Pfannenberg DTS 3000 Series Cooling Units Instruction Manual
- June 12, 2024
- Pfannenberg
Table of Contents
- DTS 3000 Series Cooling Units
- SECTION 1: HOW TO USE THIS MANUAL
- SECTION 2: RECEIVING INSPECTION
- SECTION 3: HANDLING
- SECTION 4: INSTALLATION
- SECTION 5: OPERATING CONDITIONS
- SECTION 6: UNIT START-UP
- SECTION 7: MAINTENANCE
- SECTION 8: TROUBLESHOOTING
- SECTION 9: DESIGN DATA
- SECTION 10: WARRANTY INFORMATION
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DTS 3000 Series Cooling Units
Instruction Manual DTS 3000 Series
Cooling Units
Installation, Operation and Service Manual
DTS 3000 Series Cooling Units
Safety for man, machine and the environment®
SECTION 1: HOW TO USE THIS MANUAL
This manual contains information on the installation and operation of DTS 3000
Series bolt-on cooling units intended to be door and side mounted on
electrical panels.
Conventions used:
Hint: A hint contains additional information on the action or instruction
being described
WARNING!
If the information following this is not strictly followed there is a danger
to health or life.
WARNING!
If the information following this is not strictly followed there is a danger
to health or life due to electrical shock.
The technical data specific to each cooling unit including installation
connections and operational data are contained on a separate data sheet.
SECTION 2: RECEIVING INSPECTION
2.1 Unpacking
Prior to and during unpacking the cooling unit, visually inspect it to
determine if any damage has occurred during shipping. Make sure that it does
not contain any loose components. Before discarding any packaging materials:
Look for loose parts, dented or scratched panels or fluids.
If any damage is noted it shall be reported immediately to the delivering
carrier and a claim should be filed with them. Pfannenberg cannot accept
responsibility for freight damage that may occur; we will assist you in any
way possible if the need arises to file a claim.
In case of a warranty claim, the following information is required: exact
details of the fault (including photographs, if possible), the cooling unit
part number and serial number are required.
WARNING!
Burrs caused by production may be present on the metal edges of the cooling
unit. Always wear protective gloves when carrying out installation or
maintenance work.
2.2 Included Items
The following items should be included:
Cooling unit
Mounting cutout
Manual
Technical Data Sheet
DTS 3000 Series accessory pack typically includes:
- Sealing strips
- Threaded mounting studs
- Mounting bolts, nuts and washers
- Condensate hose
- Door contact connector/jumper
2.3 Review of ID Plate
The ID plate is located on the left side of the cooling unit. The technical
data specific to the cooling unit is located on the ID plate as shown below.
SECTION 3: HANDLING
3.1 Transporting
The cooling unit shall only be moved in the fully assembled, upright
condition.
If the cooling unit is being shipped with an electrical panel enclosure it
shall be packed separately from the electrical enclosure.
WARNING!
If for any reason the cooling unit has been placed in any position other than
fully upright it shall be placed in a vertical position for a minimum of 1
hour prior to starting the unit. If this is not done the compressor may be
drained of oil. Operation of the compressor without proper oil fill may cause
permanent damage to the cooling unit and void the warranty.
3.2 Storage
The cooling unit shall not be exposed to temperatures exceeding +70ºC. Store
the unit fully assembled in the fully upright condition.
WARNING!
Failure to observe these requirements will void the warranty.
SECTION 4: INSTALLATION
4.1 Pre-installation testing
Before mounting the cooling unit to the electrical panel enclosure it should
be tested to verify function.
4.2 Installation onto the electrical panel
Before connecting the cooling unit to the power supply, verify that the
following are correct.
Voltage must be within ± 10% of the value listed on the ID plate.
Voltage frequency must be within ± 3 Hz of the value listed on the ID plate
Ambient temperature must be below +55ºC (for options see “setting the
operating parameters” section)
Place the drilling template supplied with the cooling unit onto the applicable
mounting surface of the electrical panel enclosure.
WARNING!
Metal chips from drilling and cutting the openings may damage the electrical
panel enclosure. Take precautions required to prevent chips and debris from
getting into the enclosure.
WARNING!
Watch out for sharp edges created when drilling and/or cutting the enclosure.
Drill holes in the electrical panel enclosure to match the unit and cut out
air flow openings.
Remove the cooling unit cover for handling during installation by removing the
cover mounting screws. Install the two supplied stud bolts (in the accessory
pack) into the top two mounting hole locations of the cooling unit.
WARNING!
Please note the information on the “Thread Reach for Set Screw” label attached
to the cooling unit. If the noted installed thread depth is exceeded the
cooling unit may be damaged.
Install the cooling unit mounting insulation strips (in the accessory pack) to
the cooling unit as noted on the individual cooling unit information sheet.
Make sure that the insulation strips are correctly attached and placed
correctly on the cooling unit. The correct fitting and location of the
insulation strips is required for the proper operation of the cooling unit.
Attach the cooling unit to the electrical panel enclosure by use of the stud
bolts inserted as described above.
WARNING!
Do not move the cooling unit by the piping.
Doing so will damage the cooling unit and void the warranty.
The cooling unit is then completely attached to the electrical panel enclosure
from inside the enclosure by use of the screws and washers supplied in the
accessory pack.
Tighten the fasteners until the cooling unit insulation strips are compressed
to a thickness of 2 mm (approx. .080”) Install the condensate drainage hose to
the drain located in the cooling unit base.
Reinstall the cover using the original mounting screws.
4.3 Power connection
WARNING!
Make sure that the main power supply to the cooling unit is turned off while
making the power connections.
The cooling unit power supply shall be fused as indicated on the unit ID plate
by means of a series connected power line connection. A temperature control
can not be connected in series with the cooling unit power supply.
All power connections and / or repairs, if or when required, shall only be
carried out by authorized, trained electricians.
WARNING!
The cooling unit may be damaged due to compressor rotating in the incorrect
direction.
On three phase connection (400V/460V) units the power supply connections are
phase sensitive. Make sure that the power connections are correct or the
cooling unit will not operate properly.
Power supply connection
All units are provided with either a molded cord or permanent connection
internal to the unit. permanent connection must be secured to the cooling unit
by means of a cable strain relief.![Pfannenberg DTS 3000 Series Cooling Units
- Power supply connection](https://manuals.plus/wp-content/uploads/2023/08
/Pfannenberg-DTS-3000-Series-Cooling-Units-Power-supply-connection.jpg)Both
the main power supply voltage and frequency shall correspond to the nominal
values shown on the cooling unit ID plate.
WARNING!
The cooling unit may be damaged if the supply voltage is too high.
This refers to cooling units with (460V / 400V) multiphase connections.
As an option, the control voltage can be adjusted to match the main power supply. Internal to the unit, a voltage jumper is provided to adjust the transformers incoming voltage. See technical data sheet included with cooling unit.
Connect the main power supply to the cooling unit as indicated by the label located on the cooling unit and on the individual cooling unit data sheet.
WARNING!
During installation, service technician must verify and mark voltage as connected on service cover warning sticker.
Terminal Connections:
4.4 Door contact
To avoid an increased production of condensate and for safety reasons a door limit switch should be connected to the terminals provided. The power supplied to these terminals from the cooling unit is low voltage (<20V, 20mA).
WARNING!
No external voltage may be applied to the door contact circuit or damage to the cooling unit may result. In order to prevent any interference from outside signals, it is recommended that a shielded cable with a twisted pair leads be used for the connection. The cable shielding can be connected on one side to the PE (ground) connection point provided on the cooling unit.
If the use of a shielded cable is not possible, the cable that is used must not be routed in the immediate vicinity of potential sources of interference such as power supply lines , components with a relatively high electromagnetic emission (EMI), etc.
If no door contact switch is used, the connecting terminals must be jumpered for the cooling unit to operate.
Centralized fault indicator option
To connect the fault signal line there are two connection terminals available (see the connecting diagram on the label of the individual cooling unit).
The signal of a fault in the cooling unit is displayed by the breaking of a potential-free contact.
WARNING!
These connection points may be connected to a live electrical line with a maximum of 230V, 2 A
SECTION 5: OPERATING CONDITIONS
5.1 Requirements
Before connecting the cooling unit to the power supply, verify that the
following are correct.
Voltage must be within ± 10% of the value listed on the ID plate.
Voltage frequency must be within ± 3 Hz of the value listed on the ID plate
Ambient temperature must be below +55ºC (for options see Section 6.5)
If it ever becomes necessary for servicing, use only the refrigerant specified
on the ID plate and genuine spare parts only or damage to the cooling unit may
result.
Before mounting, make sure that the cooling unit will have proper ventilation
for operation. The cooling unit must have at least 200mm of clearance between
it and any other surface.
Make sure that the airflow inside of the electrical panel enclosure is not
restricted by internal components.![Pfannenberg DTS 3000 Series Cooling Units
-
electrical panel](https://manuals.plus/wp-content/uploads/2023/08 /Pfannenberg-DTS-3000-Series-Cooling-Units-electrical-panel.jpg) WARNING!
If the cooling unit is being mounted on the door of the electrical panel enclosure, it must be confirmed that the door hinges can support the additional weight of the cooling unit and that the electrical panel enclosure is securely fastened so that the panel enclosure will not topple over.
5.2 Theory of Operation- Compressor
- Heat exchanger (condenser)
- Expansion valve/ capillary line
- Heat exchanger (evaporator)
- fan, exterior circulation
- fan, inner circulation
- Electronic control system with temperature sensor
The compressor (1) compresses the refrigerant until it becomes a high pressure
gas. During the compression process, the temperature of the refrigerant gas
increases.
As the refrigerant in the form of a high pressure, high temperature gas flows
through the condenser (2) the refrigerant cools and condenses as the heat is
dissipated to the ambient (outside of the electrical panel) air.
This is accomplished by the condenser fan (5) pulling in ambient air into the
housing and then pushes the ambient air through the fin and coils of the
condenser (2) and back out of the housing and into the ambient environment at
a higher temperature.
As the now liquid refrigerant passes through the expansion valve (3) the
pressure drops and the refrigerant becomes a liquid / gas mixture.
As the refrigerant in the form of a liquid / gas passes through the evaporator
(4) it absorbs the heat from air in the electrical panel enclosure while also
dehumidifying it.
This process lowers the temperature of the air in the electrical panel
enclosure
This is accomplished by the evaporator fan (6) pulling in the hot air from the
electrical panel enclosure and pushes it through the evaporator (4) and back
into the electrical panel enclosure at a lower temperature.
The cooling unit is electronically controlled. To accomplish this a
temperature sensor monitors the temperature inside the electrical panel
enclosure and regulates the function of the cooling unit.
The refrigerants used in the cooling unit are noncombustible and are minimally
detrimental to the atmosphere.
5.3 Condensation Consideration
During operation, the moisture in the air inside of the electrical panel
enclosure condenses on the fins of the evaporator and is collected as
condensate.
In order to avoid any damage to the electrical panel enclosure contents or to
the cooling unit, the condensate must be removed from the cooling unit.
The condensate is removed as follows: The condensate drains into a condensate
tray located at the bottom of the cooling unit and is evaporated into the
ambient air by means of an electrical heating element.
The free discharge of any accumulated condensate must be provided for to
ensure trouble-free operation of the cooling unit.
The PTC-heater starts heating immediately on the application of power to the
cooling unit. The PTCheater is self-controlled and it’s temperature will vary
depending on the level of condensate in the condensate tray. WARNING!
HOT SURFACE
Even if there is no condensate in the condensate tray the PTC-heater will be
on at a low output. In the case of excessive condensate drainage the
condensate tray located at the bottom of the cooling unit may fill with
condensate which is then drained away by means of a hose connection.
WARNING!
If there is excessive condensate formation during normal operation, check the
electrical panel enclosure seals.
We recommend that a door contact switch be installed to turn off the cooling
unit when the door to the electrical panel enclosure is opened in order to
prevent excessive condensate formation.
SECTION 6: UNIT START-UP
6.1 General
The cooling unit is equipped with an electronic
control system. The temperature of the air pulled in
from the electrical panel enclosure into the cooling
unit is measured by a temperature sensor.
WARNING!
Ambient conditions and temperatures in the electrical panel must be in
accordance with the values indicated in the cooling unit information sheet.
WARNING!
Unit must be operated with the cover installed. Unit can not cool properly
when cover is not in place.
Immediately after the main power is turned on for the cooling unit, the unit
goes into its start-up / test mode.
6.2 Fault indicator / LED Display
The cooling unit has an operational display in the form of an LED located
either on the rear of the cooling unit or on the external hood of the cooling
unit.
If the indicator light remains on when the power supply is turned on, it means
that the cooling unit is in its normal operating mode. If a fault is detected
or if the cooling unit is in its start-up / test mode, the LED will flash in a
fault code that can be used to help diagnose the problem.
6.3 Test Mode / Start-up
The start-up / test mode is activated whenever the unit has had power removed
and re-applied.
While in this mode the cooling unit operates independently from the ambient
conditions when the door contact is closed.
The cooling unit runs through a start up sequence that takes approximately 30
seconds to accomplish. The start-up mode is also activated whenever the door
limit switch is closed.
Modus | Time Curve | Characteristics |
---|---|---|
Start-up Mode | t = 0s – < 30s |
t = 30s
t = 32s| No function.
Internal fan start up.
External fan and compressor start up.
Flashing sequence of the status indicator: “off-dark-light-dark-off”.
Fault signal contact is closed.
Self Test during Start| t > 34s – 64s| Compressor and fans remains in
operation during the period.
Flashing sequence of the status indicator: “off-dark-light-off”.
Fault signal contact is open.
Should a fault arise during the test mode, the unit goes into the fault mode
and the status indicator lights up according to the fault state (See Section
8.1)
6.4 Door Contact
For safety reasons and to prevent an increased output of condensate, a door
limit switch should be connected to the terminals provided on the cooling
unit. (see the wiring diagram on the individual cooling unit or on the
individual information sheet supplied with the cooling unit.
With the switch in place, when the electrical panel enclosure door is opened
(thereby opening the switch) all of the cooling unit motors are immediately
turned off. When the electrical panel enclosure door is closed, the cooling
unit start-up mode begins and is run through which ensures a restart-up of the
cooling unit with a time lag.
6.5 Setting the Operating Parameters
Various electrical panel enclosure temperatures as well as the limit
temperatures can be selected by means of a DIP switch on individual cooling
units.
The location of the DIP switch is on the cooling unit control board as shown
on its circuit diagram.
The coding options are represented on the circuit diagram.
The circuit diagram and / or display image are to be found on the inside of
the service cover of the cooling unit or on the individual cooling unit
information sheet.
See the cooling unit information sheet for additional details.
WARNING!
Changes to the operating parameters of the cooling units should only be made
by authorized personnel.
SECTION 7: MAINTENANCE
7.1 General Maintenance
WARNING!
Disconnect the cooling unit from the power supply before any cleaning or
maintenance.
The cooling unit is largely maintenance free. The cooling circuit is a
maintenance free hermetically sealed system. It has been filled at the factory
with the required refrigerant amount, checked for leakage and run through a
series of functional tests before being shipped.
The components around the external air circuit require periodic cleaning and
maintenance depending on the environmental conditions.
7.2 Cleaning
The cleaning intervals depend upon the relevant operating conditions. In
particular, observe the following instructions:
- Disconnect the cooling unit from the power supply
- Remove the external cover
- Clean the heat exchanger regularly using a soft brush or pressurized air
- It is recommended that the condensate run off opening be checked regularly
WARNING!
Damage to the heat exchanger possible. Do not use any sharp or pointed object
to clean the condenser heat exchanger.
The heat exchanger fins should not be bent, compressed or damaged in any way
during the cleaning process.
If the cooling units are provided with a filter, clean the filter mat
regularly. The cleaning intervals or the intervals for replacement of the
filter mat mainly depends upon environmental conditions (air quality.)
You can rinse the filter mat using water heated to 40° C and commercially
available mild detergent.
It is possible to remove any dirt by knocking the mat slightly, vacuum
cleaning it or blowing it out.
If the filter mat is oily or greasy, please replace.
SECTION 8: TROUBLESHOOTING
8.1 Verifying Normal Function
Environmental conditions may eliminate the need for cooling. If the door
contact circuit (X54) is opened then closed the unit will perform it’s test
function. This will cause all the components to activate and the unit will
provide cooling for a short time. (See below.)
If cooling does not occur, please review the troubleshooting topics listed
below.
Modus | Time Curve | Characteristics |
---|---|---|
Start-up Mode | t = 0s – < 30s |
t = 30s
t = 32s| No function.
Internal fan start up.
External fan and compressor start up.
Flashing sequence of the status indicator: “off-dark-light-dark-off”. Fault
signal contact is closed.
Self Test during Start| t > 34s – 64s| Compressor and fans remains in
operation during the period.
Flashing sequence of the status indicator: “off-dark-light-off”.
Fault signal contact is open.
Should a fault arise during the test mode, the unit goes into the fault mode
and the status indicator lights up according to the fault state.
NO DIP SWITCH CHANGES ARE REQUIRED.
8.2 Fault Condition
If a fault occurs, check the following points first. If the fault is then not
cleared, call an authorized specialist.
Fault | Possible cause(s) | Remedy |
---|---|---|
Unit fails to cool. Internal fan is running. | Temperature setting is above | |
ambient. | Check temperature setting. | |
Unit fails to cool sufficiently. | Required cooling capacity exceeds capacity |
of unit. Dirty filter or condenser.
Lack of refrigerant.
Internal and external fans not working.
Air not circulating properly inside the switch cabinet.| Check ambient
temperature and internal load. Clean condenser. Clean or replace filter.
Call authorized technician. Check unit for leaks.
Call authorized specialist. Check fan capacitors. Replace fans. Ensure proper
electrical connections.
Check enclosure and air circulation inside enclosure. Air intake and exhaust
must be unimpeded by components.
Condensate accumulates in switch cabinet.| Exiting temperature is too low.
Enclosure is not sufficiently sealed.| Set cooling unit to a higher
temperature setting.
Close enclosure door and improve the seal in the enclosure.
Condensate fails to drain.| Condensate drain is clogged| Clean condensate
drainage. Condensate drainage hose must be angled downward without showing a
bend.
8.3 Error Codes
Unit Characteristics | Technical Causes | Fault Remedy |
---|
Compressor: ON
Internal Fan: ON
External Fan: ON
Status LED: flashing (seq. 3)
Fault signal contact: open| The test mode of the unit is active. This mode is
left automatically at the latest after 60 s.| The unit switches to test mode
once after each new connection to the power supply. No remedy of fault
necessary.
Compressor: OFF
Internal Fan: OFF
External Fan: OFF
Status LED: flashing (seq. 1)
Fault signal contact: closed| The input for the door limit switch is open –
e.g. as a result of a switch cabinet door not closed or a bridge not set.|
Insert link, close door contact switch, or with an engaged door contact
switch, close the door.
Compressor: OFF
Internal Fan: ON
External Fan: OFF
Status LED: flashing (seq. 2)
Fault signal contact: open| High pressure pressostat or motor protection
switch has responded (overheating). Compressor switches on again automatically
after the fault has been remedied (cooling) with a delay of 30 s.| Clean
filter mat or heat exchanger in the external circulation. Possibly check the
power dissipation in the switch cabinet to the installed cooling capacity of
the cooling unit.
Compressor: ON
Internal Fan: ON
External Fan: ON
Status LED: flashing (seq. 1)
Fault signal contact: open| The upper temperature limit (Tu) of the switch
cabinet has been exceeded.| Clean filter mat or heat exchanger in the external
circulation. Possibly check the power dissipation in the switch cabinet to the
installed cooling capacity of the cooling unit.
**Sequence 1: (User Error) *Sequence 2: (Unit Fault)
**Sequence 3: (Test/start-up mode)
SECTION 9: DESIGN DATA
Please refer to the cooling unit individual technical data sheets for the
following:
Dimensional Data
Mounting Cutout
Circuit Diagrams
9.1 SCCR Determination
Article 409 of the 2005 National Electric Code (NFPA 70) requires Industrial
Control Panels (electrical panel enclosures) to be marked with a short circuit
current rating. As specified in the National Electric Code, the Standard for
Industrial Control Equipment,
UL508A-2001, Supplement SB, provides an accepted method for determining the
short circuit current rating of the control panel. The link to spreadsheets
provide guidance for industrial control panel manufacturers who purchase the
discreet components and assemble combination motor controllers within their
panels to achieve a combination short circuit rating that is higher than the
lowest rated individual component.
Using the technical data sheet and the information on the cooling unit ID
plate, identify the full load current conditions for the appropriate voltage.
The installation of the cooling unit should be calculated as a dedicated
branch circuit for determining the SCCR value. All selections should be
evaluated based on the current UL standards for UL508a.
Table 1
Room cooling units rated-Load Current, Amperage
Single Phase3 | 3 Phase3 | 50 KA | 100 KA | 200 KA | ||||
---|---|---|---|---|---|---|---|---|
11O-120V | 200 – 208 V | 220 – 240 V | 254 – 277 V | 440 – 480 V | Peak |
Let-thru
Current2| Max
Fuse’| IP x 103| Max
Fuse’| IP x 103| Max
Fuse’| IP x 103
10.| 16.0| 5.| 9.| 5.0| 8.0| 7.| Less| 2.| Less| 1000| 15| 50 KA| | n/a| | n/a
16.| 34.0| 9.| 19.| 8.| 17.0| —| —| —| —| 2000| 30| 50 KA| 15| 100 KA| | n/a
—| —| —| —| —| —| —| —| Over| 2.| 5000| 15| 50 KA| 30| 100 KA| 30| 200 KA
1 Maximum CC class Fuse size that can achieve this branch circuit SCCR value.
Smalller values may be used and still achieve equal rating.
2 Circuit capacity amperes based on UL 484 table 52.1
3 Individual units running amperes can be obtained on each unit’s technical
data sheet.
Example 2: DTS 35xx 460V units has a 5KA IR value based on UL 484 table 52.1
(see Table 1) and the amp draw of the unit. If a 15amp Class CC current
limiting feeder circuit is used in combination with the DTS35xx 460V unit, the
maximum allowable Ipeak of the 15 amp Class CC fuse at an available RMS fault
current of 200 kA is 1700 amps (figure 2). This value does not exceed the
allowable Ipeak of this unit based on UL SCCR value of Table 52.1. Threrefore,
the individual branch circuit SCCR value of this series combination can
support 200 kA IR. (See figure 1.)
Option 1: UL 508a reference SB4.2
According to UL508A Supplement SB, if a panel contains no current-limiting
devices, its SCCR depends on the “weakest” or lowest rated component or
combination within the panel.
However, Supplement SB also states that if current- limiting fuses are used in
the feeder circuit, and if the highest instantaneous current reached during
the first half cycle of a fault is less than or equal to the lowest rated SCCR
in any branch circuit, the SCCR of the current limiting fuse can be applied to
the combination.
When the specified branch circuit protection related to the high fault short
circuit current rating is a Class CC,G,J,L,RK1, RK5 or T fuse, a fuse of a
different class is able to be used at the same high fault rating where the
peak let through current and I2t of the new fuse is not greater than that of
the specified fuse.
Option 2: UL 508a reference SB4.3
An alternate method of achieving a high short circuit rating is by applying a
power transformer with an isolated secondary winding, the short circuit
current rating on the line side of the transformer shall be one of the
following:
For a power transformer rated not more than 10 kVA, and where the short
circuit current rating of all components in the secondary circuit are not less
than 5kA, the short circuit current rating of the primary overcurrent
protective device is able to be assigned to the line side of the power
transformer circuit.
For a power transformer rated not more that 5kVA and a 120V maximum secondary
voltage, and where the short circuit current rating of all components in the
secondary circuit are not less than 2kA, the short circuit rating of the
primary overcurrent protective device is able to be assigned to the line side
of the power transformer circuit.
Option 3: UL 508a reference SB4.2
The combinations listed in the linked spreadsheets
(www.ul.com/controlequipment/shortcircuit.html)
may be applied in a manufacturer’s Listed industrial control panel without
further evaluation or specific documentation in the manufacturer’s UL
Procedure pages.
The spreadsheets cover the application of individual components, including a
disconnecting means, an over current protective device, motor controller and
motor overload protection, as a combination motor controller having specified
ratings, including a short-circuit current rating (SCCR). Each of the
individual components is Listed or Recognized to the requirements in the
applicable component Standard.
The specified ratings for the combination motor controller may be applied to
the end-product equipment only when all of the specific components listed are
provided in the end-product equipment and installed according to any
applicable conditions of acceptability.
Components other than those identified in the combination motor controller and
connected in the power circuit of the combination motor controller will
require additional evaluation.
SECTION 10: WARRANTY INFORMATION
(WARRANTY IS VALID FOR 1 YEAR)
Warranty becomes null and void:
In case of improper usage of the unit, noncompliance with operating conditions
or nonobservance of instructions the warranty becomes null and void.
If operated in rooms in which corrosives or acids are present in the
atmosphere.
In case of damage caused by contaminated or jammed air filters.
If a non-authorized person interrupts the cooling circulation, modifies the
unit or changes the serial number.
In case of damage caused by transport or by accidents. For the exchange of
parts by non-authorized companies.
In order to maintain your warranty rights please observe the following when
returning the unit.
Enclose an exact description of the fault in the shipping package.
Enclose proof of delivery (delivery note or copy of invoice).
Return the unit together with all accessories; use the original packaging or
packaging of equivalent quality, send the unit freight prepaid and covered by
an adequate transport insurance.
Pfannenberg Incorporated
68 Ward Road, Lancaster, New York 14086
Phone: 716-685-6866
Fax: 716-681-1521
email: sales@pfannenbergusa.com
www.pfannenbergusa.com Org 05/09
© 2009 Pfannenberg Incorporated