NOTIFIER PK-LCD-80 Programmable Fire Alarm Control Panels Owner’s Manual
- June 9, 2024
- NOTIFIER
Table of Contents
PK-LCD-80 Programmable Fire Alarm Control Panels
Owner’s Manual
for NOTIFIER Programmable Fire Alarm Control Panels
PK-LCD-80 Programmable Fire Alarm Control Panels
Limitations of Fire Alarm Systems
While installing a fire alarm system may make lower insurance rates
possible, it is not a substitute for fire insurance!
An automatic fire alarm system
- typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located
throughout a protected premise following the recommendations of the current
edition of the National Fire Protection Association Standard 72 (NFPA 72),
manufacturer’s recommendations, State and local codes, and the recommendations
contained in the Guide for Proper Use of System Smoke Detectors, which is made
available at no charge to all installing dealers. A study by the Federal
Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as 35% of all fires.
While fire alarm systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not function, for a
variety of reasons: Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on roofs, or on
the other side of closed doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second floor detector, for example,
may not sense a first floor or basement
fire. Particles of combustion or “smoke” from a developing fire may not reach
the sensing chambers of smoke detectors because:
- Barriers such as closed or partially closed or, walls, or chimneys may inhibit particle or smoke flow.
- Smoke particles may become “cold”, stratify, and not reach the ceiling or upper walls where detectors are located.
- Smoke particles may be blown away from detectors by air outlets.
- Smoke detectors may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors.
Smoke detectors are designed to alarm at various levels of smoke density. If
such density levels are not created by a developing fire at the location of
detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations.
Detectors that have photoelectronic sensing chambers tend to detect smoldering
fires better than flaming fires, which have little visible smoke. Detectors
that have ionizing-type sensing chambers tend to detect fast flaming fires
betters than smoldering fires. Because fires develop in different ways and are
often unpredictable in their growth, neither type of detector is necessarily
best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused
by arson, children playing with matches (especially in bedrooms), smoking in
bed, and violent explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat
on their sensors increases at a predetermined rate or reaches a predetermined
level.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector should be tested at
least once per year by a qualified fire protection specialist. Heat detectors
are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
Audible warning devices such as bells may not alert people if these devices
are located on the other side of closed or partly open doors or are located on
another floor of a building.
Any warning device may fail to alert people with a disability or those who
have recently consumed drugs, alcohol or medication. Please note that:
- Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
- Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
- In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power
fails, the system will operate from standby batteries only for a specified
time and only if the batteries have been properly maintained and replaced
regularly.
Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your
control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled. For added
protection against telephone line failure, backup radio transmission systems
are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To
keep the entire fire alarm system in excellent working order, ongoing
maintenance is required per the manufacturer’s recommendations, and UL and
NFPA standards.
At a minimum the requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement should be arranged through
the local manufacturer’s representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and should be
performed by authorized professional fire alarm installers only.
Adequate written records of all inspections should be kept.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing device pursuant to
Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a commercial
environment.
Operation of this equipment in a residential area is likely to cause
interference, in which case the user will be required to correct the
interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Installation Precautions
Adherence to the following will aid in problem-free installation with long-
term reliability:
WARNING – Several different sources of power can be connected to the fire
alarm control panel. Disconnect all sources of power before servicing. Control
unit and associated equipment may be damaged by removing and/or inserting
cards, modules, or interconnecting cables while the unit is energized. Do not
attempt to install, service, or operate this unit until this manual is read
and understood.
CAUTION – System Reaccep- tance Test after Software Changes To ensure
proper system operation, this product must be tested in accordance with NFPA
72-1996 Chapter after any programming operation or change in site-specific
software.
Reacceptance testing is required after any change, addition or deletion of
system components, or after any modification, repair or adjustment to system
hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices
that are not directly affected by the change, up to a maximum of 50 devices,
must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120ºF and at
a relative humidity of 85% RH (non-condensing) at 30º C/86º F. However, the
useful life of the system’s standby batteries and the electronic components
may be adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and all peripherals be installed
in an environment with a nominal room temperature of 1527º C/60-80ºF. Verify
that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified
device voltage.
Like all solid state electronic devices, this system may operate erratically
or can be damaged when subjected to lightning induced transients. Although no
system is completely
immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes. Consult with
the Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit
boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or
punching of the enclosure. When possible, make all cable entries from the
sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system components can fail at any time.
This system contains static-sensitive components. Always ground yourself with
a proper wrist strap before handling any circuits so that static charges are
removed from the body.
Use static suppressive packaging to protect electronic assembliesre moved
from the unit.
Follow the instructions in the installation, operating, and programming
manuals. These instructions must be followed to avoid damage to the control
panel and associated equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Installation and Startup
Introduction
This manual describes the use of the LCD-80 Programming Utility. Using this
utility, the LCD-80 can be programmed directly from most IBM PC/XT/AT or
compatible computers, including lap-tops and portables, equipped with a serial
port. LCD-80 rogram files also can be created and stored on the PC, then
downloaded to the panel. Note: This program will function only with an LCD-80
having software P/N 73323 or P/N 73448 or higher.
Before attempting to program an LCD-80 with the programming utility, the user
should have a knowledge of basic computer use and MS-DOS command structure.
After creating or modifying an LCD-80 program, the system must be thoroughly
tested with the software installed and operational. For more information refer
to the LCD-80 Manual (Document 15037).
Inventory
The LCD-80 Off Line Programming Utility contains the following:
- Two low density floppy disks, one 5.25″ (p/n 75279), one 3.5″ (p/n 75280).
- Cable, 9-pin female to LCD-80 RS-232 connection (p/n 75267).
- Adapter, 9-pin male to 25-pin female (p/n 46029).
Program Installation
You can run the LCD-80 programming application directly either from a floppy
disk or from a hard disk drive. To install on a hard drive, create a directory
called LCD-80 on
the drive. Copy the files from the floppy drive to this directory.
Getting Started
The LCD-80 Programming Utility can be used in two ways:
On-Line Connect a PC to the LCD-80 and transfer program files between the two
devices.
Off-Line Even when a PC is not connected to the LCD-80, the PC can still be
used to create or modify program files. The files can be stored on magnetic
disk for later transfer to the LCD-80.
Connecting an IBM-PC (or compatible) Computer to an LCD-80
- Connect the LCD-80 to a 24 VDC Power Source as shown in Figure 1.
- Apply power and verify that a Ground Fault is not present. If a Ground Fault is present, it must be removed before the PC is connected. Connecting a PC to a system with a Ground Fault may result in damage to the PC, LCD-80 and the Fire Alarm System.
- Remove power and connect the LCD-80 to the PC, as shown in Figure 2.
- Configure the LCD-80 for ACS Mode.
- Verify that the LCD-80 has Software P/N 73323, P/N 73448 or higher.
- Install the PK-1 Program Key on Connector P6 of LCD-80.
- Apply power to the LCD-80 and the PC.
- Transfer information between the PC and the LCD-80.
- Remove power to the LCD-80 and the PC.
- Disconnect the PC and remove the PK-1 Program Key.
- Install the LCD-80.
- Test the Fire Alarm System.
Note: Maximum LCD-80 current draw is 100 mA. Note: The LCD-80 does not have to be physically connected to the PC while you are editing the labels. The PC and the LCD-80 only need to be connected during the transfer of files between the PC and the LCD-80.
LCD-80| Wire Color| EIA Name| 9 PIN Connector| 25 PIN
Connector
---|---|---|---|---
1| Green| Tx D| 3| 2
6| Red| Signal Ground| 5| 7
7| Black| Rx D| 2| 3
No Connection| –| DTR| 4 (Note 1)| 20
No Connection| –| DSR| 6 (Note 1)| 6
Note: Pin 4 (DTR) is connected to pin 6 (DSR) in the 9 pin connector
housing.
Starting the Program
Use DOS to Start-up the LCD-80 utility program named “LCD80.EXE,” by typing
LCD80 and then pressing the Return key. The following menu should appear:
Figure 3: Menu for Selection of Com Port
Type the number of the COM port you wish to use. After selecting a COM port, the following “Main Menu” will appear on your computer screen.
Figure 4: Main Menu
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>