FX-2000 Series UL Listed Compatible Devices

FX-2000 Series UL Listed Compatible Addressable Loop Modules

Manufacturer & Model Description

Mircom
MIX-1251/B| Low-Profile Analog Ionization Smoke Sensor
MIX-2251/T| Low-Profile Analog Photoelectronic Smoke Sensor/plus Thermal
MIX-2251TM| Low-Profile Acclimate™ Intelligent Photoelectric Thermal Sensor
MIX-7251| Pinnacle™ Intelligent Laser Smoke Sensor
MIX-5251P/RP| Low-Profile Analog Thermal Sensor/Rate of Rise
MIX-5251/R| Low-Profile Analog Thermal Sensor/Rate of Rise
MIX-M500MB| Monitor Module (Universal)
MIX-5251H| Low Profile Intelligent Thermal Sensor
MIX-M500CH| Addressable Control Module
MIX-M501M| Addressable Mini-Monitor Module
MIX-M502M| Universal Monitor Module
MIX-M500R| Addressable Relay Output Module
MIX-M500S| Addressable Supervised Output Module
MIX-M500DM| Addressable Dual Input Monitor Module
MIX-DH200PL| Intelligent Smoke Detector
MIX-DH200RPL| Intelligent Smoke Detector (with relay)
MIX-210LP| 200 Series Low Profile Intelligent Base
MIX-B501BH| 200 Series Low Profile Intelligent Base with Horn
MIX-B501BHT| 200 Series Low Profile Intelligent Base with Horn (Temporal Code)
System Sensor
FTX-P1| Filtrex™ Intelligent Photoelectric Smoke Sensor
M500X| Fault Isolator Module
IM-10| Ten Input Monitor Addressable Module
CR-6| Six Relay Control Module
SC-6| Six Supervised Control Module
B224BI| Analog Base with Isolator
B501B| Analog Base
B210LP| 200 Series Low Profile Intelligent Base
System Sensor continued

B501B-FTX| Filtrex Base
B501BH| 200 Series Low Profile Intelligent Base with Horn
B501BHT| 200 Series Low Profile Intelligent Base with Horn (Temporal Code)
CZ-6| Six Addressable Universal Zone Module
BEAM200| Intelligent Addressable Beam Detector
BEAM200S| Intelligent Addressable Beam Detector (with Sens Test)

FX-2000 Series UL Listed Compatible Two-Wire Smoke Detectors
Notes:

  • Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, total standby current of all detectors must not exceed 3 mA.
  • The below listed smoke detectors are compatible with initiating circuits having Compatibility Identifier “A”.

Smoke Detector Manufacturer Model / Base| Compatibility Identifier Head / Base| Rated Standby Current| Maximum # of devices per circuit
---|---|---|---
Mircom|  |  |
MIR-525U| FDT-1| 0.10 mA| 30
MIR-525TU| FDT-1| 0.10 mA| 30
Apollo
55000-225 / 45681-251, -255, -256, -258| 225 / 251, 255, 256, 258| 0.045 mA| 30
55000-325 / 45681-251, -255, -256, -258| 325 / 251, 255, 256, 258| 0.045 mA| 30
Detection Systems Inc.
DS250| B – N/A| 0.10 mA| 30
DS250TH| B – N/A| 0.10 mA| 30
DS282| B – N/A| 0.10 mA| 30
DS282TH| B – N/A| 0.10 mA| 30
Hochiki
DCD-135/NS6-220| HD-3/HB-72| 0.035mA| 30
DCD-135/NS4-220| HD-3/HB-3| 0.035mA| 30
DCD-135/HSC-220R| HD-3/HB-3| 0.035mA| 30
DCD-190/NS6-220| HD-3/HB-3| 0.035mA| 30
DCD-190/NS4-220| HD-3/HB-3| 0.035mA| 30
DCD-190/HSC-220R| HD-3/HB-3| 0.035mA| 30
SIJ-24/NS6-220| HD-3/HB-72| 0.040mA| 30
SIJ-24/NS4-220| HD-3/HB-3| 0.040mA| 30
SIJ-24/HSC-220R| HD-3/HB-3| 0.040mA| 30
SLR-24/NS6-220| HD-3/HB-72| 0.045mA| 30
SLR-24/NS4-220| HD-3/HB-3| 0.045mA| 30
SLR-24/HSC-220R| HD-3/HB-3| 0.045mA| 30
SLR-24H/NS6-220| HD-3/HB-3| 0.045mA| 30
SLR-24H/NS4-220| HD-3/HB-3| 0.045mA| 30
Hochiki continued

SLR-24H/HSC-220R| HD-3/HB-72| 0.045mA| 30
SLR-835/NS6-220| HD-3/HB-3| 0.045mA| 30
SLR-835/NS4-220| HD-3/HB-3| 0.045mA| 30
SLR-835/HSC-220R| HD-3/HB-72| 0.045mA| 30
SLR-835B-2| HD-6| 55µa @ 24VDC| 30
NAPCO
FW-2| HD-6| 55µA @ 24VDC| 30
Sentrol – ESL
429C| S10A – N/A| 0.10 mA| 30
429CT| S10A – N/A| 0.10 mA| 30
429CST| S11A – N/A| 0.10 mA| 30
429CRT| S11A – N/A| 0.10 mA| 30
711U/701E, 701U, 702E, 702U| S10A – S00| 0.10 mA| 30
712U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA| 30
713-5U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA| 30
721U / 702E, 702U| S10A – S00| 0.10 mA| 30
732U / 702E, 702U, 702RE, 702RU| S11A – S00| 0.10 mA| 30
721UT / 702E, 702U| S10A – S00| 0.10 mA| 30
722U / 702E, 702U| S10A – S00| 0.10 mA| 30
731U / 702E, 702U, 702RE, 702RU| S11A – S00| 0.10 mA| 30
721UT / 702E, 702U| S10A – S00| 0.10 mA| 30
721UT / 702E, 702U| S10A – S00| 0.10 mA| 30
System Sensor
4451HT / B401| A – A| 0.12 mA| 25
5451 / B401B| A – A| 0.12 mA| 25
5451 / B401| A – A| 0.12 mA| 25
2451 / B401B| A – A| 0.12 mA| 25
2451 / B406B| A – A| 0.12 mA| 25
2451 / DH400| A – N/A| 0.12 mA| 25
2451TH / B406B| A – A| 0.12 mA| 25
System Sensor continued

2451 / B401| A – A| 0.12 mA| 25
2451TH / B401| A – A| 0.12 mA| 25
4451HT / B401B| A – A| 0.12 mA| 25
4451HT / B406B| A – A| 0.12 mA| 25
1100| A – N/A| 0.12 mA| 25
1151/ B110LP| A – A| 0.12 mA| 25
1151/ B116LP| A – A| 0.12 mA| 25
1400| A – N/A| 0.10 mA| 25
1451/B401| A – A| 0.12 mA| 25
1451/ B401B| A – A| 0.12 mA| 25
1451/ B406B| A – A| 0.12 mA| 25
1451DH/ DH400| A – A| 0.12 mA| 25
2100| A – N/A| 0.12 mA| 25
2100T| A – N/A| 0.12 mA| 25
2151/ B110LP| A – A| 0.12 mA| 25
5451 / B406B| A – A| 0.12 mA| 25
2151/ B116LP| A – A| 0.12 mA| 25
2400| A – N/A| 0.12 mA| 25
2400TH| A – N/A| 0.12 mA| 25
2WTA-B| A – N/A| 0.1 mA| 1
2WTR-B| A – N/A| 0.1 mA| 1
2W-B, 2WT-B| A – N/A| 0.1 mA| 30

FX-2000 Series UL Listed Compatible Four-Wire Smoke Detectors


Manufacturer & Model/Circuit

| Maximum # of Devices
---|---
Mircom
MIR-545U| 30
MIR-545TU| 30
Sentrol-ESL
541C| N/A
541CXT| N/A
709-MV-21| N/A
709-24V-21| N/A
741U WITH 702U or 702E Base| N/A
449AT, 449C, 449CT, 449CRT, 449CST, 449CSTE, 449CSRT, 449CSRH, 449CSST,

449CSSTE, 449CTE, 449CSLT

| N/A
System Sensor
1424| 25
6424| 30
6424A| 30
A77-716B|
DH400ACDCI| 8
DH400ACDCP| 8
DH400ACDCIHT| 8

FX-2000 Series UL Listed Compatible Signalling Devices

System Sensor – SpectrAlert| Wheelock continued| Wheelock continued
---|---|---
P2415| AS-2475C-FW| AMT-12/24-R-ULC
P2415W| AS-24100C-FW| AMT-24-LS-VFR-ULC
P241575| AH-24-R| MB-G6-24-R
P241575W| AH-24-WP-R| MB-G10-24-R
P2475| NS-2415W-FR| SM-12/24-R
P2475W| NS-241575W-FR| DSM-12/24-R
P24110| NS-2430W-FR|
P24110W| NS-2475W-FR
S2415| NS-24110W-FR
S2415W| NS4-2415W-FR
S241575| NS4-241575W-FR
S241575W| NS4-2430W-FR
S2475| NS4-2475W-FR
S2475W| NS4-24110W-FR
S24110| RS-2415W-FR
S24110W| RSS-241575W-FR
H12/24| RSS-2415W-FR
H12/24W| RSS-241575W-FR
MDL| RSS-2430W-FR
MDLW| RSS-2475W-FR
Wheelock| RSS-24110W-FR
AS-2415W-24-FR| RSS-2415C-FW
AS-241575W-FR| RSS-2430C-FW
AS-2430W-FR| RSS-2475C-FW
AS-2475W-FR| RSS-24100C-FW
AS-24110W-FR| MT-12/24-ULC
AS-2415C-FW| MT-24-LS-VFR-ULC
AS-2430C-FW| MT-24-WS-VFR-ULC

FX-2000 Series ULC Listed Compatible Devices

FX-2000 Series ULC Listed Compatible Addressable Loop Modules

Manufacturer & Model Description

Mircom
MIX-1551A| Analog Ionization Smoke Sensor
MIX-1251A/BA| Low-Profile Analog Ionization Smoke Sensor
MIX-2551A| Analog Photoelectronic Smoke Sensor
MIX-2251A/2551TA| Low-Profile Analog Photoelectronic Smoke Sensor / Plus Thermal
MIX-2251TMA| Low-Profile Acclimate™ Intelligent Photoelectric Thermal Sensor
MIX-7251A| Pinnacle™ Intelligent Laser Smoke Sensor
MIX-M500MA| Monitor Module (Universal)
MIX-M500CHA| Addressable Control Module
MIX-M501MA| Addressable Mini-Monitor Module
MIX-DH200PLA| Intelligent Smoke Detector
MIX-DH200RPLA| Intelligent Smoke Detector (with relay)
MIX-210LPA| 200 Series Low Profile Intelligent Base
MIX-B501BHA| 200 Series Low Profile Intelligent Base with Horn
MIX-B501BHTA| 200 Series Low Profile Intelligent Base with Horn (Temporal Code)
System Sensor
5551A| Analog Thermal Sensor
5551RA| Analog Rate of Rise Thermal Sensor
5251PA| Low-Profile Analog Thermal Sensor
5251RPA| Low-Profile Analog Rate of Rise Thermal Sensor
FTX-P1A| Filtrex™ Intelligent Photoelectric Smoke Sensor
M500X| Fault Isolator Module
B224BIA| Analog Base with Isolator
B501B| Analog Base
IM-10A| Ten Input Monitor Addressable Module
CR-6A| Six Relay Control Module
SC-6A| Six Supervised Control Module

FX-2000 Series ULC Listed Compatible Hardwire Smoke Detectors
Notes:

Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, total standby current of all detectors must not exceed 3 mA.


Manufacturer & Model

| Maximum # of Devices/ Circuit| ****

Manufacturer & Model

| Maximum # of Devices/ Circuit
---|---|---|---
Mircom| Fenwal continued
MIR-525| 30| PSD-7130/70-201000-003| base
MIR-525T| 30| PSD-7130/70-201000-005| base
MIR-1400A| 30| PSD-7128/70-201000-001| base
MIR-2400A| 25| PSD-7126/70-201000-002| base
Apollo| PSD-7126/70-201000-003| base
55000-325| 30| PSD-7126/70-201000-005| base
55000-325 / 45681-251, -255, –

256, -258

| 30| PSD-7129/70-201000-000| base
Cerebrus Pyrotronics| PSD-7125/70-201000-001| base
DI-2| base| PSD-7126/70-201000-002| base
DI-3/DB-3S| 30| PSD-7125/70-201000-003| base
Edwards| PSD-7125/70-201000-005| base
6249C| base| CPD-7021/70-201000-001| base
6250C| base| CPD-7021/70-201000-002| base
6264C| base| CPD-7021/70-201000-003| base
6266C| base| CPD-7021/70-201000-005| base
6269C| base| Hochiki
6270C| base| DCD-135/NS6-220| 30
6269C-003| base| DCD-135/NS4-220| 30
6270C-003| base| DCD-135/HSC-220R| 30
Fenwal| DCD-190/NS6-220| 30
PSD-7131/70-201000-001| base| DCD-190/NS4-220| 30
PSD-7131/70-201000-002| base| DCD-190/HSC-220R| 30
PSD-7131/70-201000-003| base| SIJ-24/NS6-220| 30
PSD-7131/70-201000-005| base| SIJ-24/NS4-220| 30
PSD-7130/70-201000-001| base| SIJ-24/HSC-220R| 30
PSD-7130/70-201000-002| base| SLR-24/NS6-220| 30
Hochiki continued| System Sensor continued
---|---
SLR-24/NS4-220| 30| 1451DH/DH400A| 30
SLR-24/HSC-220R| 30| 2451-A/DH400A| 25
SLR-24H/NS6-220| 30| 1151A| 30
SLR-24H/NS4-220| 30| 2151A| 30
SLR-24H/HSC-220R| 30| C2W-BA/C2WT-BA| 30
SLR-835/NS6-220| 30| C2WTR-B| 1
SLR-835/NS4-220| 30| C2WTA-BA| 1
SLR-835/HSC-220R| 30| NAPCO|
SLR-835B-2| 30| FW-2| 30
Mirtone|
73471| base
73494| base
73575| base
73495/73486| base
73495/73487| base
73595/73486| base
73595/73497| base
73594/73400| base
73405/73400| base
73594/73401| base
73405/73401| base
Simplex
2098-9110| base
System Sensor
1400-A| 30
2400-A| 25
1451-A/B401B| 25
1451-A/B406B| 25
2451-A/B401B| 25
2451-A/B406B| 25

FX-2000 Series Compatible Synchronized Modules and Strobes
Notes:

  1. Strobes and horns must be connected to separate circuits since the horn is a non-synchronized audible appliance.
  2. Do not mix and match sync module with strobes from different manufacturers because each manufacturer uses different synchronization protocols.

Manufacturer| Brand| Sync. Module| Strobe Model| Max. Strobe / NAC
---|---|---|---|---
Amseco / Potter| Mircom| SDM 240| FHS-240-110| 15
Gentex Corp.| Secutron| AVS44 R| MRA-HS3-24ww| 20
SpectrAlert| System Sensor| MDL| P1224 MC| 25
Wheelock| Wheelock| DSM 12/24| NS-24 MCW -FW| 25
Faraday| Faraday| 5406| 6234B-14-24| 26*

FX-350 Series UL/ULC Listed Compatible Addressable Devices

Model Description

Detectors
MIX-3000| Ionization Smoke Detector (U.S. Model Only)
MIX-3100| Photoelectric Smoke Detector
MIX-3200| Multi-sensor (photoelectric with supplemental rate-of-rise heat sensor)
Note:
Unit employs an integral heat sensor; however it must not be used as a regular heat detector.

Refer to the product data sheet for detailed functionality, operation and application. Manual configuration for the MIX-3200 is NOT PERMITTED. This device must be configured via the AUTO CONFIG.

MIX-3300| Heat Detector
Bases
MIX-2000| 4 inch Standard Base
MIX-2001| 6 inch E-Z Fit Base
MIX-2001R| 6 inch Base with Relay
MIX-2001H| 6 inch Base with Sounder
MIX-2001HT| 6 inch Base with Temporal Tone Sounder
Ancillary Modules|
MIX-100P| Priority Monitor Module
MIX-101P| Mini Priority Monitor Module
55000-820| Single Relay Output Module (1 Form C Contacts, 2 Gang Mount)
MIX-100S| Supervised Control Module
MIX-100X (Kit), 100XH

(Isolator), 100XB (Base)

| Isolator c/w Mounting Base
Addressable Duct Detectors
MIX-DH3000| Ionization Duct Smoke Detector (UL Listed)
MIX-DH3001| Photoelectric Duct Smoke Detector (UL Listed)
MIX-DH3000R| Ionization Duct Smoke Detector with relay (UL Listed)
MIX-DH3001R| Photoelectric Duct Smoke Detector with relay (UL Listed)
Addressable Pull Stations
MS-401ID(U)| Addressable Single Stage Pull Station
MS-402ID| Addressable Two Stage Pull Station (Canadian Model Only)
MS-701ID(U)| Addressable Single Stage Single Action Pull Station
Addressable Pull Stations continued

MS-702ID(U)| Addressable Two Stage Single Action Pull Station
MS-710IDU| Addressable Two Stage Dual Action Pull Station

FX-350 Compatible Receivers

DACR Receiver Model Protocols
SurGard MLR2 Multi-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco

Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI approved)| SIA-DCS and Ademco Contact ID
Osborne-Hoffman Quickalert! II Receiver (ULI approved)| SIA-DCS and Ademco Contact ID
Osborne-Hoffman OH-2000 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID

FR-320 Series UL Listed Compatible Devices

FR-320 Compatible UL Listed Two-Wire Smoke Detectors


Make Model / Base

| Compatibility Identifier Head/Base| Rated Standby Current (mA)| Maximum # of devices per circuit
---|---|---|---
Mircom
MIR-525U| FDT-1| 0.1| 30
MIR-525TU| FDT-1| 0.1| 30
MIR-1400A| A-N/A| 0.1| 30
MIR-2400A| A/ N/A| 0.1| 30
Mircom Bases MSB-65B, MSB-65B-4, MSB-65B-4R
MID-65I| MID-65I| 0.045| 25
MPD-65P| MPD-65P| 0.045| 20
MHD-65-135| MHD-65-135| 0.055| 25
MHD-65-200| MHD-65-200| 0.055| 25
Apollo
Series 60A Bases 45681-200,-220,-232,-251
Series 65A Bases 45681-255,-256,-257,-258
55000-225| 55000-225| 0.045| 25
55000-226| 55000-226| 0.045| 25
55000-227| 55000-227| 0.028| 25
55000-325| 55000-325| 0.045| 20
55000-326| 55000-326| 0.045| 20
55000-327| 55000-327| 0.04| 20
55000-328| 55000-328| N/A| 30
55000-138| 55000-138| 0.055| 25
55000-139| 55000-139| 0.055| 25
55000-140| 55000-140| 0.045| 25
Hochiki
DCD-135/HSC-220R| HD-3/HB-72| 0.035| 12
DCD-135/NS6-220| HD-3/HB-3| 0.035| 12
DCD-190/HSC-220R| HD-3/HB-72| 0.035| 12
Hochiki continued

DCD-190/NS4-220| HD-3/HB-3| 0.035| 12
DCD-190/NS6-220| HD-3/HB-3| 0.035| 12
SIJ-24/HSC-220R| HD-3/HB-72| 0.04| 12
SIJ-24/NS4-220| HD-3/HB-3| 0.04| 12
SIJ-24/NS6-220| HD-3/HB-3| 0.04| 12
SLR-24/HSC-220R| HD-3/HB-72| 0.045| 12
SLR-24/NS4-220| HD-3/HB-3| 0.045| 12
SLR-24/NS6-220| HD-3/HB-3| 0.045| 12
Sentrol-ESL
429C / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
429CRT / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
429CST / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
429CT / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
711U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
713-5U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
713-6U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
721U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
721UT / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
722U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
731U / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
732U / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
System Sensor
1100| A-N/A| 0.12| 25
1400| A-N/A| 0.1| 25
2100| A-N/A| 0.12| 25
2400| A-N/A| 0.12| 25
1151/B110LP| A-A| 0.12| 25
1151/B116LP| A-A| 0.12| 25
1451/B401| A-A| 0.12| 25
1451/B401B| A-A| 0.12| 25
System Sensor continued

1451/B406B| A-A| 0.12| 25
1451DH/DH400| A-A| 0.12| 25
2100T| A-N/A| 0.12| 25
2151/B110LP| A-A| 0.12| 25
2151/B116LP| A-A| 0.12| 25
2400TH| A-N/A| 0.12| 25
2451/B401| A-A| 0.12| 25
2451/B401B| A-A| 0.12| 25
2451/B406B| A-A| 0.12| 25
2451/DH400| A-A| 0.12| 25
2451TH/B401| A-A| 0.12| 25
2451TH/B401B| A-A| 0.12| 25
2451TH/B406B| A-A| 0.12| 25
5451/B401| A-A| 0.12| 25
5451/B401B| A-A| 0.12| 25
5451/B406B| A-A| 0.12| 25
System Sensor i3
2W-B c/w base| A-A| 0.1| 30
2WT-B c/w base| A-A| 0.1| 30

FR-320 Series ULC Listed Compatible Devices

FR-320 Series ULC Listed Compatible Two-Wire Smoke Detectors


Make Model / Base

| Maximum # of devices per circuit| ****

Make Model / Base

| Maximum # of devices per circuit
---|---|---|---
Mircom| Hochiki continued
MIR-525| 30| SLR-24/HSC-220| 12
MIR-525T| 30| SLR-24/NS4-220| 12
MIR-1400A| 30| SLR-24/NS6-220| 12
MIR-2400A| 30| System Sensor i3
Apollo| C2W-BA c/w base| 30
Series 60A Bases 45681-200,-220,-232,-251| C2WT-BA c/w base| 30
Series 65A Bases 45681-255,-256,-257,-258| System Sensor
55000-225| 30| 1400A| 20
55000-226| 30| 2400A| 20
55000-227| 30| 1451/B401B| 20
55000-325| 30| 2451/B401B| 20
55000-326| 30|
55000-327| 30
55000-328| 30
55000-138| 30
55000-139| 30
55000-140| 30
Hochiki|
DCD-135/HSC-220R| 12
DCD-135/NS6-220| 12
DCD-190/HSC-220R| 12
DCD-190/NS4-220| 12
DCD-190/NS6-220| 12
SIJ-24/HSC-220R| 12
SIJ-24/NS4-220| 12
SIJ-24/NS6-220| 12

FR-320 Series Compatible Solenoids

Manufacturer Description

ASCO 8210 series
T8210A107 24VDC|
R8210A107 24VDC|
8210A107 24VDC|
AMEREX
17014| Actuator
BSCO
510006| Actuator
Kidde Fenwal Protection Systems
486500-01| Actuator
Parker
73212| Valve Solenoid
Parker Skinner Valve Division Cardox 7-061-0006
V5L 72750| Valve Solenoid
SIEMENS
CPYEC-24|
TSP
17842| Actuator

FR-320 Fire Panel Maximum Number of Horn/Strobes

Manufacturer Maximum # of Horn/Strobes

Wheelock
NS-24MCW-FW| 13
Gentex
MRA-HS3-24| 8
System Sensor
P1224 MC| 12
Mircom
FHS-240-110| 9
Faraday
Note: Separate Circuit for Horn & Strobe
6234 Series| 9

FA-300 Series UL Listed Compatible Devices

FA-300, FA-300-6L Series UL Listed Compatible Two-Wire Smoke Detectors
Notes:

  1. Detectors of different models are not to be mixed in a circuit.
  2. Please refer to applicable installation Manual (LT-905, LT-906, LT-950 or LT-951) for specific wiring details.

Make Model / Base

| Compatibility Identifier Head/ Base| Rated Standby Current (mA)| Maximum # of devices per circuit
---|---|---|---
Mircom|  |  |
MIR-525U| FDT-1| 0.1| 30
MIR-525TU| FDT-1| 0.1| 30
MIR-1400A| A-N/A| 0.1| 30
MIR-2400A| A/ N/A| 0.1| 30
Bases MSB-65B, MSB-65B-4, MSB-65B-4R
MID-65I| MID-65I| 0.045| 25
MPD-65P| MPD-65P| 0.045| 25
MHD-65-135| MHD-65-135| 0.055| 25
MHD-65-200| MHD-65-200| 0.055| 25
Apollo
Series 60A Bases 45681-200,-220,-232,-251
Series 65A Bases 45681-255,-256,-257,-258
55000-225| 55000-225| 0.045| 30
55000-226| 55000-226| 0.045| 30
55000-227| 55000-227| 0.028| 30
55000-325| 55000-325| 0.045| 30
55000-326| 55000-326| 0.045| 30
55000-327| 55000-327| 0.04| 30
55000-328| 55000-328| N/A| 30
55000-138| 55000-138| 0.055| 30
55000-139| 55000-139| 0.055| 30
55000-140| 55000-140| 0.045| 30
Hochiki

DCD-135/HSC-220R| HD-3/HB-72| 0.035| 12
DCD-135/NS6-220| HD-3/HB-3| 0.035| 12
DCD-190/HSC-220R| HD-3/HB-72| 0.035| 12
DCD-190/NS4-220| HD-3/HB-3| 0.035| 12
DCD-190/NS6-220| HD-3/HB-3| 0.035| 12
SIJ-24/HSC-220R| HD-3/HB-72| 0.04| 12
SIJ-24/NS4-220| HD-3/HB-3| 0.04| 12
SIJ-24/NS6-220| HD-3/HB-3| 0.04| 12
SLR-24/HSC-220R| HD-3/HB-72| 0.045| 12
SLR-24/NS4-220| HD-3/HB-3| 0.045| 12
SLR-24/NS6-220| HD-3/HB-3| 0.045| 12
Sentrol-ESL
429C / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
429CRT / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
429CST / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
429CT / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
711U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
713-5U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
713-6U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
721U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
721UT / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
722U / (701E, 701U, 702E, 702U)| S10A-S00| 0.1| 30
731U / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
732U / (702E, 702RE, 702RU, 702U)| S11A-S00| 0.1| 30
System Sensor
1100| A-N/A| 0.12| 25
1400| A-N/A| 0.1| 25
2100| A-N/A| 0.12| 25
2400| A-N/A| 0.12| 25
1151/B110LP| A-A| 0.12| 25
1151/B116LP| A-A| 0.12| 25
System Sensor continued

1451/B401| A-A| 0.12| 25
1451/B401B| A-A| 0.12| 25
1451/B406B| A-A| 0.12| 25
1451DH/DH400| A-A| 0.12| 25
2100T| A-N/A| 0.12| 25
2151/B110LP| A-A| 0.12| 25
2151/B116LP| A-A| 0.12| 25
2400TH| A-N/A| 0.12| 25
2451/B401| A-A| 0.12| 25
2451/B401B| A-A| 0.12| 25
2451/B406B| A-A| 0.12| 25
2451/DH400| A-A| 0.12| 25
2451TH/B401| A-A| 0.12| 25
2451TH/B401B| A-A| 0.12| 25
2451TH/B406B| A-A| 0.12| 25
5451/B401| A-A| 0.12| 25
5451/B401B| A-A| 0.12| 25
5451/B406B| A-A| 0.12| 25
2W-B c/w base| A-A| 0.1| 30
2WT-B c/w base| A-A| 0.1| 30

FA-300 Series ULC Listed Compatible Devices

FA-300, FA-300-6L Series ULC Listed Two-Wire Smoke Detectors


Make Model / Base

| Maximum # of devices per circuit| ****

Make Model / Base

| Maximum # of devices per circuit
---|---|---|---
Mircom| Hochiki continued
MIR-525| 30| SLR-24/NS4-220| 12
MIR-525T| 30| SLR-24/NS6-220| 12
MIR-1400A| 30| System Sensor i3|
MIR-2400A| 30| C2W-BA c/w base| 30
Apollo| C2WT-BA c/w base| 30
Series 60A Bases 45681-200,-220,-232,-251| System Sensor|
Series 65A Bases 45681-255,-256,-257,-258| 1400A| 25
55000-225| 30| 2400A|
55000-226| 30| 1451/B401B|
55000-227| 30| 2451/B401B|
55000-325| 30|
55000-326| 30
55000-327| 30
55000-328| 30
55000-138| 30
55000-139| 30
55000-140| 30
Hochiki
DCD-135/HSC-220R| 12
DCD-135/NS6-220| 12
DCD-190/HSC-220R| 12
DCD-190/NS4-220| 12
DCD-190/NS6-220| 12
SIJ-24/HSC-220R| 12
SIJ-24/NS4-220| 12
SIJ-24/NS6-220| 12
SLR-24/HSC-220| 12

FA-300 and FA-300-6L Series UL and ULC Listed Supported Synchronous Horn/Strobe

Device Mircom Equivalent Part # Amseco Part #
Horns/Strobes FHS-240R/FHS-240W SH24W-153075
Strobes FS-240R/FS-240W SL24W-153075

FA-300-6L Maximum Number of Horn/Strobes

Horn/Strobe Manufacturer| Maximum # of Horn/Strobes| Horn/Strobe Manufacturer| Maximum # of Horn/Strobes
---|---|---|---
Mircom| Gentex
FHS-240-110| 20| MRA-HS3-24| 32
Faraday| System Sensor
Note: Separate Circuit for Horn & Strobe.| P1224 MC| 32
6234 Series| 16| Wheelock
 | NS-24MCW-FW| 40

FA-300 Compatible Solenoids

Manufacturer                  Description| Manufacturer Description
---|---
ASCO 8210 series| Parker
T8210A107 24VDC|  | 73212| Valve Solenoid
R8210A107 24VDC|  | Parker Skinner Valve Division Cardox 7-061- 0006
8210A107 24VDC|  | V5L 72750| Valve Solenoid
AMEREX| SIEMENS
17014| Actuator| CPYEC-24|
BSCO| TSP
510006| Actuator| 17842| Actuator
Kidde Fenwal Protection Systems|
486500-01| Actuator

FA-300 Compatible Receivers

DACR Receiver Model Protocols
SurGard MLR2 Multi-Line Receiver (ULC, ULI approved) SIA-DCS and Ademco

Contact ID
SurGard SLR Single-Line Receiver (ULC, ULI approved)| SIA-DCS and Ademco Contact ID
Osborne-Hoffman Quickalert! II Receiver (ULI approved)| SIA-DCS and Ademco Contact ID
Osborne-Hoffman OH-2000 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID
Silent Knight Model 9500 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID
Radionics Model D6500 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID
Radionics Model D6600 Receiver (ULI Approved)| SIA-DCS and Ademco Contact ID

FA-1000 & FA-100 Series UL Listed Compatible Devices

FA-1000 & FA-100 Series UL Listed Two-Wire Smoke Detectors
Notes:

  • Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, total standby current of all detectors must not exceed 3 mA.
  • The below listed smoke detectors are compatible with initiating circuits having Compatibility Identifier “A”.

Smoke Detector Make Model / Base

| Compatibility Identifier Head / Base| Rated Standby Current| Maximum # of devices per circuit
---|---|---|---
Mircom
MIR-525U| FDT-1| 0.10 mA| 30
MIR-525TU| FDT-1| 0.10 mA| 30
Apollo
55000-225 / 45681-251, -255, -256, -258| 225 / 251, 255, 256, 258| 0.045 mA| 30
55000-325 / 45681-251, -255, -256, -258| 325 / 251, 255, 256, 258| 0.045 mA| 30
Detection Systems Inc.
DS250| B – N/A| 0.10 mA| 30
DS250TH| B – N/A| 0.10 mA| 30
DS282| B – N/A| 0.10 mA| 30
DS282TH| B – N/A| 0.10 mA| 30
Edwards
C2M-PD/CM2M-PD|  |  |
EC-103-3/CSBU|  |  |
Hochiki
DCD-135/NS6-220| HD-3/HB-72| 0.035mA| 30
DCD-135/NS4-220| HD-3/HB-3| 0.035mA| 30
DCD-135/HSC-220R| HD-3/HB-3| 0.035mA| 30
DCD-190/NS6-220| HD-3/HB-3| 0.035mA| 30
DCD-190/NS4-220| HD-3/HB-3| 0.035mA| 30
DCD-190/HSC-220R| HD-3/HB-3| 0.035mA| 30
SIJ-24/NS6-220| HD-3/HB-72| 0.040mA| 30
SIJ-24/NS4-220| HD-3/HB-3| 0.040mA| 30
SIJ-24/HSC-220R| HD-3/HB-3| 0.040mA| 30
SLR-24/NS6-220| HD-3/HB-72| 0.045mA| 30
Hochiki continued

SLR-24/NS4-220| HD-3/HB-3| 0.045mA| 30
SLR-24/HSC-220R| HD-3/HB-3| 0.045mA| 30
SLR-24H/NS6-220| HD-3/HB-3| 0.045mA| 30
SLR-24H/NS4-220| HD-3/HB-3| 0.045mA| 30
SLR-24H/HSC-220R| HD-3/HB-72| 0.045mA| 30
SLR-835/NS6-220| HD-3/HB-3| 0.045mA| 30
SLR-835/NS4-220| HD-3/HB-3| 0.045mA| 30
SLR-835/HSC-220R| HD-3/HB-72| 0.045mA| 30
SLR-835B-2| HD-6| 55µa @ 24VDC| 30
Napco
FW-2| HD-6| 55µA @ 24VDC| 30
Sentrol – ESL
429C| S10A – N/A| 0.10 mA| 30
429CT| S10A – N/A| 0.10 mA| 30
429CST| S11A – N/A| 0.10 mA| 30
429CRT| S11A – N/A| 0.10 mA| 30
711U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA| 30
712U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA| 30
713-5U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA| 30
713-6U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA| 30
721U / 702E, 702U| S10A – S00| 0.10 mA| 30
732U / 702E, 702U, 702RE, 702RU| S11A – S00| 0.10 mA| 30
721UT / 702E, 702U| S10A – S00| 0.10 mA| 30
722U / 702E, 702U| S10A – S00| 0.10 mA| 30
731U / 702E, 702U, 702RE, 702RU| S11A – S00| 0.10 mA| 30
721UT / 702E, 702U| S10A – S00| 0.10 mA| 30
721UT / 702E, 702U| S10A – S00| 0.10 mA| 30
System Sensor
4451HT / B401| A – A| 0.12 mA| 25
5451 / B401B| A – A| 0.12 mA| 25
5451 / B401| A – A| 0.12 mA| 25
System Sensor continued

2451 / B401B| A – A| 0.12 mA| 25
2451 / B406B| A – A| 0.12 mA| 25
2451 / DH400| A – N/A| 0.12 mA| 25
2451TH / B406B| A – A| 0.12 mA| 25
2451 / B401| A – A| 0.12 mA| 25
2451TH / B401| A – A| 0.12 mA| 25
4451HT / B401B| A – A| 0.12 mA| 25
4451HT / B406B| A – A| 0.12 mA| 25
1100| A – N/A| 0.12 mA| 25
1151 / B110LP| A – A| 0.12 mA| 25
1151 / B116LP| A – A| 0.12 mA| 25
1400| A – N/A| 0.10 mA| 25
1451 / B401| A – A| 0.12 mA| 25
1451 / B401B| A – A| 0.12 mA| 25
1451 / B406B| A – A| 0.12 mA| 25
1451DH / DH400| A – A| 0.12 mA| 25
2100| A – N/A| 0.12 mA| 25
2100T| A – N/A| 0.12 mA| 25
2151/ B110LP| A – A| 0.12 mA| 25
5451 / B406B| A – A| 0.12 mA| 25
2151 / B116LP| A – A| 0.12 mA| 25
2400| A – N/A| 0.12 mA| 25
2400TH| A – N/A| 0.12 mA| 25
2400AT| A – N/A| 0.12 mA| 25
2400AIT| A – N/A| 0.12 mA| 25
2451TH / B401B| A – A| 0.12 mA| 25
2WTA-B| A – N/A| 0.1 mA| 1
2WTR-B| A – N/A| 0.1 mA| 1
2W-B, 2WT-B| A – N/A| 0.1 mA| 30

FA-1000 & FA-100 Series UL Listed Compatible Four-Wire Smoke Detectors


Smoke Detector Make Model / Base

| Maximum # of devices per circuit
---|---
Mircom
MIR-545U| 30
MIR-545TU| 30
Sentrol-ESL
541C| N/A
541CXT| N/A
709-MV-21| N/A
709-24V-21| N/A
741U WITH 702U or 702E Base| N/A
449AT, 449C, 449CT, 449CRT, 449CST, 449CSTE, 449CSRT,

449CSRH, 449CSST, 449CSSTE, 449CTE, 449CSLT

| N/A
System Sensor|
1424| 25
6424| 30
6424A| 30
A77-716B|
DH400ACDCI| 8
DH400ACDCP| 8
DH400ACDCIHT| 8

FA-1000 & FA-100 Series UL Listed Compatible Signaling Devices

System Sensor – SpectrAlert| Wheelock continued| Wheelock continued| Gentex continued
---|---|---|---
P2415| AS-2430C-FW| MT-24-LS-VFR-ULC| SHG24-110-1
P2415W| AS-2475C-FW| MT-24-WS-VFR-ULC| GOT24
P241575| AS-24100C-FW| AMT-12/24-R-ULC| GOS24-15-1
P241575W| AH-24-R| AMT-24-LS-VFR-ULC| GOS24-15/75
P2475| AH-24-WP-R| MB-G6-24-R| GOS24-15/75
P2475W| NS-2415W-FR| MB-G10-24-R| GOS24-30/75
P24110| NS-241575W-FR| SM-12/24-R| GOS24-110-1
P24110W| NS-2430W-FR| DSM-12/24-R| GMH-24
S2415| NS-2475W-FR| Gentex| GMS-24-15-1
S2415W| NS-24110W-FR| AVP-4-15-1| GMS-24-15/75-W
S241575| NS4-2415W-FR| AVP-4-15/75| GMS-24-30/75-W
S241575W| NS4-241575W-FR| AVP-4-30-75| GMS-24-15/75-C
S2475| NS4-2430W-FR| AVP-4-110-1| GMS-24-110-1
S2475W| NS4-2475W-FR| GXS-4-15-1| WGMS-4/75
S24110| NS4-24110W-FR| GXS-4-15/75-W| Mircom
S24110W| RS-2415W-FR| GXS-4-30/75W| FH-240R
H12/24| RSS-241575W-FR| GXS-4-15/75-C| FH-240W
H12/24W| RSS-2415W-FR| GXS-4-110-1| FHS-240R
MDL| RSS-241575W-FR| GX90S-4-15-1| FHS-240R/110
MDLW| RSS-2430W-FR| GX90S-4-15/75-W| FHS-240W
Wheelock| RSS-2475W-FR| GX90S-4-30/75W| FHS-240W/110
AS-2415W-24-FR| RSS-24110W-FR| GX90S-4-15/75-C| FS-240R
AS-241575W-FR| RSS-2415C-FW| GX90S-4-110-1| FS-240R/110
AS-2430W-FR| RSS-2430C-FW| SHG24-15-1| FS-240W
AS-2475W-FR| RSS-2475C-FW| SHG15/75-W| FS-240W/110
AS-24110W-FR| RSS-24100C-FW| SHG24-30/75-W| SDM-240
AS-2415C-FW| MT-12/24-ULC| SHG24-15/75-C|

FA-1000 & FA-100 Series ULC Listed Compatible Devices

FA-1000 & FA-100 Series ULC Listed Compatible Hardwire Smoke Detectors
Notes: Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, the total standby current of all detectors must not exceed 3 mA.

Make & Model/Base| Maximum # of Devices| Make & Model/Base| Maximum # of Devices
---|---|---|---
Mircom| Fenwal continued
MIR-525| 30| PSD-7131/70-201000-003| –
MIR-525T| 30| PSD-7131/70-201000-005| –
MIR-1400A| 30| PSD-7130/70-201000-001| –
MIR-2400A| 25| PSD-7130/70-201000-002| –
Apollo| PSD-7130/70-201000-003| –
55000-325| 30| PSD-7130/70-201000-005| –
55000-325 / 45681-251, -255,

-256, -258

| 30| PSD-7128/70-201000-001| –
Cerebrus Pyrotronics| PSD-7126/70-201000-002| –
DI-2| –| PSD-7126/70-201000-003| –
DI-3/DB-3S| 30| PSD-7126/70-201000-005| –
Edwards| PSD-7129/70-201000-000| –
6249C| –| PSD-7125/70-201000-001| –
6250C| –| PSD-7126/70-201000-002| –
6264C| –| PSD-7125/70-201000-003| –
6266C| –| PSD-7125/70-201000-005| –
6269C| –| CPD-7021/70-201000-001| –
6270C| –| CPD-7021/70-201000-002| –
6269C-003| –| CPD-7021/70-201000-003| –
6270C-003| –| CPD-7021/70-201000-005| –
C2M-PD/CM2M-PD| –| Hochiki
EC-103-3/CSBU| –| DCD-135/NS6-220| 30
Fenwal| DCD-135/NS4-220| 30
PSD-7131/70-201000-001| –| DCD-135/HSC-220R| 30
PSD-7131/70-201000-002| –| DCD-190/NS6-220| 30
Hochiki continued| System Sensor
---|---
DCD-190/NS4-220| 30| 1400-A| 30
DCD-190/HSC-220R| 30| 2400-A| 25
SIJ-24/NS6-220| 30| 1451-A/B401B| 25
SIJ-24/NS4-220| 30| 1451-A/B406B| 25
SIJ-24/HSC-220R| 30| 2451-A/B401B| 25
SLR-24/NS6-220| 30| 2451-A/B406B| 25
SLR-24/NS4-220| 30| 1451DH/DH400A| 30
SLR-24/HSC-220R| 30| 2451-A/DH400A| 25
SLR-24H/NS6-220| 30| 1151A| 30
SLR-24H/NS4-220| 30| 2151A| 30
SLR-24H/HSC-220R| 30| C2W-BA/C2WT-BA| 30
SLR-835/NS6-220| 30| C2WTR-B| 1
SLR-835/NS4-220| 30| C2WTA-BA| 1
SLR-835/HSC-220R| 30|
SLR-835B-2| 30
Mirtone
73471| –
73494| –
73575| –
73495/73486| –
73495/73487| –
73595/73486| –
73595/73497| –
73594/73400| –
73405/73400| –
73594/73401| –
73405/73401| –
NAPCO
FW-2| 30
Simplex
2098-9110| –

FX-2200 UL Listed Compatible Devices

FX-2200 UL Listed Compatible Addressable Devices

Model Description Typical Current Draw µA
MIX-1251 Ionization type smoke detector 300
MIX-1251B Ionization type smoke detector 300
MIX-2251 Photoelectric type smoke detector 300
MIX-2251B Photoelectric type smoke detector 360
MIX-2251T Photoelectric type smoke detector w/ thermal element 300
MIX-2251TB Photoelectric type smoke detector w/ thermal element 360
MIX-2251TM Acclimate Photo-Thermal Detector 300
MIX-2251TMB Acclimate Photo-Thermal Detector 360
MIX-5251P Thermal detector 200
MIX-5251B Thermal detector 300
MIX-5251RP Thermal detector w/ rate of rise 200
MIX-5251RB Thermal detector w/ rate of rise 300
MIX-5251H High Temperature Thermal detector 300
IM-10 10 Input Monitor Module 3.50 mA
CR-6 6 Relay Control Module 1.45 mA
SC-6 6 Supervised Control Module 2.25 mA
CZ-6 6 Zone Conventional Interface Module 2.00 mA
MIX-M500DM Dual Input Monitor Module 300
MIX-M500M Monitor module, Classes A/B initiating 300
MIX-M501M Mini Monitor module, Class B initiating 300
MIX-M502M Monitor Module for 2- wire smoke detectors Classes A/B initiating

200
MIX-M500S| Control module| 300
MIX-M500R| Relay Module| 300
MIX-M500X| Fault isolator module| 450

FX-2200 UL Listed Compatible Synchronized Notification Appliances


Manufacturer

| ****

Appliance Module

| ****

Candela

| # of Appliances
---|---|---|---
Mircom| FHS-210-110| 75| 18
Secutron| MRA-24 WW| 15| 24
System Sensor| P12224MC| 15| 30
Wheelock| NS-24 MCW-FW| 15| 38
Amseco| SH24W-75110| 75| 18
Gentex| GEC3-24WW| 15| 24

FA-262/FA-265 Series Compatible Devices (UL Listed)

FA-262/FA-265 Series Compatible Two-Wire Smoke Detectors (UL Listed)
Notes:

  1. Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, total standby current of all detectors must not exceed 3 mA.
  2. The below listed smoke detectors are compatible with initiating circuits having Compatibility Identifier “A”.

Smoke Detector Make Model / Base

| Compatibility Identifier Head / Base| ****

Rated Standby Current

| ****

Smoke Detector Make Model / Base

| Compatibility Identifier Head / Base| ****

Rated Standby Current

---|---|---|---|---|---
Hochiki| 2451 / DH400| A – N/A| 0.12 mA
DCD-135/NS6-220| HD-3/HB-72| 0.035mA| 2451TH / B406B| A – A| 0.12 mA
DCD-135/NS4-220| HD-3/HB-3| 0.035mA| 2451 / B401| A – A| 0.12 mA
DCD-135/HSC-220R| HD-3/HB-3| 0.035mA| 2451TH / B401| A – A| 0.12 mA
DCD-190/NS6-220| HD-3/HB-3| 0.035mA| 4451HT / B401B| A – A| 0.12 mA
DCD-190/NS4-220| HD-3/HB-3| 0.035mA| 4451HT / B406B| A – A| 0.12 mA
DCD-190/HSC-220R| HD-3/HB-3| 0.035mA| 1100| A – N/A| 0.12 mA
SIJ-24/NS6-220| HD-3/HB-72| 0.040mA| 1151/ B110LP| A – A| 0.12 mA
SIJ-24/NS4-220| HD-3/HB-3| 0.040mA| 1151/ B116LP| A – A| 0.12 mA
SIJ-24/HSC-220R| HD-3/HB-3| 0.040mA| 1400| A – N/A| 0.10 mA
SLR-24/NS6-220| HD-3/HB-72| 0.045mA| 1451/B401| A – A| 0.12 mA
SLR-24/NS4-220| HD-3/HB-3| 0.045mA| 1451/ B401B| A – A| 0.12 mA
SLR-24/HSC-220R| HD-3/HB-3| 0.045mA| 1451/ B406B| A – A| 0.12 mA
SLR-24H/NS6-220| HD-3/HB-3| 0.045mA| 1451DH/ DH400| A – A| 0.12 mA
SLR-24H/NS4-220| HD-3/HB-3| 0.045mA| 2100| A – N/A| 0.12 mA
SLR-24H/HSC-220R| HD-3/HB-72| 0.045mA| 2100T| A – N/A| 0.12 mA
SLR-835/NS6-220| HD-3/HB-3| 0.045mA| 2151/ B110LP| A – A| 0.12 mA
SLR-835/NS4-220| HD-3/HB-3| 0.045mA| 2112/24T| A – N/A| 0.12mA
SLR-835/HSC-220R| HD-3/HB-72| 0.045mA| 4451HT / B401| A – A| 0.12 mA
SLR-835B-2| HD-6| 55µa @ 24VDC| 5451 / B401B| A – A| 0.12 mA
SLR-835/NS6-220| HD-3/HB-3| 0.045mA| 5451 / B401| A – A| 0.12 mA
System Sensor| 5451 / B406B| A – A| 0.12 mA
2400AIT| A – N/A| 0.12 mA| 2151/ B116LP| A – A| 0.12 mA
2451 / B401B| A – A| 0.12 mA| 2400| A – N/A| 0.12 mA
2451 / B406B| A – A| 0.12 mA| 2400TH| A – N/A| 0.12 mA
System Sensor (cont’d)| Detection Systems Inc.
---|---
2400AT| A – N/A| 0.12 mA| DS250| B – N/A| 0.10 mA
Sentrol – ESL| DS250TH| B – N/A| 0.10 mA
429C| S10A – N/A| 0.10 mA| DS282| B – N/A| 0.10 mA
429CT| S10A – N/A| 0.10 mA| DS282TH| B – N/A| 0.10 mA
429CST| S11A – N/A| 0.10 mA| Mircom
429CRT| S11A – N/A| 0.10 mA| MIR-525U| FDT-1| 0.10 mA
711U/701E, 701U,

702E, 702U

| S10A – S00| 0.10 mA| MIR-525TU| FDT-1| 0.10 mA
712U / 701E, 701U,

702E, 702U

| S10A – S00| 0.10 mA| NAPCO|  |
713-5U / 701E,

701U, 702E, 702U

| S10A – S00| 0.10 mA| FW-2| HD-6| 55µA @ 24VDC
721U / 702E, 702U| S10A – S00| 0.10 mA| Apollo

721UT / 702E, 702U

|

S10A – S00

|

0.10 mA

|

55000-225

| 5500-225/45681

-251, -255, -256,

-258

|

0.11mA

722U / 702E, 702U

|

S10A – S00

|

0.10 mA

|

55000-325

| 5500-225/45681

-251, -255, -256,

-258

|

0.11mA

731U / 702E, 702U,

702RE, 702RU

| S11A – S00| 0.10 mA| System Sensor i3
732U / 702E, 702U,

702RE, 702RU

| S11A – S00| 0.10 mA| 2W-B| A – A| 0.10 mA
 | 2WT-B| A – A| 0.10 mA
2WTA-B| A – A| 0.10 mA
2WTR-B| A – A| 0.10 mA
Panel CID| Max.      # Detectors| Manufacturer| Model| Model

CID

| Base| Base CID| Description
---|---|---|---|---|---|---|---
01| 25| System Sensor| 1400/

1400A

| A| N/A| N/A| Ionization type smoke, 2-wire 12/24VDC
01| 25| System Sensor| 1451| A| B401

B401B

| N/A| Plug-in – Ionization type smoke detector
01| 25| System Sensor| 2400| A| N/A| N/A| Photoelectric, 2-wire, 12/24VDC
01| 25| System Sensor| 2400TH| A| N/A| N/A| Photoelectric with Thermal, 2-wire, 12/ 24VDC
01| 25| System Sensor| 2400AT| A| N/A| N/A| Photoelectric with Thermal and Horn, 2- wire, 24VDC
01| 25| System Sensor| 2400AIT| A| N/A| N/A| Photoelectric with isolated Thermal and Horn, 2-wire, 24VDC
01| 25| System Sensor| 2451| A| B401 B401B

DH400

| N/A| Plug-in – Photoelectric type smoke detector
01| 25| System Sensor| 2451TH| A| B401 B401B| N/A| Plug-in – Photoelectric type smoke detector with Thermal
01| 25| System Sensor| 1100| A| N/A| N/A| Ionization, 2-wire, 12/ 24VDC, terminal strip
01| 25| System Sensor| 2100| A| N/A| N/A| Photoelectric, 2-wire, 12/24VDC, terminal strip
01| 25| System Sensor| 2100T| A| N/A| N/A| Photoelectric, 2-wire, 12/24VDC, thermistor, terminal strip
01| 25| System Sensor| 2112/24T| A| N/A| N/A| Photoelectric, 12/ 24VDC, terminal strip
01| 25| System Sensor| 4451HT

4451HTA

| A| B401 B401B

DH400

| N/A| Plug-in – High Temp Heat 88°C (190°F)
01| 25| System Sensor| 5451| A| B401 B401B

DH400

| N/A| Plug-in – Fixed Temp/ Rate of Rise Detector
01| 25| System Sensor| 1151

1151A

| A| B401 B401B

DH400

| N/A| Plug-in – Low Profile Ion
---|---|---|---|---|---|---|---
01| 25| System Sensor| 2151

2151A

| A| B401

B401B DH400

| N/A| Plug-in – Low Profile Photo
01| 25| System Sensor| 2100S| A| N/A| N/A| 2-wire direct wire Photoelectric
01| 25| System Sensor| 2100TS| A| N/A| N/A| 2-wire direct wire Photoelectric Thermal
01| 30| System Sensor| 2100AT| A| N/A| N/A| 2-wire direct wire Photoelectric Audible Thermal
01| 30| System Sensor| 2100TR| A| N/A| N/A| 2-wire direct wire Photoelectric Thermal Auxiliary Relay

FA-262/FA-265 Series Smoke Detector Bases (UL Listed)

Max. # Detectors| Manufacturer| Model| Base CID| Description
---|---|---|---|---
25| System Sensor| B401| N/A| 2-wire standard base, 4”, 12/24VDC
25| System Sensor| B401B| N/A| 2-wire standard base, 6”, 12/24VDC
25| System Sensor| B406B| N/A| 2-wire base, 24VDC, form contact
25| System Sensor| B401BH| N/A| 24VDC sounder base for use with B401
25| System Sensor| B110LP| N/A| 2-wire, flangeless, 12/24VDC
25| System Sensor| B116LP| N/A| 2-wire base, 24VDC, form contact
25| System Sensor| DH400| N/A| Duct Detector Mount
25| System Sensor| RMK400| N/A| Recessed mount kit for Series 400

FA-262/FA-265 Series Compatible Four-Wire Smoke Detectors (UL Listed)

Manufacturer Models



System Sensor

| 1124B| 2124B| 2124TB| 2124S| 2124TS| 2124R
2124TR| 2124AT| 2124ATR| 2124AITR| 1424| 2424
2424TH| 2424AT| 1151| 2151| –| –
2424AIT| 6424| 1451| 2451| 22451TH*| –
Detector with B112LP Base    **Detector with B402B Base
Detection Systems| DS284| DS284TH| DS284THS| DS284THR| DS284THSR| DS284THCS
DS284THC| DS284THE| DS284ES| DS284IS| –| –


Gentex

| 8240| 8240T| 8240P| 8243P| 8240PH| 8243PH
8240PT| 8243PT| –| –| –| –
Mircom| MIR-545U| MIR-545TU| –| –| –| –



Sentrol-ESL

| 541C| 541CXT| 709-MV-21| 709-24V-21| 541C| –
741U WITH

702U or 702E Base

| 449AT, 449C, 449CT, 449CRT, 449CST,

449CSTE, 449CSRT, 449CSRH, 449CSST,

449CSSTE, 449CTE, 449CLTCSLT

| 741U WITH

702U or 702E Base

| ****


System Sensor

| 1424| 6424| 6424A| A77-716B| 1424|
DH400AC DCI| DH400ACD CP| DH400ACDC IHT|  | DH400ACDC I|
Hochiki| SIJ-24| SLR-24| SLR-24H| SLR-835B| –| –


DSC

| MN240| MN240T| MN240R| MN240RT| MN240S| MN240ST
MN240SR| MN240SRT| –| –| –| –
ESL| 741U| 741UT| –| –| –| –

FA-262/FA-265 Series Compatible Horns/Strobes (UL Listed)

System Sensor Type Cd Voltage (FWR)
P2415(W)(A) H/S 15 20-30
P241575(W)(A) H/S 15/75 20-30
P2475(W)(A) H/S 75 20-30
P24110(W)(A) H/S 110 20-30
S2415(W)(A) S 15 20-30
S241575(W)(A) S 15/75 20-30
S2475(W)(A) S 75 20-30
S24110(W)(A) S 110 20-30
H24(W)(A) H 20-30
MDL(W)(A) Synch Module 20-30
--- --- --- ---

No suffix = Red, suffix W = White, suffix A = Canadian version
Gentex| Type| Cd| Voltage (FWR)
---|---|---|---
GEH24| H| –| 20-31
GES24-15| S| 15| 20-31
GES24-15/75| S| 15/75| 20-31
GES24-30| S| 30| 20-31
GES24-60| S| 60| 20-31
GES24-75| S| 75| 20-31
GES24-110| S| 110| 20-31
GEC24-15| H/S| 15| 20-31
GEC24-15/75| H/S| 15/75| 20-31
GEC24-30| H/S| 30| 20-31
GEC24-60| H/S| 60| 20-31
GEC24-75| H/S| 75| 20-31
GEC24-110| H/S| 110| 20-31
Available in Red and White
Wheelock| Type| Cd| Voltage (FWR)
---|---|---|---
NS-2415W-FR(W)| H/S| 15| 20-31
NS-241575W-FR(W)| H/S| 15/75| 20-31
NS-2430W-FR(W)| H/S| 30| 20-31
NS-2475W-FR(W)| H/S| 75| 20-31
NS-24110W-FR(W)| H/S| 110| 20-31
NS4-2415W-FR(W)| H/S| 15| 20-31
NS4-241575W-FR(W)| H/S| 15/75| 20-31
NS4-2430W-FR(W)| H/S| 30| 20-31
NS4-2475W-FR(W)| H/S| 75| 20-31
NS4-24110W-FR(W)| H/S| 110| 20-31
NS = 2-wire, NS4 = 4-wire
AS-2415W-FR(W)| S| 15| 20-31
AS-241575W-FR(W)| S| 15/75| 20-31
AS-2430W-FR(W)| S| 30| 20-31
AS-2475W-FR(W)| S| 75| 20-31
AS-24110W-FR(W)| S| 110| 20-31
AS4-2415C-FR(W)| S| 15| 20-31
AS4-2430C-FR(W)| S| 30| 20-31
AS4-2475C-FR(W)| S| 75| 20-31
AS4-24110C-FR(W)| S| 110| 20-31
AH-24-R| H| –| 20-31
AH-24-WP-R| H| –| 20-31
MT-24-R| H|  | 20-31
MT4-24-R| H|  | 20-31
MT-24-SL-VFR| H/S| 15| 20-31
MT-24-SLM-VFR| H/S| 15/75| 20-31
MT-24-MS-VFR| H/S| 30| 20-31
MT-24-IS-VFR| H/S| 75| 20-31
MT-24-WM-VFR| H/S| 117| 20-31

FA-262/FA-265 Series Compatible Signalling Devices (UL Listed)

System Sensor – SpectrAlert

P2415| P2415W| P241575| P241575W| P2475
P2475W| P24110| P24110W| S2415| S2415W
S241575| S241575W| S2475| S2475W| S24110
S24110W| H12/24| H12/24W| MDL| MDLW
Wheelock
AS-2415W-24-FR| AS-2415W-FR| AS-241575W-FR| AS-2430W-FR| AS-2475W-FR
AS-24110W-FR| AS-2415C-FW| AS-2430C-FW| AS-2475C-FW| AS-24100C-FW
AS4-2415C-FR| AS4-2430C-FR| AS4-2475C-FR| AS4-24110C-FR| AH-24-R
AH-24-WP-R| AMT-12/24-R- ULC| AMT-24-LS-VFR- ULC| DSM-12/24-R| MB-G6-24-R
MB-G10-24-R| MT-12/24-ULC| MT-24-LS-VFR- ULC| MT-24-WS-VFR- ULC| MT-24-R
MT4-24-R| MT-24-SL-VFR| MT-24-SLM-VFR| MT-24-MS-VFR| MT-24-IS-VFR
MT-24-WM-VFR| NS-2415W-FR| NS-241575W-FR| NS-2430W-FR| NS-2475W-FR
NS-24110W-FR| NS4-2415W-FR| NS4-241575W-FR| NS4-2430W-FR| NS4-2475W-FR
NS4-24110W-FR| RS-2415W-FR| RSS-241575W-FR| RSS-2415W-FR| RSS-241575W-FR
RSS-2430W-FR| RSS-2475W-FR| RSS-24110W-FR| RSS-2415C-FW| RSS-2430C-FW
RSS-2475C-FW| RSS-24100C-FW| SM-12/24-R|  |
Gentex
AVP-4-15-1| AVP-4-15/75| AVP-4-30/75| AVP-4-110-1| GXS-4-15-1
GXS-4-15/75-W| GXS-4-30/75-W| GXS-4-15/75-C| GXS-4-110-1| GX90S-4-15-1
GX90S-4-15/75-W| GX90S-4-30/75W| GX90S-4-15/75-C| GX90S-4-110-1| SHG24-15-1
SHG15/75-W| SHG24-30/75-W| SHG24-15/75-C| SHG24-110-1| GOT24
GOS24-15-1| GOS24-15/75| GOS24-15/75| GOS24-30/75| GOS24-110-1
GMH-24| GMS-24-15-1| GMS-24-15/75-W| GMS-24-30/75-W| GMS-24-15/75-C
GMS-24-110-1| WGMS-4/75| GEH24| GES24-15| GES24-15/75
GES24-30| GES24-60| GES24-75| GES24-110| GEC24-15
GEC24-15/75| GEC24-30| GEC24-60| GEC24-75| GEC24-110

FA-262/FA-265 Series Hardwire Smoke Detectors (ULC Listed)

Note: Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, the total standby current of all detectors must not exceed 3 mA.

Make Model / Base| Make Model / Base| Make Model / Base| Make Model / Base
---|---|---|---
Apollo| Edwards| Mirtone (cont’d)| Fenwal
55000-225| 6249C| 73595/73497| PSD-7131/70-201000-001
55000-325| 6250C| 73594/73400| PSD-7131/70-201000-002
Hochiki| 6264C| 73405/73400| PSD-7131/70-201000-003
DCD-135/NS6-220| 6266C| 73594/73401| PSD-7131/70-201000-005
DCD-135/NS4-220| 6269C| 73405/73401| PSD-7130/70-201000-001
DCD-135/HSC-220R| 6270C| System Sensor| PSD-7130/70-201000-002
DCD-190/NS6-220| 6269C-003| 1400-A| PSD-7130/70-201000-003
DCD-190/NS4-220| 6270C-003| 2400-A| PSD-7130/70-201000-005
DCD-190/HSC-220R| Cerebrus Pyrotronics| 1451-A/B401B| PSD-7128/70-201000-001
SIJ-24/NS6-220| DI-2| 1451-A/B406B| PSD-7126/70-201000-002
SIJ-24/NS4-220| DI-3/DB-3S| 2451-A/B401B| PSD-7126/70-201000-003
SIJ-24/HSC-220R| Mircom| 2451-A/B406B| PSD-7126/70-201000-005
SLR-24/NS6-220| MIR-525| 1451DH/DH400A| PSD-7129/70-201000-000
SLR-24/NS4-220| MIR-525T| 2451-A/DH400A| PSD-7125/70-201000-001
SLR-24/HSC-220R| MIR-1400A| 1151A| PSD-7126/70-201000-002
SLR-24H/NS6-220| MIR-2400A| 2151A| PSD-7125/70-201000-003
SLR-24H/NS4-220| Mirtone| C2W-BA| PSD-7125/70-201000-005
SLR-24H/HSC-220R| 73471| C2WT-BA| CPD-7021/70-201000-001
SLR-835/NS6-220| 73494| NAPCO| CPD-7021/70-201000-002
SLR-835/NS4-220| 73575| FW-2| CPD-7021/70-201000-003
SLR-835/HSC-220R| 73495/73486| Simplex| CPD-7021/70-201000-005
SLR-835B-2| 73495/73487| 2098-9110|
 | 73595/73486|  |

FA-200 Series UL Listed Compatible Devices

FA-200 Series UL Listed Two-Wire Smoke Detectors

Smoke Detector Make Model / Base| Compatibility Identifier Head / Base| Rated Standby Current
---|---|---
Mircom
MIR-525U| FDT-1| 0.10 mA
MIR-525TU| FDT-1| 0.10 mA
Detection Systems Inc.
DS250| B – N/A| 0.10 mA
DS250TH| B – N/A| 0.10 mA
DS282| B – N/A| 0.10 mA
DS282TH| B – N/A| 0.10 mA
Hochiki
DCD-135/NS6-220| HD-3/HB-72| 0.035mA
DCD-135/NS4-220| HD-3/HB-3| 0.035mA
DCD-135/HSC-220R| HD-3/HB-3| 0.035mA
DCD-190/NS6-220| HD-3/HB-3| 0.035mA
DCD-190/NS4-220| HD-3/HB-3| 0.035mA
DCD-190/HSC-220R| HD-3/HB-3| 0.035mA
SIJ-24/NS6-220| HD-3/HB-72| 0.040mA
SIJ-24/NS4-220| HD-3/HB-3| 0.040mA
SIJ-24/HSC-220R| HD-3/HB-3| 0.040mA
SLR-24/NS6-220| HD-3/HB-72| 0.045mA
SLR-24/NS4-220| HD-3/HB-3| 0.045mA
SLR-24/HSC-220R| HD-3/HB-3| 0.045mA
SLR-24H/NS6-220| HD-3/HB-3| 0.045mA
SLR-24H/NS4-220| HD-3/HB-3| 0.045mA
SLR-24H/HSC-220R| HD-3/HB-72| 0.045mA
SLR-835/NS6-220| HD-3/HB-3| 0.045mA
SLR-835/NS4-220| HD-3/HB-3| 0.045mA
SLR-835/HSC-220R| HD-3/HB-72| 0.045mA
SLR-835B-2| HD-6| 55ua @ 24VDC
NAPCO

FW-2| HD-6| 55uA @ 24VDC
Sentrol – ESL
429C| S10A – N/A| 0.10 mA
429CT| S10A – N/A| 0.10 mA
429CST| S11A – N/A| 0.10 mA
429CRT| S11A – N/A| 0.10 mA
711U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA
712U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA
713-5U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA
713-6U / 701E, 701U, 702E, 702U| S10A – S00| 0.10 mA
721U / 702E, 702U| S10A – S00| 0.10 mA
721UT / 702E, 702U| S10A – S00| 0.10 mA
722U / 702E, 702U| S10A – S00| 0.10 mA
731U / 702E, 702U, 702RE, 702RU| S11A – S00| 0.10 mA
732U / 702E, 702U, 702RE, 702RU| S11A – S00| 0.10 mA
System Sensor
1100| A – N/A| 0.12 mA
1151 / B110LP| A – A| 0.12 mA
1151 / B116LP| A – A| 0.12 mA
1400| A – N/A| 0.10 mA
1451 / B401| A – A| 0.12 mA
1451 / B401B| A – A| 0.12 mA
1451 / B406B| A – A| 0.12 mA
1451DH / DH400| A – A| 0.12 mA
2100| A – N/A| 0.12 mA
2100T| A – N/A| 0.12 mA
2151/ B110LP| A – A| 0.12 mA
2151/ B116LP| A – A| 0.12 mA
2400| A – N/A| 0.12 mA
2400TH| A – N/A| 0.12 mA
2400AT| A – N/A| 0.12 mA
System Sensor continued

2400AIT| A – N/A| 0.12 mA
2451 / B401B| A – A| 0.12 mA
2451 / B406B| A – A| 0.12 mA
2451 / DH400| A – N/A| 0.12 mA
2451TH / B406B| A – A| 0.12 mA
2451 / B401| A – A| 0.12 mA
2451TH / B401| A – A| 0.12 mA
4451HT / B401B| A – A| 0.12 mA
4451HT / B406B| A – A| 0.12 mA
4451HT / B401| A – A| 0.12 mA
5451 / B401B| A – A| 0.12 mA
5451 / B401| A – A| 0.12 mA
5451 / B406B| A – A| 0.12 mA

FA-200 Series UL Listed Four-Wire Smoke Detectors

Mircom Sentrol-ESL System Sensor
MIR-545U 541C 1424
MIR-545TU 541CXT 6424
  709-MV-21 6424A
709-24V-21 A77-716B

741U WITH 702U or 702E

Base

| DH400ACDCI
449AT, 449C, 449CT,

449CRT, 449CST, 449CSTE,

449CSRT, 449CSRH,

449CSST, 449CSSTE,

449CTE, 449CLTCSLT

| DH400ACDCP
 | DH400ACDCIHT

FA-200 Series UL Listed Signaling Devices

Gentex System Sensor – SpecrAlert Wheelock continued
AVP-4-15-1 P2415 NS-2415W-FR
AVP-4-15/75 P2415W NS-241575W-FR
AVP-4-30/75 P241575 NS-2430W-FR
AVP-4-110-1 P241575W NS-2475W-FR
GXS-4-15-1 P2475 NS-24110W-FR
GXS-4-15/75-W P2475W NS4-2415W-FR
GXS-4-30/75-W P24110 NS4-241575W-FR
GXS-4-15/75-C P24110W NS4-2430W-FR
GXS-4-110-1 S2415 NS4-2475W-FR
GX90S-4-15-1 S2415W NS4-24110W-FR
GX90S-4-15/75-W S241575 RS-2415W-FR
GX90S-4-30/75W S241575W RSS-241575W-FR
GX90S-4-15/75-C S2475 RSS-2415W-FR
GX90S-4-110-1 S2475W RSS-241575W-FR
SHG24-15-1 S24110 RSS-2430W-FR
SHG15/75-W S24110W RSS-2475W-FR
SHG24-30/75-W H12/24 RSS-24110W-FR
SHG24-15/75-C H12/24W RSS-2415C-FW
SHG24-110-1 MDL RSS-2430C-FW
GOT24 MDLW RSS-2475C-FW
GOS24-15-1 Wheelock RSS-24100C-FW
GOS24-15/75 AS-2415W-24-FR MT-12/24-ULC
GOS24-15/75 AS-241575W-FR MT-24-LS-VFR-ULC
GOS24-30/75 AS-2430W-FR MT-24-WS-VFR-ULC
GOS24-110-1 AS-2475W-FR AMT-12/24-R-ULC
GMH-24 AS-24110W-FR AMT-24-LS-VFR-ULC
GMS-24-15-1 AS-2415C-FW MB-G6-24-R
GMS-24-15/75-W AS-2430C-FW MB-G10-24-R
GMS-24-30/75-W AS-2475C-FW SM-12/24-R
GMS-24-15/75-C AS-24100C-FW DSM-12/24-R
GMS-24-110-1 AH-24-R
WGMS-4/75 AH-24-WP-R

FA-200 Series ULC Listed Compatible Devices

FA-200 Series ULC Two-wire Smoke Detector Control Panel Compatibility
Notes: Whether mixing different models of compatible smoke detectors or using the same model on the same circuit, the total standby current of all detectors must not exceed 3 mA.

Make Model / Base Make Model / Base Make Model / Base
Hochiki 2451-A/DH400A Fenwal
DCD-135/NS6-220 Edwards PSD-7131/70-201000-001
DCD-135/NS4-220 6249C PSD-7131/70-201000-002
DCD-135/HSC-220R 6250C PSD-7131/70-201000-003
DCD-190/NS6-220 6264C PSD-7131/70-201000-005
DCD-190/NS4-220 6266C PSD-7130/70-201000-001
DCD-190/HSC-220R 6269C PSD-7130/70-201000-002
SIJ-24/NS6-220 6270C PSD-7130/70-201000-003
SIJ-24/NS4-220 6269C-003 PSD-7130/70-201000-005
SIJ-24/HSC-220R 6270C-003 PSD-7128/70-201000-001
SLR-24/NS6-220 Cerebrus Pyrotronics PSD-7126/70-201000-002
SLR-24/NS4-220 DI-2 PSD-7126/70-201000-003
SLR-24/HSC-220R DI-3/DB-3S PSD-7126/70-201000-005
SLR-24H/NS6-220 Mircom PSD-7129/70-201000-000
SLR-24H/NS4-220 MIR-525 PSD-7125/70-201000-001
SLR-24H/HSC-220R MIR-525T PSD-7126/70-201000-002
SLR-835/NS6-220 Mirtone PSD-7125/70-201000-003
SLR-835/NS4-220 73471 PSD-7125/70-201000-005
SLR-835/HSC-220R 73494 CPD-7021/70-201000-001
SLR-835B-2 73575 CPD-7021/70-201000-002
System Sensor 73495/73486 CPD-7021/70-201000-003
1400-A 73495/73487 CPD-7021/70-201000-005
2400-A 73595/73486 NAPCO
1451-A/B401B 73595/73497 FW-2
1451-A/B406B 73594/73400 Simplex
2451-A/B401B 73405/73400 2098-9110
2451-A/B406B 73594/73401
1451DH/DH400A 73405/73401