POTTER CPS-24 Conventional Photoelectric Smoke Detector Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER CPS-24 Conventional Photoelectric Smoke Detector
Features
- Suitable for in-duct applications
- 360° view of detector status LED
- Low profile, 2” high (with base)
- 2 or 4 wire base compatibility, relay bases available
- Highly stable operation, RF/Transient protection
- Low standby current, 59μA at 24VDC
- One built-in power/sensitivity supervision/alarm LED
- Automatic Sensitivity window verification function meets outlined requirements in NFPA 72, Chapter 2 & 7, Inspection, Testing and Maintenance.
- Magnetic Test Feature
Description
The CPS-24 is a reliable, high quality Photoelectric Smoke Detector. It can be used in all open areas where Photoelectric Smoke Detectors are required, including in-duct applications. The computer-designed smoke chamber makes the CPS-24 well suited for detecting smoldering fires as well as fast-flaming fires.
Operation
The CPS-24 photoelectric smoke detector utilizes one bicolored LED for
indication of status. In a normal standby condition the LED flash Green every
3 seconds. When the detector senses that its sensitivity has drifted outside
the UL listed sensitivity window the LED will flash Red every 3 seconds. When
the detector senses smoke and goes into alarm the status LED will latch on Red
The detector utilizes an infrared LED light source and silicon photodiode
receiving element in the smoke chamber. In a normal standby condition, the
receiving element receives no light from the pulsing LED light source. In the
event of a fire, smoke enters the detector smoke chamber and light is
reflected from the smoke particles to the receiving element. The light
received is converted into an electronic signal.
Fire Judgement signals are processed and compared to a reference level, and
when five consecutive signals exceeding the reference level are received
within a specified period of time, the time delay circuit triggers the SCR
switch to activate the alarm signal. The status LED lights continuously during
the alarm period.
Technical Specifications
Light Source | GaAIAs Infrared Emitting Diode |
---|---|
Rated Voltage | 12 or 24 VDC |
Working Voltage | 8 – 35.0 VDC |
Maximum Voltage | 42 VDC |
Supervisory Current | 59μA @ 24 VDC |
Surge Current | 160μA max. @ 24VDC |
Alarm Current | 150mA max. @24 VDC |
Air Velocity Range | 0-4000 fpm |
ambient Temperature | 32°F to 120°F (0°C to 49°C) |
Sensitivity Test Feature | Automatic Sensitivity window verification test |
Mounting | Refer to Potter SB Series Smoke Detector Base series, bulletin no. |
Specifications
The contractor shall furnish and install where indicated on the plans, Potter
Electric Signal CPS-24 photoelectric smoke detectors. The combination detector
head and twist-lock base shall be UL listed compatible with a UL listed fire
alarm panel.
The base shall permit direct interchange with PotterCPS-24 photoelectric smoke
detector. The base shall be appropriate twist-lock base SB Series.
In the event of partial or complete retrofit, the CPS-24 may be used in
conjunction with, or as a replacement for, Potter detectors (PS-24, PS24H and
the IS-24) on most SB base applications.
The smoke detector shall have one flashing status LED for visual supervision.
When the detector icing standby condition the LED will flash Green. When the
detector is outside the UL listed sensitivity window the
LED will flash Red. When the detector is actuated, the flashing LED will latch
on Red. The detector may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured.
The sensitivity of the detector shall be monitored automatically and
continuously to verify that it is operating within the listed sensitivity
range. To facilitate installation, the detector shall be non-polarized.
Voltage and RF transient suppression techniques shall be employed to minimize
false alarm potential. Auxiliary SPDT relays shall be installed where
indicated.
CPS-24 Sensitivity Test Feature
The Potter CPS-24 Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
- In normal condition, the status LED flashes green.
- When the sensitivity drifts outside of its sensitivity limits, the status LED flashes red.
- In the alarm state, the status LED is red continuously.
- When the sensitivity drifts outside of its sensitivity limits and the status LED flashes red, the device needs to be cleaned or returned to the factory for cleaning or calibration.
Ordering Information
Model
| Description| Stock No.
---|---|---
CPS-24| Conventional Photoelectric Smoke Detector|
1430036