POTTER PAM-1 Multi Voltage Relay Module Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PAM-1 Multi Voltage Relay Module
Features
- Single SPDT relay with LED
- Double-sided adhesive tape
- Mounting screw
- Six 12” “flying” leads 18 AWG
- 6 wire-nuts
Description
The PAM-1 Relay provides 10.0 A form “C” contacts. The relay may be energized by one of three input voltages: 24VDC, 24VAC, or 120VAC. The input voltages are polarity-sensitive and diodeprotected. PAM-1 Relays contain a red LED which indicates when the relay coil is energized.
The PAM-SD may be mounted by using the double-sided adhesive tape, the self- drilling screw, or loosely placed in an electrical backbox. PAM Relays are ideal for applications where remote relays are required for fire alarm control or status feedback. They are only suitable for use within UL864 applications and installed in accordance with NFPA 70® and NFPA 72® .
Installation
Technical Specifications
Ambient Temperature | 32°F to 120°F (0°C to 49°C) |
---|
Dimensions
| 1.50” (38mm) H x 1.20” (31mm) W x 0.77” (20mm) D
12” (304.8mm) 18 ga. wire leads
Contact Rating
| 10A at 120 VAC
7A at 24VDC
250 Microamps at 5VDC
Power Requirements| 20mA @ 24VDC, 50mA @ 24VAC and 120VAC
Relay| UL recognized SPDT
Ordering Information
Model | Description | Stock No. |
---|---|---|
PAM-1 | Multi-Voltage Relay Module | 1000262 |