POTTER S-24 and HS-24 Selectable Candela Strobe and Horn/Strobes Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
S-24 & HS-24
Selectable Candela Strobe & Horn/Strobes
Features
- 24VDC units have field selectable candela options of 15, 30, 60, 75 & 110
- Super-Slide® Bracket – Ease of Supervision Testing
- Checkmate® – Instant Voltage Verification
- Synchronize strobe and/or horn with AVSM Control Module
- Prewire entire system, install mounting bracket, then install signals
- Documented lower installation and operating costs
- Switch selection for high or low dBA
- Switch for chime, whoop, mechanical and 2400Hz tone
- Tamperproof re-entrant style grill
- Switch for continuous or temporal 3 tone (not available on whoop tone)
- Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions)
- Faceplate available in red or off-white
Description
The S-24/HS-24 Series is a low profile strobe and horn/ strobe combination
that offers dependable audible and visual alarms and the absolute lowest
current available. The S-24 & HS-24 Series 24VDC offers tamperproof field
selectable candela options of 15, 30, 60, 75, and 110 candela. The Strobe and
Horn/Strobe offers a continuous or sync temporal three in 2400Hz and
mechanical tone, a chime and whoop tone. All tones are easy for the
professional to change in the field by the use of switches. The S-24 & HS-24
Series has a minimal operating current and has a minimum flash rate of 1Hz
regardless of input voltage.
This Series is shipped with a standard 4” metal mounting plate which
incorporates the popular Super-Slide® feature that allows the installer to
easily test for supervision. The
product also features a locking mechanism which secures the product to the
bracket without any screws showing.
The S-24/HS-24 also features the patented Checkmate® -Instant V oltage
Verification feature which allows the installer to check the voltage drop draw
and match it to the blueprint.
The S-24 & HS-24 Series appliances are ANSI/UL 464 and ANSI/UL 1971, listed
for use with fire protective systems and are warranted for three years from
date of purchase.
Technical Specifications
Mounting Options| Single or Double gang, 4″ square box, and AVBB surface mount
back box
---|---
Terminals| Screw-Clamp Type
Wire Gauge| 18 —12 AWG
Operating Temp| 32°F — 120°F (0° — 49°C)
Dimensions| Height — 5″ Width — 4.5″ Depth — 2.5″
Shipping Weight| 1.05 lbs
TONE| SWITCH POSITION
---|---
3| 4| 5
Mechanical Temporal 3| ON| ON| ON
Mechanical Continuous| OFF| ON| ON
2400 Hz Temporal 3| ON| OFF| ON
2400 Hz Continuous| OFF| OFF| ON
Chime Temporal 3| ON| ON| OFF
Chime Continuous| OFF| ON| OFF
Whoop| ON| OFF| OFF
Whoop| OFF| OFF| OFF
NOTE:
- Switch Positions 1The and 2 in the OFF position to select isolated horn and strobe power inputs
- Switch Position 6 ON = HIGH dBA
- Switch Position 6 OFF = LOW dBA
Candela Selection
Super Slide® Mounting Bracket
Allows the installer to pre-wire the system, test for system supervision,
remove the signal head until occupancy, switch out signals without changing
mounting brackets and has locking edge connector for snap-in-place
installation.
Switch Locations
Checkmate™ – Instant Voltage Verification
The access holes are provided in the back of the terminal block to allow the
voltage to be measured directly without removing the device. Typically this
would be done at the
end of the line to confirm design criteria. Most measurements will be taken
using the S+ and S- locations although access is provided to other locations.
NOTE: Care should be taken to not short the test probes.
To remove bezel, grip both sides of bezel and pull in a downward and outward motion.
S-24 24 VDC Selectable Candela, Low Profile Evacuation Strobe
Model Number | Part Number | Nominal Voltage | Candela (ANSI/UL 1971) |
---|---|---|---|
S-24WR | 4890010 | 24 VDC | 15, 30, 60, 75, 110 |
S-24WW | 4890011 | 24 VDC | 15, 30, 60, 75, 110 |
HS-24 24 VDC Selectable Candela, Low Profile Evacuation Strobe
Model Number| Part Number| Nominal Voltage| Candela (ANSI/
UL 1971)| Reverberant dBA at 10
ft, per ANSI/UL 464| In Anechoic Room at
10 ft
---|---|---|---|---|---
HS-24WR| 4890030| 24 VDC| 15, 30, 60, 75, 110| 62-82| 100
HS-24WW| 4890031| _ 24 VDC| 15, 30, 60, 75, 110| 62-82| 100
S-24 & HS 24 Strobe Current Ratings
24 VDC (16 – 33 Volts)
Candela| 24 VDC| UL Max
15 cd| 30 mA| 42 mA
30 cd| 35 mA| 58 mA
60 cd| 66 mA| 97 mA
75 cd| 80 mA| 116 mA
110 cd| 103 mA| 161 mA
Model Designations:
W = Wall mount
R = Red Faceplate
W=White Faceplate
All units are available in plain (no lettering) Plain units are non-
returnable.
“ALERT” bezel available for order.
“AGENT” bezel available for order.
S-24 & HS-24 Horn Ratings
Horn Mode | Horn Decibel Levels | Horn Current Ratings |
---|
Minimum SPL at 10 ft, per
ANSI/UL 464 (HIGH)| Minimum SPL at 10 ft,
per ANSI/UL 464 (LOW)| Regulated 24 VDC Max
Operating @ High Setting (mA)
Temp 3 (2400 Hz)| 78 dBA| 71 dBA| 28 mA
Temp 3 (Mechanical)| 76 dBA| 70 dBA| 25 mA
Temp 3 (Chime)| 70 dBA| 66 dBA| 15 mA
Continuous (2400 Hz)| 81 dBA| 74 dBA| 28 mA
Continuous (Mechanical)| 80 dBA| 72 dBA| 25 mA
Continuous (Chime)| 70 dBA| 66 dBA| 15 mA
Whoop| 82 dBA| 69* dBA| 56 mA
NOTES:
- For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power see installation manual.
- Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
- The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
- Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode).
S-24 & HS-24 Series Wiring Diagram
Notes:
All strobes are designed to flash as specified with continuous applied
voltage. Strobes should not be used on coded or pulsing signaling circuits.
However, use of the Potter AVSM control module or Gentex synchronization
protocol is permitted to synchronize the strobe, horn, and/or mute the horn.
- FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC TECHNICAL SUPPORT AT 1-866-956-1211
Architect & Engineering Specifications
The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24
horn/strobe Series or approved equal and shall be listed by Underwriters
Laboratories, Inc. per ANSI/UL 1971 and/or ANSI/UL 464. The notification
appliance shall also be listed with
Factory Mutual Listing Service (FM) and the California State Fire Marshal
(CSFM).
The notification appliance (combination audible/visible) shall produce a peak
sound output of 100dBA or greater at 24VDC as measured in an anechoic chamber.
The signaling appliance shall also have the capability to silence the audible
signal while leaving the visible signal energized with the use of a single
pair of power wires. Additionally, the user shall be able to select either
continuous or temporal tone output with the temporal signal having the ability
to be synchronized.
Unit shall be capable of being installed so that any unauthorized attempt to
change the candela setting will result in a trouble signal at the fire alarm
control panel.
The audible/visible and visible signaling appliance shall also maintain a
minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The
strobe appliance shall have an operating current of 42mA or less at 24VDC for
the 15Cd strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the
system wiring. The unit shall be provided with a mounting bracket with
terminals and barriers for input/output wiring and be able to mount to a
single gang or double gang box or double workbox without the use of an adapter
plate. The unit shall have an input voltage range of 16-33 volts with either
direct current or full wave rectified power for 24VDC models.
The appliance shall be capable of testing supervision without disconnecting
wires, verify voltage without removing unit and be capable of mounting to a
surface back box.
Potter Electric Signal Company, LLC
• St. Louis, MO
• Phone: 800-325-3936
• www.pottersignal.com
8830054-REV C 6/17