Amana Distinctions DCP073A25AA Packaged Terminal Air Conditioner or Heat Pump Instruction Manual
- June 9, 2024
- Amana
Table of Contents
- Amana Distinctions DCP073A25AA Packaged Terminal Air Conditioner or Heat
- SAFETY PRECAUTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- OPERATION OF CURRENT DEVICE (OPTIONAL)
- AIR CONDITIONER FEATURES
- CONTROL PANEL OPERATION
- DIP SWITCHES CONFIGURATIONS (OPTIONAL)
- TABLE 1 DIP SWITCH CONFIGURATIONS
- DIP SWITCHES CONFIGURATIONS BY PANEL CONTROL (OPTIONAL)
- TABLE 2 DIP SWITCHES CONFIGURATIONS BY PANEL CONTROL
- WALL THERMOSTAT TERMINAL (OPTIONAL)
- INSTALLATION
- CARE AND CLEANING
- TROUBLESHOOTING
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Amana Distinctions DCP073A25AA Packaged Terminal Air Conditioner or Heat
Pump
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better
than the customer. This includes all safe-ty precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this
Instruction Manual. Pay special attention to all safety warnings.
Often during installation or repair it is possible to place yourself in a
position which is more hazardous than when the unit is in operation.
This manual must be left with the owner of the equipment.
WARNING
Only personnel that have been trained to install, adjust, service or repair(hereinafter, “service”) the equipment specified in this manual should service the equipment. The manufacturer will not be responsible for any injury or property damage arising from improper service or service procedures. If you service this unit, you assume responsibility for any injury or property damage which may result. In addition, in jurisdictions that require one or more licenses to service the equipment specified in this manual, only licensed personnel should service the equipment. Improper installation, adjustment, servicing or repair of the equipment specified in this manual, or attempting to install, adjust, service or repair the equipment specified in this manual without proper training may result in product damage, property damage, personal injury or death.
READ THIS MANUAL
Inside you will find many helpful hints on how to use and maintain your air
conditioner properly. Just a little preven-tive care on your part can save you
a great deal of time and money over the life of your air conditioner. You’ll
find many answers to common problems in the chart of trou-bleshooting tips. If
you review our chart of Troubleshooting Tips first, you may not need to call
for service at all.
Important Note to the Owner
This manual is to be used by qualified, professionally trained HVAC
technicians only. Goodman does not assume any responsibility for property
damage or personal injury for improper service procedures or services
performed by an unqualified person.
IMPORTANT NOTES:
Your warranty certificate is also supplied with the unit. Read the warranty
carefully and note what is covered. Keep the warranty certificate in a safe
place, so you can find it, if necessary.
Before using this manual, check the serial plate for proper model
identification.
THE INSTALLATION AND SERVICING OF THIS EQUIP-MENT MUST BE PERFORMED BY
QUALIFIED, EXPE-RIENCED TECHNICIANS ONLY.
Due to policy of continual product improvement, the right is reserved to
change specifications and design without notice.
Remember, it is your responsibility to install the product safely and to know
it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense…a matter of thinking before acting. Most
dealers have a list of specific good safety practices…follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
CAUTION
- This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the haz-ards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by chil-dren without supervision (This is applicable for European Countries).
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capa-bilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety (This is applicable for other countries except the European Countries).
- Children should be supervised to ensure that they do not play with the appliance.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capa-bilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety (This is applicable for other countries except the European Countries).
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified per-sons in order to avoid a hazard.
- The appliance shall be installed in accordance with national wiring regulations.
- Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
- The appliance with an electric heater shall have at least 1 meter of space to the combustible materials.
- Contact the authorized service technician for repair or maintenance of this unit.
- Contact the authorized installer for installation of this unit.
- If the air conditioner is knocked over during use, turn off the unit and unplug it from the main power supply immediate-ly. Visually inspect the unit to ensure there is no damage. If you suspect the unit has been damaged, contact a technician or customer service for assistance.
- In a thunderstorm, the power must be cut off to avoid dam-age to the machine from lightning.
- To reduce the risk of fire or electric shock, do not use this fan with any solid-state speed control device.
- Do not run cord under carpeting. Do not cover cord with throw rugs, runners, or similar coverings. Do not route cord under furniture or appliances. Arrange cord away from traffic area and where it will not be tripped over.
SAFETY PRECAUTIONS
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incor-rect operation due to ignoring instructions may cause harm or damage. The seriousness of is classified by the following indications:
WARNING
- This symbol indicates the possibility of death or serious injury.
CAUTION
- This symbol indicates the possibility of injury or damage to property.
WARNING
- Plug in power properly. Otherwise, it may cause electric shock or fire die to excess heat generation.
- Do not operate or stop the unit by inserting or pulling out the power plug. It may cause electric shock or fire do to heat generation.
- Do not damage or use an unspecified power cord. It may cause electric shock or fire. If the power cord is damaged, it must be replaced by the manufacturer or an authorized service center or a similarly qualified person in order to avoid a hazard.
- Do not modify power cord length or share the outlet with other appliances. It may cause electric shock or fire due to heat generation.
- Do not operate with wet hands or in damp environment. It may cause electric shock.
- Do not direct airflow at room occupants only. This could damage your health.
- Always ensure effective earthing. Incorrect earthing may cause electric shock.
- Do not allow water to run in electric parts. It may cause failure of machine or electric shock.
- Always install circuit breaker and a dedicated power circuit. Incorrect installation may cause fire and electric shock.
- Do not use the socket if it is loose or damaged. It may cause fire and electric shock.
- Do not open the unit during operation. It mat cause electric shock.
- Keep firearms away. It may cause fire.
- Do not use the power cord close to heating appliances. It may cause fire and electric shock.
- Do not use the power cord near flammable gas or combusti-bles, such as gasoline, benzene, thinner, etc. It may cause an explosion or fire.
- Ventilate room before operating air conditioner if there is a gas leakage from another appliance. It may cause explosion, fire, and burns.
- Do not disassemble or modify unit. It may cause failure and electric shock.
CAUTION
- When the air filter is to be removed, do not touch the metal parts of the unit. It may cause an injury.
- Do not clean the air conditioner with water. Water may enter the unit and degrade the insulation. It may cause an electric shock.
- Ventilate the room well when used together with a stove, etc. An oxygen shortage may occur.
- When the unit is to be cleaned, switch off and turn off the circuit breaker. Do not clean unit when power is on as it may cause fire and electric shock. It may also cause an injury.
- Do not put a pet or house plant where it will be exposed to direct air flow. This could injure the pet or plant.
- Do not use for special purposes. Do not use this air condi-tioner to preserve precision devices, food, pets, plants, and art objects. It may cause deterioration of quality, etc.
- Hold the plug by the head of the power plug when taking it out. It may cause electric shock and damage.
- Turn off the main power switch when not using the unit for a long time. It may cause failure of product or fire.
- Always insert the filters securely. Clean filter once every two weeks. Operation without filters may cause failure.
- Do not use strong detergent such as wax or thinner but use a soft cloth. Appearance may be deteriorated due to change of product color or scratching of its surface.
- Do not place a heavy object on the power cord and ensure that the cord is not compressed. There is a danger of fire or electric shock.
- Do not drink water drained from the air conditioner. It con-tains contaminants and could make you sick.
- Use caution when unpacking and installing. Sharp edges could cause injury.
- If water enters the unit, turn the unit off at the power outlet and switch off the circuit breaker. Isolate supply by taking the power-plug out and contact a qualified service technician.
- Clean the evaporator once every three months by profes-sional people. Otherwise it may cause failure of electric heating feature.
IMPORTANT SAFETY INSTRUCTIONS
NOTE: The power supply cord with this air conditioner contains a current detection device designed to reduce the risk of fire. Please refer to the section “Operation of Current Device” for details. In the event that the power supply cord is damaged, it cannot be repaired. It must be replaced with a cord from the Product Manufacturer.
For Your Safety
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance. Avoid fire hazard or electric shock.
Do not use an extension cord or an adapter plug. Do not remove any prong from
the power cord.
Electrical Information
Be sure the electrical service is adequate for the model you have chosen. This
information can be found on the serial plate, which is located on the side of
the cabinet and behind the grille. Be sure the air conditioner is properly
grounded. To minimize shock and fire hazards, proper grounding is important.
The power cord is equipped with a three-prong grounding plug for protection
against shock hazards. Your air conditioner must be used in a properly
grounded wall receptacle. If the wall receptacle you intend to use is not
adequately grounded or protected by a time delay fuse or circuit breaker, have
a qualified electrician install the proper receptacle. Ensure the receptacle
is ac-cessible after the unit installation. Do not run air conditioner without
side protective cover in place. This could result in mechanical damage within
the air conditioner. The appli-ance shall be installed in accordance with
national wiring regulations. Do not use an extension cord or an adapter plug.
OPERATION OF CURRENT DEVICE (OPTIONAL)
The power supply cord contains a current device that sens-es damage to the power cord. To test your supply cord, do the following:
- Plug in the Air Conditioner.
- The power supply cord will have TWO buttons on the plug head.
- Press the TEST button, you will notice a click as the RESET button pops out. Press the RESET button, again you will notice a click as the button engages.
- The power supply cord is now supplying electricity to the unit. (On some products this it also indicated by a light on the plug head.)
NOTE: Do not use this device to turn the unit on or off. Always make sure
the RESET button is pushed in for correct operation.
NOTE: The power supply must be replaced if it fails reset when either the
TEST button is pushed, or it cannot be reset. A new one can be obtained from
the product manufacturer. If power supply cord is damaged, it cannot be
repaired. It MUST be replaced by one obtained from the product manufacturer.
NOTE: When 265V units are to be installed,the power supply must be
permanent wiring. Perma-nent wiring may be done through the accessory subbase.
An exposed cord connection on 265V units are not permitted.
AIR CONDITIONER FEATURES
This unit has many features. The servicer must be familiar with these features in order to properly service the unit.
Compressor Restart Delay
This feature extends the overall life of compressor by preventing the short-
cycling of the air conditioner. When the compressor restarts, the unit is
designed to give a minimum of three minutes to have a time of equalizing the
refrigerant pressures for optimizing cycling.
Memory
The unit has memory. If power is lost, all of the control settings (mode, fan
speed, on / off and configuration) are remembered. When power is restored, the
unit will start back up in the mode (and configuration) it was in when power
was lost.
Automatic Evaporator Freeze Protection
The compressor is turned off automatically to keep the evaporator from
freezing and the indoor fan is turned on when the evaporator temperature is
too low. If the evapora-tor temperature is not too low, this function is
turned off.
Automatic Quick Warm-up (For Heat Pump Models Only)
If the room temperature falls 4.5°C / 8°F below the set point temperature, the
reverse cycle heat is shut off, and the electric strip heat is turned on for
one cycle until heating is satisfied.
LED Indicators and Buttons
The touch pad has buttons for MODE, FAN, POWER, SET POINT UP and SET POINT
DOWN. It also has LEDs that correspond to the mode, fan speed, power and set
point operation to indicate the unit’s status. LEDs for HIGH, MED, and LOW
indicate the fan speed that is selected. LEDs for FAN, COOL, and HEAT indicate
what operating mode is active. LED for POWER is the unit ON / OFF sta-tus LED.
If the unit is in ON mode, the LED will be green. If the unit is OFF, the LED
will be off.
NOTE: HEAT mode is for Cooling & Heating models only.
High Temperature Protection in Heating Operation
The compressor and / or electric heater will be switched off to prevent
damage in high indoor blow air temperature or error indoor temperature sensor.
Unit Configuration °F or °C
The unit can display in either °F or °C.
NOTE: The shape may be different according to its model.
CONTROL PANEL OPERATION
The control panel keypad will look like the following Figure 1. Power
Press the POWER button to turn the unit on or off.
Mode
Push this button to cycle through the modes from COOL-HEAT-FAN-COOL. The
indicator light beside the “MODE” option will illuminate, identifying the mode
selected.
COOL: Cooling begins automatically when the room tem-perature is above
the set point and stops when the room temperature is 2°C(4°F) below the set
point. But the com-pressor will run 5 minutes at least in COOL mode before
stopping.
HEAT: The maximum temperature can be set up to 29°C / 84°F. For heat pump
models, the unit can alternate to run between in reverse cycle heat mode and
electric heater mode according to the difference between the setting tem-
perature and the room temperature. The fan motor cycles with the compressor
stop.
NOTE: The reverse cycle and electric heater can-not be run at the same
time. In following cases, it is normal that the reverse cycle does not
operate.
- When the outdoor temperature is lower than 4°C / 40°F or the room temperature falls to 4.5°C / 8°F below the set point temperature.
- There is a 3-minute minimum compressor run time at any setting to prevent short cycling. The indoor fan motors starts before the compressor and stops after the compressor cycles off.
- Push the S1 on the DIP SWITCHES to UP (ON) position.
- When frost builds up to the evaporator coils, the unit will defrost automatically and the compressor will cycle off.
FAN: Fan operation only without heating and cooling.
NOTE: If the unit has DIP SWITCHES feature, the temperature range can be
set. See DIP SWITCHES CONFIGURATIONS on page 8 for details.
Up / Down Buttons (+ / –)
Push the UP (or DOWN) button to increase (or decrease) the set temperature of
the unit in cooling or heating mode. The temperature can be set by increments
of 1°C (1°F). The setting temperature appears in the display.
NOTE: Press and hold “+” and “–” buttons togeth-er for 3 seconds will
alternate the temperature display between “°C” & “°F” scale.
Fan (Fan Speed)
Every time you push this button, the fan speed cycles through the settings as
follows: HIGH-MED-LOW- HIGH.
Constant Fan
In cooling mode, press the button to turn on or off the constant fan function.
When the function is turned on, the constant fan light will illuminate,
identifying the fan contin-uous run for cooling. When the function is turned
off, the constant fan light will go out, identifying the fan cycle run with
compressor stop.
NOTE: Every time the unit is turned on, the func-tion will work as the
DIP SWITCHES CONFIGURA-TIONS.
Displays:
Shows the set temperature in °C or °F. While on Fan only mode, it shows the
room temperature.
Control Code (on some models):
- LC – Pads on the control panel is not available. The unit can be set by using wire controller only.
- FC – Pads on the control panel and wire controller are not available. The unit can be set by using FRONT DESK CONTROL only.
Error codes:
- AS – Room temperature sensor error;
- ES – Evaporator temperature sensor error;
- CS – Condenser temperature sensor error;
- OS – Outside temperature sensor error;
- HS – Exhaust temperature sensor error;
- LE – Wire controller error;
NOTE: When error occurs,unplug the unit and plug it back in. If error repeats, call for service.
Other Codes:
- LO – Room temperature is lower than 0°C / 32°F;
- HI – Room temperature is higher than 37°C / 99°F;
- FP – Low temp. Protection.
NOTE: All the illustrations in this manual are for explanation purpose
only. Your air conditioner may be slightly different. The actual shape shall
prevail.
NOTE: The air conditioner is designed to be operated under condition as
follows:
Cooling Operation| Outdoor Temp:| 18 – 43°C / 64 – 109°F (18 – 52°C / 64 –
125°F for special tropical models)
---|---|---
Indoor Temp:| 17 – 32°C / 62 – 90°F
Heating Operation| Outdoor Temp:| -5 – 24°C / 23 – 76°F
Indoor Temp:| 0 – 27°C / 32 – 80°F
NOTE: Performance may be reduced outside of these operating temperatures.
Accessory
NOTE: When the unit displays LC, pads on the con-trol panel is not
available. The unit can be set by using wire controller only. You can install
the Accessory on the control panel.
NOTE: For some models, there is corresponding operation happened after 3
seconds when pressing any button.
DIP SWITCHES CONFIGURATIONS (OPTIONAL)
Removing the Front Panel
- Dip switches controls are located behind front panel, through an opening below the control panel. To access, remove front panel. See Figure 2.
- Dip switches are accessible without opening the control box. See Figure 3.
- Unit must be powered OFF to effectively change their status.
DIP Switches Configurations
- See Table 1 and Figure 4 for Dip Switches configura-tions and functions of each dip switch position.
- Pull out at the bottom to release it from the tabsD.
- Then lift up 2).
No. | UP (ON) | Down (OFF) | Remarks |
---|---|---|---|
S1 | Electric Heat Only | Electric Heat and Pump Heat | For Heat Pump unit only |
S2 | Temperature Display in °F | Temperature Display in °C | |
S3 | Wall Thermostat Enable | Control Panel Enable |
S4*S5
| UPUP: 61°F – 86°F (16°C – 30°C); UPDOWN: 65°F – 78°F (17°C – 26°C); DOWN*UP: 63°F – 80°F (17°C – 27°C);
DOWN*DOWN: 68°F – 75°F (20°C – 24°C);
| Two Configurations (S4*S5) combine to select set point range.
S6| Fan Continuous Run for Heating| Fan Cycle for Heating|
S7| Fan Continuous Run for Cooling| Fan Cycle for Cooling|
S8| Low temp. Protection enable| Low temp. Protection disable| Optional
S9 (S3 UP)| Use some types of wall Thermostat|
Use PTAC other wall Thermostat
| You can consult with the
sales agency or manufacturer for details.
S9 (S3 DOWN)
|
Use Control Panel Only
|
Use Control Panel or some types of wall Thermostat
| Use Control Panel or some types of wall Thermostat, the other one
must be turned off.
Sw11| Load delay for 3 sec.| Normal| Optional
TABLE 1 DIP SWITCH CONFIGURATIONS
NOTE: On heating mode, the setting temperature can not be higher than 29°C / 84°F.
Wall Thermostat Enable
A wired wall thermostat can be connected to the unit. If it is, this dip
switch must be moved to the Wall Thermostat En-able Position before the wall
thermostat will begin control.
Low Temperature Protection (Optional)
If unit senses a room temperature below 32°F (0°C), the fan motor and electric
strip heat will turn on and warm the room to 40°F (4.4°C). The fan stops a
short time after the temperature is satisfied.
Electric Heat Only (For Heat Pump Unit Only)
This setting is typically used for Emergency Heating.
Heat and Cool Fan CON / CYC DIP-Switches
Allows the fan to operate in continuous or cycle modes while the unit is in
heating and cooling mode.
CON (Continuous)
Allows the fan to operate in time after the temperature setting is satisfied.
This switch helps to maintain the room temperature closer to the thermostat
setting.
CYC (Cycle)
This setting allows the fan to cycle on and off with the com-pressor or
electric heater. The fan stops a short time after the temperature setting is
satisfied.
Set Point Temperature Limits
Provides a restricted range of temperature control.
DIP SWITCHES CONFIGURATIONS BY PANEL CONTROL (OPTIONAL)
DIP switches configurations by Panel Control (Optional)
- Turn off the unit.
- Press the up (+) and down (-) buttons together for 3 seconds to activate the dip switches configurations by panel control (see Figure 5).
- See Table 2 for Dip Switches configurations and functions by panel control.
- NOTE: Press the up (+) and down (-) buttons together for 3 seconds again or no operation within 30 seconds to exit the dip switches configurations by panel control and the unit will save the last settings.
- Display function settings with 2 digitals in LED display window, high (left) for dip switches, low (right) for functions (see Figure 5).
- Press up (+) button to set the dip switches, press down (-) button to set the functions.
No. | High (left) | Low (Right) | Remarks |
---|---|---|---|
/ | 0 | 1 – Panel Control | 0 – by DIP Switches |
S1 | 1 | 1 – Electric Heat Only | 0 – Electric Heat and Pump Heat |
Unit Only
S2| 2| 1 – temperature display in °F| Temperature Display in °C|
S3*S9
|
3
| 3 – use control panel or some types of wall thermostat;
2 – use types of wall thermostat; 1 – use PTAC other wall thermostat; 0 – control panel enable.
| You can consult with the sales agency or manufacturer for details.
| | 4: 62°F – 86°F (17°C – 30°C); 3: 61°F – 86°F (16°C – 30°C);|
S4*S5| 4| 2: 65°F – 78°F (18°C – 26°C); 1: 63°F – 80°F (17°C – 27°C);
| | 0: 68°F – 75°F (20°C – 24°C);
S6| 6| 1 – Fan continuous run for heating| 0 – Fan cycle for heating| Not
available for “use
PTAC other wall thermostat”.
S7| 7| 1 – fan continuous for cooling| 0 – Fan cycle for cooling
S8| 8| 1 – low. Temp protection enable| 0 – low. Temp protection disable|
Optional
SW7| A| 1 – Front desk control disable| 0 – Front desk control enable|
Optional
SW11| B| 1 – Load delay for three seconds| 0 – normal| Optional
TABLE 2 DIP SWITCHES CONFIGURATIONS BY PANEL CONTROL
NOTE:
- The LED display window will show “00” when you first enter the setting mode, only when you set “01” you can start the next settings.
- To activate front desk control function, you need to pull the dip switch “SW7” to “DOWN(OFF)”, and then set the panel control to “A0”.
- After all set, press up (+) and down (-) buttons together for 3 seconds to exit the operation interface and cut off the power. When re-powered on, the settings are activated.
WALL THERMOSTAT TERMINAL (OPTIONAL)
IMPORTANT: Only trained, qualified personnel should access electrical panel on unit and install electrical accessories. Please contact your local electrical contractor, dealer, or distributor for assistance.
Thermostat Wire Routing
Thermostat wire is field supplied. Recommended wire gauge is 18 to 20 gauge
solid thermostat wire.
NOTE: It is recommended that extra wires are run to unit in case any are
damaged during installa-tion. Thermostat wire should always be routed around
or under, NEVER through, the wall sleeve. The wire should then be routed
behind the front panel to the easily accessible terminal connector.
NOTE: Refer to thermostat installation instructions for details on installing wall thermostat.
Installation Instruction of Some Types of Wall Thermostat
(You can Consult with the sales agency or manufacturer for details) Pull the
dip switch to the DOWN (OFF) position as shown below.
Insert the wire connector of the wall thermostat into the rele-vant terminal according to different shapes as shown below.
Installation Instruction of PTAC Other Wall Thermostat
Remove the two screws as shown below and take the cover panel down.
Terminal of PTAC other Wall Thermostat(MODE B)
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment dam-age or improper
operation. Improper wiring may damage unit electronics. Common busing is not
permitted. Damage or erratic operation my result.
Use terminal 4-way for heat pump connection only. Sug-gested set compressor
protection time is more than 3 minutes in the wall thermostat. If set less
than 3 minutes, the compressor will restart delay 3 minutes still.
Wall Thermostat must be heating changeover 4-way valve. For thermostats that
have only one fan speed output (on or auto), the fan speed is determined by
how the terminal connector is wired. If Low fan is desired, wire the G output
from the thermostat to (LOW-FAN) on the units terminal block. If High fan is
desired, wire the G output from the thermostat to (HI-FAN) on the units
terminal block.
The range of set temperature of wall thermostat must be in consonance with the
range of DIP switch setting. Wall Thermostat must be set the type properly in
consonance with the unit type: heat pump or no heat pump.
If the Wall Thermostat has only one electrical heater output, connect the two
terminals of HEAT 1 and HEAT 2, the unit can operate two electrical heaters
(only for the unit has two electrical heaters). Otherwise operate one
electrical heater. Please do not remove the control panel.
Front Desk Control
The controller can handle a switch signal from FC(L) and FC(N) input, called
front desk control. Input must be 24VAC. If system doesn’t receive a 24VAC
signal, it will turn unit off; otherwise, the unit runs in normal control. The
DIP switch can control the FRONT DESK CONTROL fea-ture. The DIP switch is on
the DOWN position, the unit will be turn off; otherwise the unit runs in
normal control. See Figure B.
INSTALLATION
How to Install the Unit
CAUTION
There are sharp edges that can cause serious cuts. When lifting the air conditioner, it is HEAVY. Use two people to lift.
- For existing sleeve, you should measure the wall sleeve dimensions.
- Install the new air conditioner according to these in-stallation instructions to achieve the best performance. All wall sleeves used to mount the new air conditioner must be in good structural condition and have a rear grille that securely attaches to the sleeve or the flange of the sleeve to secure the new air conditioner.
- To avoid vibration and noise, make sure the unit is installed securely and firmly.
- When installing the sleeve,make certain there is noth-ing within 20 of the back that would interfere with heat radiation and exhaust air flow. (See Figure 6)
Preparation of Sleeve Assembly (Optional)
Refer to the installation instruction of sleeve assembly for details.
Preparation of Rear Grill Assembly (Optional)
Refer to the installation instruction of rear grille assembly for details.
Unit Installation
Carefully remove shipping tapes from the front panel (See Figure 7).
Remove the front panel (See Figure 8).
Remove the shipping screw from the vent door (See Figure 9).
Dimension of air Conditioner
Dimension of sleeve assembly (optional)
- Pull out at the bottom to release it from the tabs
- Then lift up
Rotate the vent control lever to either open or close the vent door. (See
Figure 10)
NOTE: When vent control lever set at CLOSE, only the air inside the room
is circulated and filtered. When set at OPEN, some outdoor air will be drawn
into room. This will reduce heating or cooling efficiency.
Lift unit level and slide unit into wall sleeve until firmly against front of
wall sleeve and secure with 4 screws and washers (supplied in the SLEEVE
ASSEMBLY) through the unit flange holes. (See Figure 11 and Figure 12)
Reinstall from panel. (See figure 13)
Place tabs over top rail O. Push Inward at bottom until panel snaps into place
CAUTION
- Do not put obstacles around air-inlet or inside of air-outlet of the unit such as window curtain, etc.
- Always insert the filter securely, clean filter once every two weeks as required.
CARE AND CLEANING
Front Panel and Case
Turn unit off and disconnect power supply. To clean, use water and a mild
detergent. DO NOT use bleach and abra-sivers. Some commercial cleaners may
damage the plastic parts.
Outdoor Coil
Coil on outdoor side of unit should be checked regularly. Unit will need to be
removed to inspect dirt build-up that will occur on the inside of the coil. If
clogged with dirt and soot, coil should be professionally cleaned. Clean
inside and outside of outdoor coils regularly.
NOTE: Never use a high-pressure spray on coil.
CAUTION
- UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment dam-age or improper operation. Airflow restriction may cause damage to the unit.
Air Filters
IMPORTANT: Turn unit off before cleaning.
CAUTION
- UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment dam-age or improper operation. Do not operate unit without fil-ters in place. If a filter becomes torn or damaged, it should be replaced immediately. Operating without filters in place or with damaged filter will allow dirt and dust to reach in-door coil and reduce cooling, heating, airflow and efficiency of unit. Airflow restriction may cause damage to unit.
The most important thing you can do to maintain unit efficiency is to clean the filters once every two weeks as re-quired. Clogged filters reduce cooling, heating, and airflow.
Keeping filters clean will:
- Decrease cost of operation.
- Save energy.
- Prevent clogged indoor coil.
- Reduce risk of premature component failure.
To Clean Air Filters:
- Vacuum off heavy soil.
- Run water through filter.
- Dry thoroughly before replacing.
Removing Air Filter
Replacing Air Filter Vent Door Filter
IMPORTANT: TURN UNIT OFF BEFORE CLEANING.
- If the vent door is open, access requires the removal of the unit from the wall sleeve. Clean the vent filter twice a year or as required.
- Make sure to remove the shipping screw from the vent door (See Figure 9).
- Rotate the vent control lever to open the vent door (See Figure 16).
- Remove four screws from the vent door filter (See Figure 16).
- First pull out the vent door steel wire from the hole of the vent door, then take off the vent door and filter (See Figure 16).
- Clean the filter. Dry thoroughly before replacing.
- Replace the vent door and filter,reinstall the four screws.
- einsert the vent door steel wire into the hole of the vent door.
TROUBLESHOOTING
POSSIBLE CAUSES | SOLUTIONS |
---|
UNIT DOES NOT START
· Unit may have become unplugged
· Fuse may have blown
· Circuit breaker may have been tripped
· Unit may be off
· Unit may be in a protection mode
| · Check that plug is plugged securely in wall receptacle.
NOTE: Plug has a test / reset button on it. Make sure that the plug has not tripped.
· Replace the fuse. See note 1.
· Reset circuit breaker. See note 1.
· Turn unit on (bottom right button on keypad).
UNIT NOT IN COOLING / HEATING ROOM
· Unit air discharge section is blocked
· Temperature setting is not high or low enough NOTE: Setpoint limits may not allow the unit to heat or cool the room to the temperature desired. Check section on dip switch settings
· Unit air filters are dirty.
· Room is excessively hot or cold when unit is started.
· Vent door left open.
· Unit may be in protection mode.
· Compressor is in time delay.
| · Make sure that curtains, blinds, or furniture are not restricting or blocking
unit air flow.
· Reset to a lower or higher temperature setting.
· Remove and clean filters.
· Allow sufficient amount of time for unit to heat or cool the room. Start heating or cooling early before outdoor temperature, cooking heat or gatherings of people make room uncomfortable.
· Close vent door.
· Check dip switch and wall thermostat settings for desired comfort.
· Wait approximately 3 minutes for compressor to start.
DISPLAY HAS STRANGE NUMBERS / CHARACTERS
ON IT
| · The unit may be in a protection mode.
· The unit may be set for °C (instead of °F).
UNIT MAKING NOISES| · Clicking, gurgling, and whooshing noises are normal during operation of
unit.
WATER DRIPPING OUTSIDE
| · If a drain kit has not been installed, condensation runoff during very hot
and humid weather is normal. See note 2. If a dran kit has been installed and is connected to a drain system, check gaskets and fittings around drain for leaks and plugs.
WATER DRIPPING INSIDE
· Wall sleeve is not installed level
| ****
· Wall sleeve must be installed level for proper drainage of condensation. Check that installation is level and make any necessary adjustments.
POSSIBLE CAUSES | SOLUTIONS |
---|
ICE OR FROST FORMS ON INDOOR COIL
· Low outdoor temperature
· Dirty filters
| · When outdoor temperature is approximately 55°F or below, frost may form on
the indoor coil when unit is in Cooling Mode. Switch unit to FAN operation until ice or frost melts.
· Remove and clean filters
COMPRESSOR PROTECTION
· Power may have cycled, so compressor is in a restart protection.
| · Random Compressor restart – Whenever the unit is plugged in, or power has been
restarted, a random restart will occur. After a power outage, the compressor will restart after approximately 3 minutes.
· Compressor Protection – To prevent short cycling of the compressor, there is a random startup delay of 3 minutes and a minimum compressor run time of 3 minutes.
ELECTRIC HEATING FAILURE| · Clean the evaporator once every three months by professional people.
NOTES:
- If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician,
- If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit should be installed and connected to drain system.
The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details.