Features
- 24VDC fixed 15/75 candela
- FASPK-WP, SPKST24-WP series shipped with Potter SPKRBB outdoor back box
- Field selectable power taps: 1/8W, 1/4W, 1/2W, 1W, 2W, 4W
- High quality dBA output (intelligible)
- Frequency range 400-4000 Hz
- Screw terminals, separate in/out wiring (18-12 gauge)
- Tamperproof grill
- Speaker voltage 25 or 70.7 VRMS standard, field selectable
- Faceplate available in red or off-white
- Strobe synchronization with Potter AVSM module
- Product includes a 5 year warranty
Application
The potter FaSpK-Wp, SpKST24-Wp Series is an outdoor listed, wall mount, field adjustable speaker and speaker/strobe designed to meet code requirements for audio, visual, and voice communications. The SPKST24-WP speaker/strobe offers a fixed 15/75 candela strobe.
Description
The FASPK-WP Series provides a 25 or 70.7 VRMs speaker with field selectable
power taps of 1/8W, 1/4W, 1/2W, 1W, 2W, or 4W. The SPKST24-WP provides a fixed
15/75 candela strobe output. The strobe can be synchronized using the Potter
AVSM Synchronization Control Module, FACP, or power supplies that produce a
Gentex Synchronization Protocol.
The Potter FASPK-WP, SPKST24-WP Series grills are constructed of high impact
textured plastic. Included with the Potter FASPKWP, SPKST24-WP Series speaker
and speaker/strobe is the Potter SPKRBB outdoor listed back box. Using the
Potter SPKRBB back box with the Potter FASPK-WP, SPKST24-WP Series provides
protection from weather related conditions and allows the necessary full
candela output.
Product Listings
- ULS2657
- ANSI/UL 1480, ANSI/UL1638 Listed
- CSFM 7320-0328:0206 (FASPK-WP)
7320-0328:0207 (SPKSTR-24WP)
Product Compliance
- Americans with Disabilities Act (ADA)
- NFPA 72
- IBC/IFC/IRC
Technical Specifications
Speaker Operating Voltage | 25VRMs or 70.7VRMs |
---|---|
Strobe Operating Voltage | 16-33VDC |
Synchronization Module | Potter AVSM |
Environmental Limitations | -31°F to 150°F |
Unit Dimensions | FASPKR – 6.1” square X 3.19”deep SPKSTR-24 – 6.1” square X |
4.0625” deep
Back Box| Includes GBLP outdoor back box
SPKSTR-24 – 15/75 Strobe Current Rating
Candela| 15/75 cd
24 VDC| 63 mA
UL Max| 96 mA
Speaker dBA @ 10 ft.
Input Watts| 25 Volts| 70.7 Volts
1/8| 74.6 dBA| 73.7 dBA
1/4| 77.7 dBA| 76.7 dBA
1/2| 80.5 dBA| 79.6 dBA
1| 83.1 dBA| 82.5 dBA
2| 85.6 dBA| 85.4 dBA
4| 87.9 dBA| 87.9 dBA
NOTE: Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
Outdoor Evacuation Speakers (Speaker Only)
Model Number| Description| Stock Number
FASPK-WPR| Speaker Red| 4890304
FASPK-WPW| Speaker White| 4890305
Outdoor Evacuation Speaker / Strobes Fixed 15/75 candela
Model Number| Description| Stock Number
SPKSTR-24WLPR-WP| Speaker/Strobe Red Fire Label| 4890306
SPKSTR-24WLPR-WP| Speaker/Strobe White Fire Label| 4890307
SPKSTR-24WLPPR-WP| Speaker/Strobe Red Plain Label| 4890308
SPKSTR-24WLPPW-WP| Speaker/Strobe White Plain Label| 4890309
SPKSTR-15/75-AL-WP| Speaker/Strobe Red Alert Label| 4890310
SPKSTR-15/75-AL-WP| Speaker/Strobe White Alert Label| 4890311
Architect and Engineering Specifications
The fire alarm speaker shall be Potter FASPK-WP, SPKST24-WP or equivalent. The
speaker shall be capable of producing alarm tones or voice on all 25 or 70.7
VRMs audio systems. The speaker shall provide incremental tap settings of 1/8,
1/4, 1/2, 1, 2, or 4 watts. Minimum dBA ratings at 1/4 watt shall be 76.7 dBA
and at 4 watts 87.9dBA. Tap settings shall be adjustable with field selectable
jumper pins. The speaker shall also have an optional visual signal capability.
The visual signal shall have a 1 Hz flash rate regardless of input voltage.
All field wiring connections shall be made via separate in-out terminal
connections.
The appliance has extended termperature range of -31° to 150° F (-35° to 66°
C). The appliance shall satisfy all outdoor and severe environment
applications.
The GBLP back box includes a gasket that must be inserted between the box and
device. There are drain holes in the back box to allow for draingage, the seal
on the GBLP is not water tight. The speaker or speaker/strobe shall be
ANSI/UL, CSFM listed and comply with all local, state and federal fire alarm
codes/standards.
Power Tap Selection Fig 1 | Mounting Diagram Fig 2 |
---|---|
NOTE: Adjust Power taps using needle nosepliers.
Wiring Diagram
Fig 3
NOTE: DO NOT USE LOOPED WIRE UNDER TERMINALS.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTION.
- MAX WIRE DISTANCE – – X WIRE CONDUCTIVITY PANEL VOLTAGE – DEVICE MINIMUM VOLTAGE TOTAL CURRENT DRAW
- CAUTION: APPLIES ONLY TO REGULATED SUPPLIES.
- NOTICE: POWER IS SUPPLIED TO DEVICES WHEN CONTROL PANEL IS LATCHED.
Potter Electric Signal Company, LLC • St. Louis, MO
Tech Support:866-956-1211 / Customer
Service: 866-572-3005
www.pottersignal.com
firealarmresources.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>