POTTER CS-24 Indoor Wall Mount Colored Lens Strobe and Horn/Strobe Series Owner’s Manual

June 9, 2024
POTTER

POTTER CS-24 Indoor Wall Mount Colored Lens Strobe and Horn/Strobe Series Owner’s Manual
POTTER CS-24 Indoor Wall Mount Colored Lens Strobe and Horn/Strobe
Series

Features

  • Tamperproof field selectable candela settings of 15, 30, 60, 75, and 110
  • Lens colors available in amber, blue, green, and red
  • Super-Slide® Bracket – Ease of supervision testing
  • Checkmate® – Instant voltage verification
  • Synchronize strobe and/or horn with AVSM module
  • Silence audible while visual appliance remains flashing (for use in accepted jusridictions)
  • Switch for chime, whoop, mechanical, and 2400Hz tone
  • Switch for continuous or temporal 3 tone (not available on whoop)
  • Tamperproof re-entrant grill
  • Product includes a 5 year warranty

Application

The CS/CHS Series Colored Lens Signals are wall mount, low profile strobes and horn/strobes that offer dependable audible and visual signals for warning and emergency notification. Applications include emergency communication, severe weather, emergency response and many more

Description

The CS/CHS Series Colored Lens Signals are 24VDC units available in lens colors of amber, blue, green, and red. The Series offers tamperproof field selectable options of 15, 30, 60, 75, and 110 candela.
They have a minimal operating current and a minimum flash rate of 1Hz, regardless of input voltage. The strobes can be synced using a Gentex sync protocol or the AVSM Sync Module.

The Colored Lens Series is shipped with a die-cast universal 4” mounting bracket which incorporates the popular Super-Slide® feature that allows the installer to easily pre-wire the system and test for supervision. The product also features a locking mechanism that  secures the signal to the bracket without showing any screws. The Colored Lens Series also features the Checkmate® – Instant Voltage Verification Feature which allows the installer to check the voltage drop, current draw, and match against the blue print.

Product Listings

  • ANSI/UL 464 and 1638
  • CSFM 7135-0328:0210 (CHS Series)
  • CSFM 7135-0328:0209 (CS Series)

Technical Specifications

Operating Voltage Nominal 24VDC (16-33VDC)
Environmental Limitations 32°F – 120°F (0° – 49°C)Indoor Only
Dimensions 5” H x 4.5” W x 2.5” D
Wiring Connections Terminals accept 18 – 12 AWG
Mounting Single gang, double gang, or 4” square backboxSurface mount with

AVBB
Shipping Weight| 1.05 lbs.
CS Series Colored Lens Strobe, Selectable Candela

Model Number| Stock Number| Lens Color| Body Color
CS-24WAR| 4890100| Amber| Red
CS-24WAW| 4890101| Amber| Off-White
CS-24WBR| 4890102| Blue| Red
CS-24WBW| 4890103| Blue| Off-White
CS-24WGR| 4890104| Green| Red
CS-24WGW| 4890105| Green| Off-White
CS-24WRR| 4890106| Red| Red
CS-24WRW| 4890107| Red| Off-White
Optional Bezels

Wording| Color| Stock Number
AGENT| Red| 4890262
AGENT| Off-White| 4890263
ALERT| Red| 4890264
ALERT| Off-White| 4890265

All CS/CHS Series devices are plain (no wording).
AGENT/ALERT bezels can be ordered separately

CHS Series Colored Lens Strobe, Selectable Candela

Model Number| Stock Number| Lens Color| Body Color| Reverberant dBA at 10’, per ANSI/UL 464| In Anechoic Room dBA at 10’
CHS-24AR| 4890120| Amber| Red| 62-82| 100
CHS-24AW| 4890121| Amber| Off-White| 62-82| 100
CHS-24BR| 4890122| Blue| Red| 62-82| 100
CHS-24BW| 4890123| Blue| Off-White| 62-82| 100
CHS-24GR| 4890124| Green| Red| 62-82| 100
CHS-24GW| 4890125| Green| Off-White| 62-82| 100
CHS-24RR| 4890126| Red| Red| 62-82| 100
CHS-24RW| 4890127| Red| Off-White| 62-82| 100
UL Max Strobe Current Ratings (24VDC Regulated)

Candela| Amber Lens| Blue, Gree, and Red Lens
15cd| 47mA| 105mA
30cd| 64mA| 130mA
60cd| 113mA| 203mA
75cd| 145mA| 243mA
110cd| 178mA| 310mA

For unfiltered FWR ratings, see installation manual.

Horn Decibel and Current Ratings

Horn Setting| MinimumdBA at 10’,Per UL 464 (HIGH)| MinimumdBA at 10’,Per UL 464 (LOW)| Regulated 24VDC Max. Operating Current, at High Setting (mA)
Temporal 3 2400Hz| 78| 71| 28
Temporal 3 Mechanical| 76| 70
| 25
Temporal 3 Chime| 70| 66| 15
Continuous 2400Hz| 81| 74| 28
Continuous Mechanical| 80| 72
| 25
Continuous Chime| 70| 66| 15
Whoop| 82| 69*| 56

*Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode).

Tone Switch Locations

Tone Switch Position
3 4
Mechanical Temporal 3 ON
Mechanical – Continuous OFF
2400Hz – Temporal 3 ON
2400Hz – Continuous OFF
Chime – Temporal 3 ON
Chime – Continuous OFF
Whoop ON
Whoop OFF

NOTES:

  • Switch Positions 1 and 2 in the OFF position to select isolated horn and strobe power inputs
  • Switch Position 6 ON = HIGH dBA
  • Switch Position 6 OFF = LOW dBA

Super Slide® Mounting Bracket

Allows the installer to pre-wire the system, test for system supervision, remove the signal head until occupancy, switch out signals without changing mounting brackets and has locking edge connector for snap-in-place installation.

Tone Switch Locations
Tone Switch Locations

Checkmate® Instant Voltage Verification

It is often necessary to confirm the voltage drop along the line of devices. The access holes are provided in the back of the terminal block to allow the voltage to  be measured directly without removing the device. Typically, this would be done at the end of the line to confirm design criteria. Most measurements will be taken  using the S+ and S- locations althoughaccess is provided to other locations.

NOTE: Care should be taken to not short the test probes.

To remove bezel, grip both sides of bezel and pull in a download and outward motion

Wiring Diagrams

Wiring Diagrams

NOTES:

  • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn.
  • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936

Architect and Engineering Specifications

The audible and/or visible signal shall be Potter Colored Lens Series or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSI/UL 1638 and ANSI/UL 464 and shall have compliance with the polar dispersion requirements of ANSI/UL 1971. The notification appliance shall also be listed  with the California State Fire Marshal (CSFM).

The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized.

Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel.

The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 74mA or less at 24 VDC for the 15Cd strobe circuit.

The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power for 24 volt models.

The appliance shall be capable of testing supervision without disconnecting wires. Also, the appliance shall be capable of mounting to a surface back box.
The unit shall also be able to verify voltage at the unit without removing unit.