POTTER FHA Addressable Fixed Temperature Heat Detector Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
**POTTER FHA Addressable Fixed Temperature Heat Detector Owner’s Manual
**
Features
- Software adjustable 135°-185° Fahrenheit heat sensor
- Low profile
- Reliable detection technology
- LEDs for 360° viewing
- Ambient temperature listing of 32° F to 150° F
Description
The Fixed Temperature Heat Sensor (FHA) is a listed Analog
Addressable fixed temperature heat sensor compatible with any fire alarm
control panel that has the Potter/Nohmi protocol. The heat sensing portion
utilizes a proven thermistor for accurate and reliable heat detection. The
sensor and base (not included) are made of a durable plastic in an eggshell
white to blend in with the ceiling.
The FHA is UL and cUL listed with a selectable fixed temperature point from 135° to 185° Fahrenheit. This broad range allows the installer to cover a wide variety of applications with a single unit.
The FHA has two LEDs that allow for 360° viewing. The sensor is
compatible with any of the Potter/Nohmi bases. The FHA is addressed using the
hand held programmer or the control panel addressing function.
Spacing
The FHA spacing is dependent on the alarm set-point. The unit is listed from 135°F to 185°F.
However as the temperature setting increases, the spacing decreases.
Alarm set-point | FHA Spacing |
---|---|
135 to 170 °F (57 to 76 °C) | Max. 50 ft |
171 to 174 °F (77 to 79 °C) | Max. 15 ft |
175 to 185 °F (80 to 85 °C) | Max. 15 ft |
The system has a maximum of 13 LEDs that can be turned on simultaneously. If the system already has 13 LEDs on, the FHA will operate even though the LED will not illuminate.
Setting the Address
Each addressable module, smoke sensor, heat detector and combination sensor/detector must have the address set before connecting the device to the SLC loop. The address is set using the hand held device programmer or the addressing feature on the control panel
Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following:
- Power to the device is removed
- Field wiring is correctly installed.
- Field wiring has no open or short circuits.
Document discrepancies and notify appropriate personnel.
Specifications
Item | FHA |
---|---|
Working voltage range | 22.0 to 24.0 V |
Standby current | 325 µA |
Alarm indicator | 2 LEDs |
Alarm indicator current | 1.2 mA D. |
Alarm set-point range | 135 to 185 °F/ 57 to 85 °C |
Installation temperature range | 32 to 150 °F / 0 to 66 °C |
Operating relative humidity range | 0% to 93% (Non-condensing) |
Start-up time | Max. 1 sec. |
Maximum number of addresses per loop | 127 |
Maximum number of lighted indicators in alarm per zone. | 13 |
Color | Eggshell White |
Weight (without base) | 73g (2.57oz) |
Dimensions (without base) | Height: 1.50 in (38mm) |
Approvals / Listings | UL, cUL, CSFM |
Operation
The FHA is an analog/addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will latch steady if the unit is in an active status.
The FHA is a single sensor that may be used in a wide variety of applications for property protection. The FHA has a high ambient installation temperature and has been tested in these environments. The unit has a sleek design and low profile for pleasing aesthetics. The temperature sensor is protected within the mold of the unit to prevent accidental damage
Compatible Bases
All bases will mount on a single gang, double gang, octagon, 4” square or mud
ring electrical box.
Device | Description |
---|---|
AB-4 | 4” Standard Base |
AB-6 | 6” Standard Base |
AIB | 6” base with an isolator module included. The base is pre-wired with a |
pluggable jumper to the module.
ARB| 6” base with a dual relay module included. One relay is rated for 8 amps
at 240 VAC/30 VDC and the second is rated for 2 amps at 240 VAC/30 VDC. The
base is pre-wired with a pluggable jumper to the module
ASB| 6″ base with sounder module included. Sound pattern is provided from
external source. The base is pre-wired with a pluggable jumper into the
module.
Support
Potter Electric Signal Company, LLC
- St. Louis, MO
- Cust Service: 866-240-1870
- Tech Support: 866-956-1211
- Canada: 888-882-1833
- www.pottersignal.com
S24776
7165-0328: 0193