AMERISTAR A4AH4P37A1C-SUB-1D 3.0 Ton Convertible Air Handler Instructions
- June 4, 2024
- AMERISTAR
Table of Contents
- AMERISTAR A4AH4P37A1C-SUB-1D 3.0 Ton Convertible Air Handler
- Outline Drawing
- Product Specifications
- Minimum Airflow CFM
- Fixed Orifice Superheat Charging Table
- Heater Pressure Drop Table A4AH4 Air Handler Models
- Performance and Electrical Data
- Features and Benefits
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AMERISTAR A4AH4P37A1C-SUB-1D 3.0 Ton Convertible Air Handler
Outline Drawing
PRODUCT DIMENSIONS
Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
A4AH4P37| 51.27| 23.50| 21.50| 21.75| 7.01| 9.66| 24.59| TXV| 7/8
All dimensions are in inches
Product Specifications
MODEL | A4AH4P37A1C30C |
---|---|
RATED VOLTS/PH/HZ | 208-230/1/60 |
RATINGS (a) | See O.D. Specifications |
INDOOR COIL — Type | Plate Fin |
Rows — F.P.I. | 3 – 14 |
Face Area (sq. ft.) | 5.50 |
Tube Size (in.) | 3/8 |
Refrigerant Control | TXV |
Drain Conn. Size (in.)(b) | 3/4 NPT |
DUCT CONNECTIONS | See Outline Drawing |
INDOOR FAN — Type | Centrifugal |
Diameter-Width (In.) | 11 X 8 |
No. Used | 1 |
Drive – No. Speeds | Direct – 3 |
CFM vs. in. w.g. | See Fan Performance Table |
No. Motors — H.P. | 1 – 1/3 |
Motor Speed R.P.M. | 825 |
Volts/Ph/Hz | 208-230/1/60 |
F.L. Amps | 2.5 |
FILTER | |
Filter Furnished? (c) | No |
REFRIGERANT | R-410A |
Ref. Line Connections | Brazed |
Coupling or Conn. Size — in. Gas | 7/8 |
--- | --- |
Coupling or Conn. Size — in. Liq. | **** |
3/8
DIMENSIONS| H x W x D
Crated (In.)| 52–1/2 x 26 x 24
Uncrated| 51-3/8 x 23-1/2 x 21-1/8
WEIGHT|
Shipping (Lbs.) / Net (Lbs.)| 145/138
- These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
- 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
- Remote filter required.
Minimum Airflow CFM
A4AH4P37A1C30C
Heater| Minimum Heat Speed Tap
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG| ****
Low
| ****
Low
BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, BAYHTR1510LUG, BAYHTR3510LUG|
Low
| ****
Low
BAYHTR1517BRK| Low| Low
BAYHTR1523BRK| High| High
BAYHTR3517LUG| Low| Low
Fixed Orifice Superheat Charging Table
Indoor Wet Bulb Temp (F) |
---|
Outdoor Dry Bulb Temperature (F)
| | 50| 51| 52| 53| 54| 55| 56| 57| 58| 59| 60| 61| 62| 63| 64| 65| 66| 67|
68| 69| 70| 71| 72| 73| 74| 75| 76| 77| 78
55| 7| 9| 10| 11| 12| 14| 15| 17| 18| 20| 21| 23| 24| 26| 27| 29| 30| | | |
| | | | | | | |
60| 5| 7| 8| 9| 10| 12| 13| 15| 16| 18| 19| 21| 22| 24| 25| 27| 28| 30| 31| |
| | | | | | | |
65| | | 4| 6| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28| 27|
31| | | | | | | |
70| | | | | 5| 7| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27|
28| 30| 31| | | | | |
75| | | | | | | 5| 6| 7| 9| 10| 12| 14| 16| 18| 19| 21| 22| 24| 26| 28|
29| 31| 32| | | | |
80| | | | | | | | | 4| 6| 7| 9| 10| 11| 12| 14| 16| 18| 19| 21| 23|
25| 26| 28| 29| 31| 33| |
85| | | | | | | | | | | 4| 6| 7| 9| 10| 13| 14| 16| 18| 20| 21| 23|
24| 26| 28| 29| 30| 31| 32
90| | | | | | | | | | | | | 4| 6| 8| 10| 11| 13| 14| 16| 18| 20|
22| 24| 25| 27| 28| 30| 31
95| | | | | | | | | | | | | | | 4| 6| 8| 10| 13| 14| 16| 18| 20|
22| 23| 25| 26| 28| 29
100| | | | | | | | | | | | | | | | | 6| 8| 10| 12| 13| 16| 18|
20| 21| 23| 25| 27| 29
105| | | | | | | | | | | | | | | | | 4| 6| 7| 9| 11| 13| 15|
18| 20| 22| 24| 26| 28
110| | | | | | | | | | | | | | | | | | | 4| 7| 9| 11| 13|
16| 18| 21| 23| 26| 28
115| | | | | | | | | | | | | | | | | | | | | 6| 9| 12| 14|
16| 19| 21| 24| 26
Using a digital psychrometer, measure the return air wet-bulb temperature at
the unit just before the coil. Also measure the outdoor dry-bulb
temperature. Use these temperatures to locate the target superheat on the charging table. Do not attempt to charge the system if these conditions fall outside of this charging table.
ADD refrigerant to DECREASE total superheat. REMOVE refrigerant to INCREASE total superheat. Always allow 10 to 15 minutes of operation after any refrigerant or air flow change prior to determining the final superheat.
Heater Pressure Drop Table A4AH4 Air Handler Models
Airflow CFM
| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR3510| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3517| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR1523| 4
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR1525| 4
1000| 0.01| 0.03| 0.04| 0.09| |
900| 0.01| 0.03| 0.04| 0.08| |
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |
Performance and Electrical Data
- See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
- Heater model numbers may have additional suffix digits.
Table 1. Air Flow Performance
A4AH4P37A1C30C (a)
EXTERNAL STATIC
(in w.g)
| AIRFLOW
Speed Taps — 230 VOLTS| Speed Taps — 208 VOLTS
| High| Med| Low †| High| Med| Low †
0.1| 1723| 1356| 1254| 1651| 1211| 1129
0.2| 1682| 1340| 1259| 1631| 1216| 1123
0.3| 1605| 1291| 1228| 1572| 1188| 1096
0.4| 1492| 1211| 1162| 1474| 1127| 1047
0.5| 1343| 1100| 1059| 1336| 1032| 977
0.6| 1158| 957| 919| 1159| 905| 886
0.7| 998| 782| | 942| 744|
1. Values are with wet coil, no filter, and no heaters
2. CFM Correction for dry coil = Add 3%
3. † = Factory setting
(a) For the A4AH4P37A1C30C in downflow applications, airflow must not exceed 1600 cfm due to condensate blow off.
Table 2. Electrical Data
A4AH4P37A1C30C
Heater Model No.
| ****
No. of Circuits/ Phases
| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 2.5 | 3| 15| | | 2.5 | 3| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.84| 13100| 16.0| 23| 25| 2.88| 9800| 13.8|
20| 20
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.8| 16400| 20.0| 28| 30| 3.6| 12300| 17.3|
25| 25
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.68| 26200| 32.0| 43| 45| 5.76| 19700|
27.7| 38| 40
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.6| 32800| 40.0| 53| 60| 7.2| 24600| 34.6|
46| 50
BAYHTR1517BRK-
Circuit 1 (a)
| ****
2/1
| ****
9.6
| ****
32800
| ****
40.0
| ****
53
| ****
60
| ****
7.2
| ****
24600
| ****
34.6
| ****
46
| ****
50
BAYHTR1517BRK-
Circuit 2
| 4.8| 16400| 20.0| 25| 25| 3.6| 12300| 17.3| 22| 25
BAYHTR1523BRK-
Circuit 1 (a)
| ****
2/1
| ****
9.6
| ****
32800
| ****
40.0
| ****
53
| ****
60
| ****
7.2
| ****
24600
| ****
34.6
| ****
46
| ****
50
BAYHTR1523BRK-
Circuit 2
| 9.6| 32800| 40.0| 50| 50| 7.2| 24600| 34.6| 43| 45
BAYHTR3510LUG| 1/3| 9.6| 32800| 23.1| 32| 35| 7.2| 24600| 20.0| 28| 30
BAYHTR3517LUG| 1/3| 14.4| 49100| 34.6| 46| 50| 10.8| 36900| 30.0| 40| 40
BAYHTR1517BRK
with single circuit power source kit BAYSPEKT201A
| ****
1/1
| ****
14.4
| ****
49200
| ****
60.0
| ****
83
| ****
90
| ****
10.8
| ****
36900
| ****
51.9
| ****
73
| ****
80
BAYHTR1523BRK
with single circuit power source kit BAYSPEKT201A
| ****
1/1
| ****
19.2
| ****
65600
| ****
80.0
| ****
108
| ****
110
| ****
14.4
| ****
49200
| ****
69.2
| ****
94
| ****
100
- = Motor Amps
Features and Benefits
- Galvanized metal cabinet with captured foil face insulation
- 2% or less air leakage
- R-4.2 Insulating Value
- Multi-Position UP/Down Flow, Horizontal Left /Right
- ALL Aluminum Coil
- Electric Heaters with polarized plug connections (sold as accessory)
- R-410A Thermal Expansion Valve
- ECM Motor ((33..55 –– 55 TToonn MMooddeellss ))
- Low Voltage Pigtail Connections
- Draw Through Design
- Horizontal Drain pan
- Fused 24V Power
- 5 year warranty
- Optional extended warranty available
Important:: Condensate management kit is required for all 5 ton air handler models installed in downflow applications.
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor
environments for residential applications. For more information, please visit
www.trane.com or
www.americanstandardair.com.
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
A4AH4P37A1C-SUB-1D-EN 09 Mar 2022
Supersedes A4AH4P37A1C-SUB-1C-EN (September 2020)