POTTER PAD100-SB Addressable Sounder Base Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PAD100-SB Addressable Sounder Base
Features
- Integrated Sounder in base
- 75 dB (UL 464 Listed) sounder output
- Sounder independent of sensor, allows for a single station, grouped or all-call
- May be mapped to any device connected to the control panel
- Terminals accept 22 to 12 AWG wire sizes
- Supports Class A, Class X and Class B wiring
- Does not require SLC Loop address
- UUKL Listed for Smoke Control
Description
The Addressable Sounder Base 6” (PAD100-SB) is a sounder base that may be
utilized in a variety of applications. The base has a locking feature for the
sensor that may be used or removed in the field. Once the head is removed, the
sounder is accessible in the bottom of the unit.
The base has an independent sounder module that may be programmed as a single
station, zone or all call sounder. The PA D100-SB passes through the sound
pattern sent to the sounder, therefore it may reproduce in any pattern the
power supply provides.
The panel will support any combination of sensors or modules on the SLC. The
PAD100-SB does not consume an address on the loop and is fully programmable to
operate with any input. Once activated the sounder will also follow the input
from the power source and deactivate accordingly
Technical Specifications
Working Range for SLC | 24 VDC |
---|---|
Working voltage range for PWR | 16 – 33 VDC |
Active current for PWR | 30 ma |
Sound pressure level | 75dB/10ft (min.) as per UL464 |
Installation temperature range | 32°F to 120°F (0°C to 49°C) |
Operating relative humidity range | 0% to 93% (Non-condensing) |
Start-up time | Max. 1 sec. |
Maximum number of devices per zone | 127 |
Color | Eggshell White |
Dimensions (without detector) | Height: 0.75 in (19mm) Diameter: 6.3 in (166 |
mm)
Detector Base Mounting
PAD100-SB should be mounted directly on the electrical box. The mounting holes are configured for a single gang, double gang, octagon or 4” square box. See Fig. 1.
Locking Feature
Eliminate the Locking Feature
PA D100-SB include a locking feature that prevents removal of the detector and removal of the base cover without using a tool.
- To eliminate this feature, break off the locking tab and then install the detector. See Fig. 2.
Removing of Detector Head from Base
- To remove the detector from the base once the locking feature has been activated, insert a small screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counter-clockwise. See Fig. 3.
- To remove the base cover from the lower enclosure once the locking feature has been activated, insert a small screwdriver into the slot on the on the base to push the plastic tab while simultaneously turning the detector head counter-clockwise.
Ordering Information
Model
| Description|
Stock No.
---|---|---
PA D100-SB| Addressable Sounder Base|
3992729
Customer Support
Potter Electric Signal Company, LLC
St. Louis, MO
Phone:800-325-3936
www.pottersignal.com