POTTER PAM-1 Multi Voltage Relay Module Owner’s Manual

June 9, 2024
POTTER

POTTER PAL

POTTER PAM-1 Multi Voltage Relay Module

Features

  • Single SPDT relay with LED
  • Double-sided adhesive tape
  • Mounting screw
  • Six 12” “flying” leads 18 AWG
  • 6 wire-nuts

Description

The PAM-1 Relay provides 10.0 A form “C” contacts. The relay may be energized by one of three input voltages: 24VDC, 24VAC, or 120VAC. The input voltages are polarity-sensitive and diodeprotected. PAM-1 Relays contain a red LED which indicates when the relay coil is energized.

The PAM-SD may be mounted by using the double-sided adhesive tape, the self- drilling screw, or loosely placed in an electrical backbox. PAM Relays are ideal for applications where remote relays are required for fire alarm control or status feedback. They are only suitable for use within UL864 applications and installed in accordance with NFPA 70® and NFPA 72® .

Installation

Technical Specifications

Ambient Temperature 32°F to 120°F (0°C to 49°C)

Dimensions

| 1.50” (38mm) H x 1.20” (31mm) W x 0.77” (20mm) D

12” (304.8mm) 18 ga. wire leads

Contact Rating

| 10A at 120 VAC

7A at 24VDC

250 Microamps at 5VDC

Power Requirements| 20mA @ 24VDC, 50mA @ 24VAC and 120VAC
Relay| UL recognized SPDT

Ordering Information

Model Description Stock No.
PAM-1 Multi-Voltage Relay Module 1000262