ALPHA INTELLIGENT ADDRESSABLE MODULES
MIX-100 SERIES
Features
- Designed to meet a wide range of applications
- For use with the FX-350 Series Fire Alarm Control Panels
- Fast response time
- Priority Interrupt feature on monitor modules
- Monitor modules can be wired as a Class A (Style D) or Class B (Style B)
- Each module can be addressed from 1 to 126
- Eight position dip switch for address setting
- Red light indicator
- Modules mount in standard 4″ junction box
Description
Mircom’s Alpha Series Intelligent Addressable Modules are designed to meet a wide range of applications. The monitor and control modules can be used to supervise and activate sounders, strobes, door closers, pull stations, waterflow switches, conventional smoke detectors and more. An eight position dip switch allows for the address setting of the device and the wiring class/style of the devices that are connected to the module. All modules mount in a standard 4” x 4” x 2 1/8” junction box.
Intelligent Addressable Priority Monitor Module (MIX-100P)
The Intelligent Addressable Priority Monitor Module (MIX-100P) provides an
address for a group of UL/ULC Listed normally open (N.O.) initiating devices,
such as heat detectors, beam smoke detectors, 4-wire smoke detectors,
waterflow switches, manual pull stations, etc. wired in a Class A (Style D) or
Class B (Style B) initiating circuit. The MIX-100P is equipped with a priority
interrupt to provide a fast response to emergency conditions. The MIX-100P has
an activated red LED.
Intelligent Addressable Priority Mini-Monitor Module (MIX-101P)
The Intelligent Addressable Priority Mini Monitor Module provides an address
for a group of UL/ULC Listed Normally Open (N.O.) initiating devices, such as
heat detectors, projected beam smoke detectors, 4-wire smoke detectors,
waterflow switches, manual pull stations, etc. wired in a Class A (Style D) or
Class B (Style B) initiating circuit. The MIX-101P is equipped with a priority
interrupt to provide a fast response to emergency conditions. The MIX-101P has
an activated red LED.
Intelligent Addressable Relay Module (MIX-100R)
The Intelligent Addressable Relay Module connects to the same loop as the
initiating devices and provides two isolated sets of Form-C contacts to
control a variety of normally open or normally closed contact applications
cuch as fan operation and door closures. The MIX-100R has an activated red LED
which follows the state of the relay contacts.
Intelligent Addressable Supervised Control Module (MIX-100S)
The MIX-100S Control module provides supervised monitoring of wiring to signal
devices that require an external power supply to operate, such as horns,
strobes, bells or speaker isolators. Conventional signals will require a 24
VDC power source and speakers will require an audio input. The red LED will
illuminate when the module is activated. The module is capable of Class A
(Style Z) or Class B (Style Y) supervision.
Fault Isolator Module (MIX-100X)
The MIX-100X Fault Isolator Module is used to protect the system against wire-
to-wire short circuits on the analog loop. The modules should be spaced
between groups of sensors or modules in a loop to protect the rest of the
loop. In the event of a short circuit between any two fault isolator modules,
both modules immediately switch to an open circuit condition and isolate any
group of sensors between them. The remaining units on the circuit will
continue to operate in a normal fashion (must be wired in Class ‘A’ or Style
6).
Specifications
General Specifications
Operating Voltage | 16-28 VDC |
---|---|
Communication | Class A (Style D) or Class B (Style B) switch selectable |
Relative Humidity | 0% to 95% (No condensation or icing) |
Operating Temperature | 0°F to +155°F (-20°C to +70°C) |
--- | --- |
Housing/Cover Plate Finish | White Polycarbonate |
MIX-100P and MIX-101P
Current Consumption | 600 µA |
---|---|
Alarm Current | 4.6 mA (LED on) |
Dimensions
| MIX-100P| 4.0” W x 4.0” H x 1.3” D
MIX-101P| 3.0” W x 2.0” H x 0.75” D
Weight
| MIX-100P| 3.0 oz. (85.8g)
MIX-101P| 1.5 oz. (42.6g.)
MIX-100X
Current Consumption | 35µA at 24V |
---|---|
Max. Line Current | 1 Amp |
Line Resistance | 0.2 ohm |
Dimensions | 4.0” W x 4.0” H x 1.3” D |
Weight | 3.0 oz. (85.8g) |
MIX-100S
Current Consumption | 1 mA |
---|
Source Power
| Signals| 24 VDC regulated
Speakers| 70.7 V RMS
Ratings| 2A @ 30VDC, 0.6A @ 125VAC
Dimensions| 4.0” W x 4.0” H x 1.3” D
Weight| 3.0 oz. (85.8g)
MIX-100R
Current Consumption | 250 µA |
---|---|
Ratings | 2A @ 24VDC, 0.5A @ 30VAC |
Dimensions | 4.0” W x 4.0” H x 1.3” D |
Weight | 3.0 oz. (85.8g) |
Ordering Information
Model | Description |
---|---|
MIX-100P | Intelligent Addressable Priority Monitor Module |
MIX-101P | Intelligent Addressable Priority Mini Monitor Module |
MIX-100R | Intelligent Addressable Relay Module |
MIX-100S | Intelligent Addressable Supervised Control Module |
MIX-100X | Fault Isolator Module |
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO
DESCRIBE THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance,
installation, testing and certification, refer to technical literature. This
document contains intellectual property of Mircom. The information is subject
to change by Mircom without notice. Mircom does not represent or warrant
correctness or completeness. All rights reserved. All other trademarks and
registered trademarks are properties of their respective owners.
Canada
25 Interchange Way Vaughan, ON L4K 5W3 Telephone:
905-660-4655 | Fax:
905-660-4113
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free:
888-660-4655 | Fax Toll Free:
888-660-4113
www.mircom.com
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>