POTTER HPS-24 Series Remote Horn With Silencer Owner’s Manual

June 9, 2024
POTTER

POTTER logo HPS-24 Series Remote Horn With Silencer
Owner’s Manual

POTTER HPS-24 Series Remote Horn With Silencer HPS­24 SERIES
REMOTE HORN WITH SILENCER

HPS-24 Series Remote Horn With Silencer

  • cUL Listed
  • Polarized with wide operating voltage range using filtered DC or unfi ltered FWR input voltage
  • FIRE decal included
  • 4 wires for easy fi eld wiring
  • Mounts to single gang back box
  • Silencer button for 10 minute silence
  • Available in red or white
  • Optional supervised and non­supervised isolators

The HPS­24 is designed for alarm signaling in apartments, suites, or any individual room where effective audible warning is required by federal, state, or local authority having jurisdiction. The mini­horns produce a high sound output with a minimum current draw of just 15mA at 24V DC.  The HPS­24 versions are silenceable mini­orns equipped with a Silence push button and a red LED to indicate Active Signal Circuit when lit. The push button allows the user to silence the mini­ horn for a maximum of 10 minutes, upon which the mini­horn will sound again until the signal ciruit is inactive, the mini­horn is silenced again, or the fire alarm panel is reset. It is polarized for connecting to supervised fire alarm circuits.

Ordering Information

Model
Number| Stock
Number| Housing
Color| Input
Voltage| Operating
Voltage Range| Wiring
Type| Mounting Type| Temperature
Operating Range
---|---|---|---|---|---|---|---
HPS-24R| 4560031| Red| Regulated
24V DC/FWR| 19.2 – 28.8V
DC/FWR| 4-wire| Wall or Ceiling
Mount| 14°F – 140°F
(-10°C – 60°C)
HPS-24W| 4560032| White

Operating Voltage

| Sound Level
---|---
UL Spherical| Indoor (Typical)
IOVDC| 75dBA| 90dBA
24VDC| 82dBA| 98dBA
28VDC| 85dBA| 100dBA

Engineering Specifications

The audible alarm indicating appliance shall be Amseco model HPS­24 silenceable mini­horn or equivalent device. The horn shall be listed under ULC­S525­99 Standard for audible signaling appliance and shall be approved for fi re protective service. The sound ouput shall be a  minimum of 82dB at ten feet. The signaling mini horn shall operate on 24V DC from a non­coded regulated DC supply or full­wave rectified unfiltered supply. The horn shall be capable of wall or ceiling mounting to a single gang box.
Dimensions: inches (mm)
POTTER HPS-24 Series Remote Horn With Silencer -
Dimensions Mini­Horn Wiring/Mounting
Note:
 Must use minimum box size of 3.2”H x 1.9”W x .8”DPOTTER HPS-24
Series Remote Horn With Silencer - Mini-Horn Wiring
Mounting

POTTER logo Potter Electric Signal Co., LLC
St. Louis, MO
Cust Service: 866-240-1870
Tech Support: 866-956-1211
Canada 888-882-1833
www.pottersignal.com
PRINTED IN USA
MKT. #8880117 – REV B
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals