**POTTER CA-6075 Class A Expander

**

Description

The CA-6075 is a Class A Expander. The CA-6075 allows for Class A wiring of the built in SLC circuit, P-Link communication bus and two (2) built in NAC circuits. The CA-6075 mounts to the provided framework in the fire alarm control panel. The Class A operation can be independently selected for the P-Link and SLC circuits using the Potter Fire Panel Programmer Software

Installation

Connection of the CA-6075 Class A Expander to the addressable control panel:

  1. Remove two (2) #6-32×7/8 screws (item #1 shown below) from the control panel and retain for use in step #3.
  2. Install 5050793 Bracket, inserting end tabs into slots on the control panel User Interface bracket.
  3. Secure 5050793 bracket to the control panel using the two (2) screws (item #1) that were removed in step #1.
  4. Slide the CA-6075 Class A Expander over the two (2) guide pins on the 5050793 bracket. Seat the CA-6075 on the 5050793 bracket so the connector on the back of the CA-6075 is fully engaged with the connector on the control panel.
  5. Secure the CA-6075 to the 5050793 bracket using two (2) #6- 32×1/4 screws provided (shown on page 2).

Technical Specifications

Standby Current 12 mA
Alarm Current 44 mA
Ambient Operating Temperature 32°F – 120°F (0°C – 49°C) 10%-93% @

30°C (86°F) non-condensing humidity

Maximum CA-6075 Expanders| 1
Compatible Panels| IPA-60, IPA-100

AFC-50, AFC-100, ARC-100

PFC-6030, PFC-6075, PFC-6200 PFC-6075R, P100, P200, P300*

*Legacy Product
Note:
Not for use with IPA-4000, AFC-1000, PFC-6800 and P400(R) control panels.

CA-6075 Class A Installation Diagram

Installed Class A Card

Ordering Information

Model Description Stock No.
CA-6075 Class A Expander 3006459

Read User Manual Online (PDF format)