AMERISTAR A4AH4P18A1B60C 1.5 Ton Convertible Air Handler Instruction Manual

June 4, 2024
AMERISTAR

Submittal
1.5 Ton
Convertible Air Handler
A4AH4P18A1B60C March 2022
AA44AAHH44PP1188AA11BB–SSUUBB–11DD–EENN

Outline Drawing

MINIMUM UNIT CLEARANCE TABLE

| SERVICE CLEARANCE (RECOMMENDED)
SIDES| 2″
FRONT| 21″
BACK| 0″
INLET DUCT| 1″
OUTLET DUCT| N/A

NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE

PRODUCT DIMENSIONS


Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
A4AH4P18| 45.02| 18.50| 16.50| 16.75| 4.68| 7.33| 18.34| Orifice| 3/4
All dimensions are in inches

Product Specifications

MODEL A4AH4P18A1B60C
RATED VOLTS/PH/HZ 208-230/1/60
RATINGS (a) See O.D. Specifications
INDOOR COIL — Type Plate Fin
Rows — F.P.I. 3 – 14
Face Area (sq. ft.) 4.37
Tube Size (in.) 3/8
Refrigerant Control 0.052 Orifice Piston
Drain Conn. Size (in.)(b) 3/4 NPT
DUCT CONNECTIONS See Outline Drawing
INDOOR FAN — Type Centrifugal
Diameter-Width (In.) 11 X 6
No. Used 1
Drive – No. Speeds Direct – 3
CFM vs. in. w.g. See Fan Performance Table
No. Motors — H.P. 1 – 1/5
Motor Speed R.P.M. 825
Volts/Ph/Hz 208-230/1/60
F.L. Amps 1.2
FILTER
Filter Furnished? (c) No
REFRIGERANT R-410A/R-22
Ref. Line Connections Brazed
Coupling or Conn. Size — in. Gas 3/4
--- ---
Coupling or Conn. Size — in. Liq. 3/8
DIMENSIONS H x W x D
Crated (In.) 46 x 21 x 24
Uncrated 45-1/8 x 18-1/2 x 21-1/8
WEIGHT
Shipping (Lbs.) / Net (Lbs.) 116/110

(a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
(b) 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
(c) Remote filter required.

Minimum Airflow CFM

A4AH4P18A1B60C


Heater| Minimum Heat Speed Tap
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG| Med| Low
BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, BAYHTR1510LUG, BAYHTR3510LUG| Med| Low

Fixed Orifice Superheat Charging Table

|

Indoor Wet Bulb Temp (F)

---|---









Outdoor Dry Bulb Temperature (F)

| | 50| 51| 52| 53| 54| 55| 56| 57| 58| 59| 60| 61| 62| 63| 64| 65| 66| 67| 68| 69| 70| 71| 72| 73| 74| 75| 76| 77| 78
55| 7| 9| 10| 11| 12| 14| 15| 17| 18| 20| 21| 23| 24| 26| 27| 29| 30| | | | | | | | | | | |
60| 5| 7| 8| 9| 10| 12| 13| 15| 16| 18| 19| 21| 22| 24| 25| 27| 28| 30| 31| | | | | | | | | |
65| | | 4| 6| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28| 27| 31| | | | | | | |
70| | | | | 5| 7| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28| 30| 31| | | | | |
75| | | | | | | 5| 6| 7| 9| 10| 12| 14| 16| 18| 19| 21| 22| 24| 26| 28| 29| 31| 32| | | | |
80| | | | | | | | | 4| 6| 7| 9| 10| 11| 12| 14| 16| 18| 19| 21| 23| 25| 26| 28| 29| 31| 33| |
85| | | | | | | | | | | 4| 6| 7| 9| 10| 13| 14| 16| 18| 20| 21| 23| 24| 26| 28| 29| 30| 31| 32
90| | | | | | | | | | | | | 4| 6| 8| 10| 11| 13| 14| 16| 18| 20| 22| 24| 25| 27| 28| 30| 31
95| | | | | | | | | | | | | | | 4| 6| 8| 10| 13| 14| 16| 18| 20| 22| 23| 25| 26| 28| 29
100| | | | | | | | | | | | | | | | | 6| 8| 10| 12| 13| 16| 18| 20| 21| 23| 25| 27| 29
105| | | | | | | | | | | | | | | | | 4| 6| 7| 9| 11| 13| 15| 18| 20| 22| 24| 26| 28
110| | | | | | | | | | | | | | | | | | | 4| 7| 9| 11| 13| 16| 18| 21| 23| 26| 28
115| | | | | | | | | | | | | | | | | | | | | 6| 9| 12| 14| 16| 19| 21| 24| 26
Using a digital psychrometer, measure the return air wet-bulb temperature at the unit just before the coil. Also measure the outdoor dry-bulb temperature. Use these temperatures to locate the target superheat on the charging table. Do not attempt to charge the system if these conditions fall outside of this charging table. ADD refrigerant to DECREASE total superheat. REMOVE refrigerant to INCREASE total superheat. Always allow 10 to 15 minutes of operation after any refrigerant or air flow change prior to determining the final superheat.

Heater Pressure Drop Table
A4AH4 Air Handler Models


Airflow CFM

| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR3510| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3517| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR1523| 4
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR1525| 4
1000| 0.01| 0.03| 0.04| 0.09| |
900| 0.01| 0.03| 0.04| 0.08| |
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |

Performance and Electrical Data

  1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
  2. Heater model numbers may have additional suffix digits.

Table 1. Air Flow Performance

A4AH4P18A1B60C


EXTERNAL STATIC (in w.g)|

AIRFLOW

Speed Taps — 230 VOLTS

| Speed Taps — 208 VOLTS
| High| Med| Low †| High| Med| Low †
0.1| 1094| 927| 773| 1052| 849| 658
0.2| 1032| 880| 735| 990| 807| 624
0.3| 955| 818| 678| 915| 750| 578
0.4| 864| 739| 601| 826| 679| 518
0.5| 759| 645| 505| 723| 591| 441
0.6| 639| 534| 389| 606| 490|
0.7| 505| 408| | 476| 374|
1. Values are with wet coil, no filter, and no heaters
2. CFM Correction for dry coil = Add 3%
3. † = Factory setting

Table 2. Electrical Data

A4AH4P18A1B60C




Heater Model No.

| ****

No. of Circuits/ Phases

|

240 Volt

| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 1.2 | 2| 15| | | 1.2 | 2| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.84| 13100| 16.0| 22| 25| 2.88| 9800| 13.8| 19| 20
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.80| 16400| 20.0| 27| 30| 3.60| 12300| 17.3| 23| 25
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.68| 26200| 32.0| 42| 45| 5.76| 19700| 27.7| 36| 40
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.60| 32800| 40.0| 52| 60| 7.20| 24600| 34.6| 45| 45
BAYHTR3510LUG| 1/3| 9.60| 32800| 23.1| 30| 30| 7.20| 24600| 20.0| 26| 30

* = Motor Amps

Features and Benefits

  • Galvanized metal cabinet with captured foil face insulation
  • 2% or less air leakage
  • R-4.2 Insulating Value
  • Multi-Position UP/Down Flow, Horizontal Left /Right
  • ALL Aluminum Coil
  • Electric Heaters with polarized plug connections (sold as accessories)
  • R-410A/R-22 Orifice Piston
  • ECM Motor ((33..55 –– 55 TToonn MMooddeellss ))
  • Low Voltage Pigtail Connections
  • Draw Through Design
  • Horizontal Drain pan
  • Single Color
  • Fused 24V Power
  • 5-year warranty
  • optional extended warranty available

Important: Condensate management kit is required for all 5-ton air handler models installed in downflow applications.
About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable, energy-efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice.
We are committed to using environmentally conscious print practices.
A4AH4P18A1B-SUB-1D-EN 09 Mar 2022
Supersedes A4AH4P18A1B-SUB-1C-EN (September 2020) ©2022

Documents / Resources

| AMERISTAR A4AH4P18A1B60C 1.5 Ton Convertible Air Handler [pdf] Instruction Manual
A4AH4P18A1B60C 1.5 Ton Convertible Air Handler, A4AH4P18A1B60C, 1.5 Ton Convertible Air Handler, Air Handler
---|---