POTTER CM24W Wall Mount Chime Fire Alarm Owner’s Manual

June 9, 2024
POTTER

POTTER CM24W Wall Mount Chime Fire Alarm

CM24W Wall Mount Chime Fire Alarm

Introduction

  • Meets or exceeds NFPA/ANSI Standards

  • UL Listed for wall mounting

  • Screw terminal capacity up to AWG #12

  • Universal mounting plate included

  • Horn fi eld selectable tones:
    2700 Hz or 2400 Hz Temporal or Non-temporal High or low dBA output

  • Mounts to 4” square, single gang, double gang, or octagonal back box

  • Synchronization requires Sync Module (SMD10-3A)

  • Available in red or white housing

Amseco’s Select-A-Chime Series is designed to provide audible (private mode) for fi re alarm protection systems. It meets or exceeds NFPA/ ANSI audible emergency evacuation signal and UL 464 (private mode).
The CM24W provides a continuous tone or temporal pattern (code 3) tone when constant voltage from a FACP is applied. Each tone has two dBA level settings (high or low) that can be achieved with the use of mini-jumpers located on the back of the unit. The CM24W Series can be connected either independently or in unison. These appliances are polarized for connecting to supervised fi re alarm circuits.
The CM24W can by synchronized by using the SMD10-3A Sync Module.

Ordering Information

Model Number| Housing Color| Input Voltage| Operating Voltage Range| Horn Sound Output| Wiring Type| Mounting Type| Sync Module| Operating Temperature Range
---|---|---|---|---|---|---|---|---
CM24WR| Red| Regulated 24C DC/FWR| 16-33V DC 16-33V FWR| Selectable| Terminals| Wall| SMD10-3A|

32°F – 120°F (0°C – 49°C)

Engineering Specifi cations

The audible alarm indicating appliance shall be Amseco Model CM24W or equivalent device. The chime shall be listed under UL 464 standard for audible signaling appliance and shall be approved for fi re protective service. The sound output shall be field selectable. The chime shall provide two different field selectable temporal or steady tones, and a high and low field selectable sound output setting. The signaling chime shall operate on 24V DC from a non- coded, regulated DC supply or full-wave rectified, unfiltered supply. The chime shall have a universal back mounting plate, capable of wall mounting to a back box. When strobe synchronization is required, the chime shall be compatible with the Amseco SMD10-3A (daisy chain) or other source of Amseco sync protocol. Signaling devices shall be installed in accordance with current NFPA guidelines

Chime Only Current Draw Table

| PC3: Pattern
PC2: Tone PC1: Volume| Maximum RMS Operating Current (mA)|

Minimum Sound Output (dBA at 10 ft per UL 464)

---|---|---|---

Non-Temporal

|  | PC3| PC2| PC1| Regulated 24V DC| Regulated 24V FWR| Regulated 24V DC
2700 Hz|

HIGH

| 1| 1| 1| 45| 58|

66

LOW

| 1| 1| 0| 40| 52|

61

2400 Hz

| HIGH| 1| 0| 1| 44| 57| 54
LOW| 1| 0| 0| 40| 52|

50

Temporal

|

2700 Hz

| HIGH| 0| 1| 1| 45| 58| 65
LOW| 0| 1| 0| 40| 52|

60

2400 Hz

| HIGH| 0| 0| 1| 44| 57| 53
LOW| 0| 0| 0| 40| 52|

48

Dimensions: inches (mm)

Dimensions: inches \(mm\)

Wiring Diagram

Wiring Diagram
Wiring Diagram

Installation Options

Installation Options

Tone Selection

| PC3 Pattern| PC2 Tone|

PC1 Volume

---|---|---|---

Jumper

| | Non- Temporal| 2700 Hz| High
| Temporal| 2400 Hz|

Low

Customer Support

Potter Electric Signal Company
2081 Craig Road, St. Louis, MO, 63146-4161
Phone:800-325-3936/Canada 888-882-1833
www.pottersignal.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals