INTRODUCTION

The Potter Electric Model CS-24, CHS-24, CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, CCS-24G, CCHS-24G, CCS-24R, CCHS-24R strobe and horn/strobe, is a high quality visible or
audible/visible signaling appliance intended for ceiling applications. The high intensity strobe utilizes a Xenon flash tube that generates a high- intensity flash visible from all angles. This appliance
is intended to provide a visible or audible/visible, depending on the model, notification signal for the purpose of life safety and property protection. This appliance is ideal for any occupancy that
requires notification appliances per the applicable building or fire code or wherever dependable alarms are required. The CS-24 and CHS-24 strobe is listed in compliance with ANSI/UL 1971,
Signaling Appliances for the Hearing Impaired. The CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, CCS-24G, CCHS-24G, CCS-24R, CCHS-24R strobe is listed in compliance with ANSI/UL 1638,
Visual Signaling Appliances – Private Mode Emergency and General Signaling.

LOCATION

This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA
documents that provide standards on notification appliances for protective signaling systems. The CS-24, CHS-24, CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, CCS-24G, CCHS-24G, CCS-24R,
CCHS-24R is intended for indoor installations only. This appliance is not listed for outdoor or drip proof applications. Spacing for the CS-24 and CHS-24 shall be in accordance with Table A. If a
room configuration is not square, the room size that will entirely encompass the room or subdivide the room into multiple squares shall be used.

MOUNTING, ROUGH-IN BOX AND RUN WIRING

This unit is designed for mounting to most single gang boxes, 4″ square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes. Conduit entrance to boxes should be selected to
insure sufficient wiring clearance.

  1. Run a minimum 18 gauge insulated 2 or more conductor cable.
  2. Mount a box for each remote signaling appliance. Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block receptacle. Insert mounting screw as
    shown and tighten. Cover assembly with the plastic housing.

NOTICE: WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL. INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. IF TWO POWER RUNS ARE MADE TO THE SIGNAL, ONE FOR THE STROBE AND ONE FOR THE HORN, ONLY ONE OF THE RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS. A BARRIER IS PROVIDED TO PREVENT BOTH LEADS FROM BEING PLACED UNDER THE SAME TERMINAL.

CS-24 AND CHS-24 PRODUCT INFORMATION

Room Spacing for Ceiling-Mounted Visible Appliances per NFPA 72, 2013 Edition

 | Minimum Required Light Output (Effective Intensity, Cd; One Light)
Maximum Room Size| Maximum Ceiling Height
Meters| Feet| 10 Foot Ceiling| 20 Foot Ceiling| 30 Foot Ceiling
6.10 x 6.10| 20 x 20| 15| 30| 55
9.14 x 9.14| 30 x 30| 30| 45| 75
13.4 x 13.4| 44 x 44| 75| 75| NA
15.2 x 15.2| 50 x 50| NA| NA| 95

POTTER CCS-24A Selectable Candela Ceiling Strobe and Horn-Strobe
\(1\)

CAUTION: Strobe light must be installed within 16 feet of the pillow when used in a sleeping area.

POTTER CCS-24A Selectable Candela Ceiling Strobe and Horn-Strobe
\(2\)

NOTICE: THE VISUAL SIGNAL MUST BE IN THE DIRECT VIEWING AREA OF THE OCCUPANT IN ORDER TO BE SEEN. Strobe light can not be seen when objects such as doors, furniture or walls block strobe light.

NOTICE: VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED. VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.

NOTICE: THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE WILL NOT BE EFFECTIVE.

CLEAR Lens Strobe Current Ratings

Use with CS-24 & CHS-24 Products
Candela| Regulated 24VDC Max. Operating Current (mA)| Regulated 24VFWR Max. Operating Current (mA)| 24VDC Nominal Operating Current (mA)
15| 120| 190| 97
30| 120| 191| 97
75| 200| 277| 143
95| 220| 298| 148
115| 290| 418| 201
150| 321| 427| 205

NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, CCS-24G, CCHS-24G, CCS-24R AND CCHS- 24R PRODUCT INFORMATION

POTTER CCS-24A Selectable Candela Ceiling Strobe and Horn-Strobe
\(3\)

AMBER, BLUE & GREEN Lens Strobe Current Ratings

Use with CCS-24A, CCHS-24A, CCS-24B, CCHS-24B,

CCS-24G and CCHS-24G Products

Candela| Regulated 24VDC Max. Operating Current (mA)| Regulated 24VFWR Max. Operating Current (mA)
15| 124| 192
30| 124| 192
75| 139| 219
95| 205| 286
115| 212| 290

NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

Models Color Lens
CCS-24A & CCHS-24A Amber
CCS-24B & CCHS-24B Blue
CCS-24G & CCHS-24G Green
CCS-24R & CCHS-24R Red

RED Lens Strobe Current Ratings

Use with CCS-24R and CCHS-24R Products
Candela| Regulated 24VDC Max. Operating Current (mA)| Regulated 24VFWR Max. Operating Current (mA)
15| 124| 192
30| 124| 192
75| 212| 290
95| 283| 394
115| 313| 414

NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION

 | Horn Decibel Levels: Reverberant Room| Horn Current Ratings| 24VDC Nominal Horn Current Rating
---|---|---|---

Horn Mode

| Minimum SPL @ 10Ft. Per ANSI/UL 464 (HIGH)| Minimum SPL @ 10Ft. Per ANSI/UL 464 (LOW)| Regulated 24VDC Max. Operating Current (mA) HIGH Setting| Regulated 24VFWR Max. Operating Current (mA) HIGH Setting| 24VDC

Operating Current (mA) HIGH Setting

| 24VFWR

Operating Current (mA) HIGH Setting

Temp 3 2400Hz| 83 dBA| 75 dBA| 23| 45| 10.8| 26.6
Temp 3 Mechanical| 81 dBA| 73* dBA| 22| 43| 9.3| 24.4
Continuous 2400Hz| 86 dBA| 78 dBA| 23| 45| 20.7| 24.9
Continuous Mechanical| 84 dBA| 76 dBA| 22| 43| 16.5| 38.3

WIRING Wiring for synchronized strobes and horns.

Using this method you may:

  • Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place switches 1 and 2 in
    the ON position on the CHS-24, CCHS-24A, CCHS-24B, CCHS-24G, CCHS-24R).

  • Mute the horn only when the temporal horn option has been selected.

  • Use the Potter Electric AVSM synchronization protocol to provide synchronization and mute the horn, if available.

Wiring for synchronized parallel (unison) horn/strobe operation.

POTTER CCS-24A Selectable Candela Ceiling Strobe and Horn-Strobe
\(4\)

Using this method you may:

  • Use four wires where two wires are used to power and synchronize the strobe and two additional wires are used to power and synchronize the horn (place switches 1 and 2 in the OFF position on the CHS-24, CCHS-24A, CCHS-24B, CCHS-24G, CCHS-24R).
  • Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Potter Electric AVSM synchronization protocol.
  • Use the Potter Electric AVSM synchronization protocol to provide synchronization and mute the horn, if available.

NOTICE: FOR THIS OPTION, SWITCHES 1 AND 2 ON THE CHS-24, CCHS-24A, CCHS- 24B, CCHS-24G, CCHS-24R MUST BE IN THE OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE PORTION OF THE CIRCUIT.

ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE. THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN. REFERENCE AVSM CONTROL MODULE MANUAL (550-0598, dated 2-1-13) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN BE OBTAINED BY CALLING POTTER ELECTRIC SIGNAL COMPANY AT 1-800-325-3936.

Conventional Method: You may connect both the strobe and the horn directly from a source of rated power without the use of a control module. However, the horns and strobe lights will NOT be synchronized. Place switches 1 and 2 in the ON position on the CHS-24, CCHS-24A, CCHS-24B, CCHS-24G, CCHS- 24R to power both the audible and visible from a single pair of power wires. If you wish to power the horn and strobe from independent sources of power, place switches 1 and 2 in the OFF position on the CHS-24, CCHS-24A, CCHS-24B, CCHS-24G, CCHS-24R and connect power to the appropriate terminals.

POTTER CCS-24A Selectable Candela Ceiling Strobe and Horn-Strobe
\(5\)

Instant Voltage Verification

It is often necessary to confirm the voltage drop along a line of devices. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations.

NOTICE: CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES.

PRODUCT INFORMATION

This appliance is intended to provide a visible or audible/visible, depending on the model, notification signal for the purpose of life safety and property protection. This appliance is listed in compliance with CAN/ULC S525 and/or CAN/ULC S526. This appliance is intended for use in fire alarm systems and is to be installed in accordance with this manual, the National Building Code of Canada, CAN/ULC S524 and local codes that provide standards on notification appliances for protective signaling systems. Potter Electric recommends spacing notification appliances in compliance with CAN/ULC S524.

This unit is designed for mounting to most single gang boxes, 4″ square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes. Conduit entrance to boxes should be selected to
insure sufficient wiring clearance.

  1. Wiring is to be in accordance with CSA C22.1 Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations, Sec. 32
  2. Run a minimum 18 gauge insulated 2 or more conductor cable.
  3. Mount a box for each remote signaling appliance. Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block receptacle. Insert mounting screw as
    shown and tighten. Cover assembly with the plastic housing.

 | Horn Current Ratings| 24VDC Nominal Horn Current Rating|
---|---|---|---

Horn Mode

| Regulated 24VDC Max. Operating Current (mA) HIGH Setting| Regulated 24VFWR Max. Operating Current (mA) HIGH Setting| 24VDC

Operating Current (mA) HIGH Setting

| 24VFWR

Operating Current (mA) HIGH Setting

Temp 3 2400Hz| 23| 45| 10.8| 26.6
Temp 3 Mechanical| 22| 43| 9.3| 24.4
Continuous 2400Hz| 23| 45| 20.7| 24.9
Continuous Mechanical| 22| 43| 16.5| 38.3
HORN DECIBEL RATINGS IN ULC ANECHOIC ROOM (dBA @ 3 meters)
Horn Mode| Regulated 24 VDC Max. SPL Rating| Regulated 24 VFWR Max. SPL Rating| 24 VDC Nominal SPL Rating| 24 VFWR Nominal SPL Rating
Temp 3 2400Hz (HIGH)| 91.5| 92.7| 94.2| 95.2
Temp 3 2400Hz (LOW)| 83.1| 85.4| 86.5| 88.5
Temp 3 Mechanical (HIGH)| 90.8| 93.2| 93.9| 96.0
Temp 3 Mechanical (LOW)| 83.3| 86.2| 86.9| 89.3
Continuous 2400Hz (HIGH)| 91.1| 93.0| 94.0| 95.7
Continuous 2400Hz (LOW)| 83.1| 85.5| 86.7| 88.9
Continuous Mechanical (HIGH)| 90.8| 93.2| 93.8| 95.7
Continuous Mechanical (LOW)| 83.5| 86.1| 86.8| 89.4
Directional Sound Characteristic

 | Horizontal Angle
-3 dBA| v
-6 dBA| v
 | Vertical Angle
-3 dBA| 65
-6 dBA| v

NOTICE:

  • THE NATIONAL BUILDING CODE AND CAN/ULC S525 REQUIRES THAT ALL HORNS USED FOR BUILDING EVACUATION PRODUCE TEMPORAL CODED SIGNALS.
  • THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT
  • RATING. UNITS HAVE BEEN TESTED TO 0°C, 49°C AND 93% HUMIDITY.

LIMITED WARRANTY

For a period of 60 months from the date of manufacture (or as long as required by applicable law), Potter Electrical Signal Company, LLC warrants to you the original purchaser that your appliance will be free from defects in workmanship and materials under normal use and service. This warranty does not apply and is void if damage or failure is caused by: accident, abuse, misuse, abnormal use, faulty installation, liquid contact, fire, earthquake or other external cause; operating the appliance outside Potter Electrical Signal Company, LLC’s published guidelines; or service, alteration, maintenance or repairs performed by anyone other than Potter Electrical Signal Company, LLC. This warranty also does not apply to: consumable parts, such as batteries; cosmetic damage, including but not limited to scratches or dents; defects caused by normal wear and tear or otherwise due to the normal aging of the appliance, or if any serial number has been removed or defaced from the appliance.

TO THE EXTENT PERMITTED BY LAW, THIS WARRANTY AND THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, REMEDIES AND CONDITIONS, WHETHER ORAL, WRITTEN, STATUTORY, EXPRESS OR IMPLIED. POTTER ELECTRICAL SIGNAL COMPANY, LLC DISCLAIMS ALL STATUTORY AND IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND WARRANTIES AGAINST HIDDEN OR LATENT DEFECTS TO THE EXTENT PERMITTED BY LAW. TO THE EXTENT SUCH WARRANTIES CANNOT BE DISCLAIMED, SUCH IMPLIED WARRANTIES SHALL APPLY ONLY FOR THE WARRANTY PERIOD SPECIFIED ABOVE. PLEASE NOTE THAT SOME STATES (COUNTRIES AND PROVINCES) DO NOT ALLOW LIMITATION ON HOW LONG AN IMPLIED WARRANTY (OR CONDITION) LASTS. SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU. EXCEPT AS PROVIDED IN THIS WARRANTY AND TO THE EXTENT PERMITTED BY LAW, POTTER ELECTRICAL SIGNAL COMPANY, LLC WILL NOT BE LIABLE FOR ANY DIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM ANY BREACH OF WARRANTY OR CONDITION, OR ARISING IN CONNECTION WITH THE SALE, USE OR REPAIR OF THE APPLIANCE, OR UNDER ANY OTHER LEGAL THEORY, INCLUDING BUT NOT LIMITED TO LOSS OF USE, LOSS OF REVENUE, LOSS OF ACTUAL OR ANTICIPATED PROFITS, LOSS OF THE USE OF MONEY, LOSS OF BUSINESS, LOSS OF OPPORTUNITY, LOSS OF GOODWILL, AND LOSS OF REPUTATION. THE MAXIMUM LIABILITY OF POTTER ELECTRICAL SIGNAL COMPANY, LLC SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE. PLEASE NOTE THAT SOME STATES (COUNTRIES AND PROVINCES) DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU.

If a defect in workmanship or materials causes your appliance to become inoperable within the warranty period, you must return the appliance to Potter Electrical Signal Company, LLC postage prepaid to: Potter Electrical Signal Company, LLC, 1609 Park 370, Hazelwood MO 63042. You must prove to the satisfaction of Potter Electrical Signal Company, LLC the date of purchase of your appliance. You must also enclose a return address. Warranty service may only be performed by Potter Electrical Signal Company, LLC personnel at Potter Electrical Signal Company, LLC’s facilities in Hazelwood, Missouri. You must also pack the appliance to minimize the risk of it being damaged in transit. If we receive an appliance in a damaged condition as the result of shipping, we will notify you and you must seek a claim with the shipper.

If you submit a valid claim to Potter Electrical Signal Company, LLC during the warranty period, Potter Electrical Signal Company, LLC will, at its option, repair your appliance or furnish you with a
new or rebuilt appliance without charge to you except for postage required to return the appliance to us. Potter Electrical Signal Company, LLC will not reimburse you for repairs or replacement
parts provided by other parties. Your repaired or replacement appliance will be returned to you free of charge and it will be covered under the warranty for the balance of the warranty period, if any.
When a product or part is replaced, any replacement item becomes your property and the replaced item becomes property of Potter Electrical Signal Company, LLC. For additional warranty and
product information go to www.pottersignal.com.

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE (OR BY COUNTRY OR PROVINCE). BY THIS WARRANTY, POTTER ELECTRICAL SIGNAL COMPANY, LLC DOES NOT LIMIT OR EXCLUDE YOUR RIGHTS EXCEPT AS ALLOWED BY LAW. TO FULLY UNDERSTAND YOUR RIGHTS, YOU SHOULD CONSULT THE LAWS OF YOUR COUNTRY, PROVINCE OR STATE.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals