Mircom FA-1008KADS Conventional Fire Alarm Control Unit Instructions

June 9, 2024
Mircom

Mircom logo 1 CONVENTIONAL FIRE ALARM CONTROL UNIT
FA-1008KADS

Description

Mircom’s FA-1008KADS Fire Alarm Control Unit is a microprocessor based unit designed for maximum flexibility and easy installation. Fully configurable from the front panel using the push buttons and DIP switches, it enables the user to configure the system to meet their specific requirements.
The FA-1008KADS consists of one MCC-1024-6ADS Main Chassis in a UB-1024DS back box with a DOX1024DS door. The MCC-1024-6ADS Main Chassis comes complete with 8 Class B (Style B) Initiating Circuits which may be configured as 4 Class A (Style D) Circuits. It can be expanded up to 24 Class B or 12 Class A circuits with the addition of the DM1008A Initiating Circuit Module. In addition it comes equipped with 4 Class A/B (Style Z/Y) Indicating circuits which are each rated at 1.7 Amps.  The Main Chassis also includes a 6 Amp Power Supply which powers the system and supplies two 4-wire resettable regulated smoke power supply of 24 VDC 200mA maximum each.
The MCC-1024-6ADS also allows for the addition of two SGM-1004A Signal Modules or two RM-1008A Relay modules in place of the DM-1008A Initiating Circuit Adder Modules. (Maximum of 3 Adder modules) The backbox provides space for up to 18 AH Gel Cell batteries.

Features

  • Listed to UL 864, 9th edition
  • 8 Class B (Style B) Initiating Circuits which may be configured as 4 Class A (Style D) Circuits. Expandable up to 24 Class B or 12 Class A Initiating Circuits
  • 4 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.7 Amps max. per circuit)
  • Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audibles may be configured as Steady, Temporal Code, California Code or March Time
  • Each Initiating Circuit can be configured as Alarm, Supervisory, Waterflow or Trouble
  • Two LEDs per Initiating circuit; one for Trouble and one for Status
  • Initiating and Indicating Circuits may be individually disconnected by a DIP switch
  • Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation and One Man Walk Test
  • Alarm Verification on Initiating Circuits
  • Subsequent Alarm, Supervisory and Trouble operation
  • Two outputs for 4 wire resettable smoke power supply (200 mA Max. each)
  • Auxiliary relay contacts for Common Alarm and Common Supervisory as well as a Common Trouble Relay (Each relay contact Form C, 28 VDC @ 1 Amp (resistive))
  • RS-485 Interface for RA-1000 Remote Multiplex Annunciators
  • Interface for Remote Trouble Indicator
  • Easy configuration via push buttons and DIP switches on the front panel
  • Extensive Transient Protection
  • 6 Amp Power Supply

Optional Modules

  • UDACT-300A Digital Communicator
  • PR-300 Polarity Reversal and City Tie Module

Application

The Mircom FA-1008KADS is designed as an economical Microprocessor Based Fire Alarm Control Unit which is expandable up to 24 display points. Its modular design suits various applications. Ideal for applications such as small institutional and commercial buildings, shopping malls, offices and public establishments, the FA-1008KADS is configurable to meet virtually all requirements. The unit is designed to be easy in its installation, operation and maintenance. This makes the system cost effective and very reliable for its intended applications.
Dimensions
(minus built-in trim ring): 26”H x 14.5”W x 4.2”D

Electrical Ratings

AC Line Voltage 120V 601-Iz /240V 50 Hz, 2A11A primary
Power Supply Ratings 6 Amps. max. (secondary)
For Indicating Circuits 24VDC unfiltered, 5 Amps maximum
Charging Capability 10-24 A1-1 batteries
Current Consumption Standby
Alarm 350 mA

Ordering Information

Model Description

Fire Alarm Control Unit
FA-1008KADS| Microprocessor Based Fire Alarm Control Unit expandable up to 24 display points.
Includes MCC-1024-6ADS Main Chassis, UB-1024DS back box and DOX-1024DS white door.
Adder Modules
DM-1008A| Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module
SGM-1004A| Four Class A/B (Style Z/Y) Notification Appliance Circuit Module (Rated at 1.7 Amps per circuit)
RM-1008A| Eight Relay Circuit Module c/w eight Form C relays (Rated for 28 VDC @ 1 Amp. max. per relay)
Auxiliary Modules
UDACT-300A| Digital Alarm Communication Transmitter/Dialer Module
PR-300| Polarity Reversal and City Tie Module
Remote Annunciators
RAM-1016TZDS| Main Remote LED Annunciator c/w 16 Bi-Colored LEDs and 16 Trouble LEDS
RAM-1032TZDS| Main Remote LED Annunciator c/w 32 Bi-Colored LEDs and 32 Trouble LEDSs
RAX-1048TZDS| Programmable LED Annunciator Module c/w 48 Bi-Coloured LEDs and 48 Trouble LEDs
RTI-1| Remote Trouble Indicator
BB-1001| Remote Enclosure. Houses one module.  Add suffix “R” for red door.
BB-1002| Remote Enclosure. Houses two modules.  Add suffix “R” for red door.
BB-1003| Remote Enclosure. Houses three modules.  Add suffix “R” for red door.
End of Line Resistors
MP-300| EOL Resistor Plate
MP-300R| EOL Resistor Plate, Red

Mircom logo 1
Canada

25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
Web page: http://www.mircom.com
Email: [email protected]
NOT TO BE USED FOR INSTALLATION PURPOSES.
Distributed by:
CAT. 5627
ISO 9001:2008
REGISTERED
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals