Honeywell 8000 VisionPRO Thermostats Instruction Manual
- June 9, 2024
- Honeywell
Table of Contents
Honeywell 8000 VisionPRO Thermostats Instruction Manual
Installer setup
-
Press SYSTEM.
-
Press and hold these two blank buttons until the display changes.
-
Use arrows to change settings as required.
-
Press DONE to exit and save settings.
Installer setup functions
Available option and default settings vary by thermostat.
Table 1. Installer Setup
Setup functions| Setting & Options (factory default in bold)
0120| Year (first two digits)| 20 (2000-2099) 21 (2100-2178)
0130| Year (second two digits)| 06 (2006) [Other options 0-99]
0140| Month| 6 [Other options 1-12]
0150| Day| 15 [Other options 1-31
0160| Schedule format| 4 7-day programming
0 Non-programmable
0170| System type| 1 1 heat / 1 cool Conv. 2 1 heat / 1 cool heat pump (no
Aux. heat) 3 Heat only (2 wire) 4 Heat only with fan 5 Hot water Series 20 6
Cool only 7 2 heat / 1 cool heat pump (with Aux. heat) 8 2 heat / 2 cool
multistage 9 2 heat / 1 cool multistage 10 1 heat / 2 cool multistage 11 2
heat / 2 cool heat pump (no Aux. heat) 12 3 heat / 2 cool heat pump (with Aux.
heat)
0180| Fan control (heating)| 0 Gas/Oil heat (equipment controls heating fan)
1 Electric furnace (thermostat controls heating fan)
0190| Changeover valve (O/B terminal)| 0 Controls valve in cooling
1 Controls valve in heating
0200| Auxiliary heat| 0 Electric backup heat
1 Fossil fuel backup heat
0210| External fossil fuel kit| 1 External fossil fuel kit controls backup
heat
0 Thermostat controls backup heat (outdoor sensor required)
0220| First stage compressor cycle rate| 3 Recommended [Other options: 1–6]
0230| Second stage compressor cycle rate| 3 Recommended [Other options: 1–6]
0240| First stage heat cycle rate| 5 Gas or oil furnaces of less than 90%
efficiency
1 Steam or gravity 3 Hot water systems or furnaces of 90%+ efficiency
9 Electric furnaces [Other options: 1–12]
0250| Second stage heat cycle rate| 5 Gas or oil furnaces of less than 90%
efficiency
1 Steam or gravity 3 Hot water systems or furnaces of 90%+ efficiency
9 Electric furnaces [Other options: 1–12]
0260| Third stage heat cycle rate| 9 Electric auxiliary heat or electric
furnaces 1 Steam or gravity
3 Hot water systems or furnaces of 90%+ efficiency
5 Gas or oil furnaces of less than 90% efficiency [Other options: 1–12
0270| Emergency heat cycle rate| 9 Electric auxiliary heat or electric
furnaces 1 Steam or gravity
3 Hot water systems or furnaces of 90%+ efficiency
5 Gas or oil furnaces of less than 90% efficiency [Other options: 1–12]
0280| Backlight| 0 Backlight on keypress
1 Continuous backlight (requires 24VAC connection
0300| Manual/auto changeover| 0 Manual changeover (Heat/Cool/Off)
1 Automatic changeover (Heat/Cool/Auto/Off)
0310| Auto changeover deadband| 3 Heat/cool temperature 3°F apart (1.5°C)
[Other options: 2-9 (2°F9°F/1°C-5°C)]
0320| Temperature display| 0 Fahrenheit
1 Celsius
0330| Daylight savings| 1 Auto-change to daylight savings time (through 2006)
2 Auto-change to daylight savings time (2007 and beyond)
0 Daylight savings time is turned off
0340| Remote sensor| 0 No remote sensor
1 Outdoor sensor (display only)
2 Outdoor sensor for control (select heat pumps)
3 Indoor sensor
0350| Heat pump compressor lockout| 0 Off [Other options: 15, 20, 25, 30, 35,
40°F (-9.5°C to 7°C)]
0360| Heat pump auxiliary lockout| 0 Off [Other options: 40, 45, 50, 55, 60°F
(4.5°C to 15.5°C)]
0380| Dehumidification Control| 0 Off
1 A/C runs to help dehumidify
0500| Furnace filter change reminder| 0 Off
1 10-day run time (about 1 month)
2 30-day run time (about
3 months) 3 60-day run time (about
6 months)
4 90-day run time (about 9 months)
5 120-day run time (about 1 year)
6 365-day run time (about 3 years)
0510| Humidifier pad change reminder| 0 Off
1 90 calendar days
2 180 calendar days
3 365 calendar days
0520| U/V lamp change reminder| 0 Off
1 365 calendar days
0530| Adaptive Intelligent RecoveryTM| 1 On
0 Off
0540| Program periods| 4 4 periods (Wake, Leave, Return, Sleep)
2 2 periods (Wake, Sleep)
0580| Compressor protection| 5 5-minute compressor off time [Other options:
0–4 minutes]
0600| Heat temperature range stop| 90 Max. heat temperature setting is 90°F
(32°C) [Other options: 40-89°F (4°C to 32°C)]
0610| Cool temperature range stop| 50 Min. cool temperature setting is 50°F
(10°C) [Other options: 51-99°F (11°C to 37°C)]
0640| Clock format| 12 12-hour time 24 24-hour time
0650| Extended fan timer (heat)| 0 Off 90 Fan runs for
90 seconds after call for heat ends
0660| Extended fan timer (cool)| 0 Off 90 Fan runs for
90 seconds after call for cooling ends
0670| Keypad Lockout| 0 Unlocked
1 Partially locked 2 Fully locked
0680| Heat temperature control| 2 Standard temperature control (recommended) 1
Select if inside temperature is consistently over setting
3 Select if inside temperature is consistently under setting
0690| Cool temperature control| 2 Standard temperature control (recommended) 1
Select if inside temperature is consistently over setting
3 Select if inside temperature is consistently under setting
0700| Temperature display offset| 0 No offset [Other options: -3, -2, -1, 1,
2, 3°F (-1.5°C to 1.5°C)]
0710| RESET| 0 No reset
1 Reset installer options & program schedule to factory default
INSTALLER SYSTEM TEST
The Installer Test is part of the Installer Setup Menu.
-
Enter the Installer System Test by entering the Installer Setup and pressing t repeatedly until “Test” appears.
-
Use arrow to change test and system status as required.
-
Press DONE to exit.
System tests
Test the system’s heating, cooling, fan and emergency heat. Available tests vary by thermostat and system type.
Table 2. Installer System Test
System Test Number| Test Type| System Status Number and Description
Test 1| Cooling System Test| 0 Off
1 Compressor and fan on
2 Second stage compressor on
Test 2| Fan System Test| 0 Off
1 Fan on
Test 3| Heating System Test| 0 Off
1 Heat on
2 Second stage heat (Aux. heat) on
3 Third stage heat (Auxiliary heat) on
Test 4| Emergency Heat Test| 0 Off
1 Em. Heat and fan on
2 Auxiliary heat on
Press the DONE button to exit the Installer System Test.
Caution
EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed during testing. To
prevent equipment damage, avoid cycling the compressor quickly
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
US Patent No. 6595430, D509151; other
Patents Pending. All Rights Reserved
69-1871-1 M.S. Rev. 09-06