POTTER LFH Series Low Frequency Audible Sounder Owner’s Manual

June 9, 2024
POTTER

POTTER PAL

POTTER LFH Series Low Frequency Audible Sounder

Features

  • Super-Slide® Bracket – Ease of Supervision Testing
  • Wall or Ceiling mount
  • Checkmate® – Instant Voltage Verification
  • Synchronize horn with Potter GTSM module
  • Produces a 520Hz square wave, temporal 3 tone
  • Jumper selection for normal or loud dBA
  • Temporal 4 pattern available when used with GTSM module
  • Tamperproof re-entrant style grill and locking screw (Optional)
  • Faceplate available in red or off white
  • 5 year warranty

Application

The LFH Series is a high quality, low profile, audible appliance designed to meet the NFPA 72 requirements to install low frequency (520Hz) signaling in sleeping rooms.

Description

The LFH horn offers a 520Hz square wave, temporal 3 tone. A jumper selection is available for normal or loud decibel tone. A temporal 4 pattern is available when used with the Potter GTSM Synchronization

Control Module.

The LFH is equipped with a universal 4” metal mounting bracket which incorporates the popular Super-Slide® feature that allows the installer to easily pre-wire the system and test for supervision. The product also features a locking mechanism that secures the signal to the bracket without showing any screws and the Checkmate® – Instant Voltage Verification Feature which allows the installer to check the voltage drop, current draw, and match against the blue print.

Product Listings

  • Listed to ANSI/UL 464 and CAN/ULC S525
  • CSFM: Pending

Technical Specifications

Operating Voltage Nominal 24VDC (16-33VDC)
Operating Temperature 32°F – 120°F (0° – 49°C)
Dimensions 6-1/8” H x 5 1/2” W x 1-5/8” D
Wiring Connections Terminals accept 18 – 12 AWG
Mounting Single gang, double gang, or 4” square back box

Ordering Information

Model Number| Stock Number| Body Color
LFH-24R| 4890070| Red
LFH-24W| 4890071| Off-White
Horn Levels: Reverberant Room

Horn Setting

| Minimum dBA at 10’, Per UL 464 (NORMAL)| Minimum dBA at 10’, Per UL 464 (HIGH)
Temporal 3 520 Hz| 77.8 dBA| 79.8 dBA
Temporal 4* 520 Hz| 81.5 dBA| 83.4 dBA
24VDC Normal Horn Current Rating (mA)

Horn Setting| 24VDC Operating Current (NORMAL)| 24VDC Operating Current (LOUD)| 24VFWR Operating Current (NORMAL)| I24VFWR Operating Current (LOUD)
Temporal 3 520 Hz| 72.1 mA| 120.1 mA| 104.6 mA| 158.4 mA
Temporal 4* 520 Hz| 75.9 mA| 116.0 mA| 108.1 mA| 182.0 mA
Horn Current Ratings Over Input Voltage Range of 16-33V (mA)

Horn Setting

| Regulated 24VDC Max Operating Current (NORMAL)| Regulated 24VDC Operating Current (LOUD)| Regulated 24VFWR Max. Operating Current (NORMAL)| Regulated 24VFWR Max. Operating Current (LOUD)
Temporal 3 520 Hz| 99.4 mA| 155.8 mA| 152.1 mA| 213.5 mA
Temporal 4* 520 Hz| 100.1 mA| 157.2 mA| 163.1 mA| 235.2 mA

Model Designations

“R” = Red “W” = White All units are plain (no lettering)

  • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual.
  • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.
  • RMS current ratings are per ANSI/UL average RMS method. ANSI/UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units). For unfiltered FWR ratings, see installation manual.

Checkmate® Instant Voltage Verification It is often necessary to confirm the voltage drop along the line of devices. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically, this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations.

POTTER LFH Series Low Frequency Audible Sounder \(2\)

NOTE: Care should be taken to not short the test probes.

Super Slide® Mounting Bracket Allows the installer to pre-wire the system, test for system supervision, remove the signal head until occupancy, switch out signals without changing mounting brackets and has locking edge connector for snap-inplace installation.

NOTES:

POTTER LFH Series Low Frequency Audible Sounder \(3\)

  • This appliance is not recommended for use on coded or pulsing signaling circuits.
  • The four pulse temporal pattern (temporal 4) can only be obtained on this product when used in conjunction with the Potter GTSM Synchronization Module
  • ee GTSM Control Module Manual (???) for synchronization module wiring diagram. GTSM Manual can be obtained at www.Pottersignal.com/fire or call Potter Technical Support 1866-956-1211

Architect and Engineering Specifications The alarm horns shall be Potter model LFH. The appliance shall be listed with Underwriters Laboratories (ANSI/UL) for use with fire protective
signaling systems (ANSI/UL 464) and with CAN/ULC S525 with intended use in fire alarm systems. The LFH will produce a peak sound output of 88.3 dBA as measured in an anechoic chamber. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage of 16-33 volts with either direct current or full wave rectified power at 24 VDC. The appliance shall be capable of testing supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box.