Mircom CSIS-202A1 Supervised Signal Isolator Module Owner’s Manual

June 9, 2024
Mircom

Mircom CSIS-202A1 Supervised Signal Isolator Module

Description

The CSIS-202A1 is a signal isolator which provides two supervised isolator outputs. These isolators remove the bells, horns or strobes which follow it out of the circuit should there be a trouble (short). This feature provides integrity of the signal circuit, that is; should an isolated bell, horn or strobe malfunction, the rest of the bells, horns or strobes will continue to function.

Features

  • Operates with bells and horns
  • Provides 2 supervised isolator outputs
  • Signals the fire alarm control panel for a short or open on the suite signals
  • Mounts in a 4” square electrical box
  • Area on mounting plate for labeling the suite number
  • Designed for installations where disconnection of, or damage to an in-suite audible device will not interfere with the ability of system audible devices.

Electrical Ratings

  • Signal In: Regulated 24 FWR/24 VDC
  • Suite Current: 400 mA MAX per suite
  • Standby Current: 0.0 A
  • Alarm Current: 0.1 A

Mounting Diagram

Typical Wiring Diagrams

Typical Wiring of the CSIS-202A1 Supervised Signal Isolator Module

Mircom CSIS-202A1 Supervised Signal Isolator Module-
fig3

Typical Wiring of the CSIS-202A1 Supervised Signal Isolator Module using SIGSM-100 Silence Switch Module

Mircom CSIS-202A1 Supervised Signal Isolator Module-
fig4

Notes

  1. All unused screw terminals must be tightened to prevent shorting to front plate.
  2. For proper system operation refer to detailed installation instructions provided with control panel and local installation standards.
  3. Wiring supervised by the Fire Alarm Control Panel as per Code.
  4. Refer to signal device instruction for wiring gauge information.
  5. Subtract 0.1A from the total signal circuit current when using any number of these isolators i.e. 1.7A subtract 0.1A equals 1.6A available for signaling when using isolators.

Ordering Information

Model Description
CSIS-202A1 Supervised Signal Isolator Module

THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance, installation, testing and certification, refer to technical literature. This document contains intellectual property of Mircom. The information is subject to change by Mircom without notice. Mircom does not represent or warrant correctness or completeness.

Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: 905-660-4655 Fax: 905-660-4113
Website: www.mircom.com

U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655 Fax Toll Free: 888-660-4113
Email: [email protected]

firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals