Input 2: NTC10k| 16 bit| -500…500| -50…+50 °C
3×0014| Flow m3/s| 16 bit| 0…10000| 0…100 m3/s
3×0015| Flow m3/h| 16 bit| 0…30000| 0…30000 m3/h
3×0016| Flow cfm| 16 bit| 0…30000| 0…30000 cfm
3×0017| Flow I/s| 16 bit| 0…3000| 0…3000 I/s
3×0018| Velocity m/s| 16 bit| 0…1000| 0…100 m/s
3×0019| Velocity f/min| 16 bit| 0…5000| 0…5000 f/min
Function code 03 – Read input holding register
Register| Parameter description| Data Type| Value|
Range
---|---|---|---|---
4×0001| Manufacturer| 16 bit| 0…8| 0=Flakt Woods, 1=Rosenberg, 2=Nicotra-
Gebhardt, 3=Comefri, 4=Ziehl, 5=ebm-papst 6=Gebhardt, 7=Nicotra. 8=Common
probe
4×0002| Formula unit (Manufac- turer=8)| 16 bit| 0…5| 0=m3/s. 1=f/min, 2=m/s,
3=1/s. 4=cfm. 5=m3/h
4×0003| K-Factor Integer| 16 bit| 0…9999| 0…9999
4×0004| K-Factor Decimal| 16 bit| 0…999| 0…999
4×0005| Response Time| 16 bit| 0…20| 0…20 s
Function code 02 – Read input status
Register| Parameter description| Data Type| Value|
Range
---|---|---|---|---
1×0001| Input 1: BIN IN| Bit 0| 0…1| 0 = On, 1 = Off
1×0002| Input 2: BIN IN| Bit 0| 0…1| 0 = On, 1 = Off
Function 05 – Write single coil
Register| Parameter description| Data Type| Value|
Range
---|---|---|---|---
Ox0001| Zeroing function| Bit 0| 0…1| 0 = On, 1 = Off
Function code 06 – Write single register
Register| Parameter description| Data Type| Value|
Range
---|---|---|---|---
4×0001| Manufacturer| 16 bit| 0…8| O=Flakt Woods. 1=Rosenberg. 2=Nicotra-
Gebhardt. 3=Comefri, 4=Ziehl, 5=ebm-papst 6=Gebhardt. 7=Nicotra, 8=Common
probe
4×0002| Formula unit (Manufac-turer=8)| 16 bit| 0…5| 0=m3/s, 1=f/min, 2=m/s.
3=1/s. 4=cfm. 5=m3/h
4×0003| K-Factor Integer| 16 bit| 0…9999| 0…9999
4×0004| K-Factor Decimal| 16 bit| 0…999| 0…999
4×0005| Response Time| 16 bit| 0…20| 0…20 s
RECYCLING/DISPOSAL
The parts left over from installation should be recycled according to your
local instructions.
Decommissioned devices should be taken to a recycling site that specializes in
electronic waste.
WARRANTY POLICY
The seller is obligated to provide a warranty of five years for the delivered goods regarding material and manufacturing. The warranty period is considered to start on the delivery date of the product. If a defect in raw materials or a production flaw is found, the seller is obligated, when the product is sent to the seller without delay or before expiration of the warranty, to amend the mistake at his/her discretion either by repairing the defective product or by delivering free of charge to the buyer a new flawless product and sending it to the buyer. Delivery costs for the repair under warranty will be paid by the buyer and the return costs by the seller. The warranty does not comprise damages caused by accident, lightning, flood or other natural phenomenon, normal wear and tear, improper or careless handling, abnormal use, overloading, improper storage, incorrect care or reconstruction, or changes and installation work not done by the seller. The selection of materials for devices prone to corrosion is the buyer’s responsibility, unless otherwise is legally agreed upon. Should the manufacturer alter the structure of the device, the seller is not obligated to make comparable changes to devices already purchased. Appealing for warranty requires that the buyer has correctly fulfilled his/her duties arisen from the delivery and stated in the contract. The seller will give a new warranty for goods that have been replaced or repaired within the warranty, however only to the expiration of the original product’s warranty time. The warranty includes the repair of a defective part or device, or if needed, a new part or device, but not installation or exchange costs. Under no circumstance is the seller liable for damages compensation for indirect damage.
COMPANY WITH MANAGEMENT SYSTEM
CERTIFIED BY DNV ISO 9001.1SO 14001
Copyright HK Instruments 2023
www.hkinstruments.fi
Installation version 1.0 2023
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>