AMERISTAR A4AH4P18A1B60C 1.5 Ton Convertible Air Handler Instruction Manual
- June 4, 2024
- AMERISTAR
Table of Contents
Submittal
1.5 Ton
Convertible Air Handler
A4AH4P18A1B60C March 2022
AA44AAHH44PP1188AA11BB–SSUUBB–11DD–EENN
Outline Drawing
MINIMUM UNIT CLEARANCE TABLE
| SERVICE CLEARANCE (RECOMMENDED)
SIDES| 2″
FRONT| 21″
BACK| 0″
INLET DUCT| 1″
OUTLET DUCT| N/A
NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE
PRODUCT DIMENSIONS
Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
A4AH4P18| 45.02| 18.50| 16.50| 16.75| 4.68| 7.33| 18.34| Orifice| 3/4
All dimensions are in inches
Product Specifications
MODEL | A4AH4P18A1B60C |
---|---|
RATED VOLTS/PH/HZ | 208-230/1/60 |
RATINGS (a) | See O.D. Specifications |
INDOOR COIL — Type | Plate Fin |
Rows — F.P.I. | 3 – 14 |
Face Area (sq. ft.) | 4.37 |
Tube Size (in.) | 3/8 |
Refrigerant Control | 0.052 Orifice Piston |
Drain Conn. Size (in.)(b) | 3/4 NPT |
DUCT CONNECTIONS | See Outline Drawing |
INDOOR FAN — Type | Centrifugal |
Diameter-Width (In.) | 11 X 6 |
No. Used | 1 |
Drive – No. Speeds | Direct – 3 |
CFM vs. in. w.g. | See Fan Performance Table |
No. Motors — H.P. | 1 – 1/5 |
Motor Speed R.P.M. | 825 |
Volts/Ph/Hz | 208-230/1/60 |
F.L. Amps | 1.2 |
FILTER | |
Filter Furnished? (c) | No |
REFRIGERANT | R-410A/R-22 |
Ref. Line Connections | Brazed |
Coupling or Conn. Size — in. Gas | 3/4 |
--- | --- |
Coupling or Conn. Size — in. Liq. | 3/8 |
DIMENSIONS | H x W x D |
Crated (In.) | 46 x 21 x 24 |
Uncrated | 45-1/8 x 18-1/2 x 21-1/8 |
WEIGHT | |
Shipping (Lbs.) / Net (Lbs.) | 116/110 |
(a) These Air Handlers are A.H.R.I certified with various Split System Air
Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System
Outdoor Unit Product Data Guides for performance data.
(b) 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
(c) Remote filter required.
Minimum Airflow CFM
A4AH4P18A1B60C
Heater| Minimum Heat Speed Tap
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG| Med| Low
BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, BAYHTR1510LUG, BAYHTR3510LUG|
Med| Low
Fixed Orifice Superheat Charging Table
|
Indoor Wet Bulb Temp (F)
---|---
Outdoor Dry Bulb Temperature (F)
| | 50| 51| 52| 53| 54| 55| 56| 57| 58| 59| 60| 61| 62| 63| 64| 65| 66| 67|
68| 69| 70| 71| 72| 73| 74| 75| 76| 77| 78
55| 7| 9| 10| 11| 12| 14| 15| 17| 18| 20| 21| 23| 24| 26| 27| 29| 30| | | | |
| | | | | | |
60| 5| 7| 8| 9| 10| 12| 13| 15| 16| 18| 19| 21| 22| 24| 25| 27| 28| 30| 31| |
| | | | | | | |
65| | | 4| 6| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28| 27|
31| | | | | | | |
70| | | | | 5| 7| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28|
30| 31| | | | | |
75| | | | | | | 5| 6| 7| 9| 10| 12| 14| 16| 18| 19| 21| 22| 24| 26| 28| 29|
31| 32| | | | |
80| | | | | | | | | 4| 6| 7| 9| 10| 11| 12| 14| 16| 18| 19| 21| 23| 25| 26|
28| 29| 31| 33| |
85| | | | | | | | | | | 4| 6| 7| 9| 10| 13| 14| 16| 18| 20| 21| 23| 24| 26|
28| 29| 30| 31| 32
90| | | | | | | | | | | | | 4| 6| 8| 10| 11| 13| 14| 16| 18| 20| 22| 24| 25|
27| 28| 30| 31
95| | | | | | | | | | | | | | | 4| 6| 8| 10| 13| 14| 16| 18| 20| 22| 23| 25|
26| 28| 29
100| | | | | | | | | | | | | | | | | 6| 8| 10| 12| 13| 16| 18| 20| 21| 23| 25|
27| 29
105| | | | | | | | | | | | | | | | | 4| 6| 7| 9| 11| 13| 15| 18| 20| 22| 24|
26| 28
110| | | | | | | | | | | | | | | | | | | 4| 7| 9| 11| 13| 16| 18| 21| 23| 26|
28
115| | | | | | | | | | | | | | | | | | | | | 6| 9| 12| 14| 16| 19| 21| 24| 26
Using a digital psychrometer, measure the return air wet-bulb temperature at
the unit just before the coil. Also measure the outdoor dry-bulb temperature.
Use these temperatures to locate the target superheat on the charging table.
Do not attempt to charge the system if these conditions fall outside of this
charging table. ADD refrigerant to DECREASE total superheat. REMOVE
refrigerant to INCREASE total superheat. Always allow 10 to 15 minutes of
operation after any refrigerant or air flow change prior to determining the
final superheat.
Heater Pressure Drop Table
A4AH4 Air Handler Models
Airflow CFM
| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR3510| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3517| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR1523| 4
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR1525| 4
1000| 0.01| 0.03| 0.04| 0.09| |
900| 0.01| 0.03| 0.04| 0.08| |
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |
Performance and Electrical Data
- See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
- Heater model numbers may have additional suffix digits.
Table 1. Air Flow Performance
A4AH4P18A1B60C
EXTERNAL STATIC (in w.g)|
AIRFLOW
Speed Taps — 230 VOLTS
| Speed Taps — 208 VOLTS
| High| Med| Low †| High| Med| Low †
0.1| 1094| 927| 773| 1052| 849| 658
0.2| 1032| 880| 735| 990| 807| 624
0.3| 955| 818| 678| 915| 750| 578
0.4| 864| 739| 601| 826| 679| 518
0.5| 759| 645| 505| 723| 591| 441
0.6| 639| 534| 389| 606| 490|
0.7| 505| 408| | 476| 374|
1. Values are with wet coil, no filter, and no heaters
2. CFM Correction for dry coil = Add 3%
3. † = Factory setting
Table 2. Electrical Data
A4AH4P18A1B60C
Heater Model No.
| ****
No. of Circuits/ Phases
|
240 Volt
| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 1.2 | 2| 15| | | 1.2 | 2| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.84| 13100| 16.0| 22| 25| 2.88| 9800| 13.8|
19| 20
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.80| 16400| 20.0| 27| 30| 3.60| 12300|
17.3| 23| 25
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.68| 26200| 32.0| 42| 45| 5.76| 19700|
27.7| 36| 40
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.60| 32800| 40.0| 52| 60| 7.20| 24600|
34.6| 45| 45
BAYHTR3510LUG| 1/3| 9.60| 32800| 23.1| 30| 30| 7.20| 24600| 20.0| 26| 30
* = Motor Amps
Features and Benefits
- Galvanized metal cabinet with captured foil face insulation
- 2% or less air leakage
- R-4.2 Insulating Value
- Multi-Position UP/Down Flow, Horizontal Left /Right
- ALL Aluminum Coil
- Electric Heaters with polarized plug connections (sold as accessories)
- R-410A/R-22 Orifice Piston
- ECM Motor ((33..55 –– 55 TToonn MMooddeellss ))
- Low Voltage Pigtail Connections
- Draw Through Design
- Horizontal Drain pan
- Single Color
- Fused 24V Power
- 5-year warranty
- optional extended warranty available
Important: Condensate management kit is required for all 5-ton air
handler models installed in downflow applications.
About Trane and American Standard Heating and Air Conditioning Trane and
American Standard create comfortable, energy-efficient indoor environments for
residential applications. For more information, please visit
www.trane.com or
www.americanstandardair.com.
The manufacturer has a policy of continuous data improvement and it
reserves the right to change design and specifications without notice.
We are committed to using environmentally conscious print practices.
A4AH4P18A1B-SUB-1D-EN 09 Mar 2022
Supersedes A4AH4P18A1B-SUB-1C-EN (September 2020) ©2022