Mircom SPS SERIES 8 Inch Speaker-Strobes Instructions

June 9, 2024
Mircom

Mircom SPS SERIES 8 Inch Speaker-Strobes Instructions

Mircom SPS SERIES 8 Inch Speaker-Strobes.JPG

Features

  • 25 & 70 Volt line matching transformers
  • DC blocking capacitor for line supervision
  • Output power taps of ½, 1, 2 and 4 watts
  • Terminal block connection for speaker tap/output selection
  • ULC listed for Wall or Ceiling mount
  • Fire retardant cone material
  • Strobe with two field selectable settings 15/75 or 30/120cd
  • Polarized strobes with wide listed voltage ranges using filtered DC or unfiltered FWR input voltage
  • Tamper-proof candela selector switch
  • Strobe synchronization requires an SDM-240 Sync Module
  • Round or square baffles
  • Available in a white housing

Description

Mircom’s low profile fire alarm speakers are designed to generate attention grabbing tones and voice commands for emergency signaling evacuation applications. These highly efficient low profile speakers are available with field selectable taps from ¼ – 2 watts. The low profile speakers are available in two input voltage models 25 Vrms and 70.7 Vrms.

The SPS series speaker/strobe are designed with the new Select-A-Strobe. The strobe features a unique candela intensity field selector switch for switching the candela output from 15/75 to 30/120 cd. The strobe housing is clearly labelled with “FIRE” lettering and is polarized for connecting to supervised fire alarm circuits. The strobe is designed with a xenon flashtube and provides a candela intensity field selector switch for maximum performance.

The Strobe can be synchronized by using the SDM- 240 sync module. The strobe signals are listed for indoor use, ceiling and wall mount.

The SPS-Series speaker-strobe install easily using the surface or flush backboxes.

Specifications

The SPS-Series 8” Speaker-Strobes consist of a loudspeaker, 6 oz. magnet, a low profile constant voltage line matching transformer, a D.C. blocking capacitor and an all steel speaker baffle finished in an off white colour. The 25 and 70 volt transformers are of the matching type and include output power taps of: ½, 1, 2 and 4 watt(s). Tap selection is done using the speaker’s terminal block. The speaker shall be approved for fi re alarm signaling use.

The signaling strobe’s candela output shall be field selectable, having a dual setting of 15/75 cd or 30/120 cd output. The signaling strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal flash of one flash per second with continuously applied minimum voltage. The SPS-Series speakers shall be capable of WALL or CEILING mounting.

NOT TO BE USED FOR INSTALLATION PURPOSES.

Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifi cations and models and also to discontinue models.

Output & Current Draw Table

FIG 1 Output & Current Draw Table.JPG

Mounting Options & Dimensions

FIG 2 Mounting Options & Dimensions.JPG

Typical Wiring Diagram

FIG 3 Typical Wiring Diagram.JPG

Ordering Information

FIG 4 Ordering Information.JPG

NOT TO BE USED FOR INSTALLATION PURPOSES.

Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
Web page: http://www.mircom.com

U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113

Email: mail@mircom.com

firealarmresources.com

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals