POTTER PAD100-LFSB Addressable Sounder Base Owner’s Manual

June 9, 2024
POTTER

POTTER PAD100-LFSB Addressable Sounder Base Owner’s Manual

1. Description

This document provides instructions for mounting and wiring the detector bases
PAD100-LFSB and PAD100-SPKB. The following detectors are compatible with detector bases PAD100-LFSB and PAD100-SPKB.

  • PAD200-PD & PAD100-PD: Photoelectric Smoke Detector
  • PAD200-PHD & PAD100-PHD: Photoelectric Smoke / Heat Detector
  • PAD200-PCD: Photoelectric Smoke / CO Detector
  • PAD200-PCHD: Photoelectric Smoke / CO Detector/ Heat Detector
  • PAD100-HD: Heat Detector
  •  PAD100-CD: Carbon Monoxide Detector 2a. Field Wiring Diagram for PAD100-LFSB
    Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 1). The SLC supports NFPA wiring Class B, A and X. (FIGURE 1) Typical of NFPA Class B SLC (S+, S-)
    Wiring using the PAD100-LFSB base. In Class A arrangement two separate conductors would return from the last detector base to a listed compatible Fire Alarm Control Panel (FACP)

Class X Wiring (FIGURE 2), requires use of PAD100-IM (Addressable Isolator Module).
The typical field diagram is in Field Wiring Diagram(s) for PAD100-IM. The PAD100-IM manual can be obtained at www.pottersignal.com

FIGURE 1: Wiring (Class B) Using PAD100-LFSB

Class X Wiring (FIGURE 2), requires use of PAD100-IM (Addressable Isolator Module).
The typical field diagram is in Field Wiring Diagram(s) for PAD100-IM. The PAD100-IM manual can be obtained at www.pottersignal.com

FIGURE 2: Wiring (Class X) Using PAD100-LFSB and PAD100-IM

2b. Field Wiring Diagram for PAD100-SPKB

Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 4). The SLC supports NFPA wiring Class B, A and X. The PAD100-SPKB offer a choice of field selectable power taps: 1/8, 1/4, 1/2, 1, 2 and 4 watts (FIGURE 5) for use with either 25 VRMs or 70.7 VRMs audio amplifiers. The frequency range of the PAD100-SPKB is
400-4000 Hz. The PAD100-SPKB is suitable for line supervision. The PAD100-SPKB includes DC blocking capacitor which allows for supervision voltage of either polarity.

FIGURE 4: PAD100-SPKB Wiring Diagram

FIGURE 5: PAD100-SPKB Wiring and Power Tap

Wiring Instruction

  • To ensure proper installation of the detector head to the base, wires shall be dressed properly at the time of installation
  • When using PAD100-SPKB / PAD100-LFSB base, observe the correct polarity of SLC

NOTICE:

  • THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF ARTICLE 3(B) OF THE NATIONAL ELECTRICAL CODE, NFPA 70, AS WELL AS ARTICLE 210.
  • THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION STANDARD
  • DO NOT USE LOOPED WIRE UNDER BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTION.

CAUTION!

  • Break wire runs to provide supervision for connections made to each wire
  • When installing, route field wiring away from sharp projections, corners and internal

Detector Base Mounting

PAD100-LFSB / PAD100-SPKB should be mounted directly on the electrical box (FIG- URE 6a) or to the LFSBBB-W back box (FIGURE 6b). The PAD100-LFSB / PAD100-SPKB
mounting holes are configured for a 4” x 2-1/8” deep square box. Use a box for each base and run the power circuit to all base locations.
Use 12 to 18 AWG conductors to connect to terminals of bases. It is recommended that the SLC conductors be color-coded to avoid wiring errors and
assist in system troubleshooting. Improper SLC connections may prevent the system from operating normally. Disconnect power to the SLC until the detectors are installed.

  1. Wire the detector bases according to Field Wiring
  2. Use the dip switches (SECTION 11) to set address(es) (1 – 127) for each detector

NOTICE:

  • THE PAD100-LFSB /PAD100-SPKB OBTAINS THE ADDRESS FROM THE DETECTOR
  • THE DETECTORS AND THE PAD100 MODULES MUST HAVE INDIVIDUAL ADDRESS(ES).
  1. To install the detector head onto the base, match the detector heads to the base using the alignment feature and twist clockwise until the detector heads snap into place (FIGURE 6a).

FIGURE 6a: Assembly of Detector on Electrical Box

FIGURE 6b: Assembly of Detector on LFSBBB-W Back Box

4. After all detector heads, addressable bases and modules have been installed, apply power to the FACP.
5. Test the detectors as described in the Testing Section of this manual.

NOTICE: DO NOT INSTALL DETECTOR HEADS UNTIL AREA HAS BEEN THOROUGHLY
CLEANED TO REMOVE CONSTRUCTION DEBRIS, DUST, ETC., AS REQUIRED BY NFPA

4. Spacing Limitations

NOTICE: REFER TO NFPA 72 FOR SPECIFIC INFORMATION REGARDING DETECTOR SPACING, MOUNTING LOCATION AND SPECIAL APPLICATIONS.
PAD100-PD, PAD200-PD, PAD100-PHD, PAD200-PCD, PAD200-PCHD and PAD200-PHD: Photoelectric Smoke Detector PAD100-PD, PAD200-PD, PAD200-PCD, PAD200-PCHD, PAD100-PHD and PAD200- PHD are ANSI/UL listed on maximum 30ft spacing limitation with alarm set point from 135O-174O F on smooth ceiling. Refer to NFPA 72 for specific informationregarding detector spacing, placement and special applications. PAD100-HD: Heat Detector
The ANSI/UL listed spacing limitations of PAD100-HD smooth ceiling are dependent on alarm set point.

6.  Locking Feature

The PAD100-PD, PAD200-PD, PAD100-PHD, PAD200-PHD, PAD200-PCD, PAD200-
PCHD, PAD100-HD and PAD100-CD include a tamperproof feature that locks the detector and does not allow removal without the use of a tool.

  1. Once the detector has been installed the detector locks into the base. To remove the detector from the base, insert a small screwdriver into the slot on the detector (FIGURE 11) and push the plastic tab while simultaneously turning the detector head counter-clockwise.

  2. The locking feature can be To disable the locking feature, break off the locking tab before installation (FIGURE 12).

8. Detector Base Options

Model Description
PAD100-6DB 6 inch detector base. See manual number: 550-0622-000
PAD100-4DB 4 inch detector base. See manual number: 550-0622-000
PAD100-IB 6 inch detector base with short circuit isolator. See manual

number: 550-0671-000
PAD100-RB| 6 inch detector base with relay module. See manual number: 550-0671-000
PAD100-SB| 6 inch detector base with sounder module. See manual number: 550-0671-000
PAD100-LFSB| 6 inch detector base with low frequency sounder module
PAD100-SPKB| 6 inch detector base with speaker module

!9  WARNING

  • Detector will not operate without electrical power. Fire can cause power interruption, discuss with a fire protection specialist for additional safeguards.

  • Do not open PAD100-PHD, PAD200-PHD, PAD100-HD, PAD200-PCD, PAD200- PCHD or PAD100-CD detector for cleaning. If the detector is opened, product warranty becomes

  •  If the detector does not work properly, do not try and fix it yourself. This will void your warranty. For technical assistance, contact Potter Electric Signal Company at 866-956-1211 for instructions to return a detector that does not operate properly

  • Detector will not sense fires that start in areas where smoke or heat cannot reach the detector. Smoke or heat from fires in walls, roofs or on the opposite side of closed doors may not reach the

  • Keep supplied dust cover in place during installation and construction. Remove dust cover prior to operation.

  • Dust cover is not a substitute for removal of detector during new construction or

  •  The detector cannot detect smoke when the dust cover is in place.

  • Never use an open flame of any kind to test your You may ignite and damage the detector.

  • Do not cover, tape or otherwise block the openings of your detector.
    The openings are designed to allow air to pass through the detector, thus sampling the air around the detector.

  •  DO NOT stand close to the device when the alarm is sounding. Exposure at close range could result in hearing damage.

  • Detectors are not to be used with detector guards unless the combination has been evaluated by a nationally recognized testing laboratory and found suitable for that

  •  To ensure proper operation, store detector within the recommended ranges. Allow the detector to stabilize to room temperature before applying power.

  • If the detector ever fails to test properly, replace it Products under warranty may be returned to the manufacturer for replacement, see LIMITED WARRANTY.

  • For technical assistance, contact Potter Electrical Signal Company at 1-866-956-1211

10a. Specifications / Ratings for Use with Detectors: PAD100-PD,

PAD200-PD, PAD200-PCD, PAD200-PCHD, PAD100-PHD and PAD200-PHD

No.| Item| PAD100-PD| PAD100-PHD| PAD200-PCD| PAD200-PCHD| PAD200-PD| PAD200-PHD
---|---|---|---|---|---|---|---
1| Working Voltage Range| 24 VDC
2| Standby Current (*)| 300 µA
3| Alarm Indicator| 1 LED
4| Alarm Indictor Current| 1.4 mA


5

| ****

Smoke Sensitivity Range (**)

| ****

1.0-3.7 %/ft.

(3.2-11.6%/m)

| 1.0-3.7 %/ft.

(3.2-11.6%/m) / 135O to 174OF (57O to 79O C)

| ****

1.1-3.5 %/ft.

(3.6-11%/m)

| 1.1-3.5 %/ft.

(3.6-11%/m) / 135O to 174OF (57O to 79O C)

| ****

1.1-3.5 %/ft.

(3.6-11%/m)

| 1.1-3.5 %/ft.

(3.6-11%/m) / 135O to 174OF (57O to 79O C)

6| Installation Temperature Range| 32O to 120O F (0O to 49O C)| 32O to 115O F (0O to 46O C)| 32O to 120O F (0O to 49O C)| 32O to 115O F (0O to 46O C)| 32O to 120O F (0O to 49O C)| 32O to 115O F (0O to 46O C)
7| Operating Relative Humidity Range| 0% to 93% (non-condensing)
8| Start-up Time| 1 second
9| Maximum Number of Addresses per SLC Loop| 127
10| Maximum Number of Lighted Indicators in Alarm per SLC Loop| 30
11| Weight (without base)| 110.5 g (3.9 oz)| 116 g (4.1 oz)| 113 g (4.0 oz)| 118.5 g (4.2 oz)| 110.5 g (3.9 oz)| 116 g (4.1 oz)


12

| Dimensions (without base)| Height| 1.35 in (34 mm)| 1.94 in (49 mm)| 1.35 in (34 mm)| 1.94 in (49 mm)| 1.35 in (34 mm)| 1.94 in (49 mm)
Diameter| 3.93 in. (100 mm)



13

| ****


Approvals / Listings

| ****

ANSI/UL 268 6th

edition

| ****

ANSI/UL 268 6th

edition, ANSI/UL 521 7th

edition

| ****

ANSI/UL 268 7th

edition,

ANSI/UL 2075 4th

edition

| ANSI/UL 268 7th

edition, ANSI/UL 521 7th

edition, ANSI/UL 2075 4th edition

| ****

ANSI/UL 268 7th

edition

| ****

ANSI/UL 268 7th

edition, ANSI/UL 521 7th

edition

14| Permitted Mounting Location(s)| Ceiling, Wall

10b. Specifications / Ratings **for Use with Detectors:

PAD100-CD , PAD100-HD**

No. Item PAD100-HD PAD100-CD
1 Working Voltage Range 24 VDC
2 Standby Current (*) 300 µA
3 Alarm Indicator 1 LED
4 Alarm Indictor Current 1.4 mA
5 Alarm Set-Point Range (**) 135O to 174O F (57O to 79O C) 175O to 185O F
(80O to 85O C) 135O to 160O F (57O to 71O C) Fixed 70, 150, 400 PPM
6 Installation Temperature Range 32O to 100O F (0O to 38O C) 32O to 150O F
(0O to 66O C) 32O to 100O F (0O to 38O C) 32O to 100O F (0O to 38O C)
7 Operating Relative Humidity Range 0% to 93% (non-condensing)
8 Start-up Time 1 second
9 Maximum Number of Addresses per SLC Loop 127
10 Maximum Number of Lighted Indicators in Alarm per SLC Loop 30
11 Weight (without base) 82 g (2.89 oz) 92 g (3.25 oz)

12

| Dimensions (without base)| Height| 1.94 in (49 mm)| 1.43 in (36 mm)
Diameter| 3.93 in. (100 mm)
13| Approvals / Listings| ANSI/UL 521| ANSI/UL 2075
14| Permitted Mounting Location(s)| Ceiling, Wall

  • The standby current is the current that the device consumes when the device is in a non-activated condition and where no communication current is transmitted to the

**  Reference spacing requirements in Section 4.

No. Item PAD100-SPKB
1 Working Voltage Range for SLC 24 VDC
2 Standby / Alarm Current for SLC (*) 150 µA
3 Active Current (Including Indicator) 3.8 mA
4 Working Voltage for SPK 25 Volts, 70.7 Volts
5 Power Tap Selection for SPK 1/8 Watt , 1/4 Watt, 1/2 Watt, 1 Watt, 2 Watt,

4 Watt
6| Applicable SLC Wiring Style| Class B, Class A, Class X
7| Maximum Number of PAD100-SPKB per SLC Loop| 127
8| Installation Temperature Range| 32O to 150O F (0O to 66O C)
9| Operating Relative Humidity Range| 0% – 93% (non-condensing)
10| Weight (without detector head)| 460 g (16.23 oz)


11

| Dimensions (without detector head)| Height| 2.75 in (70 mm)
Diameter| 6 in x 6 in (153 mm X 153 mm)
12| Approvals / Listings| ANSI/UL 268 and ANSI/UL 1480

  • * To select the proper wattage input for the speaker, move the jumper to the appropriate
    • Always maintain electrical isolation between speaker and strobe wiring on combination
    • The PAD100-SPKB in conjunction with the EVAX EVX-100 amplifier has been tested with and complies with the Low Frequency Signal Form (520 Hz) requirements in ANSI/UL 464 and ANSI/UL
    • Do not exceed 130% of rated speaker If excessive distortion is heard, check amplifier for signal clipping. If clipping exists, reduce either amplifier input or gain.The standby current is the current that the device consumes when the device is in a non-activated condition and where no communication current is transmitted to the FACP
      PAD100-SPKB Field Selectable Power Tap Selection – Reverberant (dBA @ 10ft.)

      Voltage| 1/8 Watt| 1/4 Watt| 1/2 Watt| 1 Watt| 2 Watt| 4 Watt
      25 Volts| 75.0 dBA| 78.1 dBA| 81.2 dBA| 83.8 dBA| 86.6 dBA| 89.7 dBA
      70.7 Volts| 75.1 dBA| 78.1 dBA| 80.9 dBA| 83.8 dBA| 86.9 dBA| 89.6 dBA

SYSTEM CONSIDERATIONS

11. PAD Protocol Dip Switch Settings

The following information is for setting the dipswitches on the PAD100-PD, PAD200-PD, PAD100-PHD, PAD200-PHD, PAD200-PCD, PAD200-PCHD, PAD100-HD and PAD100-CD detectors and modules.
Setting the Address: All PAD protocol detectors and modules require an address prior to connection to the panel’s SLC loop. Each PAD device’s address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1-127 (FIGURE 15). The below examples (FIGURE 13 and FIGURE 14) illustrate a PAD device’s dip switch settings. The first example (FIGURE 13) illustrates a device not addressed where all dip switch settings are in the default OFF position. The second example (FIGURE 14) illustrates an addressed PAD device via the dip switch settings.

NOTE: Each gray box indicates that the dip switch is ON and each white box indicates the dip switch is OFF.
FIGURE 15: PAD Device Dip Switch Addresses Table (Addresses 1-127)

LIMITED WARRANTY

For a period of 60 months from the date of manufacture (or as long as required by applicable law), Potter Electric Signal Company, LLC warrants to you the original purchaser that the appliance described in this product information booklet will be free from defects in workmanship and materials under normal use and service.
This warranty does not apply and is void if damage or failure is caused by: accident, abuse, misuse, abnormal use, faulty installation, liquid contact, fire, earthquake or other external cause; operating the appliance outside Potter Electric Signal Company, LLC’s published guidelines; or service, alteration, maintenance or repairs performed by anyone other than Potter Electric Signal Company, LLC. This warranty does not transfer to subsequent owners or purchasers of this appliance. This warranty also does not apply to: consumable parts, such as batteries; cosmetic damage, including but not limited to scratches or dents; defects caused by normal wear and tear or otherwise due to the normal aging of the appliance, or if any serial number has been removed or defaced from the appliance.

TO THE EXTENT PERMITTED BY LAW, THIS WARRANTY AND THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, REMEDIES AND CONDITIONS, WHETHER ORAL, WRITTEN, STATUTORY, EXPRESS OR IMPLIED. POTTER ELECTRIC SIGNAL COMPANY, LLC DISCLAIMS ALL STATUTORY AND IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND WARRANTIES AGAINST HIDDEN OR LATENT DEFECTS TO THE EXTENT PERMITTED BY LAW. TO THE EXTENT SUCH WARRANTIES CANNOT BE DISCLAIMED, AND TO THE EXTENT PERMITTED BY APPLICABLE LAW, SUCH IMPLIED WARRANTIES SHALL APPLY ONLY FOR THE WARRANTY PERIOD SPECIFIED ABOVE. PLEASE NOTE THAT SOME STATES (COUNTRIES AND PROVINCES/TERRITORIES) DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY (OR CONDITION) LASTS. SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU. EXCEPT AS PROVIDED IN THIS WARRANTY AND TO THE EXTENT PERMITTED BY LAW, POTTER ELECTRIC SIGNAL COMPANY, LLC WILL NOT BE LIABLE FOR ANY DIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM ANY BREACH OF WARRANTY OR CONDITION, OR ARISING IN CONNECTION WITH THE SALE, USE OR REPAIR OF THE APPLIANCE, OR UNDER ANY OTHER LEGAL THEORY, INCLUDING BUT NOT LIMITED TO LOSS OF USE, LOSS OF REVENUE, LOSS OF ACTUAL OR ANTICIPATED PROFITS, LOSS OF THE USE OF MONEY, LOSS OF BUSINESS, LOSS OF OPPORTUNITY, LOSS OF GOODWILL, AND LOSS OF REPUTATION. THE MAXIMUM LIABILITY OF POTTER ELECTRICAL SIGNAL COMPANY, LLC SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE. PLEASE NOTE THAT SOME STATES (COUNTRIES AND PROVINCES/TERRITORIES) DO NOT ALLOW THE EXCLUSION OR LIMITATION OF DIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU.

If a defect in workmanship or materials causes your appliance to become inoperable within the warranty period, you must return the appliance to Potter Electric Signal Company, LLC postage prepaid to: Potter Electric Signal Company, LLC, 1609 Park 370, Hazelwood MO 63042. You must prove to the satisfaction of Potter Electric Signal Company, LLC the date of purchase of your appliance. You must also enclose a return address. Warranty service may only be performed by Potter Electric Signal Company, LLC personnel at Potter Electric Signal Company, LLC’s facilities in Hazelwood, Missouri. You must also pack the appliance to minimize the risk of it being damaged in transit. If we receive an appliance in a damaged condition as the result of shipping, we will notify you and you must seek a claim with the shipper.

If you submit a valid claim to Potter Electric Signal Company, LLC during the warranty period, Potter Electric Signal Company, LLC will, at its option, repair your appliance or furnish you with a new or rebuilt appliance without charge to you except for postage required to return the appliance to us. Potter Electric Signal Company, LLC will not reimburse you for repairs or replacement parts provided by other parties. Your repaired or replacement appliance will be returned to you free of charge and it will be covered under the warranty for the balance of the warranty period, if any. When a product or part is replaced, any replacement item becomes your property and the replaced item becomes property of Potter Electric Signal Company, LLC. For additional warranty and product information go to www.pottersignal.com.

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE (OR BY COUNTRY OR PROVINCE/TERRITORY). BY THIS WARRANTY, POTTER ELECTRIC SIGNAL COMPANY, LLC DOES NOT LIMIT OR EXCLUDE YOUR RIGHTS EXCEPT AS ALLOWED BY LAW. TO FULLY UNDERSTAND YOUR RIGHTS, YOU SHOULD CONSULT THE LAWS OF YOUR COUNTRY, PROVINCE/TERRITORY OR STATE.

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals